Standard Integrated Microstepping Motor and Drive (Non-SCL)
Step 1:
Do not apply power until all connections to the drive have been made.
Per the diagrams below, connect fused DC power to the V+ terminal on the STP-MTRD, and DC Common to the V- terminal on the STP-MTRD. Note that the NEMA 23 V+ and V­connector locations are the same as the NEMA 17 (pictured).
Requirements:
Each model accepts the following DC voltages:
STP-MTRD-17x: 12-48 VDC
STP-MTRD-23x: 12-70 VDC
If using an external fuse, the following slow blow fuses are recommended:
STP-MTRD-17x: 2 amp
STP-MTRD-23x: 4 amp
Control wiring connections:
STP-MTRD-17x: Includes a removable 11-pin
IDC connector with 12” leads. Long pre-made control cables are available (STP-CLB-CAx)
STP-MTRD-23x: Includes a removable 10-pin
field wireable connector (screw terminals).
Step 2:
Connect input signals to the drive. STEP and DIR are required, EN and OUT are optional.
See the User Manual for circuit connection details and examples (
https://cdn.automationdirect.com/
static/manuals/surestepmanual/surestepmanual.html).
STP-MTRD-17 series shown
STP-MTRD
OUT-
OUT+
EN-
EN+
DIR-
DIR+
STEP-
STEP+
N.C.
V ­V+
orange
brown
yellow
green
blue
tan
grey
black
red
pink
white
1 2 3 4 5 6 7 8 1 2 3 4
6(783
65
STP-MTRD-17x: 11-pin connector. Color code is for 12” IDC cable (included w/motor) and optional
STP-CBL-CAxx cables.
STP-MTRD-23x: 10-pin screw terminal. Pinout is identical
to NEMA 17 version, except the “N.C.” is not present.
* Not present on NEMA 23 motors
*
Step 3:
In the “S/R” (Steps/Revolution) DIP switch bank, select the desired step resolution (steps/ rev) using switches 1-4, located on the upper block of four switches (pictured above).
1234
200
1234
400
1234
800
1234
1600
1234
3200
1234
6400
1234
12800
1234
25600
1234
1000
1234
2000
1234
4000
1234
5000
1234
8000
1234
10000
1234
20000
1234
25000
Step 4:
In the “SETUP” DIP switch bank, set the motor’s running current using switches 1 and 2. This is the percentage of full current that the motor will use when the shaft is rotating.
12
100%
12
90%
12
70%
12
50%
Stepping Systems
For a complete user manual, please visit www.automationdirect.com
Data Sheet: STP-MTRD-QSP, 1st Ed – 03/12/2018
Step 8:
Optionally, you can test motor operation by activating switch 4 in the “SETUP” DIP switch bank to initiate a self test. The self test continually rotates the motor forward and backward 2 1/2 revolutions.
Additional Help and Support
• For product support, specifications, pricing and installation troubleshooting, a Hardware User Manual can be downloaded from the Online Documentation area of the AutomationDirect web site.
• For additional technical support and questions, call our Technical Support team @ 1-800-633-0405 or 770-844-4200.
Step 7:
Optional settings in the “SETUP” DIP switch bank–the default settings for these switches are typically sufficient. See the User Manual for details on these functions.
A. [Switch 5] Step Pulse Noise Filter
B. [Switch 6] Step Smoothing Filter
C. [Switch 8] Step Pulse Type (Step/
Direction is default)
6ON6
OFF
SMOOTHING
8
CW PULSE/
CCW PULSE
STEP/
DIR
8
5
150 KHZ
5
2.0
MHZ
4
ON
4
OFF
Optional Encoder:
An optional encoder is available pre-mounted on “E” models. The standard encoder is a 1000ppr, Differential line driver encoder. See below for pinouts and wire colors for the replacement cable (STP-CBL-EAxx) and included cable with the STP-MTRD.
For more information on the encoder, please see the Sure Step User Manual. Replacement encoder part number is STP-MTRA-ENC1.
PIN 1
PIN 2
Step 5:
In the “SETUP” DIP switch bank, set the motor’s idle current using switch 3. This is the percentage of running current that the motor will use when the shaft is not rotating. Choose 90% for maximum holding torque or 50% to reduce motor heating.
Step 6:
In the “SETUP” DIP switch bank, select the load-to­motor ratio category using switch 7. This is the ratio of the effective load inertia to the motor’s own rotor inertia. For high inertia loads choose 5-10X, and for low inertia loads choose 0-4X. Setting the proper range for the load will improve motor smoothness.
3
50%390%
7
5-10X
7
0-4X
Encoder connection
Note: PiN 1 aNd PiN 2 are iNterNally coNNected. PiN 7 aNd PiN 8 are iNterNally coNNected iNside
the eNcoder.
Stepping Systems
For a complete user manual, please visit www.automationdirect.com
Data Sheet: STP-MTRD-QSP, 1st Ed – 03/12/2018
IO Connector
Digital Outputs
Digital Inputs
EN Input
Connecting as a Sinking Output Connecting as a Sourcing Output
Driving a Relay
STP-MTRD
5-24 VDC
Pow er Supply
+–
Load
OUT-
OUT+
+–
OUT-
OUT+
Load
1N4935 (or equivalent) suppression diode
5-24 VDC
Pow er Supply
+–
relay
OUT-
OUT+
STP-MTRD STP-MTRD
5-24 VDC
Pow er Supply
Connecting the Input to a Switch or Relay
Connecting an PNP Type Proximity Sensor to an input
(When prox sensor activates, input goes low).
Connecting an NPN Type Proximity Sensor to an input
(When prox sensor activates, input goes low).
All
STP-MTRD
Switch or Relay
(closed = logic Low)
EN-
EN+
5-24
VDC Power Supply
-
+
NPN
Proximit y
Se nsor
output
+
5-24
VDC
Power
Supply
EN-
EN+
-
+
5-24 VDC
Power
Supply
PNP
Proximit y
Se nsor
output
+
-
+
EN-
EN+
All
STP-MTRD
All
STP-MTRD
inside drive
220 pF
STEP+
1
2
3
4
5
6
7
8
STEP-
220 pF
DIR+
DIR-
220 pF
EN+
EN-
OUT+
OUT-
STEP+
STEP-
Connecting to indexer with Sinking Outputs
Connecting to indexer with Sourcing Outputs
All
STP-MTRD
DIR+
DIR DIR-
STEP+
STEP STEP-
5-24 VDC
DIR+
DIR-
DIR-
DIR+
STEP-
STEP+
STEP
5-24 VDC
DIR
Connecting to indexer with Dierential Outputs
Indexer
or PLC
with Sinking
Outputs
Indexer
or PLC
with Sourcing
Outputs
Indexer
or PLC
with
Differential
Outputs
STEP+
STEP-
DIR+
DIR-
All
STP-MTRD
All
STP-MTRD