Swegon COOL DX 008, COOL DX Series, COOL DX 012, COOL DX 040, COOL DX 030 Installation And Maintenance Instructions Manual

...
Page 1
Chiller COOL DX version G Installation and Maintenance Instructions SILVER C, size 008-080
COOL DX
GB.COOLDX.SI.G.190603
The document was originally written in Swedish.
Page 2
GB.COOLDX.SI.G.190603
1. Overview 3
1.1. General 3
1.2 Basic function diagram 4
2 Safety Instructions 5
2.1 Safety Isolating Switch/Main Switch 5
2.2 Risks 5
2.3 Electrical equipment 5
2.4 Authorisation 5
2.5 Decals 5
3 Installation 6
3.1 Unloading/site transport 6
3.1.1 Handling with truck 6
3.1.2 Handling with crane 6
3.2 Arrangement 6
3.3 Basic Installation Diagram COOL DX 7
3.3.1 Height adaptation to SILVER C/water trap 8
3.3.2 Connection to SILVER C air handling unit, COOL DX, sizes 008-012 9
3.3.3 Connection to SILVER C air handling unit, COOL DX, sizes 020-040 10
3.3.4 Connection to SILVER C air handling unit, COOL DX, sizes 060-080 11
3.3.5 Stand-alone COOL DX 11
3.3.6 Supply air filter 11
6 Alarms 14
7 Maintenance 15
7.1 Cleaning 15
7.2 Handling of refrigerant 15
7.3 Leakage tracing interval/Obligation to report 15
7.4 Service 15
8 Trouble shooting and leakage tracing 16
8.1 Troubleshooting Schedule 16
8.2 Leakage Tracing 16
9 Dimensions 17
10 General technical data 18
11 Internal wiring diagram 19
12 Commissioning Record 23
4 Power connection 12
4.1 Supply connection 12
4.2 Connection of signal, 0 – 10 V 12
5 Commissioning 13
5.1 Preparations 13
5.1.1 Before initial start up 13
5.1.2 Control functions 13
5.1.3 Pressure sensor 13
5.1.4 Phase sequence monitor 14
5.1.5 Measure whether the phase-sequence is wrong 14
2 www.swegon.com
We reserve the right to alter specifications.
Page 3
1. OVERVIEW
1.1. General
GB.COOLDX.SI.G.190603
COOL DX Chiller
Chiller COOL DX is a complete chiller for comfort cooling in the air handling system. All the components refrigera­tion engineering-wise and electrically pre-wired and col­lected inside a common casing. The outer skin is made of galvanized sheet steel, pre-painted in Swegon’s grey metallic colour (closest comparable: RAL, 9007). The inner skin material is aluminium-zinc coated sheet steel. Envi­ronmental class C4. Panel thickness of 52 mm with inter­vening insulation consisting of mineral wool.
The cooling coil and condenser are fabricated of copper tubing and profiled aluminium fins; the casing is made of galvanized sheet steel.
The chillers are test run prior to delivery.
The COOL DX is available in 19 capacity variants spread on nine physical sizes, designed for use with the size 008 ­080 SILVER C air handling units.
Compressors
The compressor in the COOL DXchiller is of scroll compres­sor type and/or rotary compressors.
Refrigerant
The COOL DX has double refrigerant circuits, which are separate from each other. Type R410A refrigerant is used. The refrigerant circuits are charged with refrigerant on delivery. At present, this refrigerant has no known influ­ence on the ozone layer and no known future restrictions are anticipated.
Refrigerant volume
See section 10. General technical data.
Installation check/Obligation to report/ Leakage tracing interval
Must be carried out according to the F-Gas Regulation EU/517/2014 and associated local legislation.
Quality System to ISO 9001 and Environmental Management System to ISO 14001
Swegon AB works to a certified quality system that con­forms to ISO 9001 standard and a certified Environmental Management System that conforms to ISO 14001.
Completely direct-acting system
The COOL DX has a completely direct-acting system. It has an evaporation coil for direct-evaporating refrigerant on the cold side and a condenser coil on the hot side.
We reserve the right to alter specifications.
www.swegon.com 3
Page 4
GB.COOLDX.SI.G.190603
1.2 Basic function diagram
COND
VSH1
FD1FD2
IPL1IPL2
VET1VET2
EVAP
COND Condenser
VSH1 Overpressure protection
VSH2 Overpressure protection
B1-1 High pressure sensor
B2-1 Low pressure switch
B1-2 High pressure sensor
B2-2 Low pressure switch
BP1-2 High pressure switch, alarming
BP2-2 High pressure switch, alarming
M1 Compressor
M2 Compressor
M3 Compressor (size 80, cap. var. 3)
EVAP Evaporator
VET1 Expansion valve with thermostat
VET2 Expansion valve with thermostat
IPL1 Sight glass, cooling medium circuit 1
IPL2 Sight glass, cooling medium circuit 2
FD1 Filter dryer
FD2 Filter dryer
HP
HP
B1-1
M1 M2
LP
B2-1
VSH2
HP
HP
M3
LP
BP2-2BP1-2
B1-2
B2-2
The gaseous refrigerant is compressed by cooling com­pressors M1 and M2 and from there flows to condenser COND, where it is cooled by the extract air and is con­densed to liquid form.
The gaseous refrigerant flows through expansion valve VET1 and VET2, where the pressure and the temperature decrease.
From the expansion valves, the refrigerant advances to evaporator EVAP, where the refrigerant evaporates and cools down the outdoor air.
The evaporated refrigerant flows from evaporator EVAP further to the suction side by the compressors to once again be compressed.
Regulation
The cooling capacity is regulated in three binary steps by having one or two compressors in operation.
COOL DX is controlled via a signal, 0 – 10 V.
Step 1: When cooling is needed, Compressor M1 is start­ed.
Step 2: If more cooling is needed, Compressor M2 starts and at the same time Compressor M1 stops. An adjust­able time delay (a step duration of 250 seconds) ensures that Compressor M2 will not start until Compressor M1 is operating at full capacity.
Step 3: If even more cooling is needed, Compressor M1 is restarted and is run at the same time as Compressor M2. This third cooling step is also delayed by a preset time de­lay setting. In addition, the restarting time (300 seconds) for Compressor M1 shall have expired.
If less cooling is needed and the compressors are subse­quently switched out step-by-step, there will be no delay between compressors. The restarting time (300 seconds) for Compressor M1 shall have expired to enable it to start again in Step 1 after it has been operated in Step 3.
If any compressor is stopped, the restarting time must expire before a restart can take place. The restart time is calculated from one start to the next start.
If the pressure in the cooling circuit becomes too low, or if the pressure in the condenser circuit becomes too high, the compressor is stopped.
When the restart time has expired, the compressors will try to restart.
Function
There are two refrigerant circuits in the chiller. The circuits are separated from one another.
Each circuit is equipped with its own finned condenser, finned evaporator and compressor.
The two compressors are of different capacity, which makes it possible to regulate the capacity in 3 steps.
4 www.swegon.com
If the pressure increases more, high pressure switches BP1­2 and BP2-2 will trip and stop the chiller.
Alarms are shown on the hand-held terminal, see separate instructions for IC208CX control.
Pressure switches BP1-2 and BP2-2 can be manually reset by pressing a button under each protective sock on the upper side of the pressure switch. This can be done with­out removing the protective sock.
We reserve the right to alter specifications.
Page 5
GB.COOLDX.SI.G.190603
2 SAFETY INSTRUCTIONS
2.1 Safety Isolating Switch/Main Switch
The safety isolating switch is positioned on the inspection side of the chiller.
The safety switch should not be used for start or stop of the chiller.
Ensure that COOL DX is shut-off by turning off the chiller via the display.
When this has been carried out, the current can be iso­lated with the safety switch. The safety switch must be switched off in order to make it possible to open the inspection door.
Important:
Always switch off the safety isolating switch before ser­vicing the unit if not otherwise specified in the pertinent instructions.
2.3 Electrical equipment
The machine’s electrical equipment is housed in a separate cabinet inside one of the inspection doors.
2.4 Authorisation
Only authorized electricians shall be permitted to install electrical wiring in the unit.
Only an accredited refrigeration company shall be permit­ted to modify or repair the refrigeration circuit.
Other service work in the unit should only be performed by service personnel trained by Swegon.
2.5 Decals
The type number mark with type designation, serial num­ber, refrigerant volume and more is affixed on the chiller’s door.
Type designation: COOLDX-aa-F-c-d-e-f-g
SILVER C size
2.2 Risks
Warning
Before carrying out any work, make sure that the power supply to the air handling unit has been switched off.
Warning
Under no circumstances may the refrigerant circuit be opened by unauthorised personnel, since it contains gas under high pressure.
Risk areas with refrigerant
Risk area for refrigerant is in principal inside the entire chiller. For handling when leakage, see section 7.2.
Refrigerant used is R 410A.
Capacity variant
Warning
The unit’s inspection door must not be opened when the SILVER C air handling unit is operational. The door can open and injure personnel. (The safety switch on the COOL DX must be switched off in order to make it pos­sible to open the inspection door of the chiller.)
We reserve the right to alter specifications.
www.swegon.com 5
Page 6
GB.COOLDX.SI.G.190603
3 INSTALLATION
3.1 Unloading/site transport
Important:
All transport should take place with the chiller in hori­zontal position.
3.1.1 Handling with truck
3.1.2 Handling with crane
Place two line spreaders on top of the chiller and two on the underside of the pallet or below the chiller and lift in the pallet (or the chiller if the pallet is not to be included). See the illustration.
Warning
High centre of gravity! Lift the chiller carefully.
3.2 Arrangement
Place the COOL DX at a suitable location.
Safety isolating switch/main switch must have the requi­site space to serve according to applicable electrical regu­lations.
The unit can stand with the back against the wall, but to facilitate any service of the rear compressor, a distance of about 1 metre is recommended.
6 www.swegon.com
We reserve the right to alter specifications.
Page 7
3.3 Basic Installation Diagram COOL DX
Locate the COOL DX chiller against the outdoor air and exhaust air side of the SILVER C air handling unit. COOL DX can also be installed as a stand-alone unit, if you order a stand-alone COOL DX, select the variant with end con­nection panels.
The dimensions and capacity of the chiller COOL DX is matched for connection to the SILVER C air handling unit in sizes 008-080.
For a list of the capacity sizes of chillers matched to re­spective unit size,
see section 10. General technical data.
COOL DX 008
GB.COOLDX.SI.G.190603
Right-hand version Left-hand version
COOL DX 012-080
Cooling coil in lower level/SILVER C fan arrangement 1
Right-hand version
Cooling coil in upper level/SILVER C fan arrangement 2
Left-hand version
Cooling coil in upper level/SILVER C fan arrangement 1
We reserve the right to alter specifications.
Cooling coil in lower level/SILVER C fan arrangement 2
Outdoor air Supply air Extract air Exhaust air
www.swegon.com 7
Page 8
3.3.1 Height adjustment to the height of the SIL­VER C/water trap
COOL DX, size 008
In combination with the SILVER C RX 08
The SILVER C air handling unit can be mounted on base beams, a stand or some other form of foundation. Base beams and stands are available as accessories.
Appropriate base beams and stands are also available as accessories for the COOL DX. The base beams/stands are matched to one another in terms of height. The stands also provide space for accommodating a possible water trap in the lower level (right-hand unit version).
In combination with the SILVER C PX 008
The air handling unit is supplied with base beams. A set of legs (accesssory) can be mounted in the base beams.
Appropriate base beams and set of legs are also available as accessories for the COOL DX. The base beams/sets of legs are matched to one another in terms of height. The sets of legs also provide space for accommodating a pos­sible water trap in the lower level (right-hand unit version).
GB.COOLDX.SI.G.190603
COOL DX, sizes 012-080
The SILVER C air handling unit and the COOL DX cooling unit are supplied with a 100 mm high base beam.
Applicable to a cooling coil in the lower level:
If a water trap (accessory) is fitted, the SILVER C air han­dling unit and the cooling unit must be raised at least 50 mm to provide space for the water trap. Adjustable sup­port feet (accessories) can be appropriately fitted to the base beams for this purpose.
8 www.swegon.com
We reserve the right to alter specifications.
Page 9
3.3.2 Connection to SILVER C air handling unit, COOL DX, sizes 008-012
The sealing strips are factory-fitted to the unit.
The chiller is connected directly to the air handling unit by means of the supplied bolts + pre-fitted rivets nut and 2 expansion locking devices, see the figure.
Secure the chiller to the air handling unit from inside the unit via the inspection door. It may be necessary to remove the fan assembly or filter cassettes in order to reach the expansion-type locking device.
Expansion-type locking device
GB.COOLDX.SI.G.190603
COOL DX Chiller
In this case, fastening is done with the bolts and pre-fitted rivet nuts.
We reserve the right to alter specifications.
www.swegon.com 9
Page 10
GB.COOLDX.SI.G.190603
3.3.3 Connection to SILVER C air handling unit, COOL DX, sizes 020-040
The sealing strips are factory-fitted to the unit.
Dock the chiller directly to the SILVER C air handling unit by means of the supplied bolts (4 bolts) + pre-fitted rivet nuts.
To secure accessories to the rear edge
Alternative 1, External installation
Illustration 1
The SILVER C air handling unit, rear
Remove the cover and insulation. Secure the chiller to the SILVER C air handling unit with the bolts supplied and pre-fitted rivet nuts. Refit the blanking plate and the insulation.
Option 1
If there is sufficient space for working from the rear of the air handling unit, the simplest way to secure the chiller at the rear edge of the SILVER C air handling unit is by exter­nally jointing it, see Illustration 1.
Secure the chiller to the front edge of the SILVER C air handling unit within the unit via the inspection cover, see Illustration 3.
Option 2
The chiller is secured to the back edge of the SILVER C air handling unit within the casing, see Illustration 2. This requires removal of the fan assembly and filter cassettes.
Secure the chiller to the front edge of the SILVER C air handling unit within the unit via the inspection cover, see Illustration 3.
COOL DX chiller, rear
Alternative 2, Internal installation
Illustration 2
To secure accessories to the front edge
Illustration 3
COOL DX Chiller
In this case, fastening is done with the bolts supplied and pre-fitted rivet nuts in predrilled holes.
COOL DX Chiller
In this case, fastening is done with the bolts supplied and pre-fitted rivet nuts in predrilled holes.
10 www.swegon.com
We reserve the right to alter specifications.
Page 11
3.3.4 Connection to SILVER C air handling unit, COOL DX, sizes 060-080
The sealing strips are factory-fitted to the unit.
Dock the chiller directly to the SILVER C air handling unit by means of the supplied bolts (4 bolts) + pre-fitted rivet nuts, see the illustration.
You may need to remove the filter cassettes.
COOL DX Chiller
In this case, fastening is done with the bolts supplied and pre-fitted rivet nuts in predrilled holes.
GB.COOLDX.SI.G.190603
3.3.5 Stand-alone COOL DX
The variant with end connection panel should be selected.
Ducts connect between the SILVER C air handling unit and COOL DX chiller, see section 3.3 Basic Installation Diagram COOL DX.
3.3.6 Supply air filter
The supply air filter in the SILVER C air handling unit should be dismantled and moved to the COOL DX unit.
We reserve the right to alter specifications.
www.swegon.com 11
Page 12
4 POWER CONNECTION
The cross sectional dimension of the power supply cable should take into consideration the ambient temperature and way the cable is run.
Important:
Installation must be carried out by a authorised electri­cian.
4.1 Power connection
Incoming power supply
Sizes 008-020, all capacity variants, and size 030, capacity variant 1:
5-core system, 400 V ±10%.
GB.COOLDX.SI.G.190603
Size 030, capacity variants 2 and 3 and size 040-080 all capacity variants:
4-core system, 400 V ±10%.
COOL DX, sizes 008-040, 060-1/2
Open the inspection door in front of the electrical equip­ment cubicle.
Open the inspection door of the electrical equipment cubicle.
Pull the incoming cable for power supply through pre­drilled hole in the cover panel of the chiller (supplied cable gland is mounted), through the space for compressors and through the cable gland of the electrical equipment cubicle. Locate the cable in a safe way. Make sure that the cable does not touch the compressors or other compo­nents, since surfaces could be hot or vibrate.
Connect the incoming power supply to the safety switch situated in the electrical equipment cubicle, see the illus­tration. The wiring terminal for incoming earth is situated right next to the safety switch.
See section 10, Technical data.
Sizes 060–3, 080
Remove the cover on the external safety switch.
Safety switch block.
Supply is con­nected here
Connect the incoming power supply to the safety switch, see the illustration. The wiring terminal for incoming earth is situated right next to the safety switch.
See section 10, Technical data.
4.2 Connection signal 0-10 V
Terminals 103 and 104 are connected to give a signal, 0-10 V. For more information, also see the electrical wiring diagram supplied separately.
12 www.swegon.com
Factory-fitted cables
We reserve the right to alter specifications.
Page 13
GB.COOLDX.SI.G.190603
5 COMMISSIONING
5.1 Preparations
5.1.1 Before initial start up
The power supply should be connected.
Terminals 105 and 106 in COOL DX electrical cabi-
net must be connected (closed switch), otherwise the cooling machine will not start despite the signal 0 – 10 V, and no compressors are activated. (These terminals can be used to connect an external thermo­stat to activate/deactivate signal 0 – 10 V for a specific temperature).
Terminals 103 and 104 shall be connected to give a
signal, 0-10 V.
A free contact for a general alarm is located on terminals 100, 101 and 102.
5.1.2 Control functions
Silver Cool DX is equipped with two controls:
IC208CX Dixell, hardware version 7.3 or 4.2
Siemens (model: 12/24 RC 6ED1052-1MD08-0BA0)
Signal 0-10 V is received by the Siemens control which converts it to digital output signals (see below) and for­wards these to control IC208CX.
Control IC208CX is set at the factory to moto-condenser mode and starts or stops the compressors via the digital output signals from the Siemens control. All control and safety functions for the refrigerant circuit are regulated by control IC208CX.
For conversion of the signal, 0 – 10 V to digital output signals, see below.
5.1.3 Pressure sensor
The chiller has two in-service pressure switches in each cooling circuit, one for low pressure and one for high pres­sure.
If the operating pressure, in any of the circuits, exceeds or drops below a limit value, the relevant compressor is switched off. See separate instructions for IC208CX con­trol for further information.
The compressor is permitted to restart when the restart delay has expired.
Pressure sensor settings:
Value Setting Factory range settings
Compressor 1
Low pressure limitation 1-10 bar 4.5 bar High pressure limitation 25-50 bar 39.0 bar High pressure alarm limit 25-50 bar 42 bar
Compressor 2
Low pressure alarm limit 1-10 bar 4.5 bar High pressure limitation 25-50 bar 39.0 bar
High pressure alarm limit 25-50 bar 42 bar
When the 0-10 V increases:
Point 1: Q1 and Q2 = OFF
Point 2: signal increases to above 1 V, then Q1= ON
and Q2 = OFF
Point 3: signal increases to above 4 V, then Q1= OFF
and Q2 = ON
Point 4: signal increases to above 7 V, then Q1= ON
and Q2 = ON
When the 0-10 V decreases:
Point 4: signal decreases to below 7 V, then Q1= OFF
and Q2 = ON
Point 3: signal decreases to below 4 V, then Q1= ON
and Q2 = OFF
Point 2: signal decreases to below 1 V, then Q1= ON
and Q2 = OFF
Point 1: Q1 stops when the signal reaches 0 V
Q1 and Q2 are the digital output signals that are sent to control IC208CX to activate compressor 1 and 2.
Q1= compressor with lower cooling capacity Q2 = compressor with higher cooling capacity For more information about control and safety functions,
see separate instructions for IC208CX control.
We reserve the right to alter specifications.
www.swegon.com 13
Page 14
GB.COOLDX.SI.G.190603
5.1.4 Phase sequence monitor
The COOL DX unit is equipped with phase sequence guard for compressors (not size 008 capacity variant 1).
The phase sequence monitor is installed in the electrical cabinet.
Phase sequence monitor
The phase sequence is correct when LED 1 is lit. The voltage is connected when LED 2 is lit.
PSC
DPA51 3-Phase monitoring relay
1
1
2
5.1.5 Measure whether the phase-sequence is wrong
6 ALARMS
For an alarm description, see the separate instructions for IC208CX control.
Warning
May only be performed by authorised or trained service personnel.
Stop the COOL DX by selecting SHUT OFF in the menu SETTINGS.
Set the safety switch to position OFF on the COOL DX.
Switch the power supply to COOL DX.
Important:
Check that the incoming power supply to the COOL DX is isolated by measuring.
Transpose the two phase wires on the incoming power supply cable in order to obtain correct phase sequence (direction of rotation).
Switch on the power supply to COOL DX.
Set the safety switch to ON.
Start COOL DX as described in the section dealing with starting up, see Section 5.1.2.
14 www.swegon.com
We reserve the right to alter specifications.
Page 15
GB.COOLDX.SI.G.190603
7 MAINTENANCE
7.1 Cleaning
If needed, clean the inside cleaning of the unit by vacuum cleaning and wiping surfaces with a damp cloth. Inspections should be performed twice a year.
7.2 Handling of refrigerant
The refrigerant used is R 410A.
The refrigerant circuit is completely charged when the unit is delivered.
Warning
Under no circumstances may the refrigerant circuit be opened by unauthorised personnel, since it contains gas under high pressure. Only an accredited refrigera­tion company shall be permitted to modify or repair the refrigeration circuit.
The COOL DX is equipped with a safety valve to prevent excessively high pressure in the system caused by e.g. a fire.
Important:
Contact Swegon Service in the event of leakage of refrigerant.
Warning
Important:
Filling of refrigerant must be performed in accordance with the recommendations of the refrigerant manufac­turer.
Avoid direct skin contact with refrigerant and lubricant.
Use tightly sitting protective glasses, protective gloves and covering work clothes.
Arrange ventilation/point extraction.
In the event of eye contact
rinse the eyes using an eye-wash shower (or with luke­warm water) for 20 minutes. seek a doctor.
In the event of contact with skin
carefully wash with soap and lukewarm water.
In the event of frostbite
seek a doctor.
7.3 Leakage tracing interval/ Obligation to report
Must be carried out according to the F-Gas Regulation EU/517/2014 and associated local legislation.
7.4 Service
Only service personnel trained by Swegon should be per­mitted to modify the chiller.
If refrigerant is exposed to fire or in some other way becomes superheated in the atmosphere, poisonous gases can form.
We reserve the right to alter specifications.
www.swegon.com 15
Page 16
8 TROUBLE SHOOTING AND
LEAKAGE TRACING
8.1 Troubleshooting Schedule
Symptoms Possible cause Action
Compressor is not operating The voltage has been isolated.
Incorrect phase sequence. The compressor safety circuit has been broken. Defective compressor.
Too low cooling capacity The voltage has been isolated.
Incorrect phase sequence. No air flow or too low air flow across the evaporator. Thermostat/control equipment incorrectly set or defec­tive.
The compressor switches off because the low pressure sensor has measured an excessively low value.
The compressor switches off because the high pressure sensor has measured an excessively high value.
Significant freezing on the evaporator.
Inadequate refrigerant. No air flow or too low air flow across the evaporator. The expansion valve is defective. The low pressure switch is defective.
No air flow or too low air flow across the condenser. Excessively high exhaust air temperature. The high pressure sensor is defective.
The expansion valve is defective or incorrectly set. No air flow or too low air flow across the evaporator.
Check the operating/safety switch. Check the condi­tion of the fuses. Check and change the phase sequence. Check, reset if needed. Replace the compressor.
Check the operating/safety switch. Check the condi­tion of the fuses. Check and change the phase sequence. Check the air flow. Adjust the setting or replace faulty components.
The cooling system is leaking. Tighten the leak and charge with refrigerant. Check the air flow. Check, replace. Check, replace.
Check the air flow. Check the exhaust air temperature. Check, replace.
Check. Replace or adjust setting. Check the air flow.
GB.COOLDX.SI.G.190603
8.2 Leakage Tracing
Leakage tracing should be carried out at least once per year as a precaution. The leakage tracing inspection must be documented.
If the cooling system is leaking, this will become apparent firstly by impaired cooling performance, or if the leakage is substantial, when the chiller does not operate at all.
If you suspect that the cooling system is leaking refriger­ant, check the level of refrigerant in the sight glass located on the liquid line of the chiller.
If you see continuous and a substantial amount of bub­bling in the sight glass and the chiller operates at appreci­ably lower capacity than normal, the system is probably leaking. One or several bubbles appearing when the chiller is started up, operation at reduced capacity or normal operation need not necessarily indicate a refrigerant defi­ciency.
If it is bubbling in the sight glass and the chiller operates at appreciably lower capacity, call for qualified service help.
NOTE! Maintenance work in the refrigerant system is per­mitted to be carried out only by an accredited inspectorate (a company with requisite authorisation).
16 www.swegon.com
We reserve the right to alter specifications.
Page 17
9 DIMENSIONS
5050
16
K
1)
1)
16
1)
M
1)
5050 K
454521 K
1)
M
1)
COOL DX 008
GB.COOLDX.SI.G.190603
Base beams are accessories.
1)
End connection panel, optional.
COOL DX 012
M
1)
End connection panel, optional.
Size L B H K M Duct connection
008 900 995 1085 749 709 Ø 400
2)
For the locations of the duct connections, see the corresponding
SILVER C air handling unit
Size L B H K M Duct connection
012 900 1199 1395 953 709 Ø 500
2)
For the locations of the duct connections, see the corresponding
SILVER C air handling unit
2)
2)
COOL DX 020, 030, 040, 060, 080
Size L B H K M Duct connection
020 030 040 060 080
2)
For the locations of the duct connections, see the corresponding
900
900 1100 1100 1100
1400 1600 1990 2318 2637
1551 1811 2159 2288 2640
1154 1354 1744 2072 2395
709 709 884 884 884
1000 x 400 1200 x 500 1400 x 600 1600 x 800
1800 x 1000
SILVER C air handling unit
1)
End connection panel, optional.
2)
We reserve the right to alter specifications.
www.swegon.com 17
Page 18
10 GENERAL TECHNICAL DATA
Cooling system COOL DX
GB.COOLDX.SI.G.190603
Refrigerant
(kg)
Nom. COOL DX Size
008 1 0.55 0.22 9.8 2.39 1,20 1.30 3-phase+N, 400 V ±10%, 16 A 194 8
012 1 0.85 0.35 15.4 3.95 1,50 1.70 3-phase+N, 400 V ±10%, 20 A 260 10
020 1 1.1 0.45 15.4 4.06 1,20 1,50 3-phase+N, 400 V ±10%, 25 A 243 11
030 1 1.8 0.7 25,0 6.33 1,80 2.00 3-phase+N, 400 V ±10%, 32 A 322 17
040 1 2.9 1.1 38.6 8.40 3.30 4.00 3-phase, 400 V ±10%, 25 A 468 22
060 1
080 1
Cap.
flow
var-
(m
iant
2 0.70 0.3 13.9 4.33 1,20 1.30 3-phase+N, 400 V ±10%, 20 A 215 8
2 1.05 0.4 20.9 6.53 1,50 1.70 3-phase+N, 400 V ±10%, 25 A 287 10
2 1.3 0.5 23.3 5.73 2,50 2,80 3-phase+N, 400 V ±10%, 25 A 283 11
3 1.6 0.6 31.0 9.15 2,10 2.40 3-phase+N, 400 V ±10%, 40 A 314 11
2 2.0 0.8 35.8 9.34 3.00 3,20 3-phase, 400 V ±10%, 25 A 374 17
3 2.4 1.0 46.2 13.5 2.90 3.30 3-phase, 400 V ±10%, 40 A 414 17
2 3.1 1.3 48.4 12.3 3.30 4.50 3-phase, 400 V ±10%, 40 A 476 22
3 3.6 1,5 67.0 17.5 5.50 4.50 3-phase, 400 V ±10%, 50 A 529 22
2 3
2 3
air
3
3.9
4.1 5,0
5.2
6.0
7.0
/s)
Min
air
flow
(m
1,5
1.6
2.0
2.0
2.4
2.8
3
/s)
Nom.
cooling
1)
cap.
(kW)
56.2
66.7
97.5
67.0
96.5
134.0
Nom.
Power
required
(kW)
11.8
17.1
26.3
13.3
24.8
36.4
Circuit 1Circuit
2
4.50 5,00
6.00
6,60 6,50
9.00
5.50
5.20 7,50
7,30
9.00
11.50
Power supply
3-phase, 400 V ±10%, 40 A 3-phase, 400 V ±10%, 50 A 3-phase, 400 V ±10%, 80 A
3-phase, 400 V ±10%, 50 A 3-phase, 400 V ±10%, 80 A
3-phase, 400 V ±10%, 100 A
Weight
excl. end
conn. panel
(kg)
708 779 852
852 979
1035
Weight of each
end conn.
panel, if
required
(kg)
31 31 31
38 38 38
2)
1)
For an outdoor temperature of 26°C, 50% RH (capacity variant 1), 27°C, 50% RH (capacity variant 2) or 28°C, 50% RH (capacity variant 3), and
an extract air temperature of 26°C.
2)
The first weight applies to a small end connection panel; the second weight applies to a large end connection panel. COOL DX can be supplied
completely without end connection panels or with a maximum of 2 small and two large end connection panels depending on the variant selected.
Sizing
There are many factors that influence what size of chiller is required.
COOL DX is designed to handle very different prerequi­sites.
For correct sizing we refer to our ProUnit air handling unit selection program.
18 www.swegon.com
We reserve the right to alter specifications.
Page 19
11 INTERNAL WIRING DIAGRAM
2R
L3
11.1 COOL DX, size 08, capacity variant 1
1
5
2
-RM2
M2.2
RM2.1
-CS2
-CM2
GB.COOLDX.SI.G.190603
5
6
3
4
br
1
2
blue
/3.7
-QF3
-QF2
/3.3
/3.2
-KM2
1
2
-RM1
RM1.1
RM1.
-CS1
-CM1
5
6
3
4
bl
1
2
blue
/3.6
-KM1
/2.0
10
10
21
-KM2
10
21
-KM1
4G1,5 mm²
-W2
5
4G1,5 mm²
-W1
04
22
-X1
/3.7
03
22
-X1
/3.6
S
bl
RC
M
br
C2 R2 S2
-X1
C1 R1 S1
-X1
1~
blue
S
br
RC
bl
blue
-PE
-M2
M
-M1
-PE:2
1~
-PE
-PE:1
/2.0
00
00
-X1
00
-R1 -R2
-X1
/2.31/2.3
0
-QF01
7
-QF1
grey
black
brown
blue
-Q
N
L2
L1
3
230V
2
-TC1
24V 230V
LINIE KUNDENS. GESCHUEZT LIGNE PROTEGEE PAR LE CLIENT LINE PROTECTION BY CUSTOMER LINEA PROTETTA A CURA DEL CLIENTE
0
4
-PE:3
We reserve the right to alter specifications.
10
1
-QF02
Cx = Condenser
QFx = Fuse
KMx = Contactor
Q = Load separator
Rx = Crankcase heater
www.swegon.com 19
Page 20
GB.COOLDX.SI.G.190603
L3
11.2 The COOL DX size 08, capacity variants 2, size 12 and 20, all capacity variants and size 30, capacity variant 1
/3.332/3.3
L3
-L3:
L2
-L2:
L1
L1:
-PSC
brown
grey
black
/3.3
13
14
5
6
I>
3
4
I>
1
2
I>
grey
black
brown
5
6
3
4
1
2
/3.7
-KM2
-QM2
1
2
-RM1
RM1.2
RM1.1
29
14
11
WVU
grey
M
black
-W2
brown
3~
PE
-PE:2
-M2
5
grey
-CS1
-CM1
5
6
3
4
black
1
2
blueblue
/3.6
-QF2
/3.2
-KM1
/2.0
10
10
21
-KM2
10
21
-KM1
C1 R1 S1
-X1
04
22
-X1
/3.7
03
22
-X1
/3.6
S
black
RC
M
brown
1~
-W1
-PE
-M1
-PE:1
/2.0
/2.31/2.3
00
0
00
-X1
00
-R1 -R2
-X1
-QF01
7
-QF1
brown
black
blue
-Q
N
L2
L1
3
230V
2
-TC1
24V 230V
-PE:3
0
4
10
1
-QF02
20 www.swegon.com
LINIE KUNDENS. GESCHUEZT LIGNE PROTEGEE PAR LE CLIENT LINE PROTECTION BY CUSTOMER LINEA PROTETTA A CURA DEL CLIENTE
LIMITE FORNITURA
Cx = Condenser
QFx = Fuse
KMx = Contactor
PSC = Control system for phase sequence
Qmx = Motor protection
Q = Load separator
Rx = Crankcase heater
We reserve the right to alter specifications.
Page 21
GB.COOLDX.SI.G.190603
L3
13
14
11.3 COOL DX, size 30, capacity variants 2 and 3, size 40, all capacity variants and size 60, capacity variants 1 and 2, size 80, capacity variant 1
/3.3
5
6
I>
3
4
I>
1
2
I>
-QM2
/3.2
13
14
5
6
I>
3
4
I>
1
2
I>
-QM1
grey
black
brown
grey
black
brown
5
6
3
4
1
2
-W2
/3.7
-KM2
5
6
3
4
1
2
-W1
/3.6
-KM1
/3.332/3.3
L3
-L3:
L2
-L2:
L1
L1:
29
14
11
grey
black
brown
grey
black
brown
WVU
M
3~
PE
-PE:2
-M2
WVU
M
3~
PE
-PE:1
-M1
grey
-PSC
/2.0
10
10
21
-KM2
grey
black
brown
10
21
-KM1
black
brown
5
6
I>
3
4
I>
1
2
I>
3
400-415V
2
-TC1
-Q
L2
L1
-QF1
LINIE KUNDENS. GESCHUEZT LIGNE PROTEGEE PAR LE CLIENT LINE PROTECTION BY CUSTOMER LINEA PROTETTA A CURA DEL CLIENTE
24V 230V
-PE:3
7
0
4
04
22
-X1
/3.7
03
22
-X1
/3.6
-R1 -R2
-QF01
10
-QF02
/2.0
/2.31/2.3
00
0
00
-X1
00
-X1
1
Cx = Condenser
QFx = Fuse
KMx = Contactor
PSC = Control system for phase sequence
Qmx = Motor protection
Q = Load separator
Rx = Crankcase heater
We reserve the right to alter specifications.
www.swegon.com 21
Page 22
11.4 COOL DX size 60, capacity variant 3 to size 80, capacity variant 2
L3
13
14
M2M1 /3.7
/3.3
5
5
6
I>
3
4
I>
1
2
I>
-QM2
/3.2
13
14
5
6
I>
3
4
I>
1
2
I>
grey
black
brown
grey
black
brown
6
3
4
1
2
-W2
/3.7
-KM2
5
6
3
4
1
2
-W1
/3.6
-KM1
-QM1
/3.332/3.3
L3
-L3:
L2
-L2:
L1
L1:
29
14
11
grey
black
brown
grey
black
brown
WVU
M
3~
PE
-PE:2
-M2
WVU
M
3~
PE
-PE:1
-M1
GB.COOLDX.SI.G.190603
grey
-PSC
/2.0
10
10
L
N
-X1
/2.0
00
00
-X1
/2.31/2.3
0
-FTM2
10
21
-KM2
grey
black
brown
10
21
-KM1
black
brown
5
6
I>
3
4
I>
1
2
I>
3
400-415V
2
-TC1
24V 230V
-PE:3
7
0
4
-QF1
04
22
-X1
/3.7
03
22
-X1
/3.6
-R1 -R2
-QF01
10
-QF02
00
-X1
00
-X1
1
L2
L1
22 www.swegon.com
-Q
LINIE KUNDENS. GESCHUEZT LIGNE PROTEGEE PAR LE CLIENT LINE PROTECTION BY CUSTOMER LINEA PROTETTA A CURA DEL CLIENTE
Cx = Condenser
QFx = Fuse
KMx = Contactor
PSC = Control system for phase sequence
Qmx = Motor protection
Q = Load separator
Rx = Crankcase heater
We reserve the right to alter specifications.
Page 23
12 Commissioning Record
Company
Our reference
Client Date SO No.
Plant Project/Air handling unit Subject no:
Plant address Type/size
GB.COOLDX.SI.G.190603
Installation/connections
Inspection measure
Installation according to instructions
Condensate drain correctly connected, water trap filled with water
The supply air filter in the SILVER C air handling unit has been moved
to the COOL DX unit.
Electrical connections installed according to instructions
Control cable from COOL DX connected according to instructions
Appr./Exec.
Remarks
We reserve the right to alter specifications.
www.swegon.com 23
Page 24
GB.COOLDX.SI.G.190603
Checks COOL DX, size Factory-preset value Checked value
Safety switch, Compressor 1 08-1 D10
Safety switch, compressor 2 D13
Safety switch, Compressor 1
08-2 D10
Protective motor switch, Compr. 2 8.5 A
12-1 D10
8.5 A
12-2 D16
14.4 A
20-1 D10
13.0 A
20-2 D16
14.4 A
20-3 D16
18.0 A
30-1 D16
14.4 A
Protective motor switch, Compres­sor 1
Protective motor switch, compres­sor 2
30-2 13.0 A
18.0 A
30-3 14.4 A
21.0 A
40-1 13.0 A
18.0 A
40-2 14.4 A
21.0 A
40-3 18.0 A
27.0 A
60-1 14.4 A
21.0 A
60-2 18.0 A
27.0 A
60-3 21.0 A
45.0 A
80-1 14.4 A
27.0 A
80-2 21.0 A
45.0 A
80-3 27.0 A
33.0 A
Protective motor switch, Compr. 3 33.0 A
24 www.swegon.com
We reserve the right to alter specifications.
Loading...