Installation Instructions for the TBLZ-1-31-1 and TBLZ-1-31-2 Humidity sensor GOLD
1. General
Description
The humidity sensor contains a humidity sensing element, which also measures the temperature.
The humidity sensor is supplied with a 7 m long cable for bus communication and is connected with a modular con­nector.
The communication cable is used for supplying power and signal transfer.
The sensor is mounted on a ventilation duct by means of the duct connection flange supplied.
Function
Humidity and temperature values are transmitted via Modbus communication to the control circuit card of the air handling unit.
The humidity sensors are coded for supply air and extract air respectively.
The TBLZ-1-31-1 is designed for installation in the supply air and is used for the dehumidification or humidification function.
The TBLZ-1-31-2 is designed for installation in the extract air and is used for the dew-point regulation function with cooling beams or the humidification function.
2. Installation
Mount the humidity sensor in the supply or extract air duct.
The position in which the humidity sensor is mounted will no affect its performance but it is inappropriate to mount it standing with its connection pointing downwards because this may lead to moisture collecting inside the sensor.
It is important that the sensor be mounted with its sensing element (in the tip of the sensor) positioned in the centre of the duct.
GB.TBLZ31.120302
We reserve the right to alter specifications without notice.
2
www.swegon.com
3. Technical Data
Connection contact RJ 12 6/6 Supply voltage 24 V DC (Via modular connector) Measurement range, humidity 0-100 % RH Measurement range, temp. -40 – 123°C Measurement accuracy, <2 % RH, 10 - 90 % RH humidity <5 % RH, 0 - 10 % RH and 90 -100 % RH Measurement accuracy, temp <0.5°C, 15 – 40°C Resolution, humidity 0.03 % Resolution, temp. 0.01 °C Non-linearity, humidity < 1% Hysteresis, humidity ± 1 % Long term stability, humidity <0.5% / year Degree of protection: in duct IP32 to EN 60529 outside duct IP54 to EN 60529
Dimensions
300 ± 57000 ± 20
25
Ø12
Gasket
Duct connection flange Modular connector
RJ12 6/6 gold-plated contacts
Label Cable