Swegon ADAPT Parasol EXb Series, ADAPT Parasol EXb 690, ADAPT Parasol EXb 1290 Installation, Commissioning Maintenance

Page 1
ADAPT Parasol EXb
Installation – Commissioning – Maintenance
Installation
A1, B1
20191101
Art. 942428024
B2A2
Page 2
ADAPT Parasol EX
A3
A4
B3
M8
B4
A5
A6, B5
Swegon reserves the right to alter specications. 20191101
Page 3
d/2
Water
A7, B 6
ADAPT Parasol EX
DN15 (1/2”) male threads
utvändig gänga DN (1/2”)
Control equipment
A8, B7
Note that clamp ring couplings require support sleeves inside the pipes.
20191101 Swegon reserves the right to alter specications.
3
Page 4
ADAPT Parasol EX
B
Wiring
A9, B8
B C F G H I
A10 , B9
A9, B8
C F G H I
RoHS
A B C D E F G H I
VOC
RoHS
S oH R
CO
2
|
white
black
white
brown
black
brown
blue grey
black
1 2 |
3 4 |
5 6 |
7 8 |
9 10
11 12
|
1. Wiring when not using VOC sensor
2. Wiring when using VOC sensor
| 22 | 23 | 24 | 25 |
1.
white
21 | 20
18 |19 17
|13 14 15 |16
green
blue
red
yellow
Sensor
Condens
G0
G
24V
0-10V DC
G0
24V
0-10V DC
G0
Sensor
Condens
24V
G0
24V
G0
brown
brown (US=white)
blue (US=black)
brown (US=white)
blue (US=black)
2.
RoHS
4
Swegon reserves the right to alter specications. 20191101
Page 5
ADAPT Parasol EX
Zone
Room
RS 485 type Belden 9842
RK 2x0,75
CONNECT Adapt
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
23
Modbus
22
Slave
Slave
21
Master
20
Modular 6/6 RJ12
Next room with Connect Adapt
­+ C
G0
24V AC
G
Modular 8/8 RJ45
Next Zone
1 2 3 4
MB2
Super WISE
5 6 7 8
MB1
1 2 3 1 2 3
Room with ADAPT Damper extract air
MB id 5
Slave, extract air
ADAPT Damper settings
• Slave MB id (5,6,7,9,10,11 etc. if Super WISE system)
• Slave function (Application type =3 )
• Extract Air (Tempsensor use =1)
• Operation = normal (commissioning mode when delivered)
Modular 6/6 RJ12
22 23 24 25
| 1 2 | 3 4 | 5 6 | 7 8 | 9 10 11 12 |
CONTROL
MB id 1
| 22 | 23 | 24 | 25 |
Zone
20 19
|13 14 15 | 16 17 18 | 19 20 21 |
MB id 4
Master
Room
Room
Modular 6/6 RJ12
CONNECT Adapt
Slave
Modbus
23
22
22 23 24 25
MB id 4
Master
CONNECT Adapt
Slave
Modbus
23
22
21
21
Slave
Slave
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Master
20
Modular 6/6 RJ12
| 1 2 | 3 4 | 5 6 | 7 8 | 9 10 11 12 |
| 22 | 23 | 24 | 25 |
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Master
20
Room with ADAPT Parasol only (Master / Master)
Modular 6/6 RJ12
| 1 2 | 3 4 | 5 6 | 7 8 | 9 10 11 12 |
|13 14 15 | 16 17 18 | 19 20 21 |
22 23 24 25
| 22 | 23 | 24 | 25 |
|13 14 15 | 16 17 18 | 19 20 21 |
MB id 8
Master
Room with ADAPT Parasol only (Master / Slave)
Modular 6/6 RJ12
22 23 24 25
MB id 4
Master
Modular 6/6 RJ12
| 1 2 | 3 4 | 5 6 | 7 8 | 9 10 11 12 |
| 22 | 23 | 24 | 25 |
20191101 Swegon reserves the right to alter specications.
Modular 6/6 RJ12
| 1 2 | 3 4 | 5 6 | 7 8 | 9 10 11 12 |
|13 14 15 | 16 17 18 | 19 20 21 |
22 23 24 25
| 22 | 23 | 24 | 25 |
|13 14 15 | 16 17 18 | 19 20 21 |
MB id 1
Slave id 1
5
Page 6
ADAPT Parasol EX
A11, B10
A12 , B11
A13, B12
A14 , B13
TORX T-25 / 1 x 8
Click!
6
Swegon reserves the right to alter specications. 20191101
ON
1 2
ON
1 2
Page 7
A15 , B14
A16 B15
ADAPT Parasol EX
A17, B16
20191101 Swegon reserves the right to alter specications.
Page 8
ADAPT Parasol EX
A18 , B17
A19 , B18
8
Swegon reserves the right to alter specications. 20191101
Page 9
Commissioning
ADAPT Parasol EX
2
3
4
1
T-25
1 x 8
Nozzle configuration
H M L
Pi (2,4)
H =
(1,3)
P
i
M=
2
q
p = [Pa]
(
i
)
k
q = k · √p [l/s]
i
L=
[pi Pa] q [l/s] k = k-factor
ADAPT Parasol EX
690 L 1&3 0,253
690 L 2&4 0,253
690 M 1&3 0,44
690 M 2&4 0,44
690 H 1&3 0,693
690 H 2&4 0,693
129 0 L 1&3 0,253
129 0 L 2&4 0,665
129 0 M 1&3 0,44
129 0 M 2&4 1,16
129 0 H 1&3 0,693
129 0 H 2&4 1,825
Nozzle setting
per side
Side
k-factor
k (1+3) + pi (1,3) => q (1+3)
1
The K-factor of the short sides together with the commissioning pressure reading of these equals the flow of the short sides, 1&3.
k (2+4) + pi (2,4) => q (2+4)
2
The K-factor of the long sides together with the commissioning pressure reading of these equals the flow of the long sides, 2 & 4.
q tot =q (1+3) + q (2+4)
3
The product's total flow is the sum of the above.
(1,3) = pi (2,4)
NB! p
/
i
NOTE: The commissioning pressure is diffe­rent for the long sides (2 & 4) and the short sides (1 & 3).
20191101 Swegon reserves the right to alter specications.
9
Page 10
ADAPT Parasol EX
Fan-shape
X-shape
Commissioning/Checking the airflows
Constant pressure in the zone with the CONTROL Zone damper or similar damper.
• Check that all the WISE products are energized.
• Make sure that all the ADAPT Parasol EX modules have their correct K-factors.
• Make sure that all the modules are set to the max. flow commissioning mode. (On delivery, the product is set to this mode, 3 blue LEDs + 3 red LEDs are lit).
• Connect up to the control unit on the ADAPT Parasol EX (see separate SWICCT instructions) and carry out a per­formance check.
• Test the operating modes, the min./max. flows, open/ close the actuators. If the ADAPT Parasol EX has been configured at the factory, check that the settings agree with the project design data. If the module is an ADAPT Parasol EX stock (stocked product), it must be program­med according to the data for which the product has been calculated. Make also sure that the Modbus addres­ses agree if SuperWISE or some other BMS system will be used.
• If SuperWISE will be used, make sure that all products are in the SuperWISE tree structure. If all the products are not in the tree structure, look over the Modbus addresses via SWICCT and check cables and connections. (See the separate instructions for the SuperWISE).
• Make sure that the pressure sensor and sensor module have the correct Modbus address. The Master must have a 0 setting on the pressure sensor and sensor module. Set the Slaves, if required, in number sequence: 1, 2, 3, 4, 5, 6, 7, 8, 9
• Before you begin commissioning, make sure that the air handling unit is started up and the fire damper, if re­quired, is fully open and that the zone damper is in full operation.
• Check the flow compared to the max. flow in the zone, adjust the pressure set point until the correct flow is ob­tained with TUNE Control. If Max. flow is not achieved, it will be necessary to close another/other zone damper(s).
• The reference product can be found, i.e. the one with the greatest deviation from the design max. flow, by measur­ing the max. flow of all the ADAPT Parasol EX modules in the zone.
• Measure and record the airflow with the damper set to the max. position on the reference ADAPT Parasol EX in the zone. Reset the module to the min. flow setting, measure and record the airflow.
• Set the module back to the max. flow setting.
• Carry out the same procedure for all the ADAPT Parasol EX modules in the zone.
• Decrease the pressure set point on the zone damper if pressure is needed for other zones, for example: 5 Pa.
• Commission the remaining zones following the same procedure.
• Check/ adjust the previous shut off zones in the same way.
• Reset the pressure set points on all the zone dampers.
• Identifiy the reference zone, i.e. the zone with the lowest flow compared with the design max. flow (for example by checking relevant flow across each zone damper using the TUNE Control hand-held terminal).
• Set the min. flow on a number of ADAPT Parasol EX mo­dules or use the zone damper for setting the min. flow so that the ventilation system responds to the simultaneous load.
• Adjust the pressure set point of the air handling unit until the zone damper of the reference zone is 85 – 90% open. (Managed by the SuperWISE if one is used).
• Reset all the settings and set all the ADAPT Parasol EX to the normal operation setting.
• Check and measure the max. flow and min. flow with the SWICCT or the SuperWISE.
10
Swegon reserves the right to alter specications. 20191101
Page 11
ADAPT Parasol EX
Menu:
To reach the menu, hold the left-hand and right-hand buttons down for five seconds.
With the left-hand button ( ) you advance through the menus. With the right-hand button ( ) you confirm your selection.
Press the left-hand but­ton and select:
1. Alarm list
2. Commissioning air
Press the right­hand button to confirm your selection
3. Commissioning water
6. Return to menu
1. Alarm list: See the complete alarm list to the right.
In the commissioning menus:
• Navigate between the menus by pressing the left-hand button
• Confirm selections by pressing the right-hand button
• When a selection has been confirmed, the blue LED will flash for about 60 seconds.
• In order to return to normal operation, select "no adjust­ment"
2. Commissioning, Air:
2.1. Min. airflow, no occupants
2.2. Min. airflow, occupancy
2.3. Max. airflow, occupancy
2.4. Min. airflow, holiday/longer period
of no occupancy
2.5. No adjustment
3. Commissioning, Water:
3.1. Open the chilled water valve
3.2. Open heated water valve
3.3. No adjustment
4, 5 are not used
6. Return to menu
Presence detector
Diodes for temperature, commissioning or alarm indication
Function button
Diode-indicating function
- Green = Ok
- Flashing Green = Condensation alarm
- Yellow = Alarm
- Green/Yellow=Comfort alarm
Temperature sensor
(not acute)
Function button
Alarm list for the sensor module
Alarm no. Type of alarm 32 16 8 4 2 1
Alarm 1 Supply voltage low
Alarm 2 Supply voltage critically low
Alarm 3 Ext temp missing
Alarm 4 Ext temp error
Alarm 5 Condensation sensor error
Alarm 6 SM temp sensor error
Alarm 7 SM button error
Alarm 8 CO2 sensor missing
Alarm 9 VOC Error
Alarm 10 Low pressure
Al ar m 17 SM comm error
Alarm 18 Slave comm error
Alarm 19 Pressure sensor comm error
Alarm 20 VOC sensor comm error
Alarm 21 No master request (slave)
Alarm 22 Slave incompatible version
Alarm 25 Heating comfort alarm
Alarm 26 Cooling comfort alarm
Alarm 27 Temp. Set point overlap alarm
Alarm 28 Air quality comfort alarm
Alarm 29 Condensation
Alarm 33 24 V Out 1 overload error
Alarm 34 24 V Out 2 overload error
Alarm 35 24 V Out 3 overload error
Alarm 41 Slave input common alarm
Alarm 42 Slave output common alarm
The alarm is displayed by a number of diodes when you have selected Alarm list (1) in the menu.
Each diode represents a number as shown in the table above and the numbers should be added up to form an alarm number.
Ex. The centremost blue and the two last red diodes are lit (xoxxoo)
The centremost blue one corresponds to 16, the penulti­mate red one to 2 and the last red one to 1. The sum of these is 19, which is the alarm number.
Return to normal operation by pressing the right-hand button.
3 parallel RJ12 ports (Modbus) for connecting a controller, another sensor module or a computer, for example, by means of a Cable converter USB-RJ12
Dial for addressing the appropriate sensor module if several are used in the same loop. 10 senormodules can be connected to the same master,
ON
1 2
and each and one of them need an unique address.
Switch/Termination resistance. Switch 1 should be ”on” for the last sensormodule in the loop.
20191101 Swegon reserves the right to alter specications.
11
Page 12
ADAPT Parasol EX
Maintenance
1
5
6
2
7
ON
1 2
3
9
ON
1 2
8
4
12
Swegon reserves the right to alter specications. 20191101
Loading...