Sussman ES12-18, ES135-180, ES24-72, HU40-55, ES85-100 Installation, Operation And Maintenance Manual

...
Page 1
ES & HU Installation, Operation
a nd Maintenance Manual
A Division of Sussman-Automatic Corporation
43-20 34th Street, Long Island City, NY 11101 • (718) 937-4500
1-800-238-3535 • Fax: (718) 937-4676 • email: [email protected]
www.sussmanboilers.com
PUR 101137
REV
Page 2
Installation, Operation & Maintenance Manual
U S A
Designed, Engine ered and Assembled in th e
Model No. _____________________________________
Boiler Serial No. _______________________________
National Board No. ___________________________
Safety Valve Set Pressure _______________ PSIG
Power Circuit Voltage _______________________
Control Circuit Voltage ______________________
Amps __________ Phase _________ HZ __________
Steam Outlet Valve Size _____________ NPT
Products covered by this manual:
_________________________________________________________________________________
KW Max Design Work
Series Range Steam Rate* BHP Pressure Pressure
_________________________________________________________________________________
ES, HU 12-180 36-542 lbs/hr 1.2-18.4 0-100 psig 85 psig
_________________________________________________________________________________
*Steam Rate: Steam at 212˚ F with 50˚ F feed water
ES and HU boilers are of Carbon Steel construction. See page 23 for Water Quality Information.
TABLE OF CONTENTS
Dimensional Information and
Component Identification . . . . . . . . . . . . . . . . . 3
Dimensional & Clearing Specifications . . . . . . . . . 4
Wiring Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Pre-Operation Check. . . . . . . . . . . . . . . . . . . . . . . . 8
Setting Pressure Controls . . . . . . . . . . . . . . . . . . . . 9
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Blowdown. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-11
Digital Timer Operation Instructions . . . . . . . . . . 12
Timing Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Standard Equipment
Auxiliary Low Water Cut Off . . . . . . . . . . . . . . . . 14
Line Pressure Water Feed System . . . . . . . . . . . . . 14
Optional Equipment
High Pressure Water Feed System. . . . . . . . . . . . . 14
Condensate Return System. . . . . . . . . . . . . . . . . . 14
Vacuum Breaker Systems . . . . . . . . . . . . . . . . . . . 15
Automatic Blowdown System. . . . . . . . . . . . . . . . 15
Control Voltage Stepdown Transformer . . . . . . . . 15
Blowdown Separators . . . . . . . . . . . . . . . . . . . . . 15
Multistage Load Progressive Sequencers . . . . . . . . 15
Condensate Return Systems . . . . . . . . . . . . . . . . . 16
Blowdown Separator Tanks . . . . . . . . . . . . . . . . . 17
Specification Charts. . . . . . . . . . . . . . . . . . . . . . . . 18
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Gauge Glass Installation . . . . . . . . . . . . . . . . . 20-21
Element Replacement . . . . . . . . . . . . . . . . . . . . . . 22
Water Quality Information. . . . . . . . . . . . . . . . . . 23
IMPORTANT NOTE:
As you follow these instructions, you will notice warning and caution symbols. This blocked information is important for the safe and efficient installation and operation of electric boilers. These are two types of potential hazards that may occur during this installation and operation:
WAR N I N G
!
may cause serious injury or death if precautions are not followed.
states a hazard which
CA U T I ON
!
minor injury or product damage may occur if you do not follow instructions.
signals a situation where
2
IMPORTANT NOTE:
This highlights information that is especially relevant to a problem-free installation.
Page 3
Installation, Operation & Maintenance Manual
Dimensional Information & Component Identification
Models: ES, HU
A
B
Height
M
C
E
J
Width
F
G
K
D
Length
SYMBOL ITEM HU40-55 HU75-205 HU310 HU410-550
Height Overall Height 36" 46" 61" 61" Length Overall Length 28" 33" 34" 36" Width Overall Width 22" 22" 25"* 27"**
A Steam Outlet 6-1/4" 10" 8-1/4" 9" B Steam Outlet 10-1/4" 17" 17-1/4" 18-1/4" C M/M Drain Valve 5" 12" 17" 16-3/4" D M/M Drain Valve 6-1/2" 6" 6-1/4" 6-1/4" E Check Valve 14" 9" 17" 16-3/4"
F PV Drain Valve 2-3/4" 2-1/4" 2-3/4" 2-3/4"
G PV Drain Valve 6-1/4" 9-1/2" 7-3/4" 9-1/4"
J Clearance 3-3/4" 3-1/2" 4" 4"
K Check Valve 2-1/2" 2-3/4" 3" 3"
M Door Width 8-3/4" 14" 12-3/4" 14-3/4"
Allow minimum 36 inches clearance in front of doors for servicing of heating elements. Recommended clearance: 24 inches other sides of boiler for servicing.
* ES100 Width shown is for 480 volts with one front mount fuse box, 208/240 volt that includes a front and back mounted fuse box is 30" wide ** ES135 -180 Width shown is for 480 volts with one front mount fuse box, 208/240 volt that includes a front and back mounted fuse box is 32" wide All 480 volt ES100-180 include a front mounted box for fuses (shown as dotted lines) All 208 and 240 Volt ES100-180 include a front and back mounted box for fuses (shown as dotted lines) ES72 208 Volt includes a front mounted fuse box, overall width increases to 24"
ES12-18 ES24-72 ES85-100 ES135-180
MODEL 100 PSIG 15 PSIG 100 PSIG 15 PSIG
ES12-18, HU40-55 ES24-36, HU75-105 1”NPT 1”NPT
Steam Outlet Safety Valve Outlet
1
⁄
2
”
NPT
1
”
⁄
2
NPT
1
NPT
”
⁄
2
1
NPT
”
⁄
2
ES48, HU140 1”NPT 1”NPT 1” NPT ES60-72, HU175-205 1”NPT 1”NPT 1” NPT 1” NPT
1
ES85-100, HU310 1
NPT 3”NPT 1”NPT 1
”
⁄
2
ES135-180, HU410-550 2”NPT 3”NPT 1”NPT 1
Water inlets for all ES & HU boilers are 1/2" NPT Drains for all ES and HU boilers are 1" NPT
3
NPT
”
⁄
4
3
NPT
”
⁄
4
3
NPT
”
⁄
4
1
NPT
”
⁄
4
1
NPT
”
⁄
2
3
Page 4
Installation, Operation & Maintenance Manual
Dimensional & Clearance Specifications
Height
perating
Steam Outlet
A
Gauge Glass Assembly
D
Drain Valve
Width
O P C
On/Off
Switch
ressure ontrol
EL
High Limit Pressure Control
ressure
P
auge
G
Safety Valve
Liquid Level Control
ER
Water Feed Inlet
F
Length
Left Side Elevation Front Elevation
Allow 24" all around for servicing, 36” in front of doors, minimum.
__________________________________________________
Clearance from combustible surfaces
__________________________________________________
A
_________________________________________________________________________
B
_________________________________________________________________________
D
_________________________________________________________________________
EL
_________________________________________________________________________
ER
_________________________________________________________________________
F
_________________________________________________________________________
G-
_________________________________________________________________________
All 480 volt ES100 - 180 include a front mounted box for fuses (shown as dotted lines) All 208 and 240 Volt ES100 - 180 include a front and back mounted box for fuses (shown as dotted lines)
ES72 208 Volt includes a front mounted fuse box.
1" Clearance above top of boiler
A Clearance from Front of boiler. Prefix "C" to numeral indicates acceptability for
closet or alcove installations; prefix acceptability for alcove installations but not for closet installations.
1" Clearance from back of boiler.
1" Clearance from left side of boiler.
16" Clearance from right side of boiler.
C Indicates type of flooring: "NC" for non-combustible; "C" for combustible.
Total minimum free area in square inches of close ventilating openings.
4
Page 5
P1
C1
C2
C
3
C
4
P2
P2
P3
P3
(
See Note 6)
C1 C2 C3 C4
H1 H3 H5
H6
ES/SSB/CU 81600 Automatic Blowdown System (optional)
Wiring Diagram
Power Circuit and Control Circuit use different voltage
Installation, Operation & Maintenance Manual
Three Phase Main Power Supply
NOTES:
1. Power Terminal Block only on boilers with two or more contactors.
2. On boilers with only one power contactor, connect power voltage to line side of contactor.
3. Power Fuses only on boilers rated 120 amperes and larger.
4. See Parts List for contactor and heating element information.
5. Element cut-off switches and second operating pressure control on ES/SSB 100-180 without sequencer
6. Refer to boiler nameplate for control and main power voltage
5
Page 6
Installation
Installation, Operation & Maintenance Manual
REFER TO NATIONAL AND ALL APPLICABLE LOCAL CODES FOR SPECIFIC INSTALLATION REQUIREMENTS.
1. The boiler should be mounted on a solid, level foundation.
2. The boiler should be located with suitable clearances, refer to page 3 and Code requirements.
NOTE:
Allow a minimum of 36 inches clearance in front of doors for servicing of heating elements. Recommended clear­ance: 24 inches other sides of boiler for servicing.
Piping
ALL PIPING SHOULD BE INSTALLED BY A QUALIFIED LICENSED PLUMBER IN ACCOR­DANCE WITH NATIONAL AND LOCAL CODES.
1. When water feed is other than pump type the water
supply pressure must be 10 psig greater than boiler operating pressure to assure water supply maintains proper water level in the boiler. Insufficient water levels can result in improper boiler operation. (Keep feed water valves open at all times during normal operation.)
2. Connect steam line with a valve to boiler steam outlet
3. Do not install boiler in any location where water could freeze.
4. Do not install boiler outdoors.
5. Do not install boiler near flammable or corrosive materials.
6. Do not install boiler in a location where leakage from the boiler tank or piping can damage to adjacent areas or to lower floors of the structure. Provide a floor drain and properly sloped floor from the boiler towards the drain or install a suit­ably plumbed drain pan under the boiler.
NOTE:
ice higher than the maximum boiler pressure should be plumbed on the steam outlet line; failure to do so can cause heating element breakdown. See page 3 for steam outlet valve size.
4. Provide for boiler drain connection, a daily blowdown is
5. Safety valve shall be plumbed according to local code.
NOTE:
sized less than the outlet size of the safety valve.
For best performance, a valve rated for steam serv-
required. A "Blowdown Separator Tank" may be necessary, check with local code.
The safety valve shall not be plumbed with a line
6
Page 7
Installation, Operation & Maintenance Manual
Wiring
ALL ELECTRICAL WIRING MUST BE PERFORMED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES.
CA U T I ON
!
being supplied to the boiler matches the power voltage and phase of the boiler. Connecting incorrect power supply can damage boiler components or cause improper boiler opera­tion. If the boiler power requirements do not match the power to be supplied to the boiler the boiler must be returned to the factory for conversion. Boilers cannot be field converted.
ALL BOILERS ARE PRE-WIRED AND TESTED PRIOR TO SHIPMENT.
1. Ground boiler according to National Electric Code requirements to avoid shock.
2. Power wiring to boiler should be in accordance with National and Local Electrical Code requirements follow­ing wiring diagram supplied. Use proper size wire. Wire size is specified adjacent to field wiring terminals. This label states the wire size [AWG or MCM], minimum temperature rating (90 C) and conductor material (copper only). Deviation from these requirements may result in improper or unsafe boiler operation.
3. A disconnect switch employing circuit breakers or fuses should be installed between the main power source and the boiler. This disconnect switch should be located near the boiler and clearly marked for easy access and identi­fication should the boiler need to be turned off due to an emergency.
Assure that the power voltage and phase
4. Boiler control circuit is 120 Volt*. Unless boiler has an optional step down transformer, a separate 120 Volt power feed wiring is required to be connected to the control circuit terminal block. A 15 Amp circuit is required for all boilers. If a 3/4 HP feed water motor and pump assembly is connected to the boiler, then a 20 Amp circuit is required.
5. If a separate control circuit is used, it should be connected to the control circuit terminal block.
6. Remote mounted water feed systems (i.e. condensate return, motor and pump) should be connected to the junction box provided on the outside of the boiler jacket.
7. With main power off, make sure all wiring termina­tions are tight to avoid arcing, carbonizing or over­heating of contacts.
CA U T I ON
!
damage due to water line connections. An industrial type lightning/surge protector should be installed accord­ing to the manufacturer's recommendation at the service entrance. Consult your contractor or electrical dealer.
WAR N I N G
!
cation of wiring system voids the warranty and may lead to dangerous operating conditions.
Boilers are susceptible to lightning
Substitution of components or modifi-
7
Page 8
Installation, Operation & Maintenance Manual
Pre-Operation Check (All Boilers)
LWCO/PUMP CONTROL OPERATION AND TESTING
1. All valves for incoming water supply are to be fully opened. Main disconnect switch is to be in the "on" position. Boiler main switch is to be in the "on" position. Since boiler will be empty the pump or solenoid will be energized allowing the boiler to fill with water. Control will automatically fill boiler to proper operating water level and the pump/solenoid will be de­energized. Contactors will then energize, applying voltage to the heating elements.
2. Pump switch operation – at this point water should be visible approximately half way up the sight glass. Slowly open the drain valve located at the bottom of the boiler. Water level in the sight glass will begin to drop, allowing the low water cut off/pump control to energize the feed water system. Close valve for proper operation.
3. Low water cutout switch performance – open the drain valve completely. Maintain this condition until water level falls within the gauge glass enough to cause the low water cutout switch to de-energize the heating elements. All of the contactors will be in a de-energized or open state at this time. Close the drain valve, water feed system will automatically refill the boiler and the contactors will re-energize.
Pressure Controls, Operation and Testing
Boilers equipped with an auxiliary low water cut-off control with a manual re-set button (required as mandatory equipment is some states): once the correct operating water level has been reached, it will be necessary to depress the reset button in order for the contactors to re-energize.
NOTE:
down system:
• For test 1 - the blowdown time clock must be in the
• For test 2 and 3 - in order for the drain valve to open
For boilers equipped with an automatic blow-
“run” mode before the boiler will automatically fill.
the blowdown clock must be in the “off” mode. (See blowdown time clock insert) The automatic blowdown indicator light will be on when the valve is open. This light will remain on for the duration of the blowdown cycle (a few seconds). It may be nec­essary to cycle the time clock from the “run” to “off” mode several times.
NOTE:
All boilers are provided with one high limit pres-
sure control and at least one operating pressure control.
1. The high limit pressure control is equipped with a manual reset feature. There is no subtractive differential scale with this type of control
2. All pressure controls are equipped with an adjusting screw, allowing for setting of desired operational and high limit pressures. To reduce pressure setting, turn adjusting screw in direction that allows indicator to point to a lower pressure setting on the scale. To increase pressure setting turn adjusting screw in direction that allows indicator to point to a higher pressure on the scale
NOTE:
10% above the desired normal operating pressure (15 psig boilers should be set to 13 psig)
3. Operating pressure controls, except low pressure (15 psig)
4. Operating pressure control check: Close steam outlet valve
It is recommended that the high limit control be set
types have a separate differential scale. Differential indicates pressure below the main operating maximum pressure, the pressure control will re-set. The differential set point is adjusted in the same manner by turning the adjusting screw in the desired direction to increase or decrease the differential pressure value.
[supplied by customer] and adjust operating pressure
control to 20 psig (10 psig for low pressure boilers) and the differential to 10 psig (Note: Low pressure boilers do not have a differential setting). Set the high limit pressure control to 30 psig (13 psig for low pressure boilers). Switch boiler on to allow steam pressure to build-up. Pressure gauge reading will increase and the operating pressure control will de-energize the contactor(s) when the pressure gauge indicates 20 psig (10 psig for low pressure boilers). Open steam outlet valve to bleed off pressure. When the pressure gauge reading decreases below 10 psig (differential) (3 psig for low pressure boilers) the operating pressure control will re-energize the contactor(s).
5. High limit pressure control check: FOR TEST PURPOSES ONLY! Set the high limit pressure control 10 psig (5 psig for low pressure boilers) lower than the operating pressure control. Close the steam outlet valve and switch the boiler on to allow boiler to build pressure. When the pressure gauge indicates the pressure at which the high limit pressure control is set, the high limit pressure control re-set button will pop-up and the control will de­energize the contactor(s). Open the steam outlet valve to bleed off pressure. The contactor(s) should not re­energize on pressure drop. The contactor(s) should only re-energize when the pressure has dropped and the high limit pressure control reset button is depressed.
8
Page 9
Setting Pressure Controls
Installation, Operation & Maintenance Manual
1. To set the controls turn the operating pressure controller to its highest setting
2. Using the pressure gauge on the boiler adjust the high limit pressure controller to the desired set point. This is done by starting the boiler and having it build pressure to desired set point (as shown on the boiler pressure gauge).
3. Once the desired set point (always set the high limit pressure controller to at least 10% above the required operating pressure) is reached, turn the power off of the boiler and isolate the boiler by closing the steam outlet valve.
4. Proceed to lower the high limit pressure control set point until the high limit reset switch pops up.
High Limit Pressure Adjustment Screw
High Limit Pressure Reset Button
5. Once the high limit control is set proceed to set the operating pressure control in the same way as the high pressure was set as outlined in steps 2-4. There is no reset button on the operating controller so you will have to listen for a click.
6. Once the operating pressure controller is set you will need to set the differential pressure (not applicable for the 15 psi model as the default differential is set to 3 psi). The differential is set by bringing the boiler up to pressure and tripping the operating pressure controller then slowly letting down the pressure. When the operating pressure controller clicks back in that is where the differential is set. Between these two points is where the boiler will operate. The smaller the differential is the more the boiler will cycle on and off and the larger the differential the wider the pressure swings will be.
Differential Pressure Adjustment Screw
Operating Pressure
Adjustment Screw
High Limit Pressure Control
Operating Pressure Control
9
Page 10
Installation, Operation & Maintenance Manual
Operation
CA U T I ON
!
lectrical connections before energizing boiler to prevent
e arcing, carbonizing of contact and/or overheating
1. Set the desired operating pressure and differential pressure on the operating pressure control.
2. Set the high limit pressure control. (Recommended to be 10 psig above the operating pressure setting.)
3. Turn on water supply.
4. Turn main disconnect switch on.
5. Turn boiler control switch on. The water feed will begin and continue until the water level reaches half way up the gauge glass. The water feed will automatically shut off and the contactor(s) will energize.
6. Boiler steam pressure will gradually increase to the operating pressure control set point, at which time the contactor(s) will de-energize.
With main disconnect “OFF” tighten all
7. With steam demand, the boiler steam pressure will decrease. When the boiler pressure has dropped below the operating pressure control differential set amount, the contactor(s) will re-energize.
NOTE:
pressure does not drop more than 20% below reset.
8. The boiler is equipped with float type liquid level
9. The boiler should be blown down daily. (See blowdown
Adjust steam outlet valve such that the boiler
controls employing micro switches. They are extremely sensitive and reliable and will maintain the proper water level within the boiler pressure vessel automatically during boiler operation.
instructions.)
Blowdown
A daily blowdown is an essential part of boiler operation. It is the best and most important part of preventative maintenance you can give your boiler and will add years of life to the unit. Make sure a blowdown schedule is established and followed regularly.
In extremely hard water areas, blowdown may be necessary more than once a day. If there is a particular problem that applies to your local water condition (i.e. high concentrations of minerals etc.) we recommend a consultation with a reputable local water treatment­engineering firm. Pre-treating the boiler feed water may reduce mineral accumulation enough to allow a daily blowdown to be sufficient.
MANUAL BLOWDOWN INSTRUCTIONS
1. At the end of the working day, while boiler is still operating, turn boiler main switch to the “OFF” position, close water supply valve and open disconnect switch.
2. If blow down valve is plumbed into a blowdown tank, the boiler can be discharged at operating pressure.
3. If the blowdown valve is not plumbed into a blowdown tank, consult with local plumbing codes regarding boiler discharge.
4. When discharge is complete and boiler is drained, close the blowdown valve, open the water supply valve, turn boiler main switch to “ON” position and close disconnect switch.
5. When refilling is complete, turn off the boiler unless further operation is needed.
6. If boiler is equipped with a “Manual Re-set Auxiliary Low Water Cut-off” (as required in some states) the re­set button must be pushed before the boiler will begin developing steam. Do not push re-set button until the boiler has refilled with water.
10
Page 11
Installation, Operation & Maintenance Manual
0
sec
60 sec
MAX
MIN*
30
sec
10 sec
Blowdown
(cont.)
AUTOMATIC BLOWDOWN INSTRUCTIONS
(PN ES81600) 1” NPT, Starts, stops and blows down the boil-
er automatically, utilizing a programmable time clock a time­delay relay and motorized ball valve.
CA U T I ON
!
blowdown tank, the boiler can be discharged at operating pressure. If the blowdown valve is not plumbed into a blowdown tank, consult with local plumbing codes regarding boiler discharge.
NOTE:
lower float control equalization tube must be fully open for the automatic blowdown to be effective.
1. Program time clock by setting the time boiler is to turn on
2. When the time clock turns the boiler “off” the blowdown
3. Boiler will automatically refill at next programmed on
Blowdown program can be overridden to allow for unscheduled blowdown or operational cycles. Refer to the time clock instruction insert.
The manual valves from the boiler drain and the
and off daily. (Refer to instructions in time clock insert.)
is activated. A red pilot light over the time clock will come on and remain on while the motorized ball valve is open. The time duration the valve is open is set by an adjustable potentiometer built into the time delay board. The water level in the boiler after blowdown is complete, will be approximately at the lower gauge glass valve. (Elements are not exposed to air between operations.)
cycle.
If the blowdown valve is plumbed into a
DURATION ADJUSTMENT INSTRUCTIONS
WAR N I N G
!
power supplies before making any adjustments
Using a small flathead screwdriver, rotate the adjustment screw to the desired setting.
IMPORTANT:
screw past min and max stops, screw does not rotate more than 300 degrees
Hazard of Electric Shock. Disconnect all
Do not set less than 10 seconds. Do not force
FACTORY RECOMMENDED SETTINGS:
• 100 psig Trim: 50% turn (shown, 30 seconds)
• 15 psig Trim: 100% turn (shown, 60 seconds)
Back
11
Page 12
Installation, Operation & Maintenance Manual
Digital Timer - Operation Instructions
TO SET TIME & DAY OF CLOCK
1. Hold down the image of clock button for steps 2-4
2. Press the “ which are listed on the top line
3. Press the “h+” button to increase the current hour.
Note:
to the right of the minutes.
4. Press the “
TO SET TIMER ON/OFF TIMES
(there are 7 different programs that can be set)
Day
” button to cycle through the days
this will also change the
m+
” button to increase the current minute.
AM/PM
as it is listed
5. Click the “
6.
Program 1 ON
This will be when the boiler turns on. Set the day and time the same way you set the timer in steps 2-4.
7. Hit the “ onto the next setting.
8. The next setting will be This will be when the boiler turns off. Once the boiler is turned off the automatic blowdown system will activate. Follow steps 2-4 to set the date and time. Hit the “
9. Repeat steps 6-8 to set programs 2-7.
Timer
” button to go into the timer mode.
will be the first to come up.
Timer
” button to save the entry and move
Program 1 OFF
Timer
” button to save the settings.
.
ON/OFF STATUS:
Pressing the image of a hand with a pointed finger button ( ) changes the current mode of the timer. If er is currently running and if boiler is off/blowing down. Once one of the pro­grams are started the indicator will automatically turn to the grams ends it will automatically be set to the position.
ON
is indicated on the display the boil-
OFF
is indicated the
ON
position and when one of the pro-
OFF
DAYLIGHT SAVING TIME:
The timer does not automatically adjust for daylight saving time and the time will have to be adjusted manually.
PROGRAMMED COMBINATIONS:
Switch OFF commands have priority over switch ON commands.
NOTES:
1. The timer is set according to the boiler operation. When the timer is blowdown is
2. During programming, if no button is pressed after 30 seconds, the timer will revert back to normal operating mode.
3. After programming, the override button ( ) may need to be pressed to change the ON/OFF status for the current day and time.
OFF
ON
.
the boiler is
ON
and the
12
Page 13
Installation, Operation & Maintenance Manual
Mechanical Timer
PROGRAMMING
F
or electric steam boilers equipped with Automatic Blowdown Systems ES 81600, refer to the following instructions for time clock operation and settings.
Timer settings for blowdown operation are at the discretion of the owner/operator.
The weekly program dial shows the seven days of the week and AM/PM imprints for each day.
The time switch is set by pushing the captive trippers to the outer ring position for the entire period that the load is to be turned ON, i.e., 2 hours to each trip­per on the 7-day dial. When the tripper is pushed to the inside, the switch is in the OFF position.
SETTING TIME
To set the current time and day of week, turn the minute hand clockwise. Do not set the time by rotating “Outer” Dial.
Turn the minute hand clockwise until the day of the week and the time of day on the outer dial is aligned with the triangle marker on the inner dial (two o'clock).
Maintenance
CA U T I ON
!
DISCONNECT ALL ELECTRICAL POWER BEFORE WORKING ON BOILER.
Sussman Electric Steam Boilers are designed for years of trouble-free performance. To establish a good preventative maintenance program, we suggest that the facility maintenance person or engineer familiarize themselves with these simple rules.
1. Daily blowdown at pressure is essential for ideal boiler performance. Extended periods of operation may require more frequent blowdown. If the boiler is not equipped with an automatic blowdown, in order to safeguard the heating elements, it is recommended to turn both the main disconnect switch and the boiler switch to the off position before manually blowing down the boiler.
2. The sight glass should be checked frequently to assure the boiler has adequate water.
3. The sight glass should be checked daily for damage (i.e. scratches, erosion, leaks etc.) The sight glass should be replaced if damaged. (See insert.)
4. A monthly inspection should be made of the internal wiring. Open the access door and check all electrical connections for tightness. Replace any wires that show signs of damage.
NOTE:
this maintenance procedure.
The electrical power MUST be shut off during
HAZARD OF ELECTRIC SHOCK.
AM
Example for 7-day program dial Monday 10:30
.
Turn the minute hand clockwise until Monday 10:30
AM
is aligned with the triangle on the inner dial.
The hour and minute hand will show exactly 10:30.
FOR MANUAL OVERRIDE
Manual override can be accomplished at the discretion of the owner/operator as follows.
3-WAY MANUAL OVERRIDE SWITCH
I = permanent ON
= automatic
O = permanent OFF
IMPORTANT: It is recommended that for periodic and effective blowdown, the override switch be set in the automatic setting.
I
O
5. Heating element mounting bolts should be checked and tightened to a torque of 22 ft.-lbs. If there are indications of steam leaks from an element, replace the element gasket.
6. A monthly check for leaks should be made; any loose or damaged fittings should be tightened or replaced.
7. Every four months the boiler float control should be checked for proper operation. The lower equalization column can be examined visually and manually to see if is clear and clean. If there are signs of scale or mineral deposit buildup the float control must be disassembled and cleaned.
One of the lower heating elements should be removed. If scale or mineral deposits have begun to form all elements should be removed cleaned and reinstalled using new element gaskets.
Operating and high limit pressure control operation should be checked. Pressure controls should be removed and cleaned if necessary. Water feed supply check valves should be inspected and replaced if necessary.
8. If the boiler is equipped with an electronic auxiliary low water cut-off every four months the probe should be removed and checked for deposits. The probe should be cleaned and reinstalled.
13
Page 14
Installation, Operation & Maintenance Manual
Standard Equipment for ES & HU Optional Equipment
AUXILIARY LOW WATER CUT OFF
• For model ES & HU boilers PN ES81017MR (with manual reset).
Senses water level electronically using a resistance probe. When a low water condition is detected, the contactor control voltage circuit is interrupted and the heating elements are de-energized. When water level returns to proper levels voltage is restored to the contactor coils and the elements are re-energized. For controls with a manual reset button voltage to the contactor coils is not restored until the water level has returned to proper operating levels and the reset button is pushed. Do not depress the reset button before the correct water level is achieved. To test AUX LWCO, press and hold the manual reset button on the side of the boiler for 5 seconds.
A blinking light on the PC board indicates the board is having difficulty sensing water (either due to a dirty probe or low conductivity in the water). Holding the reset button for 30 seconds should reset the board back to function. See next section for maintenance schedule in locales where water quality requires regular treatment.
LINE PRESSURE WATER FEED SYSTEM
• For model ES & HU boilers PN ES99117
Water feed system used to supply makeup water to the boiler when incoming water line pressure is 10 psig greater than the operating pressure of the boiler. Completely factory plumbed and wired; 0-100 psig range; 1/2” NPT size. Consists of strainer, solenoid valve (120/1/50-60Hz), and check valve for automatic feed.
HIGH PRESSURE WATER FEED SYSTEM
• For model ES12-72 PN ES38002A
• For model ES100-180 PN ES38020A Used to supply makeup water and to maintain constant water level when the boiler operating pressure is equal to or greater than incoming water line pressure and conden­sate is not returned to the boiler.
• ES38002A – Range is 0 – 100 psig, 1/2” NPT size consisting of strainer, solenoid valve and 1/3 HP 120/1/60 motor and pump.
• ES38020A – Range is 0 – 125 psig, 3/4” NPT size consisting of strainer solenoid valve and 1/2 HP 120/1/60 motor and pump. These assemblies are mounted on rubber shocks and secured to a steel base mounting plate. These units require field plumbing and wiring to the boiler.
CONDENSATE RETURN SYSTEM
(see page 16)
• For model ES12-72 PN ES38083V; for model ES85-180 PN ES38084V.
These systems are used whenever condensed steam can be collected for reuse in the boiler. Returning the conden­sate to the boiler can save a significant amount of energy. The water returned is relatively free of corrosive minerals and carries a substantial amount of heat that does not have to be replenished. A vacuum breaker is required whenever a condensate return system is used.
Each system consists of a vertical condensate return tank, a motor and pump and support plumbing. A 1/2” inlet is located on the tank to accept make-up water. A vent fit­ting is located on the condensate tank top for atmospher­ic air venting. The return fitting is to be plumbed to the trapped condensate return line coming from the process.
A gauge glass and valve set are mounted on the side of the condensate tank. The tank has a ball check valve internally mounted, and a float arm and float ball assem­bly that serve mechanically allowing make-up water to enter the tank as the original supply is used. The pump discharge outlet is to be plumbed to the boiler check valve. The tank drain valve should be plumbed to a prop­er drain line. The motor is required to be wired to the boiler.
14
Page 15
Optional Equipment
Installation, Operation & Maintenance Manual
VACUUM BREAKER SYSTEMS
• For model ES boilers PN ES89369 A vacuum breaker will prevent a boiler from flooding as a
result of the steam condensing internally and creating a vacuum after boiler shutdown. The breaker allows air to enter the boiler shell breaking the vacuum. This system is a must for boilers connected to a condensate return tank. The vacuum breaker consists of a spring-loaded disc and associated piping and is factory plumbed to the boiler.
AUTOMATIC BLOWDOWN SYSTEM
• Extends life of boiler
• Saves labor costs
• Starts the boiler automatically every day
• Shuts down the boiler every day
• Automatically blows down the boiler every day
• Completely programmable, can skip days, different start
and shutdown times, different operational durations.
• ES81600 for all model boilers.
A stainless steel, motor driven straight-through, self-clean­ing ball valve with Teflon seats handles particles and dirty fluid without the use of an up-stream strainer or other cleaning device. A timer (Standard analog time clock is set for two hour time intervals, optional digital time clock can be programmed to one minute intervals.) and elec­tronic time delay relay control the boiler and the blow­down valve. A pilot light indicates when the blowdown valve is open. The valve shall be plumbed to a proper drain or recepta­cle. An automatic blowdown system can be installed on any boiler, regardless of size operating pressure or operat­ing duty cycle.
CONTROL VOLTAGE STEPDOWN TRANSFORMER
• Provides 120 Volt (220 Volt export) from main power
supply. Factory wired and fused.
BLOWDOWN SEPARATORS
• For models ES12-48 - PN BDT-ASME36
• For models ES60-180 PN BDT-ASME42 A separator accepts the flash steam and effluent from the
boiler blowdown and reduces the temperature and pressure to insure a safe discharge of water and sludge. Steam flash and pressure are absorbed and pass harmlessly to the out­side via a vent. The separator design utilizes a water seal at the outlet, which permits the operator to introduce cold water from the bottom to mix with the hot water and boiler steam in the blowdown separator. This reduces outlet tem­perature to a safe discharge level.
These separators require specific plumbing from the boiler
blowdown valve and require connection to a cold water sup­ply. (If the separator is less than half full of water after the boiler is blown down cold water must be added to bring the water level to the halfway mark before the next blowdown).
• 0-30 psig pressure gauge; 0-200F temperature gauge; water
sight gauge glass and valve set assembly are included.
see page 17)
(
MULTISTAGE LOAD PROGRESSIVE SEQUENCERS
Accurate control is provided by automatic progressive sequenc­ing in the use of energy and minimizing wear on electrical components. The sequencers are designed to apply power pro­gressively to larger KW boilers. A factory installed pressure sen­sitive sequential control reacting to steam boiler pressure pro­gressive energizes or de-energizes heating elements through power contactors. A delay between sequencer steps before start-up and between each subsequent step eliminates power surges. Each sequencer is matched and factory pre- set to boil­er system requirements. Electronic progressive sequencers give accurate control of multi-stage loads of the type used in steam boilers. Features include progressive sequencing (first on- first off) that equalizes the operating time of each load. Integral solid-state light emitting diodes show active stages. Should a power interruption occur, all elements are instantly de­energized for safety. Upon resumption of power the control will re-stage the loads one at a time.
15
Page 16
Condensate Return Systems
B
E
A
D
C
9
-
1
/2"
DIA COVER PLATE
EASY ACCESS FOR MAINTENANCE
C
ONDENSATE RETURN FLASH TUBE
OVERFLOW OUTLET 1" NPT (farside) O
VERFLOW (label)
S
IMPLE RUGGED LINKAGE
5" DIA UPPER FLOAT BALL 39011FB
SHUTOFF GATE VALVE
STRAINER CLEANOUT
V
ENT SAFETY BAR
F
LOAT VALVE
39010-F
7-
7
/8"
SIGHT GLASS
99074-1
S
ITE GLASS ASSY
PN 99173C
1
/2" DRAIN VALVE
PUMP EASY ACCESS
1-1/4" VENT WITH SAFETY BAR
V
ENT (label)
1/2" COLD WATER INLET COUPLING
WITH #100 MESH STRAINER
C
ONDENSATE RETURN (label)
TOP VIEW
C
OLD WATER INLET
(
label)
LIMIT MAKEUP WATER PRESSURE TO TO 30 PSI MAXIMUM” (label)
1-
1
/4" CONDENSATE
RETURN COUPLING
Models 38083V & 38084V
Installation, Operation & Maintenance Manual
NOTES:
1. Motor/Pump is closed - Coupled design
2. Pump capacity as follows:
MODEL 38083V
___________________
PSIG HEAD GPM
___________________
54 125 ft. 3.2
___________________
75 175 ft. 2.9
___________________
97 225 ft. 2.7
___________________
3. Normal cold water level approximately 1/2 to 5/8 up to visible part of gauge glass.
_____________________________________________________________________________
MODEL Used on "A" "B" "C" "D" "E"` H.P. VOLT/PH/HZ
_____________________________________________________________________________
38083V ES12 - ES72 38-1/4" 18 14-1/4" 14 18 1/3 120 / 1 / 60
_____________________________________________________________________________
38084V ES100 - ES180 51-1/2" 18 14-1/4" 14 30 1/2 120 / 1/ 60
_____________________________________________________________________________
MODEL 38084V
___________________
PSIG HEAD GPM
___________________
54 125 ft. 4.6
___________________
75 175 ft. 4.3
___________________
97 225 ft. 4.0
___________________
PUMP MOTOR
16
Page 17
Installation, Operation & Maintenance Manual
D
A
H
G
Blowdown Separator Tanks- Specifications and Data
Models BDT-ASME 36, 42, 48, 54
Dimensions and Features Suggested Hook-Up to Boiler
Pressure Gauge
"E" Vent
"B" Inlet
Water Gauge
"C" Drain
Temperature
Gauge
Inspection Port
(except BDT-ASME 36)
Blowdown
Separator
Vent to atmosphere must be full size
Blowdown Inlet
From Boiler
Blowdown Outlets
3/4" Coupling for Temperature Probe (opt.)
BOILER DIMENSIONS SHIPPING
_______________________________________________________________________
BDT-ASME 36 0-5 18" 1" 2" 12" 2" 2" 14" 32" 125
_______________________________________________________________________
BDT-ASME 42 6-25 24" 1" 2" 16" 2-1⁄2" 2" 18" 42" 230
_______________________________________________________________________
BDT-ASME 48 26-59 30" 1-1⁄4" 2" 16" 3" 2" 18" 48" 260
_______________________________________________________________________
BDT-ASME 54 60-100 38" 1-1⁄2" 3" 16" 4" 2" 18" 54" 290
________________________________________________
HP
ABCDEFGHWEIGHT
"F" Cold Water Inlet
& Washout Drain
Tempered
Blowdown
to Drain
Cold Water
Supply
Drain Valve
(closed during normal operator)
The Sussman Separator design incorporates a water seal at the outlet which permits the operator to introduce cold water from the bottom to mix with the hot water and boil­er steam blowdown in the separator. This reduces the out­let temperature to a level that makes it safe for discharge.
NOTE:
1BHP is approximately 10KW.
Maximum Boiler Working Pressure: 250 psi
Maximum Blowdown Separator Pressure: 65 psi
Blowdown Separators are sized in accordance with National Board Standards
Standard Equipment
• 0-100 lb. Pressure Gauge
• 0-200˚ Temperature Gauge
• Water Level Gauge
Constructed in accordance with Section VII Division I ASME Boiler & Pressure Vessel Code
17
Page 18
Installation, Operation & Maintenance Manual
Specifications
__________________________________________
Boiler Bhp Lbs/Hr 3-Ph
Model No. KW Rating Steam** Volts*** Amps
__________________________________________
208 34
ES-12* 12 1.22 36.2 240 29
__________________________________________
ES-18* 18 1.84 54.2 240 44
__________________________________________
ES-24* 24 2.45 72.3 240 58
__________________________________________
ES-30 30 3.06 90.4 240 73
__________________________________________
ES-36 36 3.67 108 240 87
__________________________________________
ES-48 48 4.90 145 240 116
__________________________________________
ES-60 60 6.12 181 240 145
__________________________________________
ES-72 72 7.35 217 240 174
__________________________________________
ES-85 84 8.5 256 240 204
__________________________________________
ES-100 108 11.2 325 240 260
__________________________________________
ES-135 144 14.7 434 240 347
__________________________________________
ES-160 158 16.2 475
__________________________________________
ES-180 180 18.4 542
__________________________________________
* Single phase available ** Steam at 212°F with 50°F feed water. See page 19 for sizing. *** Other voltage available
480 15
208 50
480 22
208 67
480 29 208 84
480 37
208 100
480 44
208 134
480 58
208 167
480 73
208 200
480 87
208 236
480 102
208 300
480 130
208 400
480 173
240 379 480 190
240 434 480 217
18
Steam Gauge
Pressure/
Temperature
________________
Gauge Temperature
Pressure
________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
Chart
PSIG
15 179 82
10 192 89
5 203 95
0 212 100
1 215 102
3 221 105
5 227 111
9 237 114
11 241 119
15 250 121
17 253 123
19 257 125
21 260 127
23 264 129
25 267 131
27 270 132
29 273 134
31 275 135
33 278 137
35 281 138
37 283 139
39 286 141
41 288 142
43 290 143
45 292 144
47 295 146
49 297 147
51 299 148
53 300 149
55 303 151
60 308 153
65 312 156
70 316 158
75 320 160
80 324 162
85 327 164
90 331 166
95 335 168
100 338 170
F˚ C˚
Page 19
Installation, Operation & Maintenance Manual
Sizing
Use the following Table to determine KW Boiler rating when steam load and feedwater temperatures are known.
___________________________________________________________________
Feed Water
( F˚)
___________________________________________________________________
40 .3347 .3355 .3375 .3388 .3406 .3422 .3431 .3447 .3458 .3464 .3470
___________________________________________________________________
50 .3318 .3326 .3345 .3359 .3376 .3392 .3401 .3417 .3429 .3435 .3441
___________________________________________________________________
60 .3288 .3296 .3316 .3329 .3347 .3363 .3372 .3388 .3400 .3407 .3411
___________________________________________________________________
70 .3259 .3267 .3287 .3300 .3318 .3334 .3343 .3359 .3370 .3376 .3382
___________________________________________________________________
80 .3229 .3238 .3278 .3271 .3288 .3305 .3313 .3329 .3341 .3347 .3353
___________________________________________________________________
90 .3200 .3208 .3238 .3242 .3259 .3275 .3284 .3300 .3312 .3318 .3324
___________________________________________________________________
100 .3171 .3179 .3199 .3212 .3229 .3246 .3255 .3271 .3283 .3288 .3294
___________________________________________________________________
110 .3142 .3150 .3170 .3183 .3200 .3217 .3225 .3242 .3253 .3259 .3265
___________________________________________________________________
120 .3112 .3210 .3140 .3154 .3171 .3287 .3196 .3212 .3224 .3230 .3236
___________________________________________________________________
130 .3083 .3091 .3111 .3124 .3142 .3160 .3167 .3183 .3195 .3200 .3206
___________________________________________________________________
140 .3054 .3062 .3082 .3095 .3113 .3129 .3137 .3154 .3165 .3171 .3177
___________________________________________________________________
150 .3025 .3032 .3052 .3066 .3083 .3099 .3108 .3124 .3136 .3142 .3148
___________________________________________________________________
160 .2995 .3003 .3029 .3036 .3054 .3070 .3079 .3095 .3107 .3113 .3118
___________________________________________________________________
170 .2966 .2974 .2994 .3001 .3025 .3041 .3050 .3066 .3077 .3083 .3089
___________________________________________________________________
180 .2937 .2945 .2964 .2978 2995 .3011 .3020 .3036 .3048 .3054 .3060
___________________________________________________________________
190 .2907 .2915 .2935 .2948 .2966 .2982 .2981 .3007 .3019 .3025 .3030
___________________________________________________________________
200 .2878 .2886 .2906 .2919 .2937 .2953 .2962 .2978 .2989 .2995 .3001
___________________________________________________________________
0210 15 25 40 50 75 100 125 150
Example:
Note:
Need a boiler to produce 450 lbs. steam/hr. at 75 psig with the available feedwater temperature 50˚ F.
From the chart above, find .3417 KW/Lb. of steam 450 lbs. steam/hr. x .3417= 153.8 KW boiler required
Add 20% to required kW for contingencies
19
Page 20
Gauge Glass Installation
Installation, Operation & Maintenance Manual
IMPORTANT NOTE:
Read all warnings and instructions before performing installation or maintenance. Safety glass­es and gloves should be worn at all times when working with or examining water gauge glass and connections. Pressure in generator to be at zero before proceeding. Improper installation or maintenance of gauge glass and connections can cause immediate or delayed breakage resulting in bodily injury and/or property damage.
1. Apply Teflon tape or pipe dope to pipe threads. Install
top gauge fitting (fitting without a drain valve) into the uppermost tapping. Wrench tighten the fitting until it is snug and the glass outlet is pointing at five o'clock (about 1/8 turn from its final downward vertical position).
2. Install the bottom gauge fitting (the fitting with a drain
valve) until it is snug and the glass outlet is pointing directly upward. Verify top and bottom fittings are threaded into the tappings the same number of turns (distance A= distance B).
3. Remove glass packing nut, friction washer (or packing
gland, depending upon the model), and glass packing from the fittings, and place them, in the same order, on to both ends of the gauge glass. Push both packings about an inch up the gauge glass.
4. Gently insert one end of the glass into the top gauge
fitting. Keeping the glass inside the top fitting, gently rotate the top gauge fitting clockwise until vertically aligned with the bottom gauge, then insert glass into bottom fitting until glass bottoms out on the shoulder inside the bottom fitting.
5. Carefully raise glass about 1/16" and slide lower glass
packing down until the glass packing contacts the lower gauge fitting. DO NOT allow the glass to remain in contact with any metal!
6. Carefully slide upper glass packing up as far as possible.
7. Hand tighten both glass packing nuts, then tighten 1/2
turn more by wrench. Tighten only enough to prevent leakage. DO NOT OVER TIGHTEN! If any leakage should occur, tighten lightly, a quarter turn at a time, checking for leakage after each turn.
IMPORTANT NOTE:
Read all warnings and instructions
before performing installation or maintenance.
op Gauge
T Fitting
Guard Rod
Friction Washer
(or Packing Gland)
Bottom
Gauge Fitting
WAR N I N G
!
Drain Valve
Safety glasses and gloves
A
Vessel Wall
Gauge Glass
Glass Packing Nut
Glass Packing
B
should be worn at all times when working with or examining water gauge glass and connections.
Pressure in generator to be at zero before proceeding.
Improper installation or maintenance of gauge glass and connections can cause immediate or delayed breakage resulting in bodily injury and/or property damage.
20
Page 21
Installation, Operation & Maintenance Manual
Gauge Glass Installation - Use and Care
O NOTs
D
• DO NOT use glass if it contains any scratches, chips, or any other visible signs of damage.
• DO NOT reuse any tubular glass or glass packings.
• DO NOT subject gauge glass to bending or torsional stresses.
• DO NOT over tighten glass packing nuts.
• DO NOT allow glass to touch any metal parts.
• DO NOT exceed the recommended pressure of the gauge or gauge glass.
• DO NOT clean the gauge or gauge glass while pressur­ized or in operation.
DO's
• DO verify proper gauge has been supplied.
• DO examine gauge glass and packings carefully for damage before installation.
• DO install protective guards and utilize automatic ball checks where necessary to help prevent injury
in case of glass breakage.
• DO inspect the gauge glass daily, keep maintenance records, and conduct routine replacements.
• DO protect glass from sudden changes in temperatures such as drafts, water spray, etc.
AINTENANCE
M
Examine the gauge glass regularly for any signs of clouding, scratching, erosion, or corrosion. The glass should be inspected daily until the need for replace­ment becomes apparent. This will help establish the routine inspection and routine replacement schedules.
CLEANING
Use commercial non-abrasive glass cleaners to keep glass clean. Use diluted acids such as Hydrochloric (muriatic) acid when regular cleaners do not seem to work. Do not use wire brushes or any other abrasive materials which could scratch the glass.
INSPECTION
Examine the surface of the glass for scratches, corro­sion, chips, cracks, surface flaws, or nicks. To do this, shine a very bright concentrated light at an angle of about 45 degrees. A defective glass will glisten as the light strikes imperfections. Glass which appears cloudy or roughened, and will not respond to cleaning, should be replaced.
STORING
Keep gauge glass in original packaging until ready to install.
21
Page 22
Installation, Operation & Maintenance Manual
Element Replacement
READ INSTRUCTIONS COMPLETELY BEFORE STARTING WORK
CA U T I ON
!
the McDonnell Miller low water cut-off and aux. low water cutoff (if supplied) is operating properly. The float chamber and lower equalizer column of the MM control must be completely clear of sludge or other foreign matter. Failure to do this may cause the immediate burn-out of the new elements. If the unit is probe equipped, check condition of the probes and isolator.
All elements are thoroughly checked before shipment The manufacturer cannot be responsible for burn-outs caused by a faulty low water cut-off.
The lower equalizer column can best be examined by breaking the unions on either side and then visually and manually examining the piping with your finger or probes to see if it is clear and clean.
1. Disconnect boiler from electric power supply at main safety switch or fuse panel. Then turn boiler switch to “OFF" position.
2. Close water supply valve on incoming water supply line. Drain boiler completely of water.
3. Open boiler door to access heating element.
4. Disconnect wire (electric) leads connecting element to main power system of boiler. Again, note wire connections to facilitate re-assembly. Proceed to remove and discard (6) bolts from flange.
IMPORTANT: Note the wire connections to facilitate re-assembly (see wiring schemat­ic). Remove and discard six (5/16"-18) bolts from flange. Do not reuse these bolts.
5. Thoroughly clean boiler flange of all foreign material. Be certain no part of old gasket remains on flange.
6. Apply "Slic-Tite" Gasket Compound (or equal) to both surfaces of new gasket supplied with replacement element. Proceed to install element flange assembly with gasket between boiler flange and element flange. In doing this, be careful to align flange holes so element wire connection terminals on element assembly are in line with previously disconnected wire leads to facilitate easy connections.
NOTE:
7. Use only new element flange bolts. Tighten all (6) element flange bolts to a torque
8. Connect all wires to the terminals. Tighten all element terminals to a torque value
9. Check that the wires are correctly connected to the contactor terminals and are
10. Open water valve to allow water supply to reach boiler feed mechanism.
11. As boiler automatically refills, observe the new flange assembly for possible leaks.
12. When boiler reaches working pressure, check flange assembly again for leaks.
Observe markings on element flange. Install element marking “TOP” on top.
value of 22 lb-ft each (see illustration).
of 20 lb-in each (see illustration). Make sure all wires are clean and bright to assure good electrical contact.
tightened to the torque listed on the contactor. Make sure all wires are clean and bright to assure good electrical contact.
If water is noticed, the bolts must be re-tightened. Before doing this, turn the boiler off at the main fuse safety switch.
CA U T I ON
!
Before Installing your new elements be sure
Boiler with McDonnell Miller
11⁄2”
Follow maintenance instructions provided with the boiler.
1” Steam Equalizing Pipe
Pump and Low Water Control
Normal Boiler Water Line
Cut-Off Level is Arrow Mark
Blowdown Valve
1” Water Equalizing Pipe
Torque Values:
Torque Wrench
Element Flange Bolts: 22 lb-ft
Torque Wrench
Element Terminals: 20 lb-in
Torque Wrench
Contactor Terminals: see Torque chart
For Illu st rative P ur po ses Only. Power wi ri ng shown in ap pr oximate factory -i nstalled l oc ation
TORQUE VALUES
Element Flange Bolts 22 lb-ft Element Terminals 20 lb-in Contactor Terminals: Tighten to torque
specified on contactor
22
Page 23
Installation, Operation & Maintenance Manual
Water Quality Information for Carbon Steel Boilers
For optimum results, the feedwater supply should be tested prior to initial start­up. If the mineral content exceeds the following recommended limits, various external treatment processes (water softener, reverse osmosis, etc.) may be used to correct the problem.
NOTE:
An analysis of the on-site boiler feedwater must be made by a recognized and reliable water treatment company to ascertain the existing condition and treatment required.
RECOMMENDED FEEDWATER QUALITY
HARDNESS, ppm 8 – 85 (~0.5 – 5 gpg) P-ALKALINITY, ppm 85 – 410 (~5 – 24 gpg) T-ALKALINITY, ppm 200 – 500 (~7 – 0 gpg) pH (strength of alkalinity) 8.0 – 11.4 SPECIFIC RESISTIVITY Maximum 50k Ω cm (50,000 ohm-centimeter)
Blow down the boiler on at least a once-a-day basis. If boiler water or feed-water are outside the above limits, a more frequent blowdown is required.
Water quality can affect efficiency or result in boiler damage if neglected. Boiler feedwater contains impurities in solution and suspension. These impurities concentrate in the boiler since the steam generated is essentially pure. The concentration of these impurities increases as more feedwater is introduced into the boiler and steam is produced. If the suspended solids are allowed to concentrate beyond certain limits, a deposit or “scale” will form on the boiler’s internal surfaces. This deposit can interfere with proper boiler operation and cause boiler failure.
The concentration of these impurities is generally controlled by the feedwater quality and by blowdown. Blowdown refers to removing a portion of the boiler water with high solids concentration and replacing it with make-up water of a lower concentration.
23
Page 24
U S A
Designed, Enginee red and Assembled in the
A Division of Sussman-Automatic Corporation
43-20 34th Street, Long Island City, NY 11101 • (718) 937-4500 1-800-238-3535 • Fax: (718) 937-4676 • email: [email protected]
www.sussmanboilers.com
PUR 101137
REV
5.18
Loading...