Swegon TBIQ-3-1, IQlogic+, pC05+ Function Manual

GB.BlueBox.180415
Swegon reserves the right to alter specifications.
www.swegon.com 1
GOLD version E/F, Function Guide, SMART Link/AQUA Link
1. General
For electrical wiring and functionality at connection with Nestor, see separate documentation.
1.1 Energy-saving functions
1.1.1 Control of the supply air temperature/supply flow temperature
By comparing the supply air temperature downstream of the fan with the supply flow temperature to the coil, the equipment makes sure that the valve for the coil opens only if the water has a temperature that conveys energy to the air.
This means that if there is a heat load and the water tem­perature is lower than the supply air temperature, which can occur during defrosting cycles, the valve is not allowed to open. If there is a cooling load, the reverse applies.
1.1.2 Optimisation function
A cooling unit/heat pump will be more effective if the dif­ference between the outdoor temperature and the water temperature is as small as possible. This reduces energy consumption.
The supply air energy to a water coil is controlled by a valve. Optimisation of the valve position so that it always strives to be fully open, and instead control the water temperature, saves energy.
1.1.3 AQUA Link
The AQUA Link provides both air handling units and comfort modules with cooling power. Even here energy savings are obtainable by allowing the need to control the water temperature.
Depending on whatever the specific need is (dehumidifi­cation, cooling of the supply air, cooling of the room via comfort modules), the temperature of the chilled water can be varied and the control system ensures that the chiller will not produce chilled water that is colder than necessary.
1.1 Installation
The installation work is fast and simple compared with that of other systems. It requires only hydraulic and elec­tric connection between the GOLD unit, chiller/heat pump and possible AQUA Link.
All the necessary control functions are ready to activate. One supplier of all the equipment. The IQlogic
+
module TBIQ-3-1 is included in the AQUA
Link equipment cubical.
2. Material Specification
Air handling unit GOLD RX/PX/CX/SD
Cable adapter TBLZ-1-64
IQlogic
+
module,
extra regulation sequence (SMART link) TBIQ-3-2
Chiller/heat pump manufactured by Swegon that uses glycolic water as cooling or heating media (not evapora­tive media).
Other equipment to the extent required: Set of valves, air heater, air cooler, dual-purpose coil, AQUA Link.
GB.BlueBox.180415
Swegon reserves the right to alter specifications.
2 www.swegon.com
BT1
BT50BT40
MF2
BT30
3. Operation
See below and the following pages for diagrammatic descriptions of the function.
3.1 Control of cooling/heating to the GOLD via Swegon chiller/heat pump
3.1.1 Chiller
The cooling capacity of the supply air is controlled via an IQlogic+ module (extra regulation sequence function, see
separate instructions for the TBIQ IQlogic+ module) preset for cooling (0-10 V). The function can be activated in the hand-held terminal of the GOLD air handling unit (see the Operation and Maintenance Instructions for the GOLD).
Communication with the chiller can be activated under Functions in the hand-held micro terminal of the GOLD unit. See Section 5.
If temperature sensor BT1 calls for cooling, the function transmits a refrigerant setpoint (12°C*) to the chiller via Modbus.
If the temperature by temperature sensor BT50 is lower than the temperature by temperature sensor BT30**, the function allows valve MF2 to regulate the flow.
If the temperature by temperature sensor BT50 is higher than the temperature by temperature sensor BT30**, the function does not allow valve MF2 to regulate the flow (forces it to close).
Optimisation function active:
To ensure the best functionality when the optimisation function is activated, the value for cooling diff. (2 K*) should be set to the same value as that set in the chiller, see Section 5.
If the temperature by temperature sensor BT40 (reference water) is within 2K* from the refrigerant temperature setpoint and if it has been so during a continuous period of more than 60 seconds* the optimisation function is allowed.
If the optimisation function is allowed and valve MF2 is fully open (100%*) the controller decreases the refriger­ant temperature setpoint at a rate of 0.3K/minute*.
If the optimisation function is allowed and valve MF2 is open less than 80%*, the controller increases the refriger­ant temperature setpoint at a rate of 0.6K/minute*.
* Factory setting. The value can be changed. ** Estimated temperature in the GOLD RX.
Modbus
0-10 V
GOLD
Supply
air
Swegon chiller
A pump and accumulator tank can be added and, depending on the size of the system, can be located inside or outside the chiller.
GB.BlueBox.180415
Swegon reserves the right to alter specifications.
www.swegon.com 3
BT1
BT50
MF1
BT30
BT40
Modbus
0-10 V
GOLD
Supply
air
Swegon heat pump
A pump and accumulator tank can be added and, depending on the size of the system, can be located inside or outside the heat pump.
3.1.2 Heat pump
The heating capacity of the supply air is controlled via an IQlogic+ module (extra regulation sequence function, see separate instructions for the TBIQ IQlogic+ module) preset for heating (0-10 V). The function can be activated in the hand-held terminal of the GOLD air handling unit (see the Operation and Maintenance Instructions for the GOLD).
Communication with the heat pump can be activated under Functions in the hand-held micro terminal of the GOLD unit. See Section 5.
If temperature sensor BT1 calls for heating, the function transmits a start signal and heating medium setpoint (40°C*) to the heat pump via Modbus.
If the temperature by temperature sensor BT50 is higher than the temperature by temperature sensor BT30**, the function allows valve MF1 to regulate the flow.
If the temperature by temperature sensor BT50 is lower than the temperature by temperature sensor BT30**, the function does not allow valve MF1 to regulate the flow (forces it to close).
Optimisation function active:
To ensure the best functionality when the optimisation function is activated, the heating diff. value (3 K*) should be set to the same value as that set in the heat pump. See Section 5.
If the temperature by temperature sensor BT40 (reference water) is within 3K* from the heating medium tempera­ture setpoint and if it has been so during a continuous period of more than 60 seconds* the optimisation func­tion is allowed.
If the optimisation function is allowed and valve MF1 is fully open (100%*) the controller increases the heating medium temperature setpoint at a rate of 0.3K/minute*.
If the optimisation function is allowed and valve MF1 is open less than 80%*, the controller decreases the refrig­erant temperature setpoint at a rate of 0.6K/minute*.
* Factory setting. The value can be changed. ** Estimated temperature in the GOLD RX.
GB.BlueBox.180415
Swegon reserves the right to alter specifications.
4 www.swegon.com
BT1
BT50
BT40
MF1
BT30
3.1.3 Reversible chiller/heat pump
The heating or cooling capacity of the supply air is con­trolled via an IQlogic+ module (extra regulation sequence function, see separate instructions for the TBIQ IQlogic+ module) preset for heating and cooling (0-10 V). The function can be activated in the hand-held terminal of the GOLD air handling unit (see the Operation and Mainte­nance Instructions for the GOLD).
Communication with the reversible chiller/heat pump can be activated under Functions in the hand-held micro terminal of the GOLD unit. See Section 5.
Cooling
If temperature sensor BT1 calls for cooling, the function transmits a start signal for cooling and a refrigerant set­point (12°C*) to the reversible chiller/heat pump via Mod­bus.
If the temperature by temperature sensor BT50 is lower than the temperature by temperature sensor BT30**, the function allows valve MF1 to regulate the flow.
If the temperature by temperature sensor BT50 is higher than the temperature by temperature sensor BT30**, the function does not allow valve MF1 to regulate the flow (forces it to close).
Optimisation function active:
To ensure the best functionality when the optimisation function is activated, the value for cooling diff. (2 K*) should be set to the same value as that set in the reversible chiller/heat pump. See Section 5.
If the temperature by temperature sensor BT40 (reference water) is within 2K* from the refrigerant temperature setpoint and if it has been so during a continuous period of more than 60 seconds* the optimisation function is allowed.
If the optimisation function is allowed and valve MF1 is fully open (100%*) the controller decreases the refriger­ant temperature setpoint at a rate of 0.3K/minute*.
If the optimisation function is allowed and valve MF1 is open less than 80%*, the controller increases the refriger­ant temperature setpoint at a rate of 0.6K/minute*.
Heating
If temperature sensor BT1 calls for cooling, the function transmits a start signal for heating and a heating medium setpoint (40°C*) to the reversible chiller/heat pump via Modbus.
If the temperature by temperature sensor BT50 is higher than the temperature by temperature sensor BT30**, the function allows valve MF1 to regulate the flow.
If the temperature by temperature sensor BT50 is lower than the temperature by temperature sensor BT30**, the function does not allow valve MF1 to regulate the flow (forces it to close).
Modbus
0-10 V
GOLD
Supply
air
Swegon chiller/heat pump
A pump and accumulator tank can be added and, depending on the size of the system, can be located inside or outside the chiller/heat pump. For more information, see the Swegon product brochure.
Optimisation function active:
To ensure the best functionality when the optimisation function is activated, the heating diff. value (3 K*) should be set to the same value as that set in the reversible chiller/heat pump. See Section 5.
If the temperature by temperature sensor BT40 (reference water) is within 3K* from the heating medium tempera­ture setpoint and if it has been so during a continuous period of more than 60 seconds* the optimisation func­tion is allowed.
If the optimisation function is allowed and valve MF1 is fully open (100%*) the controller increases the heating medium temperature setpoint at a rate of 0.3K/minute*.
If the optimisation function is allowed and valve MF1 is open less than 80%*, the controller decreases the heating medium temperature setpoint at a rate of 0.6K/minute*.
* Factory setting. The value can be changed. ** Estimated temperature in the GOLD RX.
GB.BlueBox.180415
Swegon reserves the right to alter specifications.
www.swegon.com 5
BT1
BT50BT40
MF2
MF1
BT30
3.1.4 Chiller and external heating
The cooling capacity of the supply air is controlled via an IQlogic+ module (extra regulation sequence function, see separate instructions for the TBIQ IQlogic+ module) preset for cooling (0-10 V). The function can be activated in the hand-held terminal of the GOLD air handling unit (see the Operation and Maintenance Instructions for the GOLD).
The function controls external heating (waterborne or electric) via the GOLD unit’s ordinary output for heat­ing (0-10 V). The air heater for heated water has a frost monitor function and is automatically activated when it is connected.
Communication with the chiller can be activated under Functions in the hand-held micro terminal of the GOLD unit. See Section 5.
If temperature sensor BT1 calls for cooling, the function transmits a refrigerant setpoint (12°C*) to the chiller via Modbus.
If the temperature by temperature sensor BT50 is lower than the temperature by temperature sensor BT30**, the function allows valve MF2 to regulate the flow.
If the temperature by temperature sensor BT50 is higher than the temperature by temperature sensor BT30**, the function does not allow valve MF2 to regulate the flow (forces it to close).
If dehumification is active, the function allows valve MF1 to regulate the flow.
Optimisation function active:
To ensure the best functionality when the optimisation function is activated, the value for cooling diff. (2 K*) should be set to the same value as that set in the chiller, see Section 5.
If the temperature by temperature sensor BT40 (reference water) is within 2K* from the refrigerant temperature setpoint and if it has been so during a continuous period of more than 60 seconds* the optimisation function is allowed.
If the optimisation function is allowed and valve MF2 is fully open (100%*) the controller decreases the refriger­ant temperature setpoint at a rate of 0.3K/minute*.
If the optimisation function is allowed and valve MF2 is open less than 80%*, the controller increases the refriger­ant temperature setpoint at a rate of 0.6K/minute*.
* Factory setting. The value can be changed. ** Estimated temperature in the GOLD RX.
Modbus
0-10 V
The external air heater can be of water-coil or electric type.
GOLD
Supply
air
Swegon chiller
A pump and accumulator tank can be added and, depending on the size of the system, can be located inside or outside the chiller.
Loading...
+ 10 hidden pages