Installation bracket TBLZ-1-53 for circular ducts or
insulated flat ducts.
The duct diameter can be as small as 100 mm
using the bracket.
• Check that the direction of the arrows is towards the direction of ow.
• Check that the plug for the test hole is properly installed.
• Check that the ow indicator shows ow (rocks).
• Full scale tests with smoke generator are recommended to check the function.
Troubleshooting.
The smoke detector deploys without any smoke
present.
• The smoke detector is faulty, dirty or positioned so that
condensation can build up, see point 8. The detector
insert must be replaced.
Only the control unit triggers an alarm.
• Check that the termination resistor is installed in the last
smoke detector.
• Check that the coil’s resistance is 2.2kΩ from the control
unit.
• Check that the control unit is OK by installing the 2.2kΩ
resistor in the smoke detector output on the control unit.
• Use a voltmeter to check that 21-24 VDC with the correct polarity is in terminal 1 (-) and terminal 2 (+).
10
8
9
The installation bracket is supplied flat.
The installation bracket is easy to
bend/shape so that it fits circular or
flat ducts.
Secure the bracket’s
legs to the duct.
Hole ø 51
mm.
Rubber
seal
Circular duct. Insulated flat duct.
Rubber
seal
Final checks
Installing different tubes in different duct widths.
Venturi tube 600 mm. Venturi tube 1200 mm.
Hole
ø 38 mm
Hole
ø 38 mm
Cut the venturi
tube to the correct
length
The Venturi tube
must go through
the entire duct.
Important!
Hole ø 51 mm
Max. tube of 30 mm outside the duct.
For ducts less than 600 mm use venturi tube of 600 mm, standard.
For ducts between 600 mm and 1400
mm, use venturi tube of 1500 mm.
• Cut the tube to the
correct length.
• Insert the end plug.
• Install the seal
• Install rubber seal TET
26-35 as a bearing.