As you follow these instructions, you will notice warning and caution symbols. This blocked information is important for the safe and efficient
installation and operation of electric boilers. These are two types of potential hazards that may occur during this installation and operation:
WAR N I N G
!
may cause serious injury or death if precautions
are not followed.
states a hazard which
CA U T I ON
!
minor injury or product damage may occur if you
do not follow instructions.
signals a situation where
2
IMPORTANT NOTE:
This highlights information that is especially
relevant to a problem-free installation.
Page 3
Installation, Operation & Maintenance Manual
Dimensional Information & Component Identification
Allow minimum 36 inches clearance in front of doors for servicing of heating elements.
Recommended clearance: 24 inches other sides of boiler for servicing.
* ES100 Width shown is for 480 volts with one front mount fuse box, 208/240 volt that includes a front and back mounted fuse box is 30" wide
** ES135 -180 Width shown is for 480 volts with one front mount fuse box, 208/240 volt that includes a front and back mounted fuse box is 32" wide
All 480 volt ES100-180 include a front mounted box for fuses (shown as dotted lines)
All 208 and 240 Volt ES100-180 include a front and back mounted box for fuses (shown as dotted lines)
ES72 208 Volt includes a front mounted fuse box, overall width increases to 24"
All 480 volt ES100 - 180 include a front mounted box for fuses (shown as dotted lines)
All 208 and 240 Volt ES100 - 180 include a front and back mounted box for fuses (shown as dotted lines)
ES72 208 Volt includes a front mounted fuse box.
1"Clearance above top of boiler
AClearance from Front of boiler. Prefix "C" to numeral indicates acceptability for
closet or alcove installations; prefix acceptability for alcove installations but not
for closet installations.
1"Clearance from back of boiler.
1"Clearance from left side of boiler.
16"Clearance from right side of boiler.
CIndicates type of flooring: "NC" for non-combustible; "C" for combustible.
Total minimum free area in square inches of close ventilating openings.
4
Page 5
P1
C1
C2
C
3
C
4
P2
P2
P3
P3
(
See Note 6)
C1C2C3C4
H1H3H5
H6
ES/SSB/CU 81600
Automatic Blowdown
System (optional)
Wiring Diagram
Power Circuit and
Control Circuit use
different voltage
Installation, Operation & Maintenance Manual
Three Phase Main Power Supply
NOTES:
1. Power Terminal Block only on boilers with two or more contactors.
2. On boilers with only one power contactor, connect power voltage to line side of contactor.
3. Power Fuses only on boilers rated 120 amperes and larger.
4. See Parts List for contactor and heating element information.
5. Element cut-off switches and second operating pressure control on ES/SSB 100-180 without sequencer
6. Refer to boiler nameplate for control and main power voltage
5
Page 6
Installation
Installation, Operation & Maintenance Manual
REFER TO NATIONAL AND ALL APPLICABLE LOCAL
CODES FOR SPECIFIC INSTALLATION REQUIREMENTS.
1. The boiler should be mounted on a solid, level foundation.
2. The boiler should be located with suitable clearances, refer
to page 3 and Code requirements.
NOTE:
Allow a minimum of 36 inches clearance in front of
doors for servicing of heating elements. Recommended clearance: 24 inches other sides of boiler for servicing.
Piping
ALL PIPING SHOULD BE INSTALLED BY A
QUALIFIED LICENSED PLUMBER IN ACCORDANCE WITH NATIONAL AND LOCAL CODES.
1. When water feed is other than pump type the water
supply pressure must be 10 psig greater than boiler
operating pressure to assure water supply maintains
proper water level in the boiler. Insufficient water levels
can result in improper boiler operation. (Keep feed
water valves open at all times during normal operation.)
2. Connect steam line with a valve to boiler steam outlet
3. Do not install boiler in any location where water
could freeze.
4. Do not install boiler outdoors.
5. Do not install boiler near flammable or corrosive
materials.
6. Do not install boiler in a location where leakage
from the boiler tank or piping can damage to
adjacent areas or to lower floors of the structure.
Provide a floor drain and properly sloped floor
from the boiler towards the drain or install a suitably plumbed drain pan under the boiler.
NOTE:
ice higher than the maximum boiler pressure should be
plumbed on the steam outlet line; failure to do so can cause
heating element breakdown. See page 3 for steam outlet
valve size.
4. Provide for boiler drain connection, a daily blowdown is
5. Safety valve shall be plumbed according to local code.
NOTE:
sized less than the outlet size of the safety valve.
For best performance, a valve rated for steam serv-
required. A "Blowdown Separator Tank" may be
necessary, check with local code.
The safety valve shall not be plumbed with a line
6
Page 7
Installation, Operation & Maintenance Manual
Wiring
ALL ELECTRICAL WIRING MUST BE PERFORMED BY A QUALIFIED ELECTRICIAN
IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES.
CA U T I ON
!
being supplied to the boiler matches the power voltage and
phase of the boiler. Connecting incorrect power supply can
damage boiler components or cause improper boiler operation. If the boiler power requirements do not match the
power to be supplied to the boiler the boiler must be
returned to the factory for conversion. Boilers cannot be
field converted.
ALL BOILERS ARE PRE-WIRED AND TESTED
PRIOR TO SHIPMENT.
1. Ground boiler according to National Electric Code
requirements to avoid shock.
2. Power wiring to boiler should be in accordance with
National and Local Electrical Code requirements following wiring diagram supplied. Use proper size wire. Wire
size is specified adjacent to field wiring terminals. This
label states the wire size [AWG or MCM], minimum
temperature rating (90 C) and conductor material
(copper only). Deviation from these requirements
may result in improper or unsafe boiler operation.
3. A disconnect switch employing circuit breakers or fuses
should be installed between the main power source and
the boiler. This disconnect switch should be located near
the boiler and clearly marked for easy access and identification should the boiler need to be turned off due to
an emergency.
Assure that the power voltage and phase
4. Boiler control circuit is 120 Volt*. Unless boiler has an
optional step down transformer, a separate 120 Volt
power feed wiring is required to be connected to the
control circuit terminal block. A 15 Amp circuit is
required for all boilers. If a 3/4 HP feed water motor
and pump assembly is connected to the boiler, then a
20 Amp circuit is required.
5. If a separate control circuit is used, it should be
connected to the control circuit terminal block.
6. Remote mounted water feed systems (i.e. condensate
return, motor and pump) should be connected to the
junction box provided on the outside of the boiler
jacket.
7. With main power off, make sure all wiring terminations are tight to avoid arcing, carbonizing or overheating of contacts.
CA U T I ON
!
damage due to water line connections. An industrial
type lightning/surge protector should be installed according to the manufacturer's recommendation at the service
entrance. Consult your contractor or electrical dealer.
WAR N I N G
!
cation of wiring system voids the warranty and may lead
to dangerous operating conditions.
Boilers are susceptible to lightning
Substitution of components or modifi-
7
Page 8
Installation, Operation & Maintenance Manual
Pre-Operation Check (All Boilers)
LWCO/PUMP CONTROL OPERATION AND TESTING
1. All valves for incoming water supply are to be fully opened.
Main disconnect switch is to be in the "on" position. Boiler main
switch is to be in the "on" position. Since boiler will be empty
the pump or solenoid will be energized allowing the boiler to
fill with water. Control will automatically fill boiler to proper
operating water level and the pump/solenoid will be deenergized. Contactors will then energize, applying voltage to
the heating elements.
2. Pump switch operation – at this point water should be visible
approximately half way up the sight glass. Slowly open the drain
valve located at the bottom of the boiler. Water level in the
sight glass will begin to drop, allowing the low water cut
off/pump control to energize the feed water system. Close valve
for proper operation.
3. Low water cutout switch performance – open the drain valve
completely. Maintain this condition until water level falls within
the gauge glass enough to cause the low water cutout switch to
de-energize the heating elements. All of the contactors will be
in a de-energized or open state at this time. Close the drain
valve, water feed system will automatically refill the boiler and
the contactors will re-energize.
Pressure Controls, Operation and Testing
Boilers equipped with an auxiliary low water cut-off
control with a manual re-set button (required as
mandatory equipment is some states): once the correct
operating water level has been reached, it will be
necessary to depress the reset button in order for the
contactors to re-energize.
NOTE:
down system:
• For test 1 - the blowdown time clock must be in the
• For test 2 and 3 - in order for the drain valve to open
For boilers equipped with an automatic blow-
“run” mode before the boiler will automatically fill.
the blowdown clock must be in the “off” mode.
(See blowdown time clock insert) The automatic
blowdown indicator light will be on when the valve
is open. This light will remain on for the duration of
the blowdown cycle (a few seconds). It may be necessary to cycle the time clock from the “run” to
“off” mode several times.
NOTE:
All boilers are provided with one high limit pres-
sure control and at least one operating pressure control.
1. The high limit pressure control is equipped with a manual
reset feature. There is no subtractive differential scale with
this type of control
2. All pressure controls are equipped with an adjusting screw,
allowing for setting of desired operational and high limit
pressures. To reduce pressure setting, turn adjusting screw
in direction that allows indicator to point to a lower
pressure setting on the scale. To increase pressure setting
turn adjusting screw in direction that allows indicator to
point to a higher pressure on the scale
NOTE:
10% above the desired normal operating pressure (15 psig
boilers should be set to 13 psig)
4. Operating pressure control check: Close steam outlet valve
It is recommended that the high limit control be set
types have a separate differential scale. Differential
indicates pressure below the main operating maximum
pressure, the pressure control will re-set. The differential set
point is adjusted in the same manner by turning the
adjusting screw in the desired direction to increase or
decrease the differential pressure value.
[supplied by customer] and adjust operating pressure
control to 20 psig (10 psig for low pressure boilers) and
the differential to 10 psig (Note: Low pressure boilers do
not have a differential setting). Set the high limit
pressure control to 30 psig (13 psig for low pressure
boilers). Switch boiler on to allow steam pressure to
build-up. Pressure gauge reading will increase and the
operating pressure control will de-energize the
contactor(s) when the pressure gauge indicates 20 psig
(10 psig for low pressure boilers). Open steam outlet
valve to bleed off pressure. When the pressure gauge
reading decreases below 10 psig (differential) (3 psig for
low pressure boilers) the operating pressure control will
re-energize the contactor(s).
5. High limit pressure control check: FOR TEST PURPOSES
ONLY! Set the high limit pressure control 10 psig (5 psig
for low pressure boilers) lower than the operating
pressure control. Close the steam outlet valve and switch
the boiler on to allow boiler to build pressure. When the
pressure gauge indicates the pressure at which the high
limit pressure control is set, the high limit pressure
control re-set button will pop-up and the control will deenergize the contactor(s). Open the steam outlet valve to
bleed off pressure. The contactor(s) should not reenergize on pressure drop. The contactor(s) should only
re-energize when the pressure has dropped and the high
limit pressure control reset button is depressed.
8
Page 9
Setting Pressure Controls
Installation, Operation & Maintenance Manual
1. To set the controls turn the operating pressure
controller to its highest setting
2. Using the pressure gauge on the boiler adjust the
high limit pressure controller to the desired set point.
This is done by starting the boiler and having it build
pressure to desired set point (as shown on the boiler
pressure gauge).
3. Once the desired set point (always set the high limit
pressure controller to at least 10% above the required
operating pressure) is reached, turn the power off of
the boiler and isolate the boiler by closing the steam
outlet valve.
4. Proceed to lower the high limit pressure control set
point until the high limit reset switch pops up.
High Limit Pressure
Adjustment Screw
High Limit Pressure
Reset Button
5. Once the high limit control is set proceed to set the
operating pressure control in the same way as the
high pressure was set as outlined in steps 2-4. There
is no reset button on the operating controller so you
will have to listen for a click.
6. Once the operating pressure controller is set you will
need to set the differential pressure (not applicable
for the 15 psi model as the default differential is set
to 3 psi). The differential is set by bringing the boiler
up to pressure and tripping the operating pressure
controller then slowly letting down the pressure.
When the operating pressure controller clicks back in
that is where the differential is set. Between these
two points is where the boiler will operate. The
smaller the differential is the more the boiler will
cycle on and off and the larger the differential the
wider the pressure swings will be.
Differential Pressure
Adjustment Screw
Operating Pressure
Adjustment Screw
High Limit Pressure Control
Operating Pressure Control
9
Page 10
Installation, Operation & Maintenance Manual
Operation
CA U T I ON
!
lectrical connections before energizing boiler to prevent
e
arcing, carbonizing of contact and/or overheating
1. Set the desired operating pressure and differential pressure
on the operating pressure control.
2. Set the high limit pressure control. (Recommended to be
10 psig above the operating pressure setting.)
3. Turn on water supply.
4. Turn main disconnect switch on.
5. Turn boiler control switch on. The water feed will begin
and continue until the water level reaches half way up the
gauge glass. The water feed will automatically shut off and
the contactor(s) will energize.
6. Boiler steam pressure will gradually increase to the
operating pressure control set point, at which time the
contactor(s) will de-energize.
With main disconnect “OFF” tighten all
7. With steam demand, the boiler steam pressure will
decrease. When the boiler pressure has dropped below
the operating pressure control differential set amount,
the contactor(s) will re-energize.
NOTE:
pressure does not drop more than 20% below reset.
8. The boiler is equipped with float type liquid level
9. The boiler should be blown down daily. (See blowdown
Adjust steam outlet valve such that the boiler
controls employing micro switches. They are extremely
sensitive and reliable and will maintain the proper
water level within the boiler pressure vessel
automatically during boiler operation.
instructions.)
Blowdown
A daily blowdown is an essential part of boiler operation.
It is the best and most important part of preventative
maintenance you can give your boiler and will add years
of life to the unit. Make sure a blowdown schedule is
established and followed regularly.
In extremely hard water areas, blowdown may be
necessary more than once a day. If there is a particular
problem that applies to your local water condition (i.e.
high concentrations of minerals etc.) we recommend a
consultation with a reputable local water treatmentengineering firm. Pre-treating the boiler feed water may
reduce mineral accumulation enough to allow a daily
blowdown to be sufficient.
MANUAL BLOWDOWN INSTRUCTIONS
1. At the end of the working day, while boiler is still
operating, turn boiler main switch to the “OFF”
position, close water supply valve and open disconnect
switch.
2. If blow down valve is plumbed into a blowdown tank,
the boiler can be discharged at operating pressure.
3. If the blowdown valve is not plumbed into a blowdown
tank, consult with local plumbing codes regarding
boiler discharge.
4. When discharge is complete and boiler is drained, close
the blowdown valve, open the water supply valve, turn
boiler main switch to “ON” position and close
disconnect switch.
5. When refilling is complete, turn off the boiler unless
further operation is needed.
6. If boiler is equipped with a “Manual Re-set Auxiliary
Low Water Cut-off” (as required in some states) the reset button must be pushed before the boiler will begin
developing steam. Do not push re-set button until the
boiler has refilled with water.
10
Page 11
Installation, Operation & Maintenance Manual
0
sec
60
sec
MAX
MIN*
30
sec
10 sec
Blowdown
(cont.)
AUTOMATIC BLOWDOWN INSTRUCTIONS
(PN ES81600) 1” NPT, Starts, stops and blows down the boil-
er automatically, utilizing a programmable time clock a timedelay relay and motorized ball valve.
CA U T I ON
!
blowdown tank, the boiler can be discharged at operating
pressure. If the blowdown valve is not plumbed into a
blowdown tank, consult with local plumbing codes
regarding boiler discharge.
NOTE:
lower float control equalization tube must be fully open for
the automatic blowdown to be effective.
1. Program time clock by setting the time boiler is to turn on
2. When the time clock turns the boiler “off” the blowdown
3. Boiler will automatically refill at next programmed on
Blowdown program can be overridden to allow for
unscheduled blowdown or operational cycles. Refer to the
time clock instruction insert.
The manual valves from the boiler drain and the
and off daily. (Refer to instructions in time clock insert.)
is activated. A red pilot light over the time clock will come
on and remain on while the motorized ball valve is open.
The time duration the valve is open is set by an adjustable
potentiometer built into the time delay board. The water
level in the boiler after blowdown is complete, will be
approximately at the lower gauge glass valve. (Elements
are not exposed to air between operations.)
cycle.
If the blowdown valve is plumbed into a
DURATION ADJUSTMENT INSTRUCTIONS
WAR N I N G
!
power supplies before making any adjustments
Using a small flathead screwdriver, rotate the adjustment
screw to the desired setting.
IMPORTANT:
screw past min and max stops, screw does not rotate more
than 300 degrees
Hazard of Electric Shock. Disconnect all
Do not set less than 10 seconds. Do not force
FACTORY RECOMMENDED SETTINGS:
• 100 psig Trim: 50% turn (shown, 30 seconds)
• 15 psig Trim: 100% turn (shown, 60 seconds)
Back
11
Page 12
Installation, Operation & Maintenance Manual
Digital Timer - Operation Instructions
TO SET TIME & DAY OF CLOCK
1. Hold down the image of clock buttonfor steps 2-4
2. Press the “
which are listed on the top line
3. Press the “h+” button to increase the current hour.
Note:
to the right of the minutes.
4. Press the “
TO SET TIMER ON/OFF TIMES
(there are 7 different programs that can be set)
Day
” button to cycle through the days
this will also change the
m+
” button to increase the current minute.
AM/PM
as it is listed
5. Click the “
6.
Program 1 ON
This will be when the boiler turns on.
Set the day and time the same way you set the timer in
steps 2-4.
7. Hit the “
onto the next setting.
8. The next setting will be
This will be when the boiler turns off. Once the boiler
is turned off the automatic blowdown system will
activate. Follow steps 2-4 to set the date and time. Hit
the “
9. Repeat steps 6-8 to set programs 2-7.
Timer
” button to go into the timer mode.
will be the first to come up.
Timer
” button to save the entry and move
Program 1 OFF
Timer
” button to save the settings.
.
ON/OFF STATUS:
Pressing the image of a hand with a pointed
finger button () changes the current mode of
the timer. If
er is currently running and if
boiler is off/blowing down. Once one of the programs are started the indicator will automatically
turn to the
grams ends it will automatically be set to the
position.
ON
is indicated on the display the boil-
OFF
is indicated the
ON
position and when one of the pro-
OFF
DAYLIGHT SAVING TIME:
The timer does not automatically adjust for
daylight saving time and the time will have
to be adjusted manually.
PROGRAMMED COMBINATIONS:
Switch OFF commands have priority over
switch ON commands.
NOTES:
1. The timer is set according to the boiler operation.
When the timer is
blowdown is
2. During programming, if no button is pressed
after 30 seconds, the timer will revert back to
normal operating mode.
3. After programming, the override button
() may need to be pressed to change the
ON/OFF status for the current day and time.
OFF
ON
.
the boiler is
ON
and the
12
Page 13
Installation, Operation & Maintenance Manual
Mechanical Timer
PROGRAMMING
F
or electric steam boilers
equipped with Automatic
Blowdown Systems
ES 81600, refer to the
following instructions
for time clock operation
and settings.
Timer settings for blowdown operation are at
the discretion of the owner/operator.
The weekly program dial shows the seven days of
the week and AM/PM imprints for each day.
The time switch is set by pushing the captive trippers
to the outer ring position for the entire period that
the load is to be turned ON, i.e., 2 hours to each tripper on the 7-day dial. When the tripper is pushed to
the inside, the switch is in the OFF position.
SETTING TIME
To set the current time and day of week, turn
the minute hand clockwise. Do not set the time
by rotating “Outer” Dial.
Turn the minute hand clockwise until the day of
the week and the time of day on the outer dial is
aligned with the triangle marker on the inner dial
(two o'clock).
Maintenance
CA U T I ON
!
DISCONNECT ALL ELECTRICAL POWER BEFORE
WORKING ON BOILER.
Sussman Electric Steam Boilers are designed for years of
trouble-free performance. To establish a good preventative
maintenance program, we suggest that the facility
maintenance person or engineer familiarize themselves with
these simple rules.
1. Daily blowdown at pressure is essential for ideal boiler
performance. Extended periods of operation may require
more frequent blowdown. If the boiler is not equipped with
an automatic blowdown, in order to safeguard the heating
elements, it is recommended to turn both the main
disconnect switch and the boiler switch to the off position
before manually blowing down the boiler.
2. The sight glass should be checked frequently to assure the
boiler has adequate water.
3. The sight glass should be checked daily for damage (i.e.
scratches, erosion, leaks etc.) The sight glass should be
replaced if damaged. (See insert.)
4. A monthly inspection should be made of the internal wiring.
Open the access door and check all electrical connections for
tightness. Replace any wires that show signs of damage.
NOTE:
this maintenance procedure.
The electrical power MUST be shut off during
HAZARD OF ELECTRIC SHOCK.
AM
Example for 7-day program dial Monday 10:30
.
Turn the minute hand clockwise until Monday 10:30
AM
is aligned with the triangle on the inner dial.
The hour and minute hand will show exactly 10:30.
FOR MANUAL OVERRIDE
Manual override can be accomplished at the
discretion of the owner/operator as follows.
3-WAY MANUAL OVERRIDE SWITCH
I = permanent ON
= automatic
O = permanent OFF
IMPORTANT: It is recommended that for periodic
and effective blowdown, the override switch be set
in theautomatic setting.
I
O
5. Heating element mounting bolts should be checked and
tightened to a torque of 22 ft.-lbs. If there are indications of
steam leaks from an element, replace the element gasket.
6. A monthly check for leaks should be made; any loose or
damaged fittings should be tightened or replaced.
7. Every four months the boiler float control should be checked
for proper operation. The lower equalization column can be
examined visually and manually to see if is clear and clean. If
there are signs of scale or mineral deposit buildup the float
control must be disassembled and cleaned.
One of the lower heating elements should be removed. If
scale or mineral deposits have begun to form all elements
should be removed cleaned and reinstalled using new
element gaskets.
Operating and high limit pressure control operation should
be checked. Pressure controls should be removed and
cleaned if necessary. Water feed supply check valves should
be inspected and replaced if necessary.
8. If the boiler is equipped with an electronic auxiliary low
water cut-off every four months the probe should be
removed and checked for deposits. The probe should be
cleaned and reinstalled.
13
Page 14
Installation, Operation & Maintenance Manual
Standard Equipment for ES & HUOptional Equipment
AUXILIARY LOW WATER CUT OFF
• For model ES & HU boilers PN ES81017MR
(with manual reset).
Senses water level electronically using a resistance probe.
When a low water condition is detected, the contactor
control voltage circuit is interrupted and the heating
elements are de-energized. When water level returns to
proper levels voltage is restored to the contactor coils
and the elements are re-energized. For controls with a
manual reset button voltage to the contactor coils is not
restored until the water level has returned to proper
operating levels and the reset button is pushed. Do not
depress the reset button before the correct water level
is achieved.
To test AUX LWCO, press and hold the manual reset
button on the side of the boiler for 5 seconds.
A blinking light on the PC board indicates the board is
having difficulty sensing water (either due to a dirty
probe or low conductivity in the water). Holding the
reset button for 30 seconds should reset the board back
to function. See next section for maintenance schedule in
locales where water quality requires regular treatment.
LINE PRESSURE WATER FEED SYSTEM
• For model ES & HU boilers PN ES99117
Water feed system used to supply makeup water to the
boiler when incoming water line pressure is 10 psig
greater than the operating pressure of the boiler.
Completely factory plumbed and wired; 0-100 psig range;
1/2” NPT size. Consists of strainer, solenoid valve
(120/1/50-60Hz), and check valve for automatic feed.
HIGH PRESSURE WATER FEED SYSTEM
• For model ES12-72 PN ES38002A
• For model ES100-180 PN ES38020A
Used to supply makeup water and to maintain constant
water level when the boiler operating pressure is equal to
or greater than incoming water line pressure and condensate is not returned to the boiler.
• ES38002A – Range is 0 – 100 psig, 1/2” NPT size consisting
of strainer, solenoid valve and 1/3 HP 120/1/60 motor and
pump.
• ES38020A – Range is 0 – 125 psig, 3/4” NPT size
consisting of strainer solenoid valve and 1/2 HP 120/1/60
motor and pump.
These assemblies are mounted on rubber shocks and
secured to a steel base mounting plate. These units require
field plumbing and wiring to the boiler.
CONDENSATE RETURN SYSTEM
(see page 16)
• For model ES12-72 PN ES38083V; for model
ES85-180 PN ES38084V.
These systems are used whenever condensed steam can
be collected for reuse in the boiler. Returning the condensate to the boiler can save a significant amount of energy.
The water returned is relatively free of corrosive minerals
and carries a substantial amount of heat that does not
have to be replenished. A vacuum breaker is required
whenever a condensate return system is used.
Each system consists of a vertical condensate return tank,
a motor and pump and support plumbing. A 1/2” inlet is
located on the tank to accept make-up water. A vent fitting is located on the condensate tank top for atmospheric air venting. The return fitting is to be plumbed to the
trapped condensate return line coming from the process.
A gauge glass and valve set are mounted on the side of
the condensate tank. The tank has a ball check valve
internally mounted, and a float arm and float ball assembly that serve mechanically allowing make-up water to
enter the tank as the original supply is used. The pump
discharge outlet is to be plumbed to the boiler check
valve. The tank drain valve should be plumbed to a proper drain line. The motor is required to be wired to the
boiler.
14
Page 15
Optional Equipment
Installation, Operation & Maintenance Manual
VACUUM BREAKER SYSTEMS
• For model ES boilers PN ES89369
A vacuum breaker will prevent a boiler from flooding as a
result of the steam condensing internally and creating a
vacuum after boiler shutdown. The breaker allows air to
enter the boiler shell breaking the vacuum. This system is
a must for boilers connected to a condensate return tank.
The vacuum breaker consists of a spring-loaded disc and
associated piping and is factory plumbed to the boiler.
AUTOMATIC BLOWDOWN SYSTEM
• Extends life of boiler
• Saves labor costs
• Starts the boiler automatically every day
• Shuts down the boiler every day
• Automatically blows down the boiler every day
• Completely programmable, can skip days, different start
and shutdown times, different operational durations.
• ES81600 for all model boilers.
A stainless steel, motor driven straight-through, self-cleaning ball valve with Teflon seats handles particles and dirty
fluid without the use of an up-stream strainer or other
cleaning device. A timer (Standard analog time clock is set
for two hour time intervals, optional digital time clock
can be programmed to one minute intervals.) and electronic time delay relay control the boiler and the blowdown valve.
A pilot light indicates when the blowdown valve is open.
The valve shall be plumbed to a proper drain or receptacle. An automatic blowdown system can be installed on
any boiler, regardless of size operating pressure or operating duty cycle.
CONTROL VOLTAGE STEPDOWN
TRANSFORMER
• Provides 120 Volt (220 Volt export) from main power
supply. Factory wired and fused.
BLOWDOWN SEPARATORS
• For models ES12-48 - PN BDT-ASME36
• For models ES60-180 PN BDT-ASME42
A separator accepts the flash steam and effluent from the
boiler blowdown and reduces the temperature and pressure
to insure a safe discharge of water and sludge. Steam flash
and pressure are absorbed and pass harmlessly to the outside via a vent. The separator design utilizes a water seal at
the outlet, which permits the operator to introduce cold
water from the bottom to mix with the hot water and boiler
steam in the blowdown separator. This reduces outlet temperature to a safe discharge level.
These separators require specific plumbing from the boiler
blowdown valve and require connection to a cold water supply. (If the separator is less than half full of water after the
boiler is blown down cold water must be added to bring the
water level to the halfway mark before the next blowdown).
• 0-30 psig pressure gauge; 0-200F temperature gauge; water
sight gauge glass and valve set assembly are included.
see page 17)
(
MULTISTAGE LOAD PROGRESSIVE
SEQUENCERS
Accurate control is provided by automatic progressive sequencing in the use of energy and minimizing wear on electrical
components. The sequencers are designed to apply power progressively to larger KW boilers. A factory installed pressure sensitive sequential control reacting to steam boiler pressure progressive energizes or de-energizes heating elements through
power contactors. A delay between sequencer steps before
start-up and between each subsequent step eliminates power
surges. Each sequencer is matched and factory pre- set to boiler system requirements. Electronic progressive sequencers give
accurate control of multi-stage loads of the type used in steam
boilers. Features include progressive sequencing (first on- first
off) that equalizes the operating time of each load. Integral
solid-state light emitting diodes show active stages. Should a
power interruption occur, all elements are instantly deenergized for safety. Upon resumption of power the control
will re-stage the loads one at a time.
15
Page 16
Condensate Return Systems
B
E
A
D
C
9
-
1
/2"
DIA COVER PLATE
EASY ACCESS FOR MAINTENANCE
C
ONDENSATE RETURN FLASH TUBE
OVERFLOW OUTLET 1" NPT (farside)
O
VERFLOW (label)
S
IMPLE RUGGED LINKAGE
5" DIA UPPER FLOAT BALL
39011FB
SHUTOFF GATE VALVE
STRAINER CLEANOUT
V
ENT SAFETY BAR
F
LOAT VALVE
39010-F
7-
7
/8"
SIGHT GLASS
99074-1
S
ITE GLASS ASSY
PN 99173C
1
/2" DRAIN VALVE
PUMP EASY ACCESS
1-1/4" VENT WITH SAFETY BAR
V
ENT (label)
1/2" COLD WATER INLET COUPLING
WITH #100 MESH STRAINER
C
ONDENSATE RETURN (label)
TOP VIEW
C
OLD WATER INLET
(
label)
LIMIT MAKEUP WATER PRESSURE
TO TO 30 PSI MAXIMUM” (label)
1-
1
/4" CONDENSATE
RETURN COUPLING
Models 38083V & 38084V
Installation, Operation & Maintenance Manual
NOTES:
1. Motor/Pump is closed - Coupled design
2. Pump capacity as follows:
MODEL 38083V
___________________
PSIGHEADGPM
___________________
54125 ft.3.2
___________________
75175 ft.2.9
___________________
97225 ft.2.7
___________________
3. Normal cold water level approximately 1/2 to 5/8 up to visible part of gauge glass.
The Sussman Separator design incorporates a water seal at
the outlet which permits the operator to introduce cold
water from the bottom to mix with the hot water and boiler steam blowdown in the separator. This reduces the outlet temperature to a level that makes it safe for discharge.
NOTE:
1BHP is approximately 10KW.
Maximum Boiler Working Pressure: 250 psi
Maximum Blowdown Separator Pressure: 65 psi
Blowdown Separators are sized in accordance with National Board Standards
Standard Equipment
• 0-100 lb. Pressure Gauge
• 0-200˚ Temperature Gauge
• Water Level Gauge
Constructed in accordance with Section VII Division I ASME Boiler
& Pressure Vessel Code
17
Page 18
Installation, Operation & Maintenance Manual
Specifications
__________________________________________
BoilerBhpLbs/Hr3-Ph
Model No. KWRatingSteam**Volts***Amps
__________________________________________
20834
ES-12*121.2236.224029
__________________________________________
ES-18*181.8454.224044
__________________________________________
ES-24*242.4572.324058
__________________________________________
ES-30303.0690.424073
__________________________________________
ES-36363.6710824087
__________________________________________
ES-48484.90145240116
__________________________________________
ES-60606.12181240145
__________________________________________
ES-72727.35217240174
__________________________________________
ES-85848.5256240204
__________________________________________
ES-10010811.2325240260
__________________________________________
ES-13514414.7434240347
__________________________________________
ES-16015816.2475
__________________________________________
ES-18018018.4542
__________________________________________
* Single phase available
** Steam at 212°F with 50°F feed water. See page 19 for sizing.
*** Other voltage available
48015
20850
48022
20867
48029
20884
48037
208100
48044
208134
48058
208167
48073
208200
48087
208236
480102
208300
480130
208400
480173
240379
480190
240434
480217
18
Steam Gauge
Pressure/
Temperature
________________
GaugeTemperature
Pressure
________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
Chart
PSIG
1517982
1019289
520395
0212100
1215102
3221105
5227111
9237114
11241119
15250121
17253123
19257125
21260127
23264129
25267131
27270132
29273134
31275135
33278137
35281138
37283139
39286141
41288142
43290143
45292144
47295146
49297147
51299148
53300149
55303151
60308153
65312156
70316158
75320160
80324162
85327164
90331166
95335168
100338170
F˚C˚
Page 19
Installation, Operation & Maintenance Manual
Sizing
Use the following Table to determine KW Boiler rating when steam load and feedwater temperatures are known.
Need a boiler to produce 450 lbs. steam/hr. at 75 psig with the available feedwater temperature 50˚ F.
From the chart above, find .3417 KW/Lb. of steam
450 lbs. steam/hr. x .3417= 153.8 KW boiler required
Add 20% to required kW for contingencies
19
Page 20
Gauge Glass Installation
Installation, Operation & Maintenance Manual
IMPORTANT NOTE:
Read all warnings and instructions
before performing installation or maintenance. Safety glasses and gloves should be worn at all times when working
with or examining water gauge glass and connections.
Pressure in generator to be at zero before proceeding.
Improper installation or maintenance of gauge glass and
connections can cause immediate or delayed breakage
resulting in bodily injury and/or property damage.
1. Apply Teflon tape or pipe dope to pipe threads. Install
top gauge fitting (fitting without a drain valve) into the
uppermost tapping. Wrench tighten the fitting until it is
snug and the glass outlet is pointing at five o'clock
(about 1/8 turn from its final downward vertical
position).
2. Install the bottom gauge fitting (the fitting with a drain
valve) until it is snug and the glass outlet is pointing
directly upward. Verify top and bottom fittings are
threaded into the tappings the same number of turns
(distance A= distance B).
gland, depending upon the model), and glass packing
from the fittings, and place them, in the same order, on
to both ends of the gauge glass. Push both packings
about an inch up the gauge glass.
4. Gently insert one end of the glass into the top gauge
fitting. Keeping the glass inside the top fitting, gently
rotate the top gauge fitting clockwise until vertically
aligned with the bottom gauge, then insert glass into
bottom fitting until glass bottoms out on the shoulder
inside the bottom fitting.
5. Carefully raise glass about 1/16" and slide lower glass
packing down until the glass packing contacts the lower
gauge fitting. DO NOT allow the glass to remain in
contact with any metal!
6. Carefully slide upper glass packing up as far as possible.
7. Hand tighten both glass packing nuts, then tighten 1/2
turn more by wrench. Tighten only enough to prevent
leakage. DO NOT OVER TIGHTEN! If any leakage should
occur, tighten lightly, a quarter turn at a time, checking
for leakage after each turn.
IMPORTANT NOTE:
Read all warnings and instructions
before performing installation or maintenance.
op Gauge
T
Fitting
Guard Rod
Friction Washer
(or Packing Gland)
Bottom
Gauge
Fitting
WAR N I N G
!
Drain Valve
Safety glasses and gloves
A
Vessel Wall
Gauge Glass
Glass Packing
Nut
Glass Packing
B
should be worn at all times when working
with or examining water gauge glass and
connections.
Pressure in generator to be at zero before
proceeding.
Improper installation or maintenance of gauge
glass and connections can cause immediate or
delayed breakage resulting in bodily injury
and/or property damage.
20
Page 21
Installation, Operation & Maintenance Manual
Gauge Glass Installation - Use and Care
O NOTs
D
• DO NOT use glass if it contains any scratches, chips, or
any other visible signs of damage.
• DO NOT reuse any tubular glass or glass packings.
• DO NOT subject gauge glass to bending or torsional
stresses.
• DO NOT over tighten glass packing nuts.
• DO NOT allow glass to touch any metal parts.
• DO NOT exceed the recommended pressure of the
gauge or gauge glass.
• DO NOT clean the gauge or gauge glass while pressurized or in operation.
DO's
• DO verify proper gauge has been supplied.
• DO examine gauge glass and packings carefully for
damage before installation.
• DO install protective guards and utilize automatic ball
checks where necessary to help prevent injury
in case of glass breakage.
• DO inspect the gauge glass daily, keep maintenance
records, and conduct routine replacements.
• DO protect glass from sudden changes in temperatures
such as drafts, water spray, etc.
AINTENANCE
M
Examine the gauge glass regularly for any signs of
clouding, scratching, erosion, or corrosion. The glass
should be inspected daily until the need for replacement becomes apparent. This will help establish the
routine inspection and routine replacement schedules.
CLEANING
Use commercial non-abrasive glass cleaners to keep
glass clean. Use diluted acids such as Hydrochloric
(muriatic) acid when regular cleaners do not seem to
work. Do not use wire brushes or any other abrasive
materials which could scratch the glass.
INSPECTION
Examine the surface of the glass for scratches, corrosion, chips, cracks, surface flaws, or nicks. To do this,
shine a very bright concentrated light at an angle of
about 45 degrees. A defective glass will glisten as the
light strikes imperfections. Glass which appears cloudy
or roughened, and will not respond to cleaning,
should be replaced.
STORING
Keep gauge glass in original packaging until ready to
install.
21
Page 22
Installation, Operation & Maintenance Manual
Element Replacement
READ INSTRUCTIONS COMPLETELY BEFORE STARTING WORK
CA U T I ON
!
the McDonnell Miller low water cut-off and aux. low water cutoff
(if supplied) is operating properly. The float chamber and lower
equalizer column of the MM control must be completely clear of
sludge or other foreign matter. Failure to do this may cause the
immediate burn-out of the new elements. If the unit is probe
equipped, check condition of the probes and isolator.
All elements are thoroughly checked before shipment The
manufacturer cannot be responsible for burn-outs caused by a
faulty low water cut-off.
The lower equalizer column can best be examined by breaking
the unions on either side and then visually and manually
examining the piping with your finger or probes to see if it is
clear and clean.
1. Disconnect boiler from electric power supply at main safety switch or fuse panel.
Then turn boiler switch to “OFF" position.
2. Close water supply valve on incoming water supply line. Drain boiler completely of
water.
3. Open boiler door to access heating element.
4. Disconnect wire (electric) leads connecting element to main power system of boiler.
Again, note wire connections to facilitate re-assembly. Proceed to remove and
discard (6) bolts from flange.
IMPORTANT: Note the wire connections to facilitate re-assembly (see wiring schematic). Remove and discard six (5/16"-18) bolts from flange. Do not reuse these bolts.
5. Thoroughly clean boiler flange of all foreign material. Be certain no part of old
gasket remains on flange.
6. Apply "Slic-Tite" Gasket Compound (or equal) to both surfaces of new gasket
supplied with replacement element. Proceed to install element flange assembly
with gasket between boiler flange and element flange. In doing this, be careful to
align flange holes so element wire connection terminals on element assembly are
in line with previously disconnected wire leads to facilitate easy connections.
NOTE:
7. Use only new element flange bolts. Tighten all (6) element flange bolts to a torque
8. Connect all wires to the terminals. Tighten all element terminals to a torque value
9. Check that the wires are correctly connected to the contactor terminals and are
10. Open water valve to allow water supply to reach boiler feed mechanism.
11. As boiler automatically refills, observe the new flange assembly for possible leaks.
12. When boiler reaches working pressure, check flange assembly again for leaks.
Observe markings on element flange. Install element marking “TOP” on top.
value of 22 lb-ft each (see illustration).
of 20 lb-in each (see illustration). Make sure all wires are clean and bright to assure
good electrical contact.
tightened to the torque listed on the contactor. Make sure all wires are clean and
bright to assure good electrical contact.
If water is noticed, the bolts must be re-tightened. Before doing this, turn the
boiler off at the main fuse safety switch.
CA U T I ON
!
Before Installing your new elements be sure
Boiler with
McDonnell Miller
11⁄2”
Follow maintenance instructions provided with the boiler.
1” Steam Equalizing Pipe
Pump and Low Water Control
Normal Boiler Water Line
Cut-Off Level is Arrow Mark
Blowdown Valve
1” Water Equalizing Pipe
Torque Values:
Torque
Wrench
Element Flange Bolts: 22 lb-ft
Torque
Wrench
Element Terminals: 20 lb-in
Torque
Wrench
Contactor Terminals: see Torque chart
For Illu st rative P ur po ses Only.
Power wi ri ng shown in ap pr oximate
factory -i nstalled l oc ation
TORQUE VALUES
Element Flange Bolts22 lb-ft
Element Terminals20 lb-in
Contactor Terminals:Tighten to torque
specified on contactor
22
Page 23
Installation, Operation & Maintenance Manual
Water Quality Information for Carbon Steel Boilers
For optimum results, the feedwater supply should be tested prior to initial startup. If the mineral content exceeds the following recommended limits, various
external treatment processes (water softener, reverse osmosis, etc.) may be used to
correct the problem.
NOTE:
An analysis of the on-site boiler feedwater must be made by a
recognized and reliable water treatment company to ascertain the existing
condition and treatment required.
Blow down the boiler on at least a once-a-day basis. If boiler water or feed-water
are outside the above limits, a more frequent blowdown is required.
Water quality can affect efficiency or result in boiler damage if neglected. Boiler
feedwater contains impurities in solution and suspension. These impurities
concentrate in the boiler since the steam generated is essentially pure. The
concentration of these impurities increases as more feedwater is introduced into
the boiler and steam is produced. If the suspended solids are allowed to
concentrate beyond certain limits, a deposit or “scale” will form on the boiler’s
internal surfaces. This deposit can interfere with proper boiler operation and
cause boiler failure.
The concentration of these impurities is generally controlled by the feedwater
quality and by blowdown. Blowdown refers to removing a portion of the boiler
water with high solids concentration and replacing it with make-up water of a
lower concentration.
23
Page 24
U S A
Designed, Enginee red
and Assembled in the
A Division of Sussman-Automatic Corporation
43-20 34th Street, Long Island City, NY 11101 • (718) 937-4500
1-800-238-3535 • Fax: (718) 937-4676 • email: [email protected]
www.sussmanboilers.com
PUR 101137
REV
5.18
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.