Surna 24-1, 42-1, 60-1, 90-3, 120-3 Operating & Maintenance Manual

Page 1
www.surna.com
303.993.5271
Surna Commercial Chiller
Operating & Maintenance Manual
Models: 24-1, 42-1, 60-1, 90-3, 120-3 Revised: February 2015
Page 2
Page 3
Table of Contents
Limited Warranty 4 Limitation of Liability 4 Warranty Disclaimer 4 Product Suitability 4 Service Under Warranty 5 Service NOT Under Warranty 5
Warnings 6 Safety Symbols 6
Surna Chiller Safety Guide 6
Parts List 8 Installation Instructions 9 Location 9
Electrical 9 Plumbing 9
Plumbing Tips 10
Operations Instructions 12 Temperature Settings 12
System Maintenance Instructions 12 and Recommendations
System Specications 14
Troubleshooting 18 Temperature Controller has no 18
Power Temperature controller is on, but 18 the Chiller Won’t Start
Fan Turns on and off, Even Though 19
the Compressor is Running
3
Page 4
Warranty Information
Limitation of Liability
Thank you for choosing the Surna Chiller System. Because your chiller is built with leading technologies and the highest quality components, with proper care and maintenance, it will provide you with years of worry-free service. Please examine the unit upon arrival to be sure there is no damage as a result of shipping. If shipping damage has occurred, please note the damage on the receiving slip, and contact Surna immediately.
If you are missing parts or believe that you have a warranty issue, DO NOT return this item to the store of purchase. You must contact Surna at 303-993-5271 for troubleshooting and service
instructions.
Limited Warranty
A 90-day all-inclusive warranty for: parts, labor, and shipping (including refrigerant). Choice of repair facility and technician is at the discretion of Surna.
A 1-year warranty on any defective part is also provided (including refrigerant). Choice of repair facility and technician is at the discretion of the chiller’s owner, although Surna is happy to assist with locating a technician. If Surna chooses the technician, limited labor coverage may apply.
A 5-year warranty is provided for standard compressors (excluding refrigerant and labor). Choice of repair facility and technician is at the discretion of the chiller’s owner, although Surna is happy to assist with locating a technician.
To the extent allowable under applicable law, Surna’s liability for consequential and incidental damages is expressly disclaimed. Surna’s liability in all events is limited to and shall not exceed the cost of repair. Shipping damage is not covered under warranty. In the event that the item(s) arrive with shipping damage, Surna will assist with the repair or replacement of the damaged item ONLY if the damage is noted on the delivery receipt.
Warranty Disclaimer
Surna provides product information in this
literature for the sole purpose of identication,
and does not state or imply that the products are
merchantable, or t for a particular purpose, or
that the products will conform to the descriptions.
Product Suitability
Many jurisdictions have codes and regulations governing sales, construction, installation, and/ or use of products for certain purposes, which may vary from those in neighboring areas. While Surna attempts to ensure that its products comply with such codes, it cannot guarantee compliance, and cannot be responsible for how the product is installed or used. Before purchase and use of a product, review the product applications, and all applicable national and local codes and be sure that the product, installation and use will comply with them.
A 10-year warranty is provided for high efciency
compressors (excluding refrigerant and labor). Choice of repair facility and technician is at the discretion of the chiller’s owner, although Surna is happy to assist with locating a technician.
Note: Extended warranty for parts, labor and shipping are available for purchase for a nominal fee. Contact Surna within 15 days of your chiller’s arrival if you would like to purchase an extended
warranty.
4
Page 5
Service Under Warranty
This product is warranted by Surna against defects due to fault in workmanship or materials.
If the product has been damaged under normal use, it will be entitled to warranty service of the type described and within the timeframes outlined. Damage caused by abnormal use, or after the timeframes outlined have expired, carry no such guarantee. Service under warranty is provided only upon presentation of reasonable evidence (purchase receipt) that the date of claim is within the warranty period.
Service NOT Under Warranty
The warranty is not valid if the defect is due to accidental damage, misuse, shipping damage, neglect, or in the case of alterations or repair carried out by unauthorized persons. Surna can, at its discretion, assist the consumer with shipping claims in the case of damage incurred during shipping, so long as the customer follows the instructions outlined above.
5
Page 6
Warnings
Safety Symbols Used
CAUTION: Important information, consult
product manual and read the provided instructions carefully.
WARNING: Potential electric shock hazard.
Protective Earth Connection
Action Prohibited
Surna Chiller Safety Guide
Please read the information in this document carefully prior to attempting the installation, operation and/or servicing of the Surna Chiller. This document contains all information required to install and operate the Surna Chiller commercial line of water-cooling devices. Failure to follow the directions provided herein may impair the safeties provided and could cause damage to the Surna Chiller equipment and or accessory equipment, damage to building facilities, and/or cause serious injury or death to the operator. Please adhere to all applicable safety guideline requirements in this document and all applicable electrical and mechanical jurisdictional codes.
Prior to providing power to the equipment, be sure to inspect the area for water spills, which may present a shock hazard to the user. Take extra care to mount accessory electrical equipment away from areas regularly exposed to water and be sure to provide secure wire and cable routing to protect personnel from shock hazards.
Only operate the equipment with an appropriately sized breaker in place and wire sizes with adequate current carrying capacity. Consult with an electrician before attempting electrical installation.
Using the Surna Chiller equipment in a manner not described in this manual may void its warranty.
Following unit installation and maintenance activities, the user shall observe the system operation to verify that normal operation has resumed prior to leaving the equipment to operate unattended.
6
Page 7
Only use parts provided with, or specied for use
with, the Surna Chiller equipment.
DO NOT operate the Surna Chiller at a
temperature setting lower than 45°F (7°C) or risk freezing the evaporator, which is not covered under the product warranty.
DO NOT operate the Surna Chiller without an
appropriate mixture of Propylene Glycol. For optimum performance, Surna recommends using a 50%/50% (glycol/water) mixture. The system requires a minimum of 30%/70% (glycol/water) mixture to operate safely. A 50%/50% (glycol/water) mixture is needed when outdoor temps fall below 20°F (-7°C).
DO NOT operate the Surna Chiller without
adequate water ow. These chiller systems
require 2.5 GPM (Gallons per Minute) per ton of cooling to prevent freezing of the evaporator.
DO NOT remove the grounded connection
while power is being supplied to the Surna Chiller equipment. Doing so presents an electric shock hazard to users and service personnel.
Our chiller systems are approved for use with devices used in water chilled applications that allow for the use of propylene glycol and require a temperature of 45°F (7°C) or higher. Any such devices shall be used in accordance with the safety regulations in your local jurisdiction. Please contact Surna if you are unsure about how to properly incorporate our chillers within your system.
DO NOT use the Surna Chiller indoors without
proper ventilation. If the indoor temperatures are greater than 100°F (38°C), the room does not have adequate ventilation.
7
Page 8
Surna Chiller Parts List
Below is a list of all parts provided with each Surna Chiller system.
1. Surna Chiller Product Manual
2. Chiller Unit
3. Strainer
4. Flow Meter
3. Brass Strainer
4. Flow Meter (front and side view)2. Chiller Unit
8
Page 9
Installation Instructions
Location
Only install the Surna Chiller equipment on a at,
level surface. Acceptable surfaces include con­crete slabs, A/C pads, or pressure treated wood. Before attempting installation, be sure to verify that the mounting surface exhibits suitable load bearing capacity. Please consult the
specication section of this document for the
weight information for each chiller model. The unit shall be placed on a hard surface that extends a minimum of 6 inches from all sides of the chiller housing. This is to prevent dirt and debris from entering the condenser, which will
affect cooling efciency. DO NOT place the unit
directly on the ground. Damage caused by debris striking the condenser is not covered under warranty. Roof mounting is acceptable so long as the roof joists are rated to support the chillers weight load. Consult your local building codes and guidelines before attempting roof mounting.
Following installation, verify that there is a minimum of 24 inches of clearance from obstruction on all sides and no obstructions
above the unit to ensure proper airow over the
condenser.
Electrical
Contact an electrician if you are not familiar with the local codes and standards in your jurisdiction. Before attempting electrical installation, be sure to verify that appropriately sized circuit breakers are in place to handle the electrical load of your chiller. The ampacity is provided for each
chiller unit in the Specications section of this
document along with recommendations for sizing your circuit breaker. The cross-sectional wire sizing to be used for the power connections is a product of the chiller unit’s ampacity and the length of wire needed. Consult an electrician for more information on power wire sizing and connection.
Plumbing
IMPORTANT: You must use a mixture of Propylene
Glycol and water in your reservoir. Your reservoir should contain 30% Propylene Glycol to 70% water (minimum), and contain up to 50% Propylene Glycol to 50% water (maximum). We recommend a 50%/50% mixture for optimum
cooling efciency. A 50%/50% mixture is
necessary when outdoor temperatures fall below 20°F (-7°C). Failure to use an appropriate amount of Propylene Glycol may result in degradation of system performance and/or damage to the chiller unit which is not covered under warranty.
DO NOT use standard car antifreeze in the Surna
Chiller System (Ethylene Glycol).
Reservoir size is dependent on the type and amount of equipment being cooled. If your chiller is properly sized, a reservoir size of greater than 50 gallons per 10 Tons of cooling is rarely necessary, although larger reservoirs will result in longer cycle times.
Depending on the size of your unit, the plumbing connections will come in either 1” or
3/4” connections. Refer to the Specications
section in this document for information on your chiller’s plumbing inlet/outlet connections. It is our recommendation that you use tubing that is sized 1/4” larger than the provided plumbing
connections on your specic chiller unit (use
an appropriate adapter for connection to the
chiller). This is to ensure maximum water ow
without restriction.
Be sure to install the water connections to the appropriately labeled “WATER IN” and “WATER OUT” ports on the chiller unit. This equipment will not function if these connections are reversed.
9
Page 10
Important Plumbing Tips
• ALWAYS use a backup wrench when
installing water ttings. Failure to do so can
cause damage to the copper lines, which is not covered under warranty.
• ALWAYS use the brass strainer that is
provided with the unit. This strainer should be installed on the supply line water connection and is meant to prevent particles from entering the heat exchanger so as to
maintain optimum water ow and efciency.
• Periodically check the strainer to verify that
the chiller is receiving the desired water ow.
We recommend installing in-line water valves both before and after the strainer. This will allow you to inspect the strainer regularly without losing Glycol.
• If 90 degree bends are required in your layout, we recommend using long-turn 90’s
or exible spa tubing to prevent restriction of water ow. Spa tubing can be glued with PVC glue or PVC tting. In either case, we
recommend using piping/tubing that is sized 1 size larger that the chiller water connections provided.
• Your chiller requires a ow rate of 2.5 GPM/
ton (i.e. 5 GPM for a 2 ton chiller, 25 GPM for a 10 ton chiller, etc.). Failure to ensure
adequate water ow through the chiller may
result in system degradation, damage to the evaporator, and/or damage to the compressor.
• The chiller is provided with an appropriate
ow meter for your system so that you can verify adequate ow through the chiller.
Always install this meter INDOORS where it can be easily monitored. Maintaining proper
ow rates through your chiller is critical to the efciency of the unit and to prevent
damaging the evaporator.
• The proper pump sizing will vary based on water line lengths, equipment being pumped to, lift rates, etc. Please contact Surna for more details on properly sizing your pump.
Flow Diagram
Single pump layout. Consult Surna if your layout requires multiple pumps or chillers.
10
Page 11
Installation Connections
A
B
C
D E
F
Installation Connections
A – Water Inlet B – Water Outlet C – Electrical Panel D – Power Connections (beneath contactor) E – Cable Routing Port F – Delay Timer
2, 3.5 & 5-Ton Power 7.5 & 10-Ton Power
Grounding
Power Connectors
NOTE: If the compressor makes an unusual noise after applying 3-Phase power (7.5 and 10-ton units), you have installed the
power wiring backwards. Shut the unit off immediately, shut the electric supply off at the breaker, and reverse any 2 of the 3 line conductor wires.
11
Page 12
Operation Instructions
Temperature Settings
After you have made all of the appropriate electrical and plumbing connections per the instructions provided above, you may power on the chiller unit and set your desired temperature using the following procedure:
• Turn the chiller on using the switch on the temperature controller.
• Press “Set” once: Choose Celsius or Fahrenheit using up or down arrows.
• Press “Set” twice: Using the up and down arrows, set your desired chiller temperature set point (NEVER set this below 45°F / 7°C)
• Press “Set” three times: This is your temperature differential and should NEVER be changed from the factory preset of 3 degrees. Reducing this will cause rapid cycling of the chiller’s compressor, which will shorten the life-span of the unit. Increasing this number could lead to temperature spikes.
• Press “Set” four times: This should always read “C1” per the factory preset. If this menu reads anything other than “C1,” the chiller will not function.
• All other settings should never be changed from the factory presets.
System Maintenance Instructions and Recommendations
• ALWAYS maintain a clean condensing coil
for maximum efciency. Chiller units located
indoors will need to be cleaned often due to dust build-up. Units located outdoors are often washed by rainfall.
• ALWAYS maintain 24” of clearance on all
sides of the unit and an unobstructed clearance on the top of the unit. Make sure the unit has plenty of fresh air available for heat exchange. We recommend outdoor use.
• DO NOT use the chiller indoors without
proper ventilation. If temperatures in the room reach 100°F (38°C), the room is not properly ventilated.
• If using the chiller in an environment with freezing ambient temperatures, a compressor heater is needed to prevent the compressor from freezing. Damage caused due to failure to use a compressor heater is not covered under warranty. The compressor heater can be installed at the factory, or be purchased aftermarket and be installed on-site by a
qualied technician.
• When using the chiller unit with water-cooled air handlers: Start the chiller temperature at 55°F (13°C) and adjust up or down based on
cooling and dehumidication needs. NEVER
set this temperature below 45°F (7°C).
• When using your chiller with other water-cooled devices, such as Ice Boxes or Cool Coils: Start the chiller temperature at 65°F (18°C) and adjust up or down based on cooling needs. NEVER set this temperature below 45°F (7°C).
12
• ALWAYS provide a minimum of 2.5 GPM
(Gallons per Minute) per ton of chiller capacity to prevent freezing of the evaporator and to achieve optimum system performance.
• ALWAYS install the strainer/lter provided
with the equipment to prevent debris from clogging the heat exchanger.
• We strongly recommend a 50%/50% (glycol/ water) mixture to operate your chiller system under optimum conditions. At a minimum, a 30%/70% (glycol/water) mixture must be used for chiller operation. Not using the prescribed
Page 13
glycol/water mixture may cause system
inefciencies or damage to the evaporator,
which is not covered under warranty.
• NEVER set the chiller below 45°F (7°C) or risk
freezing the evaporator, which is not covered under warranty.
• Only use properly sized breakers and wiring with an appropriate ampacity or damage to the compressor could occur. The further the unit is away from the breaker box, the larger the wire gauge must be to carry
sufcient amperage when the compressor
starts. Damage caused by improper wiring is not covered under warranty. Please consult
with a qualied electrician for more
information on proper breaker and wire sizing if you are not sure.
• Chillers must be installed on concrete or an A/C condenser pad. Failure to do so can cause the condenser to become dirty sooner from splashing dirt and debris when it rains. This will also cause premature rusting of the chiller base where it contacts the ground.
• Proper voltage must always be maintained.
Consult the System Specication section of
this document for more information.
13
Page 14
System Specications
14
Page 15
10-Ton Chiller Chiller Control Panel Connections
A
F
Control Panel Components
A – Control Panel Exterior B – Heat Exchanger C – Temperature Controller D – Thermal Expansion Valve E – Flow Switch F – Low Pressure Switch G – Fan Cycle Switch *High Pressure Switch located inside unit
G
B
C
D
5-Ton Chiller Control Panel Connections
A
E
F
Control Panel Components
A – Control Panel Exterior B – Heat Exchanger C – Temperature Controller D – Thermal Expansion Valve E – High Pressure Switch F – Low Pressure Switch G – Fan Cycle Switch H- Flow Switch (behind E)
G
B
C
D
H
E
15
Page 16
10-ton Chiller Wiring Diagram
16
Page 17
2-7.5 ton Chiller Wiring Diagram
Page 18
Troubleshooting
This unit is equipped with safety sensors that may include high and low pressure sensors for the
refrigeration circuit and also a ow switch to help
prevent freezing if there is a pump failure or other
loss of ow. If any of these sensors are not satised, they will not allow the chiller to function.
Some of the troubleshooting steps listed below can be performed by the end user, and some of these steps must be performed by a licensed HVAC technician. Retain this guide should your chiller ever require servicing in the future.
sure you are getting 24VAC across the sensor
while sufcient water is owing. If there is no
voltage across the sensor leads with a
proper ow-rate, then the sensor needs to be
replaced.
9. Check the direction of ow in the water circuit. If water is owing backwards, the ow switch will
not allow power to the temperature controller, and the unit will not function properly.
Temperature controller is on, but the unit will not
start Temperature controller has no power
1. Check and make sure switch is in the on position.
2. Check breaker for proper function.
3. Check ow meter for adequate water ow (2.5 GPM per ton). Insufcient ow will cause
loss of power.
4. QUALIFIED SERVICE PERSONNEL ONLY: Check
ow for proper voltage at the unit with an
electric volt-meter.
5. Visually check for any loose wires.
6. QUALIFIED SERVICE PERSONNEL ONLY: Remove the front cover of the temperature sensor and check voltage. If 24 VAC is present, and all wires are installed and tight, then most likely the controller will need to be replaced. If no voltage is present, see the next step.
7. The controller is wired so that it will not come
on if there is not sufcient water ow to the unit.
If there is no voltage at the controller, check
the ow and verify that the chiller is receiving at
least 2.5 GPM for each ton of cooling required.
If there is sufcient ow, see the next step.
8. Check connections of the ow sensor (the ow sensor is installed in the water line) to make
1. The unit has a 5-minute delay on start-up
before beginning normal operation. Before
troubleshooting, ensure that 5 minutes have
passed.
2. Check the temperature set-points of the
controller to verify that the desired settings are
still in place. The factory differential temperature
should be 3 degrees, and shouldn’t be changed.
For example, with the factory set differential
temperature setting of 3 degrees, and a desired
temperature setting of 45°F (8°C), the unit will not
start until the water reaches 48°F (9°C).
4. Check to make sure the controller is set to C1.
5. QUALIFIED SERVICE PERSONNEL ONLY: Check
voltage at relay (space terminals on each side),
which should be 24VAC while the temperature
controller is calling for cooling, then check for a
loose wire on the controller. If none are found,
check for power at the relay inside the controller.
If you have power there the other cause would
be a tripped high/low pressure sensor, in which
case an HVAC technician will need to service
your unit. He/she should check the refrigeration
pressures with a gauge set to verify that there is
not a problem with system pressures. If no
problems are found with pressure, then the high/
low pressure sensor may need to be replaced.
6. QUALIFIED SERVICE PERSONNEL ONLY: Check
the voltage across the ENDS of the main relay
with a meter. This should be 240VAC on each
side when the temperature controller is
18
Page 19
calling for cooling. If there is not 240VAC on each side, the relay is malfunctioning and needs to be replaced.
Fan turns on & off even
though the compressor is
7. QUALIFIED SERVICE PERSONNEL ONLY: If there is voltage across the relay when the temperature controller is calling for cooling and the compressor, fan, or both are not coming, the capacitor could be malfunctioning and needs to be replaced. Check voltage across the capacitor to verify. Bulging capacitors are an indication of a problem.
8. If both the compressor and fan are not engaging, then the problem is almost certainly an easily replaced bolt on component, and not with the fan or compressor themselves. If one of the two components is not running after these troubleshooting steps have been attempted, there could be a problem with one of those components and they may need to be replaced. The fan motor is simple to replace and can be done by the end user after all power has been disconnected from the unit. If compressor replacement is required, a licensed refrigeration technician must complete the associated repairs.
running
1. The unit is equipped with a fan cycle switch, in which case the fan will come on only when absolutely needed. The cycling of the fan is most common in cooler weather.
9. QUALIFIED SERVICE PERSONNEL ONLY: If the refrigerant charge of the unit is in question, the best avenue for checking this is to recover and weigh the charge. The amount of refrigerant in the system is written on the product label. Pressures are an unreliable indicator of proper charge.
19
Page 20
303.993.5271 [email protected] surna.com
1780 55th Street Suite A, Boulder, CO 80301
Loading...