GB.TBLZ481.160408
Installation equipment cabinet for smoke funct. TBLZ-1-48-1
GOLD/COMPACT
1. General
Equipment cubicle for smoke function consists of a control unit installed in a box with transparent cover.
There are necessary terminals for external connection.
The equipment cubicle is equipped with knockout grommets.
2. Range of Application
The equipment cubicle is used together with smoke detectors TBLZ-2-49-a. In the event of an error indication the
unit is designed to control dampers and stop the unit and
give an alarm. Connected damper actuators must be suitable for a 230 V supply.
3. Function control unit smoke
The control unit is designed to meet the requirements set
to provide reliable fire protection together with our smoke
detectors. Equipped with relay contactors for controlling
dampers and fans. Besides smoke alarms, the control unit
is equipped with a service alarm and error alarm relays.
In the event of a smoke alarm, a red LED lights and the
alarm relays trip at the same time.
In the event of a service alarm on the smoke detector,
the LED for the service alarm flashes quickly for 1 minute.
Then the service alarm relay is active and the LED lights
continuously. If the service alarm on the detector resets,
the relay trips and the LED starts to flash slowly: Alarm
memory.
Short-circuits and open-circuits cause fault relays and
alarm relays to activate at the same time as the respective
LED lights (open-circuit, approx. 10 seconds delay). If a
short-circuit or open-circuit recurs, the relays trip and the
respective LED starts to flash slowly: Alarm memory.
Exercising the relays: keep the reset button depressed for
5 seconds.
4. Installation
Use the four screws to mount the equipment cabinet on
the wall, unit or similar.
5. Technical Data
Supply voltage 230VAC, 50-60Hz
Power consumption
(control unit)
Degree of protection IP 65
Ambient temperature 0-50°C
Dimensions (WxHxD) 175 x 125 x 100mm
Weight 740g
Specifications are subject to alteration without notice.
1.8VA
www.swegon.com 1

6. Electrical Connections
The electrical connections are to be wired by a qualified
electrician in accordance with local electrical safety regulations.
GOLD RX/PC/CX/SD version E/F, GOLD LP, COMPACT
SMOKE FUNCTION
GOLD RX/PX/CX/SD
Terminals on the
control unit and in
electrical equipment cubicle
101
102
GB.TBLZ481.160408
SMOKE DETECTOR CONTROL UNIT
Wiring terminal
Ext. fire alarm
Ext. alarm 2
6
7
12
13
GOLD LP/COMPACT
Wiring terminals
inside electrical equipment cubicle
Wiring terminals
on the control
unit
*Should be selected for ext. fire alarm in the
micro terminal.
**Should be selected for ext. alarm in the micro
terminal.
**
201
202
5
*
6
7
8
Terminal block
2,2
Function:
In the event that the smoke detector B7 in the duct trips, the alarm
is forwarded to GOLD/COMPACT,
external fire alarm. Damper actuator MG7 is controlled via control
unit B6.
When the smoke detectors become
dirty, a service alarm is initiated in
control unit B6 and is forwarded to
GOLD/COMPACT via the external
alarm 2.
Alarms can be reset on control unit
B6 and in the air handling unit’s
hand-held micro terminal.
2 www.swegon.com
MG7: MG7: B7: B7:
Damper
actuator
If additional smoke damper
actuators are installed, they must
be connected in parallel in the
terminal block.
Damper
actuator
Smoke detec-
tor
If additional smoke detectors are
installed, they must be connected in series (install the termination resistor on the last smoke
detector only).
Specifications are subject to alteration without notice.