Sussman ES series, HU series, ES 12, ES 18, ES 24 Installation, Operation And Maintenance Manual

...
Page 1
ES & HU Installation, Operation and Maintenance Manual
Model No. _____________________________________
Boiler Serial No. _______________________________
National Board No. ___________________________
Safety Valve Set Pressure _______________ PSIG
Power Circuit Voltage _______________________
Control Circuit Voltage ______________________
Amps __________ Phase _________ HZ __________
Steam Outlet Valve Size _____________ NPT
IMPORTANT:
This data file contains the National Board Registration Certificate approving your boiler. It must be kept near the boiler at all times.
Products covered by this manual:
_________________________________________________________________________________
KW Max Design Work
Series Range Steam Rate* BHP Pressure Pressure
_________________________________________________________________________________
ES, HU 12-180 36-542 lbs/hr 1.2-18.4 0-100 psig 85 psig
_________________________________________________________________________________
*Steam Rate: Steam at 212˚ F with 50˚ F feed water
ES and HU boilers are of Carbon Steel construction. See page 23 for Water Quality Information.
TABLE OF CONTENTS
Dimensional Information and
Component Identification . . . . . . . . . . . . . . . . . 2
Dimensional & Clearing Specifications. . . . . . . . . 3
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Installation
Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Pressure Controls, Operation & Testing . . . . . . . 10
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Blowdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Digital Timer Operation Instructions. . . . . . . . . . 12
Timing Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Standard Equipment
Auxiliary Low Water Cut Off . . . . . . . . . . . . . . . . 14
Line Pressure Water Feed System . . . . . . . . . . . . . 14
Optional Equipment
High Pressure Water Feed System. . . . . . . . . . . . . 14
Condensate Return System. . . . . . . . . . . . . . . . . . 14
Vacuum Breaker Systems . . . . . . . . . . . . . . . . . . . 15
Automatic Blowdown System. . . . . . . . . . . . . . . . 15
Control Voltage Stepdown Transformer . . . . . . . . 15
Blowdown Separators . . . . . . . . . . . . . . . . . . . . . 15
Multistage Load Progressive Sequencers . . . . . . . . 15
Condensate Return Systems . . . . . . . . . . . . . . . . 16
Blowdown Separator Tanks . . . . . . . . . . . . . . . . . 17
Specification Charts . . . . . . . . . . . . . . . . . . . . . . . 18
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Gauge Glass Installation . . . . . . . . . . . . . . . . . 20-21
Water Quality Information
for Carbon Steel Boilers . . . . . . . . . . . . . . . . . . 23
IMPORTANT NOTE:
As you follow these instructions, you will notice warning and caution symbols. This blocked information is important for the safe and efficient installation and operation of electric boilers. These are two types of potential hazards that may occur during this installation and operation:
WARN I N G
!
may cause serious injury or death if precautions are not followed.
states a hazard which
CAUTIO N
!
minor injury or product damage may occur if you do not follow instructions.
A Division of Sussman-Automatic Corporation
43-20 34th Street, Long Island City, NY 11101 • (718) 937-4500 1-800-238-3535 • Fax: (718) 937-4676 • email: [email protected]
www.sussmanboilers.com
signals a situation where
IMPORTANT NOTE:
This highlights information that is especial­ly relevant to a problem-free installation.
M A D E I N U S A
PUR 101137 4.13
Page 2
Installation, Operation & Maintenance Manual
Dimensional Information & Component Identification
Models: ES, HU
Height
Width
_________________________________
SYMBOL ITEM ES12-18 ES24-72 ES100 ES135-180
___________________________________
Height Overall Height 36" 44" 59" 61"
__________________________________________________________________
Length Overall Length 28" 33" 34" 38"
__________________________________________________________________
Width Overall Width 20" 22" 26" 30"
__________________________________________________________________
A Steam Outlet 6-1/4" 10" 8-1/4" 9"
__________________________________________________________________
B Steam Outlet 10-1/4" 17" 17-1/4" 18-1/4"
__________________________________________________________________
C M/M Drain Valve 5" 12" 17" 16-3/4"
__________________________________________________________________
D M/M Drain Valve 6-1/2" 6" 6-1/4" 6-1/4"
__________________________________________________________________
E Check Valve 14" 9" 17" 16-3/4"
__________________________________________________________________
F PV Drain Valve 2-3/4" 2-1/4" 2-3/4" 2-3/4"
__________________________________________________________________
G PV Drain Valve 6-1/4" 9-1/2" 7-3/4" 9-1/4"
__________________________________________________________________
J Clearance 3-3/4" 3-1/2" 4" 4"
__________________________________________________________________
K Check Valve 2-1/2" 2-3/4" 3" 3"
__________________________________________________________________
M Door Width 8-3/4" 14" 12-3/4" 14-3/4"
__________________________________________________________________
Allow 24 inches all around for servicing.
Length
_______________________________________
MODEL HW L INLET OUTLET
_______________________________________
ES 12, 18; HU 40–55 36" 20" 28" 1/2” NPT 1/2”NPT
_________________________________________________
ES 24–72; HU 75–205 44" 23" 33" 1/2”NPT 1” NPT
_________________________________________________
ES 100; HU 310 59" 28" 34" 1/2”NPT 1-1/2”NPT
_________________________________________________
ES 135–180; HU 410–550 61" 30" 36" 1/2”NPT 2” NPT
_______________________________________
Allow minimum 21 inches clearance in front of door for servicing of heating elements. Recommended clearance: 24 inches all around boiler for servicing.
WATER STEAM
2
Page 3
Installation, Operation & Maintenance Manual
Dimensional & Clearance Specifications
Height
SteamOutlet
Operating Pressure
A
Gauge Glass Assembly
Control
On/Off
Switch
High Limit Pressure Control
D
E
L
Pressure Gauge
SafetyValve
LiquidLevel Control
E
R
B
Water Feed Inlet
Drain Valve
FrontLeft
Width Length
F
Side Elevation Front Elevation
Allow 24" all around for servicing.
__________________________________________________
Clearance from combustible surfaces
__________________________________________________
A
_________________________________________________________________________
B
_________________________________________________________________________
D
_________________________________________________________________________
EL
_________________________________________________________________________
ER
_________________________________________________________________________
F
_________________________________________________________________________
G-
_________________________________________________________________________
1" Clearance above top of boiler
A Clearance from Front of boiler. Prefix "C" to numeral indicates acceptability for
closet or alcove installations; prefix acceptability for alcove installations but not for closet installations.
1" Clearance from back of boiler.
1" Clearance from left side of boiler.
16" Clearance from right side of boiler.
C Indicates type of flooring: "NC" for non-combustible; "C" for combustible.
Total minimum free area in square inches of close ventilating openings.
3
Page 4
H1 H3 H5 H7
FB1 FB2 FB3 FB4
FIELD WIRING
FACTORY WIRING
PILOT LIGHT
480V
120V
H2 H4 H6 H8
TO CONTROL
CIRCUIT
HEATING
ELEMENTS
TRANSFORMER
(optional)
TB 1
TB
FB
C
H
L1
L2
L3
G
POWER FUSES
(see Note 2)
CONTACTORS C1 C2 C3 C4
SINGLE PHASE
MAIN POWER SUPPLY
L1 L2 G
T1
TERMINAL POWER BLOCK (see note 1)
THREE PHASE
MAIN POWER
SUPPLY
Installation, Operation & Maintenance Manual
Typical Wiring Diagrams:
a.
Three phase power circuit with separate 120Volt control circuit. (With singe phase power circuit insert.)
b.
Three phase power circuit with step down transformer.
c.
Detailed ES81017MR auxiliary low water cut off wiring.
d.
ES81600 Auto blowdown wiring diagram.
e.
Detailed sequencer package wiring diagram.
Wiring Diagram Power Circuit
ES Electric Boilers (Power Circuit)
NOTES:
1. Power Terminal Block only on boilers with two or more contactors.
2. On boilers with only one power contactor, connect power voltage to line side of contactor.
3. Power Fuses only on boilers rated 120 amperes and larger.
4. See Parts List for contactor and heating element information.
4
Page 5
RELAY
FIELD WIRING
FACTORY WIRING
PILOT LIGHT
L
OPERATING
PRESSURE
CONTROL
AUX LWCO PC BOARD
MANUAL RESET
PILOT LIGHT
L1
G
NC
COM
NO
L2
HIGH LIMIT
PRESSURE
CONTROL
LIQUID
LEVEL
CONTROL
ON-OFF SWITCH
CONTROL TERMINAL BLOCK
120V 1PH
INPUT
L
N
TO
PROBE
SOLENOID VALVE
CONTACTORS
PUMP MOTOR
P2
P1
R
C1
C2
S
M
GND
LOW
RESET
RELAY
FIELD WIRING
FACTORY WIRING
PILOT LIGHT
L
OPERATING
PRESSURE
CONTROL
HIGH LIMIT
PRESSURE
CONTROL
LIQUID
LEVEL
CONTROL
ON-OFF SWITCH
CONTROL TERMINAL BLOCK
120V 1PH
INPUT
L
L1 L2
N
SOLENOID VALVE
CONTACTORS
PUMP MOTOR
P2
P1
R
C1
C2
S
M
Installation, Operation & Maintenance Manual
Wiring Diagram Control Circuit
ES Electric Boilers (Basic Control Circuit)
ES Electric Boilers with Manual Reset Auxiliary Low Water Cutoff
5
Page 6
Wiring Diagram Control Circuit
RELAY
F
IELD WIRING
F
ACTORY WIRING
P
ILOT
L
IGHT
L
OPERATING
PRESSURE
CONTROL
PROPORTIONING PRESSURE CONTROL
135 OHM
COM
SEQUENCER
HIGH LIMIT
PRESSURE
CONTROL
LIQUID
LEVEL
CONTROL
ON-OFF
S
WITCH
CONTROL TERMINAL BLOCK
120V 1PH
I
NPUT
L
N
L1 L2
SOLENOID VALVE
C1
C2
C3
C4
CONTACTORS
1
2
3
4
P
UMP MOTOR
P2
P3
P1
R
1
20V COM
M
S
M
Installation, Operation & Maintenance Manual
ES Electric Boilers with Sequencer
ES 100 and up with Element Cutoff Switches
6
Page 7
RELAY
F
IELD WIRING
F
ACTORY WIRING
PILOT LIGHT
PILOT LIGHT
L
OPERATING
PRESSURE
CONTROL
HIGH LIMIT
PRESSURE
CONTROL
LIQUID
LEVEL
CONTROL
O
N-OFF
SWITCH
CONTROL T
ERMINAL
BLOCK
120V 1PH
I
NPUT
L
N
7-DAY 24-HR
T
IMER
TIME DELAY RELAY
E
S81600 AUTOMATIC BLOWDOWN SYSTEM
C1
C2
CONTACTORS
S
M
SOLENOID VALVE
PUMP MOTOR
P2
P1
R
2
OPEN
CLOSE
3
D
T
M
OTORI ZED
B
LOWDO WN
VALVE
1
Installation, Operation & Maintenance Manual
Wiring Diagram Control Circuit
ES Electric Boilers with Automatic Blowdown System
7
Page 8
Installation, Operation & Maintenance Manual
Installation
REFER TO NATIONAL AND ALL APPLICABLE LOCAL CODES FOR SPECIFIC INSTALLATION REQUIREMENTS.
1. The boiler should be mounted on a solid, level foundation.
2. The boiler should be located with suitable clearances, refer to page 3 and Code requirements.
NOTE: Allow minimum of 21 inches clearance in front of door for servicing of heating elements.
3. Do not install boiler in any location where water could freeze.
4. Do not install boiler outdoors.
5. Do not install boiler near flammable or corrosive materials.
6. Do not install boiler in a location where leakage from the boiler tank or piping can damage to adjacent areas or to lower floors of the structure. Provide a floor drain and properly sloped floor from the boiler towards the drain or install a suitably plumbed drain pan under the boiler.
NOTE: Allow a minimum of 36 inches of clearance in front of door for servicing of heating elements.
Piping
ALL PIPING SHOULD BE INSTALLED BY A QUALIFIED LICENSED PLUMBER IN ACCORDANCE WITH NATIONAL AND LOCAL CODES.
1. When water feed is other than pump type the water supply pressure must be 10 psig greater than boil-
er operating pressure to assure water supply maintains proper water level in the boiler. Insufficient water levels can result in improper boiler operation. (Keep feed water valves open at all times during normal operation.)
2. If pump and boiler are plumbed within 30 feet (pipe length) a minimum of 2 check valves are required to avoid damage to pump.
3. Connect steam line with customer supplied outlet valve to boiler steam outlet.
NOTE: For best performance, a globe valve rated for steam service higher than the maximum boiler pres-
sure should be plumbed on the steam outlet line; failure to do so can cause heating element breakdown. See page 1 for steam outlet valve size.
4. Provide for boiler drain connection, a daily blowdown is required. A "Blowdown Separator Tank" may be necessary, check with local code.
5. Safety valve shall be plumbed according to local code.
NOTE: The safety valve shall not be plumbed with a line sized less than the outlet size of the safety valve.
8
Page 9
Installation, Operation & Maintenance Manual
Wiring
ALL ELECTRICAL WIRING MUST BE PERFORMED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES.
CAUTIO N
!
matches the power voltage and phase of the boiler. Connecting incorrect power supply can damage boiler components or cause improper boiler operation. If the boiler power requirements do not match the power to be supplied to the boiler the boiler must be returned to the factory for conversion. Boilers cannot be field converted.
ALL BOILERS ARE PRE-WIRED AND TESTED PRIOR TO SHIPMENT.
1.
Ground boiler according to National Electric Code requirements to avoid shock.
2.
Power wiring to boiler should be in accordance with National and Local Electrical Code requirements fol­lowing wiring diagram supplied. Use proper size wire. Wire size is specified adjacent to field wiring terminals. This label states the wire size [AWG or MCM], mini­mum temperature rating (90 C) and conductor material (copper only). Deviation from these requirements may result in improper or unsafe boiler operation.
3.
A disconnect switch employing circuit breakers or fuses should be installed between the main power source and the boiler. This disconnect switch should be located near the boiler and clearly marked for easy access and identification should the boiler need to be turned off due to an emergency.
4.
Boiler control circuit is 120 Volt*. Unless boiler has an optional step down transformer, a separate 120 Volt power feed wiring is required to be connected to the control circuit terminal block. A 15 Amp circuit is required for all boilers. If a 3/4 HP feed water motor and pump assembly is connected to the boiler, then a 20 Amp circuit is required.
Assure that the power voltage and phase being supplied to the boiler
5.
If a separate control circuit is used, it should be con­nected to the control circuit terminal block.
6.
Remote mounted water feed systems (i.e. condensate return, motor and pump) should be connected to the junction box provided on the outside of the boiler jacket.
7.
With main power off, make sure all wiring termina­tions are tight to avoid arcing, carbonizing or over­heating of contacts.
CAUTIO N
!
damage due to water line connections. An industrial type lightning/surge protector should be installed according to the manufacturer's recommendation at the service entrance. Consult your contractor or electrical dealer.
WARN I N G
!
cation of wiring system voids the warranty and may lead to dangerous operating conditions.
Boilers are susceptible to lightning
Substitution of components or modifi-
9
Page 10
Installation, Operation & Maintenance Manual
Pre-Operation Check (All Boilers)
LWCO/PUMP CONTROL OPERATION AND TESTING
1.
All valves for incoming water supply are to be fully opened. Main disconnect switch is to be in the "on" position. Boiler main switch is to be in the "on" position. Since boiler will be empty the pump or solenoid will be energized allowing the boiler to fill with water. Control will automatically fill boiler to proper operating water level and the pump/solenoid will be de-ener­gized. Contactors will then energize, applying voltage to the heating elements.
2.
Pump switch operation – at this point water should be visible approximately half way up the sight glass. Slowly open the drain valve located at the bottom of the boiler. Water level in the sight glass will begin to drop, allowing the low water cut off/pump control to energize the feed water system. Close valve for proper operation.
3.
Low water cutout switch performance – open the drain valve completely. Maintain this condition until water level falls within the gauge glass enough to cause the low water cutout switch to de-energize the heating elements. All of the contactors will be in a de-energized or open state at this time. Close the drain valve, water feed system will automatically refill the boiler and the contactors will re-energize.
Pressure Controls, Operation and Testing
Boilers equipped with an auxiliary low water cut-off control with a manual re-set button (required as mandatory equipment is some states): once the correct operating water level has been reached, it will be nec­essary to depress the reset button in order for the con­tactors to re-energize.
NOTE:
down system:
• For test 1 - the blowdown time clock must be in the
• For test 2 and 3 - in order for the drain valve to open
For boilers equipped with an automatic blow-
“run” mode before the boiler will automatically fill.
the blowdown clock must be in the “off” mode. (See blowdown time clock insert) The automatic blowdown indicator light will be on when the valve is open. This light will remain on for the duration of the blowdown cycle (a few seconds). It may be nec­essary to cycle the time clock from the “run” to “off” mode several times.
NOTE:
All boilers are provided with one high limit pressure control and at least one operating pressure control.
1.
The high limit pressure control is equipped with a manual reset feature. There is no subtractive differential scale with this type of control
2.
All pressure controls are equipped with an adjusting
screw, allowing for setting of desired operational and high limit pressures. To reduce pressure setting, turn adjusting screw in direction that allows indicator to point to a lower pressure setting on the scale. To increase pres­sure setting turn adjusting screw in direction that allows indicator to point to a higher pressure on the scale
NOTE:
10 psig above the desired normal operating pressure.
3.
It is recommended that the high limit control be set
Operating pressure controls, except low pressure (15psig)
types have a separate differential scale. Differential indi­cates pressure below the main operating maximum pres­sure, the pressure control will re-set. The differential set point is adjusted in the same manner by turning the adjusting screw in the desired direction to increase or decrease the differential pressure value.
4.
Operating pressure control check: Close steam outlet
valve [supplied by customer] and adjust operating pres­sure control to 20psig and the differential to 10psig. Set the high limit pressure control to 30psig. Switch boiler on to allow steam pressure to build-up. Pressure gauge reading will increase and the operating pressure control will de-energize the contactor(s) when the pres­sure gauge indicates 20psig. Open steam outlet valve to bleed off pressure. When the pressure gauge read­ing decreases below 10psig (differential) the operating pressure control will re-energize the contactor(s).
5.
High limit pressure control check: FOR TEST PURPOSES
ONLY! Set the high limit pressure control 10psig lower
than the operating pressure control. Close the steam outlet valve and switch the boiler on to allow boiler to build pressure. When the pressure gauge indicates the pressure at which the high limit pressure control is set, the high limit pressure control re-set button will pop­up and the control will de-energize the contactor(s). Open the steam outlet valve to bleed off pressure. The contactor(s) should not re-energize on pressure drop. The contactor(s) should only re-energize when the pres­sure has dropped and the high limit pressure control reset button is depressed.
10
Page 11
Installation, Operation & Maintenance Manual
Operation
CAUTIO N
!
lectrical connections before energizing boiler to prevent
e arcing, carbonizing of contact and/or overheating
1. Set the desired operating pressure and differential pressure
on the operating pressure control.
2. Set the high limit pressure control. (Recommended to be 10 psig above the operating pressure setting.)
3. Turn on water supply.
4. Turn main disconnect switch on.
5. Turn boiler control switch on. The water feed will begin
and continue until the water level reaches half way up the gauge glass. The water feed will automatically shut off and the contactor(s) will energize.
6. Boiler steam pressure will gradually increase to the operat-
With main disconnect “OFF” tighten all
ing pressure control set point, at which time the con­tactor(s) will de-energize.
7. With steam demand, the boiler steam pressure will decrease. When the boiler pressure has dropped below the operating pressure control differential set amount, the contactor(s) will re-energize.
Note: Adjust steam outlet valve such that the boiler pres­sure does not drop more than 20% below reset.
8. The boiler is equipped with float type liquid level con­trols employing micro switches. They are extremely sensitive and reliable and will maintain the proper water level within the boiler pressure vessel automati­cally during boiler operation.
9. The boiler should be blown down daily. (See blow­down instructions.)
Blowdown
A daily blowdown is an essential part of boiler operation. It is the best and most important part of preventative maintenance you can give your boiler and will add years of life to the unit. Make sure a blowdown schedule is established and followed regularly.
In extremely hard water areas, blowdown may be necessary more than once a day. If there is a particular problem that applies to your local water condition (i.e. high concentra­tions of minerals etc.) we recommend a consultation with a reputable local water treatment-engineering firm. Pre-treating the boiler feed water may reduce mineral accumulation enough to allow a daily blowdown to be sufficient.
MANUAL BLOWDOWN INSTRUCTIONS
1. At the end of the working day, while boiler is still operating,
turn boiler main switch to the “OFF” position, close water supply valve and open disconnect switch.
2. If blow down valve is plumbed into a blowdown tank, the boiler can be discharged at operating pressure.
3. If the blowdown valve is not plumbed into a blowdown tank, consult with local plumbing codes regarding boiler discharge.
4. When discharge is complete and boiler is drained, close the blowdown valve, open the water supply valve, turn boiler main switch to “ON” position and close disconnect switch.
5. When refilling is complete, turn off the boiler unless further operation is needed.
6. If boiler is equipped with a “Manual Re-set Auxiliary Low Water Cut-off” (as required in some states) the re-set button must be pushed before the boiler will begin developing steam. Do not push re-set button until the boiler has refilled with water.
AUTOMATIC BLOWDOWN INSTRUCTIONS
(PN ES81600) 1” NPT, Starts, stops and blows down the
boiler automatically, utilizing a programmable time clock a time-delay relay and motorized ball valve.
CAUTIO N
!
a blowdown tank, the boiler can be discharged at operat­ing pressure. If the blowdown valve is not plumbed into a blowdown tank, consult with local plumbing codes regarding boiler discharge.
NOTE:
lower float control equalization tube must be fully open for the automatic blowdown to be effective.
1. Program time clock by setting the time boiler is to turn
2. When the time clock turns the boiler “off” the blow-
3. Boiler will automatically refill at next programmed on
Blowdown program can be overridden to allow for unscheduled blowdown or operational cycles. Refer to the time clock instruction insert.
11
The manual valves from the boiler drain and the
on and off daily. (Refer to instructions in time clock insert.)
down is activated. A red pilot light over the time clock will come on and remain on while the motorized ball valve is open. The time duration the valve is open is set by an adjustable potentiometer built into the time delay board. The water level in the boiler after blowdown is complete, will be approximately at the lower gauge glass valve. (Elements are not exposed to air between operations.)
cycle.
If the blowdown valve is plumbed into
Page 12
Installation, Operation & Maintenance Manual
Mo Tu We T
h Fr S
a Su
14
16
18
20
22
24
+- Menu OK
Res.
+1h
Digital Timer - Operation Instructions
TO SET TIME & DAY OF CLOCK
1. Press Menu
2. 24h AM or PM blinking, press + or – to select, press OK
3. Hour (12:00) blinking, press + or – to select, press OK
4. Minute (12:00) blinking, press + or – to select, press OK
5. Arrows for days
press + or – to select, press OK
6. Go to step 8 to continue with programming or press
Menu to end.
TO SET TIMER ON/OFF TIMES
7. Press Menu and press OK four times to go
current time/day setting above
8. prog 01 blinking and ON symbol or – to select, press OK
9. Hour (12:00) blinking, press + or – to select, press OK
10. Minute (12:00) blinking, press + or – to select, press
OK
11. Arrows for days
blinking, press + or – to select,
press OK
12. prog 02 blinking and
OFF
symboldisplayed,
press + or – to select, press OK
13. Hour (12:00) blinking, press + or – to select, press OK
14. Minute (12:00) blinking, press + or – to select, press
OK
15. Arrows for days
blinking, press + or – to select. See
possible combinations below.
16. Press Menu to end or press OK and repeat steps 8 to 15 to set more ON/OFF times.
displayed, press +
blinking,
ON/OFF STATUS
ON
symboldisplayed when timer isonand
OFF
symboldisplayed when timer is off.
OVERRIDE/AUTOMATIC
When the timer is the timer
OVR
arrow
Offand display arrowwill point to
. Press + again to go back to
will point to
When the timer is the timer
OVR
Onand display arrowwill point to
.
Press + again to go back to
will point to
When the timer is in the override mode timer will stay in that position until the next pro­grammed time, at which time the arrow_will point to
AUTO
and continue in the automatic mode.
On, press + to manually turn
Onand display
AUTO
.
Off, press + to manually turn
Offand display arrow
AUTO
.
(on
OVR
HOURLY ON/OFF SETTING FOR THE DAY
Hash marks on the upper and right edges of the dis­play show the hourly On times for the day. Absence of hash mark on a specific hour indicates that the timer is Off on that hour.
DAYLIGHT SAVING TIME.
In the Run mode, use a pencil point and press+ for Daylight Saving Time and current time advances
hr
one hour and + Standard Time, press + one hour and +
displayed. To revert back to
hr
and current time falls back
hr
display disappears.
hr
),
PROGRAMMED DAY COMBINATIONS:
Every day (arrowson all days) Monday to Saturday Monday to Friday Saturday and Sunday Any individual day
RUN MODE
On Run mode, display will show current time/ date, on/off status, override/automatic status, hourly on/off setting for the day and Daylight Saving Time.
PROGRAMMING CONFLICTS.
Switch Off commands have priority over switch On commands.
NOTES:
1. The timer is set according to the boiler operation.
ON
When the timer is blowdown is
OFF
the boiler is
.
2. Timer must be powered up during programming
to display
On/Off
status.
3. During programming, if no button is pressed after
1 minute, the timer will revert back to Run mode.
12
ON
and the
Page 13
Installation, Operation & Maintenance Manual
24-Hour and 7-Day Time Switches
PROGRAMMING
F
or electric steam boilers equipped with Automatic Blowdown Systems ES 81600, refer to the following instructions for time clock operation and settings.
Timer settings for blowdown operation are at the discretion of the owner/operator.
The weekly program dial shows the seven days of the week and AM/PM imprints for each day.
The time switch is set by pushing the captive trippers to the outer ring position for the entire period that the load is to be turned ON, i.e., 2 hours to each trip­per on the 7-day dial. When the tripper is pushed to the inside, the switch is in the OFF position.
SETTING TIME
To set the current time and day of week, turn the minute hand clockwise. Do not set the time by rotating “Outer” Dial.
Turn the minute hand clockwise until the day of the week and the time of day on the outer dial is aligned with the triangle marker on the inner dial (two o'clock).
AM
Example for 7-day program dial Monday 10:30 Turn the minute hand clockwise until Monday 10:30
AM
is aligned with the triangle on the inner dial.
The hour and minute hand will show exactly 10:30.
FOR MANUAL OVERRIDE
Manual override can be accomplished at the discretion of the owner/operator as follows.
3-WAY MANUAL OVERRIDE SWITCH
I = permanent ON
= automatic
O = permanent OFF
I
O
.
Maintenance
CAUTIO N
!
DISCONNECT ALL ELECTRICAL POWER BEFORE WORKING ON BOILER.
ussman Electric Steam Boilers are designed for years of trou-
S
ble-free performance. To establish a good preventative mainte­nance program, we suggest that the facility maintenance per­son or engineer familiarize themselves with these simple rules.
1.
Daily blowdown at pressure is essential for ideal boiler performance. Extended periods of operation may require more frequent blowdown. If the boiler is not equipped with an automatic blowdown, in order to safeguard the heating elements, it is recommended to turn both the main disconnect switch and the boiler switch to the off position before manually blowing down the boiler.
2.
The sight glass should be checked frequently to assure the
boiler has adequate water.
3.
The sight glass should be checked daily for damage (i.e.
scratches, erosion, leaks etc.) The sight glass should be replaced if damaged. (See insert.)
4.
A monthly inspection should be made of the internal wiring.
Open the access door and check all electrical connections for tightness. Replace any wires that show signs of damage.
NOTE:
this maintenance procedure.
5.
6.
7.
8.
The electrical power MUST be shut off during
Heating element mounting bolts should be checked and
tightened to a torque of 22 ft.-lbs. If there are indications of steam leaks from an element, replace the element gasket.
A monthly check for leaks should be made; any loose or
damaged fittings should be tightened or replaced.
Every four months the boiler float control should be
checked for proper operation. The lower equalization column can be examined visually and manually to see if is clear and clean. If there are signs of scale or mineral deposit buildup the float control must be disassembled and cleaned.
One of the lower heating elements should be removed. If scale or mineral deposits have begun to form all elements should be removed cleaned and reinstalled using new element gaskets.
Operating and high limit pressure control operation should be checked. Pressure controls should be removed and cleaned if necessary. Water feed supply check valves should be inspected and replaced if necessary.
If the boiler is equipped with an electronic auxiliary low
water cut-off every four months the probe should be removed and checked for deposits. The probe should be cleaned and reinstalled.
HAZARD OF ELECTRIC SHOCK.
IMPORTANT: It is recommended that for periodic and effective blowdown,the override switch be set in the automatic setting.
13
Page 14
Installation, Operation & Maintenance Manual
Standard Equipment for ES & HU Optional Equipment
AUXILIARY LOW WATER CUT OFF
• For model ES & HU boilers PN ES81017MR (with manual reset).
Senses water level electronically using a resistance probe. When a low water condition is detected, the contactor control voltage circuit is interrupted and the heating elements are de-energized. When water level returns to proper levels voltage is restored to the contactor coils and the elements are re-energized. For controls with a manual reset button voltage to the contactor coils is not restored until the water level has returned to proper operating levels and the reset button is pushed. Do not depress the reset button before the correct water level is achieved.
LINE PRESSURE WATER FEED SYSTEM
• For model ES & HU boilers PN ES99117
Water feed system used to supply makeup water to the boiler when incoming water line pressure is 10 psig greater than the operating pressure of the boiler. Completely factory plumbed and wired; 0-100psig range; 1/2” NPT size. Consists of strainer, solenoid valve (120/1/50-60Hz), and check valve for automatic feed.
HIGH PRESSURE WATER FEED SYSTEM
• For model ES12-72 PN ES38002A
• For model ES100-180 PN ES38020A Used to supply makeup water and to maintain constant water level when the boiler operating pressure is equal to or greater than incoming water line pressure and conden­sate is not returned to the boiler.
• ES38002A – Range is 0 – 100 psig, 1/2” NPT size consisting of strainer, solenoid valve and 1/3 HP 120/1/60 motor and pump.
• ES38020A – Range is 0 – 125 psig, 3/4” NPT size consisting of strainer solenoid valve and 1/2 HP 120/1/60 motor and pump. These assemblies are mounted on rubber shocks and secured to a steel base mounting plate. These units require field plumbing and wiring to the boiler.
CONDENSATE RETURN SYSTEM
(see page 16)
• For model ES12-72 PN ES38083V; for model ES85-180 PN ES38084V.
These systems are used whenever condensed steam can be collected for reuse in the boiler. Returning the conden­sate to the boiler can save a significant amount of energy. The water returned is relatively free of corrosive minerals and carries a substantial amount of heat that does not have to be replenished. A vacuum breaker is required whenever a condensate return system is used.
Each system consists of a vertical condensate return tank, a motor and pump and support plumbing. A 1/2” inlet is located on the tank to accept make-up water. A vent fit­ting is located on the condensate tank top for atmospher­ic air venting. The return fitting is to be plumbed to the trapped condensate return line coming from the process.
A gauge glass and valve set are mounted on the side of the condensate tank. The tank has a ball check valve internally mounted, and a float arm and float ball assem­bly that serve mechanically allowing make-up water to enter the tank as the original supply is used. The pump discharge outlet is to be plumbed to the boiler check valve. The tank drain valve should be plumbed to a prop­er drain line. The motor is required to be wired to the boiler.
14
Page 15
Installation, Operation & Maintenance Manual
Optional Equipment
ACUUM BREAKER SYSTEMS
V
For model ES boilers PN ES89369
•
(cont.)
A vacuum breaker will prevent a boiler from flooding as a
result of the steam condensing internally and creating a vacuum after boiler shutdown. The breaker allows air to enter the boiler shell breaking the vacuum. This system is a must for boilers connected to a condensate return tank. The vacuum breaker consists of a spring-loaded disc and associated piping and is factory plumbed to the boiler.
AUTOMATIC BLOWDOWN SYSTEM
• Extends life of boiler
• Saves labor costs
• Starts the boiler automatically every day
• Shuts down the boiler every day
• Automatically blows down the boiler every day
• Completely programmable, can skip days, different start and shutdown times, different operational durations.
• ES81600 for all model boilers. A stainless steel, motor driven straight-through, self-clean-
ing ball valve with Teflon seats handles particles and dirty fluid without the use of an up-stream strainer or other cleaning device. A timer (Standard analog time clock is set for two hour time intervals, optional digital time clock can be programmed to one minute intervals.) and elec­tronic time delay relay control the boiler and the blow­down valve. A pilot light indicates when the blowdown valve is open. The valve shall be plumbed to a proper drain or recepta­cle. An automatic blowdown system can be installed on any boiler, regardless of size operating pressure or operat­ing duty cycle.
CONTROL VOLTAGE STEPDOWN TRANSFORMER
• Provides 120 Volt (220 Volt export) from main power supply. Factory wired and fused.
BLOWDOWN SEPARATORS
(see page 17)
• For models ES12-48 - PN BDT-ASME36
• For models ES60-180 PN BDT-ASME42 A separator accepts the flash steam and effluent from the
boiler blowdown and reduces the temperature and pressure to insure a safe discharge of water and sludge. Steam flash and pressure are absorbed and pass harmlessly to the out­side via a vent. The separator design utilizes a water seal at the outlet, which permits the operator to introduce cold water from the bottom to mix with the hot water and boiler steam in the blowdown separator. This reduces outlet tem­perature to a safe discharge level.
These separators require specific plumbing from the boiler
blowdown valve and require connection to a cold water sup­ply. (If the separator is less than half full of water after the boiler is blown down cold water must be added to bring the water level to the halfway mark before the next blowdown).
• 0-30 psig pressure gauge; 0-200F temperature gauge; water
sight gauge glass and valve set assembly are included.
MULTISTAGE LOAD PROGRESSIVE SEQUENCERS
Accurate control is provided by automatic progressive sequenc­ing in the use of energy and minimizing wear on electrical components. The sequencers are designed to apply power pro­gressively to larger KW boilers. A factory installed pressure sen­sitive sequential control reacting to steam boiler pressure pro­gressive energizes or de-energizes heating elements through power contactors. A delay between sequencer steps before start-up and between each subsequent step eliminates power surges. Each sequencer is matched and factory pre- set to boil­er system requirements. Electronic progressive sequencers give accurate control of multi-stage loads of the type used in steam boilers. Features include progressive sequencing (first on- first off) that equalizes the operating time of each load. Integral solid-state light emitting diodes show active stages. Should a power interruption occur, all elements are instantly de­energized for safety. Upon resumption of power the control will re-stage the loads one at a time.
15
Page 16
Condensate Return Systems
B
E
A
D
C
9
-
1
/2"
DIA COVER PLATE
EASY ACCESS FOR MAINTENANCE
C
ONDENSATE RETURN FLASH TUBE
OVERFLOW OUTLET 1" NPT (farside) O
VERFLOW (label)
S
IMPLE RUGGED LINKAGE
5" DIA UPPER FLOAT BALL 39011FB
SHUTOFF GATE VALVE
STRAINER CLEANOUT
V
ENT SAFETY BAR
F
LOAT VALVE
39010-F
7-
7
/8"
SIGHT GLASS
99074-1
S
ITE GLASS ASSY
PN 99173C
1
/2" DRAIN VALVE
PUMP EASY ACCESS
1-1/4" VENT WITH SAFETY BAR
V
ENT (label)
1/2" COLD WATER INLET COUPLING
WITH #100 MESH STRAINER
C
ONDENSATE RETURN (label)
TOP VIEW
C
OLD WATER INLET
(
label)
LIMIT MAKEUP WATER PRESSURE TO TO 30 PSI MAXIMUM” (label)
1-
1
/4" CONDENSATE
RETURN COUPLING
Models 38083V & 38084V
Installation, Operation & Maintenance Manual
Notes:
1.
Motor/Pump is closed - Coupled design
2.
Pump capacity as follows:
MODEL 38083V
___________________
PSIG HEAD GPM
___________________
54 125 ft. 3.2
___________________
75 175 ft. 2.9
___________________
97 225 ft. 2.7
___________________
3.
Normal cold water level approximately 1/2 to 5/8 up to visible part of gauge glass.
_____________________________________________________________________________
MODEL Used on "A" "B" "C" "D" "E"` H.P. VOLT/PH/HZ
_____________________________________________________________________________
38083V ES12 - ES72 38-1/4" 18 14-1/4" 14 18 1/3 120 / 1 / 60
_____________________________________________________________________________
38084V ES100 - ES180 51-1/2" 18 14-1/4" 14 30 1/2 120 / 1/ 60
_____________________________________________________________________________
MODEL 38084V
___________________
PSIG HEAD GPM
___________________
54 125 ft. 4.6
___________________
75 175 ft. 4.3
___________________
97 225 ft. 4.0
___________________
PUMP MOTOR
16
Page 17
Installation, Operation & Maintenance Manual
D
A
H
G
Blowdown Separator Tanks- Specifications and Data
Models BDT-ASME 36, 42, 48, 54
Dimensions and Features Suggested Hook-Up to Boiler
Pressure Gauge
"E"Vent
Blowdown Separator
Ventto atmosphere must be full size
Blowdown Inlet
"B"Inlet
Water Gauge
"C" Drain
Temperature
Gauge
3/4"Coupling for Temperature Probe(opt.)
BOILER DIMENSIONS SHIPPING
_______________________________________________________________________
BDT-ASME36 0-5 18" 1" 2" 12" 2" 2" 14" 32" 125
_______________________________________________________________________
BDT-ASME42 6-25 24" 1" 2" 16" 2-1⁄2" 2" 18" 42" 230
_______________________________________________________________________
BDT-ASME48 26-59 30" 1-1⁄4" 2" 16" 3" 2" 18" 48" 260
_______________________________________________________________________
BDT-ASME54 60-100 38" 1-1⁄2" 3" 16" 4" 2" 18" 54" 290
________________________________________________
HP
ABCDEFGHWEIGHT
Handhole Assembly 3"x4"
(exceptBDT-ASME 36)
"F"ColdWater Inlet
&WashoutDrain
Tempered
Blowdown
to Drain
From Boiler Blowdown Outlets
ColdWater Supply
DrainValve (closed duringnormal operator)
The Sussman Separator design incorporates a water seal at the outlet which permits the operator to introduce cold water from the bottom to mix with the hot water and boil­er steam blowdown in the separator. This reduces the out­let temperature to a level that makes it safe for discharge.
NOTE:
1BHP is approximately 10KW.
Maximum Boiler Working Pressure: 250 psi
Maximum Blowdown Separator Pressure: 65 psi
Blowdown Separators are sized in accordance with National Board Standards
Standard Equipment
• 0-100 lb. Pressure Gauge
• 0-200˚ Temperature Gauge
• Water Level Gauge
Constructed in accordance with Section VII Division I ASME Boiler & Pressure Vessel Code
17
Page 18
Installation, Operation & Maintenance Manual
Specifications
__________________________________________
Boiler Bhp Lbs/Hr 3-Ph
Model No. KW Rating Steam** Volts*** Amps
__________________________________________
208 34
ES-12* 12 1.22 36.2 240 29
__________________________________________
ES-18* 18 1.84 54.2 240 44
__________________________________________
ES-24* 24 2.45 72.3 240 58
__________________________________________
ES-30 30 3.06 90.4 240 73
__________________________________________
ES-36 36 3.67 108 240 87
__________________________________________
ES-48 48 4.90 145 240 116
__________________________________________
ES-60 60 6.12 181 240 145
__________________________________________
ES-72 72 7.35 217 240 174
__________________________________________
ES-100 108 11.2 325 240 260
__________________________________________
ES-135 144 14.7 434 240 347
__________________________________________
ES-160 158 16.2 475
__________________________________________
ES-180 180 18.4 542
__________________________________________
* Single phase available ** Steam at 212°F with 50°F feed water. See page 19 for sizing. *** Other voltage available
480 15
208 50
480 22
208 67
480 29 208 84
480 37
208 100
480 44
208 134
480 58
208 167
480 73
208 200
480 87
208 300
480 130
208 400
480 173
240 379 480 190
240 434 480 217
18
Steam Gauge
Pressure/
Temperature
________________
Gauge Temperature
Pressure
________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
Chart
PSIG
15 179 82
10 192 89
5 203 95
0 212 100
1 215 102
3 221 105
5 227 111
9 237 114
11 241 119
15 250 121
17 253 123
19 257 125
21 260 127
23 264 129
25 267 131
27 270 132
29 273 134
31 275 135
33 278 137
35 281 138
37 283 139
39 286 141
41 288 142
43 290 143
45 292 144
47 295 146
49 297 147
51 299 148
53 300 149
55 303 151
60 308 153
65 312 156
70 316 158
75 320 160
80 324 162
85 327 164
90 331 166
95 335 168
100 338 170
F˚ C˚
Page 19
Installation, Operation & Maintenance Manual
Sizing
Use the following Table to determine KW Boiler rating when steam load and feedwater temperatures are known.
___________________________________________________________________
Feed Water
( F˚)
___________________________________________________________________
40 .3347 .3355 .3375 .3388 .3406 .3422 .3431 .3447 .3458 .3464 .3470
___________________________________________________________________
50 .3318 .3326 .3345 .3359 .3376 .3392 .3401 .3417 .3429 .3435 .3441
___________________________________________________________________
60 .3288 .3296 .3316 .3329 .3347 .3363 .3372 .3388 .3400 .3407 .3411
___________________________________________________________________
70 .3259 .3267 .3287 .3300 .3318 .3334 .3343 .3359 .3370 .3376 .3382
___________________________________________________________________
80 .3229 .3238 .3278 .3271 .3288 .3305 .3313 .3329 .3341 .3347 .3353
___________________________________________________________________
90 .3200 .3208 .3238 .3242 .3259 .3275 .3284 .3300 .3312 .3318 .3324
___________________________________________________________________
100 .3171 .3179 .3199 .3212 .3229 .3246 .3255 .3271 .3283 .3288 .3294
___________________________________________________________________
110 .3142 .3150 .3170 .3183 .3200 .3217 .3225 .3242 .3253 .3259 .3265
___________________________________________________________________
120 .3112 .3210 .3140 .3154 .3171 .3287 .3196 .3212 .3224 .3230 .3236
___________________________________________________________________
130 .3083 .3091 .3111 .3124 .3142 .3160 .3167 .3183 .3195 .3200 .3206
___________________________________________________________________
140 .3054 .3062 .3082 .3095 .3113 .3129 .3137 .3154 .3165 .3171 .3177
___________________________________________________________________
150 .3025 .3032 .3052 .3066 .3083 .3099 .3108 .3124 .3136 .3142 .3148
___________________________________________________________________
160 .2995 .3003 .3029 .3036 .3054 .3070 .3079 .3095 .3107 .3113 .3118
___________________________________________________________________
170 .2966 .2974 .2994 .3001 .3025 .3041 .3050 .3066 .3077 .3083 .3089
___________________________________________________________________
180 .2937 .2945 .2964 .2978 2995 .3011 .3020 .3036 .3048 .3054 .3060
___________________________________________________________________
190 .2907 .2915 .2935 .2948 .2966 .2982 .2981 .3007 .3019 .3025 .3030
___________________________________________________________________
200 .2878 .2886 .2906 .2919 .2937 .2953 .2962 .2978 .2989 .2995 .3001
___________________________________________________________________
0210 15 25 40 50 75 100 125 150
Example:
Note:
Need a boiler to produce 450 lbs. steam/hr. at 75 psig with the available feedwater temperature 50˚ F.
From the chart above, find .3417 KW/Lb. of steam 450 lbs. steam/hr. x .3417= 153.8 KW boiler required
Add 20% to required kW for contingencies
19
Page 20
Gauge Glass Installation
Installation, Operation & Maintenance Manual
IMPORTANT NOTE:
Read all warnings and instructions before performing installation or maintenance. Safety glass­es and gloves should be worn at all times when working with or examining water gauge glass and connections. Pressure in generator to be at zero before proceeding. Improper installation or maintenance of gauge glass and connections can cause immediate or delayed breakage resulting in bodily injury and/or property damage.
1.
Apply Teflon tape or pipe dope to pipe threads. Install top gauge fitting (fitting without a drain valve) into the uppermost tapping. Wrench tighten the fitting until it is snug and the glass outlet is pointing at five o'clock (about 1/8 turn from its final downward vertical posi­tion).
2.
Install the bottom gauge fitting (the fitting with a drain valve) until it is snug and the glass outlet is pointing directly upward. Verify top and bottom fittings are threaded into the tappings the same number of turns (distance A= distance B).
3.
Remove glass packing nut, friction washer (or packing gland, depending upon the model), and glass packing from the fittings, and place them, in the same order, on to both ends of the gauge glass. Push both packings about an inch up the gauge glass.
4.
Gently insert one end of the glass into the top gauge fit­ting. Keeping the glass inside the top fitting, gently rotate the top gauge fitting clockwise until vertically aligned with the bottom gauge, then insert glass into bottom fitting until glass bottoms out on the shoulder inside the bottom fitting.
5.
Carefully raise glass about 1/16" and slide lower glass packing down until the glass packing contacts the lower gauge fitting. DO NOT allow the glass to remain in con­tact with any metal!
6.
Carefully slide upper glass packing up as far as possible.
7.
Hand tighten both glass packing nuts, then tighten 1/2 turn more by wrench. Tighten only enough to prevent leakage. DO NOT OVER TIGHTEN! If any leakage should occur, tighten lightly, a quarter turn at a time, checking for leakage after each turn.
IMPORTANT NOTE:
Read all warnings and instructions before performing instal­lation or maintenance.
Top Gauge Fitting
Guard Rod
Friction Washer
(or Packing Gland)
Bottom
Gauge Fitting
WARN I N G
!
Drain Valve
Safety glasses and gloves
A
Vessel Wall
Gauge Glass
Glass Packing Nut
Glass Packing
B
should be worn at all times when working with or examining water gauge glass and con­nections.
Pressure in generator to be at zero before pro­ceeding.
Improper installation or maintenance of gauge glass and connections can cause immediate or delayed breakage resulting in bodily injury and/or property damage.
20
Page 21
Installation, Operation & Maintenance Manual
Gauge Glass Installation - Use and Care
O NOTs
D
• DO NOT use glass if it contains any scratches, chips, or any other visible signs of damage.
• DO NOT reuse any tubular glass or glass packings.
• DO NOT subject gauge glass to bending or torsional stresses.
• DO NOT over tighten glass packing nuts.
• DO NOT allow glass to touch any metal parts.
• DO NOT exceed the recommended pressure of the gauge or gauge glass.
• DO NOT clean the gauge or gauge glass while pressur­ized or in operation.
DO's
• DO verify proper gauge has been supplied.
• DO examine gauge glass and packings carefully for damage before installation.
• DO install protective guards and utilize automatic ball checks where necessary to help prevent injury
in case of glass breakage.
• DO inspect the gauge glass daily, keep maintenance records, and conduct routine replacements.
• DO protect glass from sudden changes in temperatures such as drafts, water spray, etc.
AINTENANCE
M
Examine the gauge glass regularly for any signs of clouding, scratching, erosion, or corrosion. The glass should be inspected daily until the need for replace­ment becomes apparent. This will help establish the routine inspection and routine replacement schedules.
CLEANING
Use commercial non-abrasive glass cleaners to keep glass clean. Use diluted acids such as Hydrochloric (muriatic) acid when regular cleaners do not seem to work. Do not use wire brushes or any other abrasive materials which could scratch the glass.
INSPECTION
Examine the surface of the glass for scratches, corro­sion, chips, cracks, surface flaws, or nicks. To do this, shine a very bright concentrated light at an angle of about 45 degrees.A defective glass will glisten as the light strikes imperfections. Glass which appears cloudy or roughened, and will not respond to cleaning, should be replaced.
STORING
Keep gauge glass in original packaging until ready to install.
21
Page 22
Installation, Operation & Maintenance Manual
Element Replacement
READ INSTRUCTIONS COMPLETELY BEFORE STARTING WORK
CAUTIO N
!
McDonnell Miller low water cut-off and aux. low water cutoff (if sup­plied) is operating properly. The float chamber and lower equalizer col­umn of the MM control must be completely clear of sludge or other for­eign matter. Failure to do this may cause the immediate burn-out of the new elements. If the unit is probe equipped, check condition of the probes and isolator.
All elements are thoroughly checked before shipment The manufacturer cannot be responsible for burn-outs caused by a faulty low water cut-off.
The lower equalizer column can best be examined by breaking the unions on either side and then visually and manually examining the piping with your finger or probes to see if it is clear and clean.
1.
Disconnect boiler from electric power supply at main safety switch or fuse panel.
Then turn boiler switch to “OFF" position.
2.
Close water supply valve on incoming water supply line. Drain boiler completely of water.
3.
Open boiler door to access heating element.
4.
Disconnect wire (electric) leads connecting element to main power system of boiler.
Again, note wire connections to facilitate re-assembly. Proceed to remove and discard (6) bolts from flange.
IMPORTANT:
Remove and discard six (5/16"-18) bolts from flange. Do not reuse these bolts.
5.
Thoroughly clean boiler flange of all foreign material. Be certain no part of old gasket
remains on flange.
6.
Apply "Slic-Tite" Gasket Compound (or equal) to both surfaces of new gasket supplied
with replacement element. Proceed to install element flange assembly with gasket between boiler flange and element flange. In doing this, be careful to align flange holes so element wire connection terminals on element assembly are in line with previously disconnected wire leads to facilitate easy connections.
NOTE:
7.
8.
9.
10.
11.
12.
!
Observe markings on element flange. Install element marking “TOP” on top.
Use only new element flange bolts. Tighten all (6) element flange bolts to a torque value
of 22 lb-ft each (see illustration).
Connect all wires to the terminals. Tighten all element terminals to a torque value of
20 lb-in each (see illustration). Make sure all wires are clean and bright to assure good electrical contact.
Check that the wires are correctly connected to the contactor terminals and are tightened
to a torque value of 45 lb-in. (see illustration). Make sure all wires are clean and bright to assure good electrical contact.
Open water valve to allow water supply to reach boiler feed mechanism.
As boiler automatically refills, observe the new flange assembly for possible leaks. If water is noticed, the bolts must be re-tightened. Before doing this, turn the boiler off at the main fuse safety switch.
When boiler reaches working pressure, check flange assembly again for leaks.
CAUTIO N
Before Installing your new elements be sure the
Boiler with McDonnell Miller
11⁄2”
Note the wire connections to facilitate re-assembly (see wiring schematic).
Follow maintenance instructions provided with the boiler.
1”Steam EqualizingPipe
Pumpand LowWater Control
Normal BoilerWater Line
Cut-Off Level isArrowMark
Blowdown Valve
1”Water Equalizing Pipe
Torque Values:
Torque Wrench
Element Flange Bolts: 22 lb-ft
Torque Wrench
Element Terminals: 20 lb-in
Torque Wrench
Contactor Terminals: see Torque chart
For I llustrat ive Purposes Only. Power wiri ng show n in appr oxi mate factory- ins talled l ocation
TORQUE VALUES
Element Flange Bolts 22 lb-ft Element Terminals 20 lb-in Contactor Terminals 50 amp 25 lb-in
60 amp 45 lb-in 75 amp 75 lb-in
22
Page 23
Installation, Operation & Maintenance Manual
Water Quality Information for Carbon Steel Boilers
For optimum results, the feedwater supply should be tested prior to initial start-up. If the mineral content exceeds the following recommended limits, various external treatment processes (water softener, reverse osmosis, etc.) may be used to correct the problem.
NOTE:
An analysis of the on-site boiler feedwater must be made by a recognized and reliable water treatment company to ascertain the existing condition and treatment required.
RECOMMENDED FEEDWATER QUALITY
HARDNESS, ppm 8 – 85 (~0.5 – 5 gpg) P-ALKALINITY, ppm 85 – 410 (~5 – 24 gpg) T-ALKALINITY, ppm 200 – 500 (~7 – 0 gpg) pH (strength of alkalinity) 8.0 – 11.4 SPECIFIC RESISTIVITY ~50k Ω cm (50,000 ohm-centimeter)
Blow down the boiler on at least a once-a-day basis. If boiler water or feed-water are outside the above limits, a more frequent blowdown is required.
Water quality can affect efficiency or result in boiler damage if neglected. Boiler feedwater contains impurities in solution and suspension. These impurities concentrate in the boiler since the steam generated is essentially pure. The concentration of these impurities increases as more feedwater is introduced into the boiler and steam is produced. If the suspended solids are allowed to concentrate beyond certain limits, a deposit or “scale” will form on the boiler’s internal surfaces. This deposit can interfere with proper boiler operation and cause boiler failure.
The concentration of these impurities is generally controlled by the feedwater quality and by blowdown. Blowdown refers to removing a portion of the boiler water with high solids concentration and replacing it with make-up water of a lower concentration.
23
Page 24
A Division of Sussman-Automatic Corporation
43-20 34th Street, Long Island City, NY 11101 • (718) 937-4500 1-800-238-3535 • Fax: (718) 937-4676 • email: [email protected]
www.sussmanboilers.com
M A D E I N U S A
PUR 101137 4.13
Loading...