Swagelok VCM User Manual

Page 1
www.swagelok.com
Digital Valve
Control Module
(VCM)
This manual contains important information for the safe and effective operation of the Swagelok® digital valve control module. Users should read and understand its contents before operating the valve control module.
User’s Manual
Page 2
2 Valve Control Module Use r’s Manual
Contents
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Product Information . . . . . . . . . . . . . . . . . . . . . . 4
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 5
Control Drawing . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Air Supply Quality . . . . . . . . . . . . . . . . . . . . . . 7
Power Supply. . . . . . . . . . . . . . . . . . . . . . . . .8
DeviceNet™ Network Cable . . . . . . . . . . . . . . . . . 8
Tubing Connections . . . . . . . . . . . . . . . . . . . . . 9
Proximity Sensor . . . . . . . . . . . . . . . . . . . . . . 10
Terminal Strip (SS-VCM-D-6-2). . . . . . . . . . . . . 10
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electronic Data Sheet (EDS) . . . . . . . . . . . . . . . . 12
General Tab . . . . . . . . . . . . . . . . . . . . . . . 13
Parameter Tab . . . . . . . . . . . . . . . . . . . . . 13
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Commanding the VCM . . . . . . . . . . . . . . . . . . 16
Response from the VCM . . . . . . . . . . . . . . . . . . 16
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 17
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 18
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Safety
Signal Words Used in this Manual
NOTICE Statements that indicate a hazardous situation which, if not avoided, could result in damage to the
equipment or other property.
Page 3
Valve Control Module User’s Manual 3
Introduction
The Swagelok VCM uses a sophisticated control and monitoring system to operate up to six pneumatic stream selecting valves or other discrete valves. This compact system reduces complicated cabling and minimizes overall power consumption.
The solenoid pilot valves are connected to a common air supply inlet and a common exhaust or vent. Each pilot valve is also connected to a dedicated outlet used to actuate an external, pneumatic stream selecting valve or other discrete valve.
An indicator LED shows activation status for each pilot valve. Additionally ODVA-compliant DeviceNet indicators show module and network status.
Each VCM contains a DeviceNet network interface. The interface includes power for energizing the electronics inside the VCM and the communication signals, which allow a programmable logic controller (PLC) or similar system controller to exchange digital data with the VCM. Using the DeviceNet network, each pilot valve can be commanded to open a pneumatic ow path between the supply inlet and the associated outlet. The VCM pilot valves are normally closed and will open a ow path between the exhaust and the associated outlet in this position. See Fig.1.
The VCM is available with proximity sensor inputs and various ingress protection options. Inputs connect to proximity sensors integrated into the external valves actuated by the VCM. The VCM can be congured to monitor the sensor inputs and return the sensor state as part of the DeviceNet poll message response.
Network interface
and module power
Inlet IN
Outlet 1
Outlet 2
Outlet 3
Outlet 4
Outlet 5
Optional
proximity
sensors
Pilot valve closed. Outlet connected to exhaust EXH.
Outlet 6
Exhaust EXH
Pilot valve open. Outlet connected to inlet, IN.
Fig. 1 VCM Schematic
Page 4
4 Valve Control Module Use r’s Manual
Product Information
Network LED
M12 Network
Connector Plug
Module LED
Valve #1 LED
Cable gland
Interface cover
Mounting holes
Inlet
Grounding lug
Mounting holes
Outlets
Exhaust
Fig. 2 MS-VCMD-6-2
Page 5
Specifications
Power
Voltage 24 V (dc), nominal
Current < 310 mA (dc) at 24 V (dc)
Wattage < 7.5 W at 24 V (dc)
Temperature
Operating (Ambient) Minimum 23°F
Maximum 122°F (50°C)
Media Minimum 23°F (–5°C)
Maximum 122°F (50°C)
Storage Minimum 4°F (–20°C)
Maximum 140°F (60°C)
Weight 3.5 lb (1.6 kg)
Ingress Protection IP64
Inlet Air
Entity Parameters
Supported Communication Baud Rates
Pressure 40 to 116 psig
Air Quality Filtered compressed
See control drawing VCM-DN-0011­SCHEDULE on page 6.
Auto-baud function, allowing the device to detect the speed of network trafc. It is compatible with 125, 250, and 500 kbaud rates.
(1.6 to 7.9 bar)
air, lubricated or
unlubricated, grade of
filtration 40 μm
Valve Control Module User’s Manual 5
(–5°C)
Note: Before installing the VCM in a hazardous location, review the control drawing on page 6.
This will help ensure all electrical connections to and from the VCM comply with safety requirements. For an electronic copy of this document, see Swagelok.com
Page 6
6 Valve Control Module Use r’s Manual
Control Drawing
D
1
VCM-DN-0011-SCHEDULE
2
DWG.
NO.
HAZARDOUS LOCATION
Class I, Div. 2, Groups C, D
3
4
Any associated apparatus power
NON-HAZARDOUS LOCATION
5
NONINCENDIVE FIELD
WIRING - POWER CIRCUIT
(PINS 2,3)
supply with Entity Concept
Parameters (1) appropriate for
connection to an nonincendive
device with Entity concept
parameters listed in Table 1.
CONTROL
EQUIPMENT
C
NONINCENDIVE FIELD/
ASSOCIATED APPARATUS
WIRING - SIGNAL CIRCUIT
(PINS 4,5)
Any nonincendive or associated
apparatus communication
controller with Entity Concept
parameters (1) (Vmax, Imax, Ci,
Li) appropriate for connections to
nonincendive devices with Entity
Concept parameters listed in
Table 1.
B
1 - Drain bare
2 - V+ red
3 - V- black
4 - CAN_H white
5 - CAN_L blue
1
Male
5
3 2
Field Wiring Diagram
4
1, 4, 7, 11, 14, 17: Sensor V+
2, 5, 8, 12, 15, 18: Sensor Response
3, 6, 9, 13, 16, 19: Sensor V-
10, 20: No Connect
Sensor Interface
A
-
SHEET
SCALE
1 of 1
NONE
REV.
1
VCM-DN-0011-SCHEDULE
2
DWG.
NO.
Jul-9-12
Jul-9-12
DATE
DATE
JEK
MJR
3
DRAWN BY
CHECK/APR BY
4
APPROVAL/SCHEDULE DRAWING
© Swagelok Company All Rights Reserved
TITLE
.015
.031
5
1 DEGREE
UNLESS OTHERWISE SPECIFIED
TOLERANCE ON ENGLISH DIMENSIONS
6
H/ft.
µ
Sensor Interface
TABLE 3:
7
Associated Apparatus
TABLE 2:
WARNING: ANY CHANGES MADE TO THIS DOCUMENT MUST BE REVIEWED AND APPROVED BY SWAGELOK COMPLIANCE DPT
Voc (or Uo) Voc (or Uo)
Po Po
La (or Lo) La (or Lo)
Isc (or lo) Isc (or lo)
8
DCN
REVISIONS
REV.
Notes:
(1) The Entity Concept allows interconnection of nonincendive apparatus with
associated apparatus not specifically examined in combination as a system when the
approved values of Voc and Isc of the associated apparatus are less than or equal to
Vmax and Imax of the nonincendive apparatus and the approved values of Ca and
La of the associated apparatus are greater than Ci+Ccable and Li+Lcable respectively
for the nonincendive apparatus.
(2) Capacitance and inductance of the field wiring from the nonincendive equipment
to the associated apparatus shall be calculated and must be included in the system
D
Ca (or Co) Ca (or Co)
calculations as shown in Table 1. Cable capacitance, Ccable, plus nonincendive
equipment capacitance, Ci, must be less than the marked capacitance (Lcable, Li
and La or Lo, respectively). Where the cable capacitance per foot are not known, the
following values shall be used: Ccable = 60 pF/ft., Lcable = 0.2
TABLE 1:
Ci
Li
If Po of the associated apparatus is not known, it may be calculated using the formula:
Po = (Voc * Isc)/4 = (Uo * Io)/4.
Nonincendive Equipment
V max (or Ui)
I max (or Ii)
P max (or Pi)
C
(3) Associated apparatus must be installed in accordance with its manufacturer's
control drawing and Article 504 of the National Electrical Code (ANSI/NFPA 70), the
Canadian Electrical Code, or other local installation codes, as applicable. The
resistance of the ground path must be less than 1 ohm.
(4) When required by the manufacturer's control drawing, the associated apparatus
must be connected to a suitable ground electrode per the National Electrical Code
(ANSI/NFPA 70), the Canadian Electrical Code, or other local installation codes, as
applicable. The resistance of the ground path must be less than 1 ohm.
(5) The VCM is powered by two separate nonincendive circuits, designated Power and
Signal as indicated in Tables 1, 2 and 3. Cable and wiring for these two circuits must
maintain the separations for different nonincendive circuits required by Article 504 of
the National Electrical Code (ANSI/NFPA 70), ISA RP12.6 for installing nonincendive
circuits, or other local codes, as applicable.
(6) Associated apparatus must not be used in combination unless permitted by
associated apparatus certification.
(7) WARNING: Substitution of components may impair safety.
(8) The ambient operating (Tamb) range for this product is -5C to 50C.
B
Each unit must be connected to an IP64 or higher rated connector or IP rating will be void.
DESCRIPTION: SWAGELOK DEVICENET PTX CONTROL DRAWING
MATERIAL: NA
(9)
THIS PRINT IS THE EXCLUSIVE PROPERTY OF SWAGELOK COMPANY. IT MUST BE RETURNED ON
REQUEST ALONG WITH ANY DOCUMENTS CONTAINING INFORMATION OBTAINED FROM THIS
A
Fig. 3 VCM-DN-0011 SCHEDULE
ANGLES
.XXX
.XX
-- DIMENSIONS ARE INCHES NEXT TO [MILLIMETERS].
6
7
8
PRINT. NEITHER THIS PRINT NOR ANY PART OF IT NOR ANY INFORMATION CONCERNING IT MAY
BE COPIED, DISCLOSED TO OTHERS OR USED FOR ANY PURPOSE EXCEPT IN FURTHERANCE OF
YOUR BUSINESS WITH SWAGELOK. THE PARTS REFERRED TO ON THIS PRINT MAY BE THE
SUBJECT OF PATENTS AND/OR PENDING APPLICATIONS AND MAY NOT BE MANUFACTURED
WITHOUT PERMISSION FROM SWAGELOK COMPANY.
Page 7
Valve Control Module User’s Manual 7
Installation
Mounting
The VCM can be mounted using the mounting holes located on the feet of the enclosure. Mounting holes on the feet of the device are 0.22 inches (5.6 mm) in diameter, and can accommodate a #10 or M5 machine screw. Tighten the screws to wrench tight.
3.26
(82.8)
1.76
(44.7)
2.33
(59.2)
1.76
(44.7)
2.55
(64.8)
3.21
(81.5)
3.70
(94.0)
6.17
(157)
5.33
(140)
Fig. 4 Mounting Diagram
Grounding
The VCM must be grounded while in operation. This unit can be grounded either through the surface to which it is mounted (in the event that the VCM is mounted to a grounded plate), or a grounding wire attached to the ground lug on the side of the VCM. The ground lug is a #10-32 thread and can accommodate a #10 ring lug connector. The grounding wire should be at least 12 AWG wire. The total resistance between the VCM and ground should be less than 1 Ω.
Air Supply Quality
The supply air must be ltered to ensure that particles larger than 40 μm have been removed. The air can be lubricated or unlubricated.
Page 8
8 Valve Control Module Use r’s Manual
Power Supply
Power supply voltage must be within the range of the DeviceNet standard, which states: 24 volts ±1 % or adjustable to 0.2 %. Use of a lower voltage network power supply will decrease the reliability of the network and may make it inoperable. Swagelok validated the performance of the VCM operating at 11, 24, and 28 V (dc).
Note: Due to cable lengths and other devices operating on a network, the supply voltage at the device may not
be the same as at the power supply.
Hazardous Location Power Supply
It is required that a Class 2 power supply be used when the VCM is used in Class 1 Division 2 hazardous locations. Class 2 power supplies have a maximum power outlet of 100 W.
DeviceNet Network Cable
Cable Length
DeviceNet network cable lengths are dened in ODVA’s DeviceNet Planning and Installation Manual, chapter1, www.odva.org. Using cable lengths longer than those recommended can result in degradation of signal integrity and decrease of supply voltage.
Hazardous Location Cable Length
To use the cable in a hazardous location, the total inductance and capacitance of the network must be below the values set by the power supply being used. The total value can be determined by adding together the inductance and capacitance values of the devices on the network along with that of the cable.
The Swagelok VCM adds 0 µH and 0 µF to the network.
Cable parameters can be determined from the manufacturer’s datasheet. Assume values of 60 pF/ft and
0.2µH/ft when that information is not available.
Cable Bend Radius
The DeviceNet network cable should not be bent too tightly, as this causes excess strain on the cable and the attachment point on the device. After the cable has been installed, the bend radius can be adjusted as long as it is not smaller than its xed radius. Typical cables and their bend radii are presented in the table below. These values may change based on the manufacturer’s recommendations.
Cable Bend Radii
Cable Type Nominal Cable Dia Installation Bend Radius Fixed Bend Radius
Thick Cable 0.41 in.
Thin Cable 0.24 in. (6.1 mm) 4.80 in. (122 mm) 1.70 in. (43.0 mm)
(10.4 mm) 8.20 in. (210 mm) 2.87 in. (73.0 mm)
Connecting the Cable
Connect the micro M12 connector end of the network cable to the network interface plug on the VCM. Connect the opposite end to the system network.
Tubing Connections
Mechanical key
Drain
Fig. 5 M12 Female Connector End
2 3
1
4
V-V+
5
CAN_L
CAN_H
V+ = 24 V (dc) supply V– = Ground CAN_H = High signal of CAN differential
signal
CAN_ L = Low signal of the CAN differential
signal
Drain = Cable shield, ground at the power
supply end
Page 9
Valve Control Module User’s Manual 9
The VCM accommodates #10-32 thread connections (ex. face sealed push-to-connect) for 1/8 in. exible tubing. Face sealed push-to-connects should be installed according to the manufacturer’s instructions.
Max OD = 0.35 in. (8.9 mm)
Inlet
Fig. 6 #10-32 Push-to-Connect Fittings
Numbered outlets
Exhaust
Fig. 7 VCM with #10-32 Push-to-Connect Fittings
1. Connect supply air to the inlet.
Notice: Do not exceed 116 psig (7.9 bar).
2. Connect system valves to any of the numbered outlets. It is not necessary to cap unused outlets.
3. Connect the exhaust to a system vent line.
Page 10
10 Valve Control Module User’s M anual
Proximity Sensor
The Swagelok VCM model number SS-VCM-D-6-2 is designed to work with the Bi1-EG05-AP6X proximity sensor manufactured by Turck Inc. These sensors can be added as an option to the applicable Swagelok valve at the time of purchase. An alternate option is a compatible three-wire, 12 V (dc), PNP proximity sensor.
Note: The SS-VCM-D-6-0 model does not have any capability to interface with proximity sensors.
Terminal Strip with Sealed Enclosure, IP64 (SS-VCM-D-6-2)
For the SS-VCM-D-6-2 model, the proximity sensor wires must be passed through the enclosure before attachment to the proximity sensor terminal strip.
1. Use a Number 1 Phillips screwdriver to remove the six enclosure mounting screws. Remove the enclosure and gasket.
Mounting screws
Washers
Enclosure
Gasket
Fig. 8 Remove Enclosure
2. Use an 8 mm wrench to loosen a cable gland nut.
Note: Use a backup wrench to ensure the tting body does not loosen from the enclosure.
8 mm wrench
Backup wrench
Fig. 9 Loosen a Cable Gland Nut
3. Pass the sensor wire through the cable gland body and enclosure gasket.
Note: In order to seal properly, the cable diameter must be between 0.080 and 0.13 inch (2.0 to 3.3 mm).
Page 11
Valve Control Module User’s Manual 11
4. Connect each wire to the appropriate input on the terminal strip. Connect a brown, a black, and a blue wire for each valve to be controlled by the VCM.
a. Loosen the set screw for each wire.
b. Insert the wire in the appropriate location. See Fig. 10.
c. Tighten the set screw.
Note: Put a strain relief in place to prevent the wires from being accidentally pulled out.
Brown
Set
screw
Note: Terminal inputs 10 and 20 are no connects.
Black
Blue
Fig. 10 Connect Wire to Terminal Strip
5. Repeat steps 2 through 4 for each proximity sensor to be attached to the VCM.
6. Place the enclosure and gasket against the VCM body, lining up both with the mounting holes.
7. Tighten each cable gland nut on the enclosure to 1.00 in. · lb (0.11 N · m) to maintain IP rating.
8. Insert the six enclosure mounting screws with PTFE washers. Tighten the screws hand-tight in the pattern shown.
1
5
3
4
6
2
Fig. 11 Tighten Enclosure Screws
Page 12
12 Valve Control Module User’s Manual
9. Cap any unused cable glands using the caps and O-rings provided to maintain IP rating.
10. Remove the cable gland nut using a 8 mm wrench. Slide an O-ring onto the cable gland body until it is seated at the base of the threads.
11. Thread on a cap and tighten to 1.00 in. · lb (0.11 N · m) using a 10 mm wrench.
Fig 12 Cap and O-ring Assembly
Setup
Notice: The VCM must be disconnected from the system while performing setup functions.
Electronic Data Sheet (EDS)
1. Download the electronic data sheet (EDS) le from www.swagelok.com.
Note: Altering the EDS in any way voids the product warranty.
2. Open your network conguration tool, such as RSNetWorx™ for DeviceNet.
3. Register the EDS using the network conguration tool.
4. Connect the VCM to the network.
5. Scan the network for the VCM, and click on the device.
6. Use the network conguration tool to set the elds.
Page 13
Valve Control Module User’s Manual 13
General Tab
Device Address (MAC ID)
The VCM will have a factory set address of 63 when initially powered on. Addresses between 0 and 63 are valid DeviceNet addresses. Do not duplicate addresses. Duplicate addresses will cause the devices at that address to be unable to communicate with the network. As noted, new devices will be set to address 63, so it is recommended to leave that address open to accommodate new hardware.
Assign higher priority devices a low network address as the lowest network address will be given priority during network arbitration.
Fig 13 General Tab
Parameter Tab
These elds can be set for each of the attached valves. Select the valve to edit and then the desired eld(s).
Fig 14 Parameter Tab
Page 14
14 Valve Control Module User’s Manual
Fault and Idle Actions
The VCM can be congured to go into a known state, or maintain its last commanded state, in the event of a Fault or Idle state. The dropdown options are:
Fault Value— The Fault Value parameter will determine whether the valve is turned on or off during a fault with
a 1 indicating the valve will be on and a 0 indicating the valve is off.
Hold Last State—The valve will remain in the last commanded state in the event of a fault.
The Idle Action dropdown options are the same as the Fault Action dropdown options.
Fig 15 Setting Fault Action
Cycle Count and Limit
The VCM will track how many cycles each valve has had since manufacture. In addition, the user can set the Cycle Limit eld to send an alarm at a desired cycle count to plan for maintenance. Setting the Cycle Limit to 0 will make that function inoperative.
NOTE: The cycle count is stored to non-volatile memory each time the cycle count grows by more than 10%.
It is not stored each and every time a valve is actuated.
Fig 16 Cycle Count and Limit
Page 15
Valve Control Module User’s Manual 15
Sensor Configuration
The Sensor Available eld should be set to True when the valve has a proximity sensor attached. Valves without sensors set to False will provide feedback on the last commanded state. This eld cannot be set for the SS-VCM-D-6-0 model but will still display on the screen.
Operation
1. Connect the VCM to the system.
2. Verify the system air is on.
Fig 17 Sensor Available
Fig 18 SS-VCM-D-6-2 connected to a SSV series
Page 16
16 Valve Control Module User’s M anual
Commanding the VCM
The VCM command is a one byte poll request with the valve commands encoded as shown in the table below.
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0
A valve command of 1 represents an open pilot valve, meaning that pressurized air from the inlet will pass to the system valve attached to the outlet. A command of 0 closes that pilot valve. For example, a poll request of 0x01 will turn on valve 1.
Multiple valves can be turned on simultaneously. A poll message of 0x03 would turn on valves 1 and 2.
Valve 6
Command
Valve 5
Command
Valve 4
Command
Valve 3
Command
Valve 2
Command
Valve 1
Command
Response from the VCM
The VCM will send a two byte response to all poll requests. The rst byte is the Status Byte, the second the State Byte. They are described in the tables below.
Status Byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0
Valve 6
Cycle
Status
Valve 5
Cycle
Status
Valve 4
Cycle
Status
Valve 3
Cycle
Status
Valve 2
Cycle
Status
Valve 1
Cycle
Status
The Valve # Cycle Status will return a 0 when the valve’s cycle count is less than or equal to the cycle limit and a 1 if the cycle limit has been exceeded. If the Cycle Limit has been set to 0, the Valve # Cycle Status should always be 0.
State Byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0
The State Byte will return the value of the valve states as they were before the poll request requesting the response.
Note: Due to timing restrictions of the DeviceNet protocol, the State Byte response will not reect the command
that was just sent. In order to monitor VCM valve states without changing which valves are on, send an identical poll request.
For example:
Valve 1 is currently open, the user would like to open Valve 4, and verify both valves are actuated.
Poll request: 0x09 (keeps Valve 1 open and opens Valve 4)
Poll response: 0x01 (previous state, Valve 1 open)
Poll request: 0x09 (repeat previous message)
Poll response: 0x09 (VCM state, reecting last command)
Valve 6
State
Valve 5
State
Valve 4
State
Valve 3
State
Valve 2
State
Valve 1
State
Page 17
Valve Control Module User’s Manual 17
Note: The State Byte will return the value of the sensor if a valve is congured to use a proximity sensor. This
means that the poll response may not be the same value as the command sent.
For example, when valve 1 is connected to a normally closed valve with a BI 1-EG05-AP6X sensor and is congured to accept sensor input, the response will look like:
Valve State
Off Closed On On 1
On Open Off Off 0
Valve
Position
Sensor
State
Valve Indicator
Light Poll Response
Fig 19 Valve Indicator Light
Maintenance
There are no eld-maintainable parts within the VCM. Contact your authorized Swagelok representative for assistance.
The following hardware kit is available:
Enclosure Hardware Kit (MS-VCM-KIT1)
This kit contains the components used to attach and seal the interface cover included with the valve control module, SS-VCM-D-6-2. The contents of this kit are included with that model when shipped from the factory.
6 screws
6 washers
1 interface cover gasket
6 acorn nuts
6 cable gland O-rings
6 cable glands and nuts
Connector Kit (MS-VCM-KIT2)
This kit contains eight #10-32 face seal push-to-connect ttings for use when connecting 1/8 in. plastic tubing to the valve control module (VCM).
Page 18
18 Valve Control Module User’s Manual
Troubleshooting
Problem Cause Remedy
Module (MOD) LED
Off No power applied to the device. Connect power.
Green Normal operation. No action needed.
Flashing Green Device needs to be configured Configure device.
Red Device has an unrecoverable fault.
Flashing Red Device has invalid configuration. Check configuration setup.
Network (NET) LED
The device has no power or the channel
Off
Green Normal operation. No action needed.
Flashing Green
Red
Flashing Red
System valves do
not actuate.
System valves
do not return to
normal state
Valve indicator
LED is on when
valve is closed
System valve
is on when the
proximity sensor
is off.
System valves
actuate when the
pilot valve is off.
is disabled for communication due to
bus off condition, loss of network power,
or has been intentionally disabled.
The channel is enabled but no
communication is occurring.
The two-digit numeric display for the
channel indicates an error code that
provides more information about the
condition of the channel.
The communication channel has failed.
The two-digit numeric display for the
channel indicates an error code that
provides more information about the
condition of the channel.
This may indicate a defective scanner.
At least one of the devices in the
scanner’s scan list table has failed to
communicate with the scanner. The
network has faulted.
The two-digit numeric display for the
channel indicates an error code that
provides more information about the
condition of the channel.
General
VCM inlet pressure is too low.
VCM exhaust may be blocked.
The valve has been configured to read
the feedback from the proximity sensor.
The valve and sensor have different
“polarities.”
The inlet pressure is too high.
Cycle power to device. If device fails to recover,
contact your authorized Swagelok representative.
Power-up the scanner, provide network power
to channel, and make sure channel is enabled in
both the scanner configuration table and module
command word.
Configure scan list table for channel to add
device.
Reset scanner. If failures continue,
replace scanner.
Examine the failed device and examine the
scan list table for accuracy.
The system valve actuation pressure may be
different from the VCM operating pressure. Ensure the inlet pressure is suitable for the
system valve.
Ensure that the VCM exhaust is able to properly
vent.
The valve indicator LED will reflect the value of
the sensor not the position of the valve.
This is normal system operation.
Lower the inlet pressure going to the VCM.
Notice: Applying inlet pressure above the VCM
product rating can permanently damage the pilot
valves.
Page 19
Valve Control Module User’s Manual 19
Glossary
Term Definition
VCM DeviceNet Valve Control Module
Supply Inlet VCM port to which compressed air supply is connected.
Exhaust VCM port to which exhaust air is vented.
Outlet
System Valve A pneumatically actuated valve which directly controls flow of media.
Pilot Valve
PLC Programmable Logic Controller
Proximity Sensor A proximity sensor allows the VCM to monitor the system valve state.
DeviceNet
Ingress Protection (IP) A measurement of the device’s ability to keep water and dust out of the enclosure.
LED Light Emitting Diodes
MOD LED The Module LED (MOD LED) provides feedback on the status of the module.
NET LED
Electronic Data Sheet (EDS)
Controller Area Network (CAN)
Entity Parameters Values used to determine the suitability of the device for use in hazardous environments.
MAC ID Media access controller identifier.
VCM port to which compressed air is passed through when the associated pilot valve is actuated. These are the ports which will be connected to the system valves.
A small valve that controls actuation air to a system valve. Pilot valves are useful because they allow a small and easily operated feed to control a much higher pressure or higher flow feed, which would otherwise require a much larger force to operate.
A CAN based, multi-drop network that connects and serves as a communication network between industrial controllers and I/O devices.
The Network LED (NET LED) provides feedback on the status of the VCM network connection.
A data file used by node commissioning tools to interpret parameters on the device.
A message based communication protocol originally designed for automotive application.
Page 20
Swagelok—TM Swagelok Company DeviceNet—TM ODVA RSNetWorx—TM Rockwell Automation, Inc. © 2012 Swagelok Company Printed in U.S.A. Octobe r 2012, R0 MS -13 -221
Loading...