Swegon COOL DX 008, COOL DX Series, COOL DX 012, COOL DX 040, COOL DX 030 Installation And Maintenance Instructions Manual

...
Chiller COOL DX version G Installation and Maintenance Instructions SILVER C, size 008-080
COOL DX
GB.COOLDX.SI.G.190603
The document was originally written in Swedish.
GB.COOLDX.SI.G.190603
1. Overview 3
1.1. General 3
1.2 Basic function diagram 4
2 Safety Instructions 5
2.1 Safety Isolating Switch/Main Switch 5
2.2 Risks 5
2.3 Electrical equipment 5
2.4 Authorisation 5
2.5 Decals 5
3 Installation 6
3.1 Unloading/site transport 6
3.1.1 Handling with truck 6
3.1.2 Handling with crane 6
3.2 Arrangement 6
3.3 Basic Installation Diagram COOL DX 7
3.3.1 Height adaptation to SILVER C/water trap 8
3.3.2 Connection to SILVER C air handling unit, COOL DX, sizes 008-012 9
3.3.3 Connection to SILVER C air handling unit, COOL DX, sizes 020-040 10
3.3.4 Connection to SILVER C air handling unit, COOL DX, sizes 060-080 11
3.3.5 Stand-alone COOL DX 11
3.3.6 Supply air filter 11
6 Alarms 14
7 Maintenance 15
7.1 Cleaning 15
7.2 Handling of refrigerant 15
7.3 Leakage tracing interval/Obligation to report 15
7.4 Service 15
8 Trouble shooting and leakage tracing 16
8.1 Troubleshooting Schedule 16
8.2 Leakage Tracing 16
9 Dimensions 17
10 General technical data 18
11 Internal wiring diagram 19
12 Commissioning Record 23
4 Power connection 12
4.1 Supply connection 12
4.2 Connection of signal, 0 – 10 V 12
5 Commissioning 13
5.1 Preparations 13
5.1.1 Before initial start up 13
5.1.2 Control functions 13
5.1.3 Pressure sensor 13
5.1.4 Phase sequence monitor 14
5.1.5 Measure whether the phase-sequence is wrong 14
2 www.swegon.com
We reserve the right to alter specifications.
1. OVERVIEW
1.1. General
GB.COOLDX.SI.G.190603
COOL DX Chiller
Chiller COOL DX is a complete chiller for comfort cooling in the air handling system. All the components refrigera­tion engineering-wise and electrically pre-wired and col­lected inside a common casing. The outer skin is made of galvanized sheet steel, pre-painted in Swegon’s grey metallic colour (closest comparable: RAL, 9007). The inner skin material is aluminium-zinc coated sheet steel. Envi­ronmental class C4. Panel thickness of 52 mm with inter­vening insulation consisting of mineral wool.
The cooling coil and condenser are fabricated of copper tubing and profiled aluminium fins; the casing is made of galvanized sheet steel.
The chillers are test run prior to delivery.
The COOL DX is available in 19 capacity variants spread on nine physical sizes, designed for use with the size 008 ­080 SILVER C air handling units.
Compressors
The compressor in the COOL DXchiller is of scroll compres­sor type and/or rotary compressors.
Refrigerant
The COOL DX has double refrigerant circuits, which are separate from each other. Type R410A refrigerant is used. The refrigerant circuits are charged with refrigerant on delivery. At present, this refrigerant has no known influ­ence on the ozone layer and no known future restrictions are anticipated.
Refrigerant volume
See section 10. General technical data.
Installation check/Obligation to report/ Leakage tracing interval
Must be carried out according to the F-Gas Regulation EU/517/2014 and associated local legislation.
Quality System to ISO 9001 and Environmental Management System to ISO 14001
Swegon AB works to a certified quality system that con­forms to ISO 9001 standard and a certified Environmental Management System that conforms to ISO 14001.
Completely direct-acting system
The COOL DX has a completely direct-acting system. It has an evaporation coil for direct-evaporating refrigerant on the cold side and a condenser coil on the hot side.
We reserve the right to alter specifications.
www.swegon.com 3
GB.COOLDX.SI.G.190603
1.2 Basic function diagram
COND
VSH1
FD1FD2
IPL1IPL2
VET1VET2
EVAP
COND Condenser
VSH1 Overpressure protection
VSH2 Overpressure protection
B1-1 High pressure sensor
B2-1 Low pressure switch
B1-2 High pressure sensor
B2-2 Low pressure switch
BP1-2 High pressure switch, alarming
BP2-2 High pressure switch, alarming
M1 Compressor
M2 Compressor
M3 Compressor (size 80, cap. var. 3)
EVAP Evaporator
VET1 Expansion valve with thermostat
VET2 Expansion valve with thermostat
IPL1 Sight glass, cooling medium circuit 1
IPL2 Sight glass, cooling medium circuit 2
FD1 Filter dryer
FD2 Filter dryer
HP
HP
B1-1
M1 M2
LP
B2-1
VSH2
HP
HP
M3
LP
BP2-2BP1-2
B1-2
B2-2
The gaseous refrigerant is compressed by cooling com­pressors M1 and M2 and from there flows to condenser COND, where it is cooled by the extract air and is con­densed to liquid form.
The gaseous refrigerant flows through expansion valve VET1 and VET2, where the pressure and the temperature decrease.
From the expansion valves, the refrigerant advances to evaporator EVAP, where the refrigerant evaporates and cools down the outdoor air.
The evaporated refrigerant flows from evaporator EVAP further to the suction side by the compressors to once again be compressed.
Regulation
The cooling capacity is regulated in three binary steps by having one or two compressors in operation.
COOL DX is controlled via a signal, 0 – 10 V.
Step 1: When cooling is needed, Compressor M1 is start­ed.
Step 2: If more cooling is needed, Compressor M2 starts and at the same time Compressor M1 stops. An adjust­able time delay (a step duration of 250 seconds) ensures that Compressor M2 will not start until Compressor M1 is operating at full capacity.
Step 3: If even more cooling is needed, Compressor M1 is restarted and is run at the same time as Compressor M2. This third cooling step is also delayed by a preset time de­lay setting. In addition, the restarting time (300 seconds) for Compressor M1 shall have expired.
If less cooling is needed and the compressors are subse­quently switched out step-by-step, there will be no delay between compressors. The restarting time (300 seconds) for Compressor M1 shall have expired to enable it to start again in Step 1 after it has been operated in Step 3.
If any compressor is stopped, the restarting time must expire before a restart can take place. The restart time is calculated from one start to the next start.
If the pressure in the cooling circuit becomes too low, or if the pressure in the condenser circuit becomes too high, the compressor is stopped.
When the restart time has expired, the compressors will try to restart.
Function
There are two refrigerant circuits in the chiller. The circuits are separated from one another.
Each circuit is equipped with its own finned condenser, finned evaporator and compressor.
The two compressors are of different capacity, which makes it possible to regulate the capacity in 3 steps.
4 www.swegon.com
If the pressure increases more, high pressure switches BP1­2 and BP2-2 will trip and stop the chiller.
Alarms are shown on the hand-held terminal, see separate instructions for IC208CX control.
Pressure switches BP1-2 and BP2-2 can be manually reset by pressing a button under each protective sock on the upper side of the pressure switch. This can be done with­out removing the protective sock.
We reserve the right to alter specifications.
GB.COOLDX.SI.G.190603
2 SAFETY INSTRUCTIONS
2.1 Safety Isolating Switch/Main Switch
The safety isolating switch is positioned on the inspection side of the chiller.
The safety switch should not be used for start or stop of the chiller.
Ensure that COOL DX is shut-off by turning off the chiller via the display.
When this has been carried out, the current can be iso­lated with the safety switch. The safety switch must be switched off in order to make it possible to open the inspection door.
Important:
Always switch off the safety isolating switch before ser­vicing the unit if not otherwise specified in the pertinent instructions.
2.3 Electrical equipment
The machine’s electrical equipment is housed in a separate cabinet inside one of the inspection doors.
2.4 Authorisation
Only authorized electricians shall be permitted to install electrical wiring in the unit.
Only an accredited refrigeration company shall be permit­ted to modify or repair the refrigeration circuit.
Other service work in the unit should only be performed by service personnel trained by Swegon.
2.5 Decals
The type number mark with type designation, serial num­ber, refrigerant volume and more is affixed on the chiller’s door.
Type designation: COOLDX-aa-F-c-d-e-f-g
SILVER C size
2.2 Risks
Warning
Before carrying out any work, make sure that the power supply to the air handling unit has been switched off.
Warning
Under no circumstances may the refrigerant circuit be opened by unauthorised personnel, since it contains gas under high pressure.
Risk areas with refrigerant
Risk area for refrigerant is in principal inside the entire chiller. For handling when leakage, see section 7.2.
Refrigerant used is R 410A.
Capacity variant
Warning
The unit’s inspection door must not be opened when the SILVER C air handling unit is operational. The door can open and injure personnel. (The safety switch on the COOL DX must be switched off in order to make it pos­sible to open the inspection door of the chiller.)
We reserve the right to alter specifications.
www.swegon.com 5
GB.COOLDX.SI.G.190603
3 INSTALLATION
3.1 Unloading/site transport
Important:
All transport should take place with the chiller in hori­zontal position.
3.1.1 Handling with truck
3.1.2 Handling with crane
Place two line spreaders on top of the chiller and two on the underside of the pallet or below the chiller and lift in the pallet (or the chiller if the pallet is not to be included). See the illustration.
Warning
High centre of gravity! Lift the chiller carefully.
3.2 Arrangement
Place the COOL DX at a suitable location.
Safety isolating switch/main switch must have the requi­site space to serve according to applicable electrical regu­lations.
The unit can stand with the back against the wall, but to facilitate any service of the rear compressor, a distance of about 1 metre is recommended.
6 www.swegon.com
We reserve the right to alter specifications.
3.3 Basic Installation Diagram COOL DX
Locate the COOL DX chiller against the outdoor air and exhaust air side of the SILVER C air handling unit. COOL DX can also be installed as a stand-alone unit, if you order a stand-alone COOL DX, select the variant with end con­nection panels.
The dimensions and capacity of the chiller COOL DX is matched for connection to the SILVER C air handling unit in sizes 008-080.
For a list of the capacity sizes of chillers matched to re­spective unit size,
see section 10. General technical data.
COOL DX 008
GB.COOLDX.SI.G.190603
Right-hand version Left-hand version
COOL DX 012-080
Cooling coil in lower level/SILVER C fan arrangement 1
Right-hand version
Cooling coil in upper level/SILVER C fan arrangement 2
Left-hand version
Cooling coil in upper level/SILVER C fan arrangement 1
We reserve the right to alter specifications.
Cooling coil in lower level/SILVER C fan arrangement 2
Outdoor air Supply air Extract air Exhaust air
www.swegon.com 7
3.3.1 Height adjustment to the height of the SIL­VER C/water trap
COOL DX, size 008
In combination with the SILVER C RX 08
The SILVER C air handling unit can be mounted on base beams, a stand or some other form of foundation. Base beams and stands are available as accessories.
Appropriate base beams and stands are also available as accessories for the COOL DX. The base beams/stands are matched to one another in terms of height. The stands also provide space for accommodating a possible water trap in the lower level (right-hand unit version).
In combination with the SILVER C PX 008
The air handling unit is supplied with base beams. A set of legs (accesssory) can be mounted in the base beams.
Appropriate base beams and set of legs are also available as accessories for the COOL DX. The base beams/sets of legs are matched to one another in terms of height. The sets of legs also provide space for accommodating a pos­sible water trap in the lower level (right-hand unit version).
GB.COOLDX.SI.G.190603
COOL DX, sizes 012-080
The SILVER C air handling unit and the COOL DX cooling unit are supplied with a 100 mm high base beam.
Applicable to a cooling coil in the lower level:
If a water trap (accessory) is fitted, the SILVER C air han­dling unit and the cooling unit must be raised at least 50 mm to provide space for the water trap. Adjustable sup­port feet (accessories) can be appropriately fitted to the base beams for this purpose.
8 www.swegon.com
We reserve the right to alter specifications.