Sussman ES12-18, ES135-180, ES24-72, HU40-55, ES85-100 Installation, Operation And Maintenance Manual

...
ES & HU Installation, Operation
a nd Maintenance Manual
A Division of Sussman-Automatic Corporation
43-20 34th Street, Long Island City, NY 11101 • (718) 937-4500
1-800-238-3535 • Fax: (718) 937-4676 • email: seb@sussmancorp.com
www.sussmanboilers.com
PUR 101137
REV
Installation, Operation & Maintenance Manual
U S A
Designed, Engine ered and Assembled in th e
Model No. _____________________________________
Boiler Serial No. _______________________________
National Board No. ___________________________
Safety Valve Set Pressure _______________ PSIG
Power Circuit Voltage _______________________
Control Circuit Voltage ______________________
Amps __________ Phase _________ HZ __________
Steam Outlet Valve Size _____________ NPT
Products covered by this manual:
_________________________________________________________________________________
KW Max Design Work
Series Range Steam Rate* BHP Pressure Pressure
_________________________________________________________________________________
ES, HU 12-180 36-542 lbs/hr 1.2-18.4 0-100 psig 85 psig
_________________________________________________________________________________
*Steam Rate: Steam at 212˚ F with 50˚ F feed water
ES and HU boilers are of Carbon Steel construction. See page 23 for Water Quality Information.
TABLE OF CONTENTS
Dimensional Information and
Component Identification . . . . . . . . . . . . . . . . . 3
Dimensional & Clearing Specifications . . . . . . . . . 4
Wiring Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Pre-Operation Check. . . . . . . . . . . . . . . . . . . . . . . . 8
Setting Pressure Controls . . . . . . . . . . . . . . . . . . . . 9
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Blowdown. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-11
Digital Timer Operation Instructions . . . . . . . . . . 12
Timing Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Standard Equipment
Auxiliary Low Water Cut Off . . . . . . . . . . . . . . . . 14
Line Pressure Water Feed System . . . . . . . . . . . . . 14
Optional Equipment
High Pressure Water Feed System. . . . . . . . . . . . . 14
Condensate Return System. . . . . . . . . . . . . . . . . . 14
Vacuum Breaker Systems . . . . . . . . . . . . . . . . . . . 15
Automatic Blowdown System. . . . . . . . . . . . . . . . 15
Control Voltage Stepdown Transformer . . . . . . . . 15
Blowdown Separators . . . . . . . . . . . . . . . . . . . . . 15
Multistage Load Progressive Sequencers . . . . . . . . 15
Condensate Return Systems . . . . . . . . . . . . . . . . . 16
Blowdown Separator Tanks . . . . . . . . . . . . . . . . . 17
Specification Charts. . . . . . . . . . . . . . . . . . . . . . . . 18
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Gauge Glass Installation . . . . . . . . . . . . . . . . . 20-21
Element Replacement . . . . . . . . . . . . . . . . . . . . . . 22
Water Quality Information. . . . . . . . . . . . . . . . . . 23
IMPORTANT NOTE:
As you follow these instructions, you will notice warning and caution symbols. This blocked information is important for the safe and efficient installation and operation of electric boilers. These are two types of potential hazards that may occur during this installation and operation:
WAR N I N G
!
may cause serious injury or death if precautions are not followed.
states a hazard which
CA U T I ON
!
minor injury or product damage may occur if you do not follow instructions.
signals a situation where
2
IMPORTANT NOTE:
This highlights information that is especially relevant to a problem-free installation.
Installation, Operation & Maintenance Manual
Dimensional Information & Component Identification
Models: ES, HU
A
B
Height
M
C
E
J
Width
F
G
K
D
Length
SYMBOL ITEM HU40-55 HU75-205 HU310 HU410-550
Height Overall Height 36" 46" 61" 61" Length Overall Length 28" 33" 34" 36" Width Overall Width 22" 22" 25"* 27"**
A Steam Outlet 6-1/4" 10" 8-1/4" 9" B Steam Outlet 10-1/4" 17" 17-1/4" 18-1/4" C M/M Drain Valve 5" 12" 17" 16-3/4" D M/M Drain Valve 6-1/2" 6" 6-1/4" 6-1/4" E Check Valve 14" 9" 17" 16-3/4"
F PV Drain Valve 2-3/4" 2-1/4" 2-3/4" 2-3/4"
G PV Drain Valve 6-1/4" 9-1/2" 7-3/4" 9-1/4"
J Clearance 3-3/4" 3-1/2" 4" 4"
K Check Valve 2-1/2" 2-3/4" 3" 3"
M Door Width 8-3/4" 14" 12-3/4" 14-3/4"
Allow minimum 36 inches clearance in front of doors for servicing of heating elements. Recommended clearance: 24 inches other sides of boiler for servicing.
* ES100 Width shown is for 480 volts with one front mount fuse box, 208/240 volt that includes a front and back mounted fuse box is 30" wide ** ES135 -180 Width shown is for 480 volts with one front mount fuse box, 208/240 volt that includes a front and back mounted fuse box is 32" wide All 480 volt ES100-180 include a front mounted box for fuses (shown as dotted lines) All 208 and 240 Volt ES100-180 include a front and back mounted box for fuses (shown as dotted lines) ES72 208 Volt includes a front mounted fuse box, overall width increases to 24"
ES12-18 ES24-72 ES85-100 ES135-180
MODEL 100 PSIG 15 PSIG 100 PSIG 15 PSIG
ES12-18, HU40-55 ES24-36, HU75-105 1”NPT 1”NPT
Steam Outlet Safety Valve Outlet
1
2
NPT
1
2
NPT
1
NPT
2
1
NPT
2
ES48, HU140 1”NPT 1”NPT 1” NPT ES60-72, HU175-205 1”NPT 1”NPT 1” NPT 1” NPT
1
ES85-100, HU310 1
NPT 3”NPT 1”NPT 1
2
ES135-180, HU410-550 2”NPT 3”NPT 1”NPT 1
Water inlets for all ES & HU boilers are 1/2" NPT Drains for all ES and HU boilers are 1" NPT
3
NPT
4
3
NPT
4
3
NPT
4
1
NPT
4
1
NPT
2
3
Installation, Operation & Maintenance Manual
Dimensional & Clearance Specifications
Height
perating
Steam Outlet
A
Gauge Glass Assembly
D
Drain Valve
Width
O P C
On/Off
Switch
ressure ontrol
EL
High Limit Pressure Control
ressure
P
auge
G
Safety Valve
Liquid Level Control
ER
Water Feed Inlet
F
Length
Left Side Elevation Front Elevation
Allow 24" all around for servicing, 36” in front of doors, minimum.
__________________________________________________
Clearance from combustible surfaces
__________________________________________________
A
_________________________________________________________________________
B
_________________________________________________________________________
D
_________________________________________________________________________
EL
_________________________________________________________________________
ER
_________________________________________________________________________
F
_________________________________________________________________________
G-
_________________________________________________________________________
All 480 volt ES100 - 180 include a front mounted box for fuses (shown as dotted lines) All 208 and 240 Volt ES100 - 180 include a front and back mounted box for fuses (shown as dotted lines)
ES72 208 Volt includes a front mounted fuse box.
1" Clearance above top of boiler
A Clearance from Front of boiler. Prefix "C" to numeral indicates acceptability for
closet or alcove installations; prefix acceptability for alcove installations but not for closet installations.
1" Clearance from back of boiler.
1" Clearance from left side of boiler.
16" Clearance from right side of boiler.
C Indicates type of flooring: "NC" for non-combustible; "C" for combustible.
Total minimum free area in square inches of close ventilating openings.
4
P1
C1
C2
C
3
C
4
P2
P2
P3
P3
(
See Note 6)
C1 C2 C3 C4
H1 H3 H5
H6
ES/SSB/CU 81600 Automatic Blowdown System (optional)
Wiring Diagram
Power Circuit and Control Circuit use different voltage
Installation, Operation & Maintenance Manual
Three Phase Main Power Supply
NOTES:
1. Power Terminal Block only on boilers with two or more contactors.
2. On boilers with only one power contactor, connect power voltage to line side of contactor.
3. Power Fuses only on boilers rated 120 amperes and larger.
4. See Parts List for contactor and heating element information.
5. Element cut-off switches and second operating pressure control on ES/SSB 100-180 without sequencer
6. Refer to boiler nameplate for control and main power voltage
5
Installation
Installation, Operation & Maintenance Manual
REFER TO NATIONAL AND ALL APPLICABLE LOCAL CODES FOR SPECIFIC INSTALLATION REQUIREMENTS.
1. The boiler should be mounted on a solid, level foundation.
2. The boiler should be located with suitable clearances, refer to page 3 and Code requirements.
NOTE:
Allow a minimum of 36 inches clearance in front of doors for servicing of heating elements. Recommended clear­ance: 24 inches other sides of boiler for servicing.
Piping
ALL PIPING SHOULD BE INSTALLED BY A QUALIFIED LICENSED PLUMBER IN ACCOR­DANCE WITH NATIONAL AND LOCAL CODES.
1. When water feed is other than pump type the water
supply pressure must be 10 psig greater than boiler operating pressure to assure water supply maintains proper water level in the boiler. Insufficient water levels can result in improper boiler operation. (Keep feed water valves open at all times during normal operation.)
2. Connect steam line with a valve to boiler steam outlet
3. Do not install boiler in any location where water could freeze.
4. Do not install boiler outdoors.
5. Do not install boiler near flammable or corrosive materials.
6. Do not install boiler in a location where leakage from the boiler tank or piping can damage to adjacent areas or to lower floors of the structure. Provide a floor drain and properly sloped floor from the boiler towards the drain or install a suit­ably plumbed drain pan under the boiler.
NOTE:
ice higher than the maximum boiler pressure should be plumbed on the steam outlet line; failure to do so can cause heating element breakdown. See page 3 for steam outlet valve size.
4. Provide for boiler drain connection, a daily blowdown is
5. Safety valve shall be plumbed according to local code.
NOTE:
sized less than the outlet size of the safety valve.
For best performance, a valve rated for steam serv-
required. A "Blowdown Separator Tank" may be necessary, check with local code.
The safety valve shall not be plumbed with a line
6
Installation, Operation & Maintenance Manual
Wiring
ALL ELECTRICAL WIRING MUST BE PERFORMED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES.
CA U T I ON
!
being supplied to the boiler matches the power voltage and phase of the boiler. Connecting incorrect power supply can damage boiler components or cause improper boiler opera­tion. If the boiler power requirements do not match the power to be supplied to the boiler the boiler must be returned to the factory for conversion. Boilers cannot be field converted.
ALL BOILERS ARE PRE-WIRED AND TESTED PRIOR TO SHIPMENT.
1. Ground boiler according to National Electric Code requirements to avoid shock.
2. Power wiring to boiler should be in accordance with National and Local Electrical Code requirements follow­ing wiring diagram supplied. Use proper size wire. Wire size is specified adjacent to field wiring terminals. This label states the wire size [AWG or MCM], minimum temperature rating (90 C) and conductor material (copper only). Deviation from these requirements may result in improper or unsafe boiler operation.
3. A disconnect switch employing circuit breakers or fuses should be installed between the main power source and the boiler. This disconnect switch should be located near the boiler and clearly marked for easy access and identi­fication should the boiler need to be turned off due to an emergency.
Assure that the power voltage and phase
4. Boiler control circuit is 120 Volt*. Unless boiler has an optional step down transformer, a separate 120 Volt power feed wiring is required to be connected to the control circuit terminal block. A 15 Amp circuit is required for all boilers. If a 3/4 HP feed water motor and pump assembly is connected to the boiler, then a 20 Amp circuit is required.
5. If a separate control circuit is used, it should be connected to the control circuit terminal block.
6. Remote mounted water feed systems (i.e. condensate return, motor and pump) should be connected to the junction box provided on the outside of the boiler jacket.
7. With main power off, make sure all wiring termina­tions are tight to avoid arcing, carbonizing or over­heating of contacts.
CA U T I ON
!
damage due to water line connections. An industrial type lightning/surge protector should be installed accord­ing to the manufacturer's recommendation at the service entrance. Consult your contractor or electrical dealer.
WAR N I N G
!
cation of wiring system voids the warranty and may lead to dangerous operating conditions.
Boilers are susceptible to lightning
Substitution of components or modifi-
7
Installation, Operation & Maintenance Manual
Pre-Operation Check (All Boilers)
LWCO/PUMP CONTROL OPERATION AND TESTING
1. All valves for incoming water supply are to be fully opened. Main disconnect switch is to be in the "on" position. Boiler main switch is to be in the "on" position. Since boiler will be empty the pump or solenoid will be energized allowing the boiler to fill with water. Control will automatically fill boiler to proper operating water level and the pump/solenoid will be de­energized. Contactors will then energize, applying voltage to the heating elements.
2. Pump switch operation – at this point water should be visible approximately half way up the sight glass. Slowly open the drain valve located at the bottom of the boiler. Water level in the sight glass will begin to drop, allowing the low water cut off/pump control to energize the feed water system. Close valve for proper operation.
3. Low water cutout switch performance – open the drain valve completely. Maintain this condition until water level falls within the gauge glass enough to cause the low water cutout switch to de-energize the heating elements. All of the contactors will be in a de-energized or open state at this time. Close the drain valve, water feed system will automatically refill the boiler and the contactors will re-energize.
Pressure Controls, Operation and Testing
Boilers equipped with an auxiliary low water cut-off control with a manual re-set button (required as mandatory equipment is some states): once the correct operating water level has been reached, it will be necessary to depress the reset button in order for the contactors to re-energize.
NOTE:
down system:
• For test 1 - the blowdown time clock must be in the
• For test 2 and 3 - in order for the drain valve to open
For boilers equipped with an automatic blow-
“run” mode before the boiler will automatically fill.
the blowdown clock must be in the “off” mode. (See blowdown time clock insert) The automatic blowdown indicator light will be on when the valve is open. This light will remain on for the duration of the blowdown cycle (a few seconds). It may be nec­essary to cycle the time clock from the “run” to “off” mode several times.
NOTE:
All boilers are provided with one high limit pres-
sure control and at least one operating pressure control.
1. The high limit pressure control is equipped with a manual reset feature. There is no subtractive differential scale with this type of control
2. All pressure controls are equipped with an adjusting screw, allowing for setting of desired operational and high limit pressures. To reduce pressure setting, turn adjusting screw in direction that allows indicator to point to a lower pressure setting on the scale. To increase pressure setting turn adjusting screw in direction that allows indicator to point to a higher pressure on the scale
NOTE:
10% above the desired normal operating pressure (15 psig boilers should be set to 13 psig)
3. Operating pressure controls, except low pressure (15 psig)
4. Operating pressure control check: Close steam outlet valve
It is recommended that the high limit control be set
types have a separate differential scale. Differential indicates pressure below the main operating maximum pressure, the pressure control will re-set. The differential set point is adjusted in the same manner by turning the adjusting screw in the desired direction to increase or decrease the differential pressure value.
[supplied by customer] and adjust operating pressure
control to 20 psig (10 psig for low pressure boilers) and the differential to 10 psig (Note: Low pressure boilers do not have a differential setting). Set the high limit pressure control to 30 psig (13 psig for low pressure boilers). Switch boiler on to allow steam pressure to build-up. Pressure gauge reading will increase and the operating pressure control will de-energize the contactor(s) when the pressure gauge indicates 20 psig (10 psig for low pressure boilers). Open steam outlet valve to bleed off pressure. When the pressure gauge reading decreases below 10 psig (differential) (3 psig for low pressure boilers) the operating pressure control will re-energize the contactor(s).
5. High limit pressure control check: FOR TEST PURPOSES ONLY! Set the high limit pressure control 10 psig (5 psig for low pressure boilers) lower than the operating pressure control. Close the steam outlet valve and switch the boiler on to allow boiler to build pressure. When the pressure gauge indicates the pressure at which the high limit pressure control is set, the high limit pressure control re-set button will pop-up and the control will de­energize the contactor(s). Open the steam outlet valve to bleed off pressure. The contactor(s) should not re­energize on pressure drop. The contactor(s) should only re-energize when the pressure has dropped and the high limit pressure control reset button is depressed.
8
Loading...
+ 16 hidden pages