Swegon SILVER C RX 100, SILVER C CX 100, SILVER C RX 120, SILVER C CX 120 Installation Instructions Manual

Installation instructions for the SILVER C RX/CX version F, size 100/120
GB.SILVERF120.181005
We reserve the right to alter specifications.
The document was originally written in Swedish.
www.swegon.com 1
Contents
1. Installation ............................................... 3
1.3.1 Document pocket ............................................. 3
1.5.1 SILVER C RX ...................................................... 3
1.5.2 SILVER C CX ...................................................... 3
1.6.1 With a fork-lift truck ......................................... 4
1.6.2 With a crane ..................................................... 4
1.6.2.1 Complete units ............................................ 4
1.6.2.2 Heat exchanger section, supplied split into two
casing sections and rotor (SILVER C RX only) ............. 5
1.7 To assemble the heat exchanger unit section, if
1.7.1 Alternative 1 ..................................................... 7
1.7.2 Alternative 2 ................................................... 11
1.7.3 Common for Alternatives 1 and 2 ................... 15
1.7.3.1 To adjust the rotor’s inclination ................... 15
1.7.3.2 Sealing plates/purging sector ...................... 16
1.7.3.3 Pressing roller ............................................. 16
1.7.3.4 Vinyl-coated fabric seal .............................. 16
1.7.3.5 Sealing ....................................................... 17
1.8.1 SILVER C RX .................................................... 18
1.8.2 SILVER C CX .................................................... 18
1.9.1 Fan/filter/coil heat exchanger sections
(Coil heat exchanger sections SILVER C CX only) ....... 19
1.9.2 Fastening, front/middle section ....................... 20
1.9.3 Fixation, rear of the unit .................................. 20
1.12 Installation of pipework package
GB.SILVERF120.181005
2. Dimensions ............................................23
2 www.swegon.com
We reserve the right to alter specifications.
GB.SILVERF120.181005
3440
1070
1. Installation
1.1 General
All staff concerned must acquaint themselves with these instructions before beginning any work on the unit. Any damages to the unit or parts of it due to improper han­dling or misuse by the purchaser or the fitter cannot be considered subject to guarantee if these instructions have not been followed correctly.
The product identification label is affixed on the inspection side of the air handling unit. Refer to the particulars on the product identification plate when you contact Swegon.
The air handling unit is supplied in packaged condition.
Possible ordered accessories are supplied in separate pack­aging with the unit.
1.2 Transport within the site
Before removing the transport pallet/transport cradle, if used, determine whether a forklift truck or a pallet trans­porter will be used for further transporting the unit within the site to the spot where it will be installed.
1.3 Parts packed together with the unit
Components such as the commissioning plates, bolts and document pocket are supplied in separate packaging and delivered together with the air handling unit.
1.5 Method of delivery
1.5.1 SILVER C RX
The SILVER C RX 120 is normally supplied in five separate sections: Two fan sections, two filter sections and one heat exchanger section.
The heat exchanger section can also be supplied split into two casing sections and rotor, in which case the rotor is supplied tilted in a transport cradle (transport height = 2,930 mm, minimum transport width = 2,350 mm). See Section 1.7 for installation particulars.
For other dimensions and weights, see Section 2.1.
Heat exchanger section supplied as a separate unit
3440
1070
1.3.1 Document pocket
Secure the document pocket to the exterior of the air handling unit or another appropriate place.
1.4 Arrangement
The air handling unit must be mounted horizontally on a flat and firm supporting surface and this surface must be constructed in a way enabling it to support the weight of the unit.
When installing the air handling unit and connecting pipe­work and electric cables, make sure that adequate free space is provided for opening the inspection doors and covers and withdrawing functional sections, such as filter cassettes and fan assemblies, clear of the unit casing.
Inspection space required
A clear space of 1,000 mm should be provided in front of the unit for opening the inspection doors.
Heat exchanger section, sup­plied split into two casing sec­tions and rotor
Rotor, Ø 3150
2930
1070
1868
1170 2350
1861
Transport cradle
1.5.2 SILVER C CX
The SILVER C CX 120 is supplied in six separate sections: Two fan sections, two filter sections and two coil heat exchanger sections.
For dimensions and weights, see Section 2.2.
We reserve the right to alter specifications.
www.swegon.com 3
1.6 Lifting
1.6.1 With a fork-lift truck
GB.SILVERF120.181005
NOTE! High centre of gravity!
1.6.2 With a crane
1.6.2.1 Complete units
Rotary heat exchanger (SILVER C RX only).
L
L
NOTE! Make sure that forks of the fork-lift truck are sufficiently long!
Other sections
L
L
NOTE! Make sure that forks of the fork-lift truck are sufficiently long!
NOTE! A line spreader must be used!
NOTE! High centre of gravity!
Rotary heat exchanger (SILVER C RX only).
4 www.swegon.com
NOTE! A line spreader must be used!
Other sections
We reserve the right to alter specifications.
GB.SILVERF120.181005
1.6.2.2 Heat exchanger section, supplied split into two casing sections and rotor (SILVER C RX only)
NOTE! A line spreader must be used!
Lower casing section
Upper casing section
We reserve the right to alter specifications.
www.swegon.com 5
Rotor
GB.SILVERF120.181005
Remove the wooden stud
Remove the anchor plate
Guard plate
6 www.swegon.com
NOTE! Carefully raise the rotor so that it will not be damaged! Make sure that the lifting device rests against the protecting plate at the top edge.
We reserve the right to alter specifications.
1.7 To assemble the heat exchanger unit section, if required (SILVER C RX only)
If the heat exchanger unit section is supplied in parts, they must be jointed together. This can be done in two ways: Alternative 1 is appropriate for use if there is sufficient free space upward since this alternative is simpler. If sufficient space is not available, Alternative 2 should be used.
If the heat exchanger unit section is supplied as one unit, go on to Section 1.8.
1.7.1 Alternative 1
GB.SILVERF120.181005
Remove the upper shaft bracket and the sealing plate (2x)
Shaft mounting brackets
We reserve the right to alter specifications.
Lower casing section
www.swegon.com 7
Lift the rotor into the lower casing section (see Section 1.6).
NOTE! IMPORTANT! The smooth side of the rotor hub (with­out holes) should face the pressing roller! Be careful not to damage the rotor!
Hub side
GB.SILVERF120.181005
Pressing roller
8 www.swegon.com
Mount the upper shaft bracket and the sealing plate (2x)