Swegon TBLZ-1-48-1 Installation Manual

Page 1
GB.TBLZ481.160408
Installation equipment cabinet for smoke funct. TBLZ-1-48-1 GOLD/COMPACT
1. General
Equipment cubicle for smoke function consists of a con­trol unit installed in a box with transparent cover. There are necessary terminals for external connection. The equipment cubicle is equipped with knockout grom­mets.
2. Range of Application
The equipment cubicle is used together with smoke detec­tors TBLZ-2-49-a. In the event of an error indication the unit is designed to control dampers and stop the unit and give an alarm. Connected damper actuators must be suit­able for a 230 V supply.
3. Function control unit smoke
The control unit is designed to meet the requirements set to provide reliable fire protection together with our smoke detectors. Equipped with relay contactors for controlling dampers and fans. Besides smoke alarms, the control unit is equipped with a service alarm and error alarm relays.
In the event of a smoke alarm, a red LED lights and the alarm relays trip at the same time.
In the event of a service alarm on the smoke detector, the LED for the service alarm flashes quickly for 1 minute. Then the service alarm relay is active and the LED lights continuously. If the service alarm on the detector resets, the relay trips and the LED starts to flash slowly: Alarm memory.
Short-circuits and open-circuits cause fault relays and alarm relays to activate at the same time as the respective LED lights (open-circuit, approx. 10 seconds delay). If a short-circuit or open-circuit recurs, the relays trip and the respective LED starts to flash slowly: Alarm memory.
Exercising the relays: keep the reset button depressed for 5 seconds.
4. Installation
Use the four screws to mount the equipment cabinet on the wall, unit or similar.
5. Technical Data
Supply voltage 230VAC, 50-60Hz
Power consumption (control unit)
Degree of protection IP 65
Ambient temperature 0-50°C
Dimensions (WxHxD) 175 x 125 x 100mm
Weight 740g
Specifications are subject to alteration without notice.
1.8VA
www.swegon.com 1
Page 2
6. Electrical Connections
The electrical connections are to be wired by a qualified electrician in accordance with local electrical safety regula­tions.
GOLD RX/PC/CX/SD version E/F, GOLD LP, COMPACT
SMOKE FUNCTION
GOLD RX/PX/CX/SD
Terminals on the control unit and in electrical equip­ment cubicle
101
102
GB.TBLZ481.160408
SMOKE DETECTOR CONTROL UNIT
Wiring terminal
Ext. fire alarm
Ext. alarm 2
6
7
12
13
GOLD LP/COMPACT
Wiring terminals inside electrical equip­ment cubicle
Wiring terminals on the control unit
*Should be selected for ext. fire alarm in the micro terminal. **Should be selected for ext. alarm in the micro terminal.
**
201
202
5
*
6
7
8
Terminal block
2,2
Function: In the event that the smoke detec­tor B7 in the duct trips, the alarm is forwarded to GOLD/COMPACT, external fire alarm. Damper actua­tor MG7 is controlled via control unit B6. When the smoke detectors become dirty, a service alarm is initiated in control unit B6 and is forwarded to GOLD/COMPACT via the external alarm 2. Alarms can be reset on control unit B6 and in the air handling unit’s hand-held micro terminal.
2 www.swegon.com
MG7: MG7: B7: B7:
Damper actuator
If additional smoke damper actuators are installed, they must be connected in parallel in the terminal block.
Damper actuator
Smoke detec-
tor
If additional smoke detectors are installed, they must be connect­ed in series (install the termina­tion resistor on the last smoke detector only).
Specifications are subject to alteration without notice.
Smoke detec-
tor