Installation Instructions for EBP450X and EBP450F
IMPORTANT SAFEGUARDS
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS
BE OBSERVED INCLUDING THE FOLLOWING:
1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS
2. Do not use outdoors.
3. Do not mount near gas or electric heaters.
. Equipment should be mounted in locations and at heights where it will not readily be subject to
4
tampering by unauthorized personnel.
5. The use of accessory equipment not recommended by Sure-Lites may cause an unsafe condition.
6. Do not use this equipment for other than its intended purpose.
7.
SAVE THESE INSTRUCTIONS
Note 1. To prevent high voltage from being present on the output terminals (red/white, red, and yellow), do not connect the test button indicator light to
the EBP until Step 7 of the installation instructions.
Note 2. This product is for use with most 2’ through 8’ (13W-215W single and bipin fluorescent lamps including energy saving, circline, U-shaped and
biax. For specific lamp compatibility, please see the table later in the instructions.
Note 3. Make sure all of the connections are in accordance with the National Electrical Code and any local regulations.
Note 4. To reduce the risk of electrical shock, disconnect both normal and emergency power supplies and the test button indicator light (which
disconnects the battery) before servicing.
Note 5. This emergency ballast is for factory or field installation in the ballast channel.
Note 6. This product is for use in indoor fixtures. This product is not intended for use near air handling heated air outlets or in wet or hazardous locations.
Note 7. An unswitched AC power source is required (120, 240, or 277 volts).
Note 8. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field replaceable. Contact the manufacturer for
information on service.
Note 9. Servicing should be performed by qualified service personnel.
For use in temperature rating
20°C to 55°C
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801 4/12/11 024-115
EBP450XEBP450F
E
mergency
Ballast
T
est Button/
Indicator Light
Ballast
Channel
Cover
E
mergency
Ballast
Test Button/
Indicator Light
AUX
COMMON
AUX
N.O.
AUX
N.C.
LINE HOT
120/240/277
LINE
NEUTRAL
A
U
X
C
O
M
A
U
X
N
.
O
.
AUX N.C.
L
I
N
E
H
O
T
1
2
0
/
2
4
0
/
2
7
7
L
I
N
E
N
E
U
T
R
A
L
RED / WH
RED
BLUE
BLUE / WH
YELLOW
YELLOW / BK
T
E
S
T
B
U
L
I
G
H
T
C
1
1
2
1
H
i
g
h
w
a
y
P
e
a
c
h
t
r
e
e
C
i
t
y
E
m
e
r
g
e
n
c
S
u
i
t
a
b
l
e
f
o
W
ire Bundle
C
over
Drill 1/8˝ Hole
for Mounting Screws
Emergency
B
allast
Wire Bundle
C
over
1
/2˝ Std. Knockout
7
/8˝ Hole w/Bushing
EBP450X and EBP450F
SURE-LITES
INSTALLATION
WARNING: TO PREVENT HIGH VOLTAGE ON RED / WHITE, RED, AND YELLOW OUTPUT TERMINALS PRIOR TO
INSTALLATION, THE TEST BUTTON / INDICATOR LIGHT MUST BE DISCONNECTED. CONNECT THE TEST BUTTON /
INDICATOR LIGHT AFTER INTSALLATION.
Note: Make sure that the necessary branch circuit wiring is available. An unswitched source of power is required.
Step 1. Disconnect AC power from the fixture. Remove the ballast channel cover and install the emergency ballast either in the
ballast channel (see illustrations 1 & 2) or on top of the fixture (see illustration 3 / EBP450X only).
page 2
ILLUSTRATION 1
ILLUSTRATION 2ILLUSTRATION 3
EBP450X only
Step 2. Select the appropriate wiring diagram to connect the emergency ballast to the AC ballast and lamp. Make sure all
connections are in accordance with the National Electrical Code and any local regulations. (See Illustrations 4 and
5 for terminals).
ILLUSTRATION 4ILLUSTRATION 5
Terminal labels located
here.
Color coded label
located here.
Step 3.Refer to proper lamp compatibility table for the HIGH (Red) or Low (Red / White) connection per the lamp being
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801 4/12/11 024-115
illuminated by the emergency ballast.
Test Button / Indicator Light Connector
SURE-LITES
Emergency
Ballast
Ballast Channel
Cover
7/8" Punch
Plastic Tubing
(cut to necessary
length)
Test Button/Indicator Light
Leads to
Test Button/
Indicator Light
7/8" Bushing
Inserted into
Ballast Channel
Cover
TROFFER STYLE FIXTURE
Fixture
Test Button/
Indicator Light
Nut
STRIP STYLE FIXTURE
EBP450X and EBP450F
page 3
Lamp Compatibility Tables
Lamp Type
Number of
Lamps
Lamps Connected to
Low/High (Red) Output
Wattage
T51HIGH (RED)13-21
T51LOW (RED / WHITE)28-35
T5HO1LOW (RED / WHITE)24-54
T5,T9 CIRC1LOW (RED / WHITE)20-55
T81HIGH (RED)25-32
T81LOW (RED / WHITE)36-59
T8HO1LOW (RED / WHITE)48-86
T8U1HIGH (RED)32
T121HIGH (RED)34-40
T121LOW (RED / WHITE)56-75
T12HO1LOW (RED / WHITE)95-110
T12VHO1LOW (RED / WHITE)95-215
BIAX1HIGH (RED)40
BIAX1LOW (RED / WHITE)55
Step 4. Install the test button / indicator light through the ballast channel cover of a troffer (Illustration 1 & 6) or through the
side of a strip fixture (Illustration 2 & 7). Drill or punch a7/8” hole to install the test button / indicator light as shown in
illustration 6. Drill or punch a 1/2” hole to install the test button / indicator light as shown in illustration 7. Install the test
button / indicator light as shown in the selected illustration. Apply the two included labels (“Charging Indicator Light”
and “Emergency Light Push to Test”) adjacent to the test button indicator light.
Step 5.In a readily visible location, attach the included label “CAUTION – This unit Has More Than One Power Connection
Point. To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses and the Test
Button / Indicator Light Before Servicing”.
Step 6.In an area readily visible during relamping, attach the included relamping label. Write in the lamp type and wattage.
Step 7.After installation is complete, connect the test button / indicator light, supply AC power to the emergency ballast, and
replace covers while being careful not to pinch wires.
Step 8.A short term discharge test may be conducted after the emergency ballast has been charging for one hour.
Charge for 24 hours before conducting a long – term discharge test. Refer to OPERATION.
ILLUSTRATION 6ILLUSTRATION 7
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801 4/12/11 024-115
BLUE
BLUE
LINE NEUTRAL
RED
RED
AC BALLAST
LINE HOT
YELLOW/BK
YELLOW
BLUE/WH
BLUE
RED OR RED/WH
LAMP ("EMERGENCY")
EMERGENCY BALLAST
CHOOSE BASED
ON LAMP
AUX COM
LINE NEUTRAL
LINE NEUTRAL
AUX NO
SWITCHED OR UNSWITCHED LINE HOT
AUX NC
LINE HOT
(UNSWITCHED) 120/240/277
LINE HOT
YELLOW/BK
YELLOW
BLUE/WH
BLUE
RED OR RED/WH
LAMP ("EMERGENCY")
CHOOSE BASED
ON LAMP
AUX COM
AUX NO
AUX NC
LINE HOT
LINE NEUTRAL
SWITCHED OR UNSWITCHED LINE HOT
(UNSWITCHED) 120/240/277
LINE NEUTRAL
BLUE
LINE NEUTRAL
RED
AC BALLAST
EMERGENCY BALLAST
EBP450X and EBP450F
SURE-LITES
OPERATION:
When AC power is applied, the charging indicator light is illuminated, indicating the battery is being charged. When
power fails, the emergency ballast automatically switches to emergency power, operating one lamp at reduced
illumination for at least 90 minutes.
MAINTENANCE:
Although no routine maintenance is required to keep the emergency ballast functional, it should be checked
periodically to comply with local codes. The following schedule is recommended:
Step 1.Visually inspect the charging light monthly. It should be illuminated
Step 2.Test the emergency operation of the fixture at 30 day intervals for a minimum of 30 seconds. One lamp should
operate at reduced illumination.
Step 3.Conduct a 90 – minute discharge test once a year. One lamp should operate at reduced illumination for at least
90 minutes.
Refer any service requirements indicated by these checks to qualified personnel.
page 4
Note: After installing the test button / indicator light, mark it with the appropriate label.
WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLAST. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS
1 LAMP RAPID START
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801 4/12/11 024-115
1 LAMP INSTANT START
BLUE
BLUE
LINE NEUTRAL
RED
RED
AC BALLAST
LINE HOT
YELLOW/BK
YELLOW
BLUE/WH
BLUE
RED OR RED/WH
LAMP-2
CHOOSE BASED
ON LAMP
AUX COM
AUX NO
("EMERGENCY")
LAMP-1
YELLOW
YELLOW
AUX NC
LINE HOT
LINE NEUTRAL
SWITCHED OR UNSWITCHED LINE HOT
(UNSWITCHED) 120/240/277
LINE NEUTRAL
EMERGENCY BALLAST
BLUE
BLUE
LINE NEUTRAL
RED
RED
AC BALLAST
LINE HOT
YELLOW/BK
YELLOW
BLUE/WH
BLUE
RED OR RED/WH
LAMP-2
CHOOSE BASED
ON LAMP
AUX COM
AUX NO
("EMERGENCY")
LAMP-1
YELLOW
YELLOW
AUX NC
LINE HOT
LINE NEUTRAL
SWITCHED OR UNSWITCHED LINE HOT
(UNSWITCHED) 120/240/277
LINE NEUTRAL
EMERGENCY BALLAST
SURE-LITES
BLUE
BLUE
LINE NEUTRAL
RED
RED
AC BALLAST
LINE HOT
YELLOW/BK
YELLOW
BLUE/WH
BLUE
RED OR RED/WH
LAMP-2
CHOOSE BASED
ON LAMP
AUX COM
AUX NO
("EMERGENCY")
LAMP-1
YELLOW
YELLOW
AUX NC
LINE HOT
LINE NEUTRAL
SWITCHED OR UNSWITCHED LINE HOT
(UNSWITCHED) 120/240/277
LINE NEUTRAL
EMERGENCY BALLAST
LINE HOT
YELLOW/BK
YELLOW
BLUE/WH
BLUE
RED OR RED/WH
LAMP-2 ("EMERGENCY")
CHOOSE BASED
ON LAMP
AUX COM
AUX NO
LAMP-1
AUX NC
LINE HOT
LINE NEUTRAL
SWITCHED OR UNSWITCHED LINE HOT
(UNSWITCHED) 120/240/2277
LINE NEUTRAL
EMERGENCY BALLAST
BLUE
LINE NEUTRAL
RED
AC BALLAST
BLUE
WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLAST. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS
EBP450X and EBP450F
page 5
SERIES YELLOW FILAMENT
2 LAMP INSTANT START
2 LAMP RAPID START SERIES LAMP
PARALLEL YELLOW FILAMENT
LAMP PARALLEL YELLOW FILAMENT
2 LAMP RAPID START SERIES / PARALLEL LAMP
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801 4/12/11 024-115
2 LAMP RAPID START OSRAM SYLVANIA SERIES
BLUE/WHT
BLUE/WHT
LINE NEUTRAL
RED
RED
AC BALLAST
BLUE
BLUE
LINE HOT
YELLOW/BK
YELLOW
BLUE/WH
BLUE
RED OR RED/WH
LAMP-2
CHOOSE BASED
ON LAMP
AUX COM
AUX NO
("EMERGENCY")
LAMP-1
YELLOW
YELLOW
LAMP-3
AUX NC
LINE HOT
LINE NEUTRAL
SWITCHED OR UNSWITCHED LINE HOT
(UNSWITCHED) 120/240/277
LINE NEUTRAL
EMERGENCY BALLAST
LINE HOT
YELLOW/BK
YELLOW
BLUE/WH
BLUE
RED OR RED/WH
LAMP-2
CHOOSE BASED
ON LAMP
AUX COM
AUX NO
LAMP-1
LAMP-3 ("EMERGENCY")
AUX NC
LINE NEUTRAL
LINE HOT
SWITCHED OR UNSWITCHED LINE HOT
LINE NEUTRAL
(UNSWITCHED) 120/240/277
EMERGENCY BALLAST
BLUE
LINE NEUTRAL
RED OR YELLOW
AC BALLAST
BLUE
BLUE
SURE-LITES
BLUE/WHT
BLUE/WHT
LINE NEUTRAL
RED
RED
AC BALLAST
BROWN
BROWN
BLUE
BLUE
LINE HOT
YELLOW/BK
YELLOW
BLUE/WH
BLUE
RED OR RED/WH
LAMP-2
CHOOSE BASED
ON LAMP
AUX COM
("EMERGENCY")LAMP-4
YELLOW
YELLOW
LAMP-3
LAMP-1
AUX NO
AUX NC
LINE HOT
LINE NEUTRAL
SWITCHED OR UNSWITCHED LINE HOT
(UNSWITCHED) 120/240/277
LINE NEUTRAL
EMERGENCY
BALLAST
BLUE
LINE NEUTRAL
AC BALLAST
BLUE
RED
RED
LINE HOT
YELLOW/BK
YELLOW
BLUE/WH
BLUE
RED OR RED/WH
LAMP-3
CHOOSE BASED
ON LAMP
AUX COM
AUX NO
LAMP-2
LAMP-4 ("EMERGENCY")
LAMP-1
YELLOW
YELLOW
AUX NC
LINE HOT
LINE NEUTRAL
SWITCHED OR UNSWITCHED LINE HOT
(UNSWITCHED) 120/240/277
LINE NEUTRAL
EMERGENCY BALLAST
WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLAST. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS
EBP450X and EBP450F
page 6
3 LAMP INSTANT START
4 LAMP INSTANT START
PARALLEL YELLOW FILAMENT
3 LAMP RAPID START SERIES LAMP
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801 4/12/11 024-115
PARALLEL YELLOW FILAMENT
4 LAMP RAPID START SERIES LAMP
RED/WHT
LINE NEUTRAL
RED
RED
AC BALLAST
BLUE
BLUE
RED/WHT
LINE HOT
YELLOW/BK
YELLOW
BLUE/WH
BLUE
RED OR RED/WH
LAMP-2
CHOOSE BASED
ON LAMP
AUX COM
AUX NO
("EMERGENCY")LAMP-3
YELLOW
YELLOW
LAMP-1
AUX NC
LINE HOT
LINE NEUTRAL
SWITCHED OR UNSWITCHED LINE HOT
(UNSWITCHED) 120/240/277
LINE NEUTRAL
EMERGENCY
BALLAST
BLUE/WHT
LINE NEUTRAL
RED
RED
AC BALLAST
RED/WHT
RED/WHT
BLUE/WHT
BLUE
BLUE
LINE HOT
YELLOW/BK
YELLOW
BLUE/WH
BLUE
RED OR RED/WH
LAMP-2
CHOOSE BASED
ON LAMP
AUX COM
AUX NO
LAMP-3
YELLOW
YELLOW
LAMP-1
("EMERGENCY")LAMP-4
AUX NC
LINE HOT
LINE NEUTRAL
SWITCHED OR UNSWITCHED LINE HOT
(UNSWITCHED) 120/240/277
LINE NEUTRAL
EMERGENCY
BALLAST
SURE-LITES
YELLOW/BK
YELLOW
BLUE/WH
BLUE
RED OR RED/WH
CHOOSE BASED
ON LAMP
AUX COM
AUX NO
AUX NC
LINE HOT
LINE NEUTRAL
(UNSWITCHED) 120/240/277
LINE NEUTRAL
WIRE LAMPS USING DIAGRAM PER
# OF LAMPS AND BALLAST TYPE
SWITCHED LINE HOT
SWITCHED LINE HOT
LINE NEUTRAL
BI-LEVEL
AC BALLAST
EMERGENCY BALLAST
WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLAST. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS
EBP450X and EBP450F
page 7
PARALLEL YELLOW FILAMENT
4 LAMP RAPID START PARALLEL LAMP
BI LEVEL BALLAST
PARALLEL YELLOW FILAMENT
3 LAMP RAPID START PARALLEL LAMP
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801 4/12/11 024-115
When using the auxillary relay to switch the
neutral line, the Emergency and A.C. ballasts
must be on the same branch circuit.