Swegon CASA series Installation, Operation And Maintenance Instructions

Installation, operation and maintenance instructions for design engineers, installation engineers and service personnel
PTH_a_EN–m
Swegon CASA® Regulation for
Important information
Only qualified personnel
Only qualified personnel should carry out installation, configuration and commissioning.
Important details to consider during installation
The installation point affects the measurement result. The sensor must be installed at a point where the airflow is as even as possible.
Commissioning
The pressure sensor may not be installed until all work that produces large quantities of sanding dust or other impurities has been completed.
Make sure that the ducts are clean and that there are no loose objects in them before commissioning.
NOTE! The manual’s original language is Finnish.
!
Included in the delivery:
• Pressure sensor
• Measuring tube
• Measurement tapping
• Instructions
2
PTH.191017
Swegon reserves the right to make changes.www.swegonhomesolutions.com
3.1. Installation of the sensor in the duct system
Install the pressure sensor close to the measurement point. When measuring the (positive) pressure on the supply air duct, connect the measuring tube to the tap­ping on the pressure sensor (+). When measuring the (negative) pressure on the extract air duct, connect the measuring tube to the tapping on the pressure sensor (-).
3.2. Electric and control cables
Connect the 3-wire cable from the pressure sensor to the ventilation unit’s I/O connection according to the wiring diagram.
NOTE! Make sure that the strain relief is arranged for the connections according to the electrical safety directives.
3. Installation
The constant duct pressure function on the Smart venti­lation unit attempts to regulate the fan speeds to main­tain the duct pressure at the set value. Individual setting values for the duct pressure should be determined for each operating mode (away, home, boost). The operat­ing mode can be switched as normal when the constant duct pressure function is used.
1. General Description
2. Planning
Select the position of the measurement tapping point in the duct with care, so that as far as possible it repre­sents the pressure in the entire duct system. For exam­ple, a suitable location is close to the ventilation unit, yet so the airflow is still uniform in the measurement point. The measurement is based on the pressure differ­ence, and therefore the other measurement sensor must be positioned so it represents the air that surrounds the duct, and where the air is stable.
Important
Only a qualified electrician may make the electrical connections.
!
!
4. Commissioning
The commissioning of regulation for constant air pres­sure is performed with a Smart control panel. Main
menu/Settings/(1234)/IO controls
IO controls
IO 1
IO 2
IO 3 (ext.)
IO 4 (ext.)
Pa Extract - AI
Away - DI
Emg.Stop_NO - DI
Pa Supply - AI
IO 5 (ext.)
DDC control - AI
Select connections that correspond to the IO-points Pa Supply - AI / Pa Extract - AI. Example: “Pa Supply - AI”
as a function for IO 1 and “Pa Extract - AI” as a function for IO 2.
The pressure setting values and airflows must be adjust­ed for all operating modes (Home, Away, Boost), so that the ventilation unit functions in all conditions.
NOTE! The constant duct pressure function is not activated until you have set the values for all oper­ating modes.
The control type for the ventilation unit is selected and the airflow is set from the menu Main menu/settings/ (1234)/Airflow adjustments.
Airflow adjustments
Commissioning mode
Home (exhaust)
Away (supply)
Away (exhaust)
Boost (supply)
Boost (exhaust)
Travelling (supply)
Max Smart boost (supply)
50 Pa
35 Pa
38 Pa
90 Pa
92 Pa
35 Pa
82 Pa
Control type Pa
Home (supply) 48 Pa
Select “Pa” as the control type of both ducts that are to be regulated for a constant duct pressure. If the control type is set to “Pa Supply” or “Pa Extract”, the selected duct is solely regulated for constant duct pressure and
5. Settings
Loading...
+ 2 hidden pages