Chiller COOL DX version G
Installation and Maintenance Instructions
SILVER C, size 008-080
COOL DX
GB.COOLDX.SI.G.190603
The document was originally written in Swedish.
CONTENTS
GB.COOLDX.SI.G.190603
1. Overview 3
1.1. General 3
1.2 Basic function diagram 4
2 Safety Instructions 5
2.1 Safety Isolating Switch/Main Switch 5
2.2 Risks 5
2.3 Electrical equipment 5
2.4 Authorisation 5
2.5 Decals 5
3 Installation 6
3.1 Unloading/site transport 6
3.1.1 Handling with truck 6
3.1.2 Handling with crane 6
3.2 Arrangement 6
3.3 Basic Installation Diagram COOL DX 7
3.3.1 Height adaptation to SILVER C/water trap 8
3.3.2 Connection to SILVER C air handling unit,
COOL DX, sizes 008-012 9
3.3.3 Connection to SILVER C air handling unit,
COOL DX, sizes 020-040 10
3.3.4 Connection to SILVER C air handling unit,
COOL DX, sizes 060-080 11
3.3.5 Stand-alone COOL DX 11
3.3.6 Supply air filter 11
6 Alarms 14
7 Maintenance 15
7.1 Cleaning 15
7.2 Handling of refrigerant 15
7.3 Leakage tracing interval/Obligation to report 15
7.4 Service 15
8 Trouble shooting and leakage tracing 16
8.1 Troubleshooting Schedule 16
8.2 Leakage Tracing 16
9 Dimensions 17
10 General technical data 18
11 Internal wiring diagram 19
12 Commissioning Record 23
4 Power connection 12
4.1 Supply connection 12
4.2 Connection of signal, 0 – 10 V 12
5 Commissioning 13
5.1 Preparations 13
5.1.1 Before initial start up 13
5.1.2 Control functions 13
5.1.3 Pressure sensor 13
5.1.4 Phase sequence monitor 14
5.1.5 Measure whether the phase-sequence is wrong 14
2 www.swegon.com
We reserve the right to alter specifications.
1. OVERVIEW
1.1. General
GB.COOLDX.SI.G.190603
COOL DX Chiller
Chiller COOL DX is a complete chiller for comfort cooling
in the air handling system. All the components refrigeration engineering-wise and electrically pre-wired and collected inside a common casing. The outer skin is made
of galvanized sheet steel, pre-painted in Swegon’s grey
metallic colour (closest comparable: RAL, 9007). The inner
skin material is aluminium-zinc coated sheet steel. Environmental class C4. Panel thickness of 52 mm with intervening insulation consisting of mineral wool.
The cooling coil and condenser are fabricated of copper
tubing and profiled aluminium fins; the casing is made of
galvanized sheet steel.
The chillers are test run prior to delivery.
The COOL DX is available in 19 capacity variants spread
on nine physical sizes, designed for use with the size 008 080 SILVER C air handling units.
Compressors
The compressor in the COOL DXchiller is of scroll compressor type and/or rotary compressors.
Refrigerant
The COOL DX has double refrigerant circuits, which are
separate from each other. Type R410A refrigerant is used.
The refrigerant circuits are charged with refrigerant on
delivery. At present, this refrigerant has no known influence on the ozone layer and no known future restrictions
are anticipated.
Refrigerant volume
See section 10. General technical data.
Installation check/Obligation to report/
Leakage tracing interval
Must be carried out according to the F-Gas Regulation
EU/517/2014 and associated local legislation.
Quality System to ISO 9001
and Environmental Management System to ISO
14001
Swegon AB works to a certified quality system that conforms to ISO 9001 standard and a certified Environmental
Management System that conforms to ISO 14001.
Completely direct-acting system
The COOL DX has a completely direct-acting system. It has
an evaporation coil for direct-evaporating refrigerant on
the cold side and a condenser coil on the hot side.
We reserve the right to alter specifications.
www.swegon.com 3
GB.COOLDX.SI.G.190603
1.2 Basic function diagram
COND
VSH1
FD1FD2
IPL1IPL2
VET1VET2
EVAP
COND Condenser
VSH1Overpressure protection
VSH2Overpressure protection
B1-1High pressure sensor
B2-1Low pressure switch
B1-2High pressure sensor
B2-2Low pressure switch
BP1-2High pressure switch, alarming
BP2-2High pressure switch, alarming
M1Compressor
M2Compressor
M3Compressor (size 80, cap. var. 3)
EVAPEvaporator
VET1Expansion valve with thermostat
VET2Expansion valve with thermostat
IPL1Sight glass, cooling medium circuit 1
IPL2Sight glass, cooling medium circuit 2
FD1Filter dryer
FD2Filter dryer
HP
HP
B1-1
M1M2
LP
B2-1
VSH2
HP
HP
M3
LP
BP2-2BP1-2
B1-2
B2-2
The gaseous refrigerant is compressed by cooling compressors M1 and M2 and from there flows to condenser
COND, where it is cooled by the extract air and is condensed to liquid form.
The gaseous refrigerant flows through expansion valve
VET1 and VET2, where the pressure and the temperature
decrease.
From the expansion valves, the refrigerant advances to
evaporator EVAP, where the refrigerant evaporates and
cools down the outdoor air.
The evaporated refrigerant flows from evaporator EVAP
further to the suction side by the compressors to once
again be compressed.
Regulation
The cooling capacity is regulated in three binary steps by
having one or two compressors in operation.
COOL DX is controlled via a signal, 0 – 10 V.
Step 1: When cooling is needed, Compressor M1 is started.
Step 2: If more cooling is needed, Compressor M2 starts
and at the same time Compressor M1 stops. An adjustable time delay (a step duration of 250 seconds) ensures
that Compressor M2 will not start until Compressor M1 is
operating at full capacity.
Step 3: If even more cooling is needed, Compressor M1 is
restarted and is run at the same time as Compressor M2.
This third cooling step is also delayed by a preset time delay setting. In addition, the restarting time (300 seconds)
for Compressor M1 shall have expired.
If less cooling is needed and the compressors are subsequently switched out step-by-step, there will be no delay
between compressors. The restarting time (300 seconds)
for Compressor M1 shall have expired to enable it to start
again in Step 1 after it has been operated in Step 3.
If any compressor is stopped, the restarting time must
expire before a restart can take place. The restart time is
calculated from one start to the next start.
If the pressure in the cooling circuit becomes too low, or
if the pressure in the condenser circuit becomes too high,
the compressor is stopped.
When the restart time has expired, the compressors will try
to restart.
Function
There are two refrigerant circuits in the chiller. The circuits
are separated from one another.
Each circuit is equipped with its own finned condenser,
finned evaporator and compressor.
The two compressors are of different capacity, which
makes it possible to regulate the capacity in 3 steps.
4 www.swegon.com
If the pressure increases more, high pressure switches BP12 and BP2-2 will trip and stop the chiller.
Alarms are shown on the hand-held terminal, see separate
instructions for IC208CX control.
Pressure switches BP1-2 and BP2-2 can be manually reset
by pressing a button under each protective sock on the
upper side of the pressure switch. This can be done without removing the protective sock.
We reserve the right to alter specifications.
GB.COOLDX.SI.G.190603
2 SAFETY INSTRUCTIONS
2.1 Safety Isolating Switch/Main Switch
The safety isolating switch is positioned on the inspection
side of the chiller.
The safety switch should not be used for start or stop of
the chiller.
Ensure that COOL DX is shut-off by turning off the chiller
via the display.
When this has been carried out, the current can be isolated with the safety switch. The safety switch must be
switched off in order to make it possible to open the
inspection door.
Important:
Always switch off the safety isolating switch before servicing the unit if not otherwise specified in the pertinent
instructions.
2.3 Electrical equipment
The machine’s electrical equipment is housed in a separate
cabinet inside one of the inspection doors.
2.4 Authorisation
Only authorized electricians shall be permitted to install
electrical wiring in the unit.
Only an accredited refrigeration company shall be permitted to modify or repair the refrigeration circuit.
Other service work in the unit should only be performed
by service personnel trained by Swegon.
2.5 Decals
The type number mark with type designation, serial number, refrigerant volume and more is affixed on the chiller’s
door.
Type designation: COOLDX-aa-F-c-d-e-f-g
SILVER C size
2.2 Risks
Warning
Before carrying out any work, make sure that the power
supply to the air handling unit has been switched off.
Warning
Under no circumstances may the refrigerant circuit be
opened by unauthorised personnel, since it contains gas
under high pressure.
Risk areas with refrigerant
Risk area for refrigerant is in principal inside the entire
chiller.
For handling when leakage, see section 7.2.
Refrigerant used is R 410A.
Capacity variant
Warning
The unit’s inspection door must not be opened when
the SILVER C air handling unit is operational. The door
can open and injure personnel. (The safety switch on the
COOL DX must be switched off in order to make it possible to open the inspection door of the chiller.)
We reserve the right to alter specifications.
www.swegon.com 5
GB.COOLDX.SI.G.190603
3 INSTALLATION
3.1 Unloading/site transport
Important:
All transport should take place with the chiller in horizontal position.
3.1.1 Handling with truck
3.1.2 Handling with crane
Place two line spreaders on top of the chiller and two on
the underside of the pallet or below the chiller and lift in
the pallet (or the chiller if the pallet is not to be included).
See the illustration.
Warning
High centre of gravity! Lift the chiller carefully.
3.2 Arrangement
Place the COOL DX at a suitable location.
Safety isolating switch/main switch must have the requisite space to serve according to applicable electrical regulations.
The unit can stand with the back against the wall, but to
facilitate any service of the rear compressor, a distance of
about 1 metre is recommended.
6 www.swegon.com
We reserve the right to alter specifications.
3.3 Basic Installation Diagram COOL DX
Locate the COOL DX chiller against the outdoor air and
exhaust air side of the SILVER C air handling unit. COOL
DX can also be installed as a stand-alone unit, if you order
a stand-alone COOL DX, select the variant with end connection panels.
The dimensions and capacity of the chiller COOL DX is
matched for connection to the SILVER C air handling unit
in sizes 008-080.
For a list of the capacity sizes of chillers matched to respective unit size,
see section 10. General technical data.
COOL DX 008
GB.COOLDX.SI.G.190603
Right-hand versionLeft-hand version
COOL DX 012-080
Cooling coil in lower level/SILVER C fan arrangement 1
Right-hand version
Cooling coil in upper level/SILVER C fan arrangement 2
Left-hand version
Cooling coil in upper level/SILVER C fan arrangement 1
We reserve the right to alter specifications.
Cooling coil in lower level/SILVER C fan arrangement 2
Outdoor air Supply air Extract air Exhaust air
www.swegon.com 7
3.3.1 Height adjustment to the height of the SILVER C/water trap
COOL DX, size 008
In combination with the SILVER C RX 08
The SILVER C air handling unit can be mounted on base
beams, a stand or some other form of foundation. Base
beams and stands are available as accessories.
Appropriate base beams and stands are also available as
accessories for the COOL DX. The base beams/stands are
matched to one another in terms of height. The stands
also provide space for accommodating a possible water
trap in the lower level (right-hand unit version).
In combination with the SILVER C PX 008
The air handling unit is supplied with base beams. A set of
legs (accesssory) can be mounted in the base beams.
Appropriate base beams and set of legs are also available
as accessories for the COOL DX. The base beams/sets of
legs are matched to one another in terms of height. The
sets of legs also provide space for accommodating a possible water trap in the lower level (right-hand unit version).
GB.COOLDX.SI.G.190603
COOL DX, sizes 012-080
The SILVER C air handling unit and the COOL DX cooling
unit are supplied with a 100 mm high base beam.
Applicable to a cooling coil in the lower level:
If a water trap (accessory) is fitted, the SILVER C air handling unit and the cooling unit must be raised at least 50
mm to provide space for the water trap. Adjustable support feet (accessories) can be appropriately fitted to the
base beams for this purpose.
8 www.swegon.com
We reserve the right to alter specifications.
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.