AC EXIT INSTALLATION
WALL MOUNTING
Step 1. De-energize the circuit at the junction box (J-box) where the exit sign
is to be installed.
Step 2. Extend unswitched 24 hour AC supply of rated voltage from the
J-box. Use the black, orange, and white extension leads and wire
nuts provided. Determine the line voltage to be supplied to the exit
and follow the instructions in the table below.
NOTE:
If the junction box is not grounded, attach ground wire to hole marked gnd
on mounting plate with green grounding screw provided.
Step 3. Remove the exit sign stencil and backplate from the exit frame.
Step 4. Knock out the appropriate mounting pattern and the wire pass hole
in the exit backplate to fit the J-box being used.
Step 5. Thread the extension leads through the wire pass hole and securely
mount the exit sign backplate to the J-box. Snap the exit frame onto
the backplate.
Step 6. Using the backplate clip and the exit sign wire channels route the
extension leads to the appropriate push-in connector per the
schematic.
Step 7. Trim and strip (strip length .375 ) any excess wire allowing enough slack
to insert the stripped ends into the appropriate push-in connector.
Step 8. Insert the wires into the appropriate push-in connector.
Step 9. Energize AC supply, LED display will come on.
Step 10. Place the exit stencil back on the exit frame.
SURE-LITES
Installation Instructions For AC L.E.D. Exit Signs LPX Series
IMPORTANT SAFEGUARDS
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS
BE OBSERVED INCLUDING THE FOLLOWING:
1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS
2. Do not use outdoors.
3. Do not mount near gas or electric heaters.
4. Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized
personnel.
5. The use of accessory equipment not recommended by Sure-Lites may cause an unsafe condition.
6. Do not use this equipment for other than its intended purpose.
7.
SAVE THESE INSTRUCTIONS
Line voltage to J-box 120V J-box 277V J-box Neutral
Be supplied line line line
120 Volts Extend using N/A Extend using
the black lead the white lead
277 Volts N/A Extend using Extend using
the orange lead the white lead