Supreme Heating AquaGen 5 User Manual

The AQAUGEN 5 is a premium automatic solar controller
with temperature adjustment, manual, cooling
and standby mode features.
NATIONAL
AquaGen 5
Controller
User Manual
AquaGen 5 Controller
2
Controller Mounting
Find a suitable location to mount the control box. Ideally as with all pool equipment it should be installed out of direct weather and no closer than 3 meters from the water’s edge and a minimum 600mm above ground. Fix the mounting bracket to a solid structure and slide the controller on, keeping in mind that the power cable is 1.8m long and should be plugged directly into a general power outlet, not into an extension lead.
Pump Connection
The solar pump plugs into the 240V socket labelled PUMP. The maximum load is 9.98 AMPS at 2395W.
Pool Sensor
The pool sensor must be tted into the heating circuit, as close to the pool as practical, preferably in a position out of direct sunlight. It is recommended that a 14.5mm hole be drilled in the side of the PVC pipe (not the top of the pipe where water will collect). This can be carried out using a Dontek PD01 grinding drill or a small pilot hole can be drilled with a 14.0mm drill-bit spinning in a counter clockwise direction to minimise the chance of shattering pipe. Insert the grommet into the pipe and gently push in the sensor barb. Ideally ~30cm of the cable from the sensor should be tied to the shaded side of the pipe to prevent extreme ambient conditions leeching into the sensor via the copper in the cable. The blue sensor plug is to be tted to the plug socket marked POOL.
Roof Sensor
The roof sensor must be tted into a small piece of collector material away from the main collector but on the same aspect, preferably no more than 50cm from the roof gutter (for ease of sensor replacement). If required, the roof sensor can be on a dierent roof as the solar collector as long as the alignment to the sun is similar to the solar collector. For encapsulated collector panels, use the manufacturer’s instructions for roof sensor placement. The red sensor plug is to be tted to the plug socket marked ROOF.
SENSOR NOTES: All excess cable must be removed; coils of cable are not permitted under any circumstances and must not be tied to 240V wiring. If the cable is to be extended with non­genuine cable a size of 14/020 should be used. Any cable joins should be soldered. Heat shrink is to be used over soldered joints to eliminate moisture ingress, and the cable end is to be retted to the plug sockets. Once cables have been correctly tted the unit can then be turned on.
Installation Instructions
This appliance is not intended for use by young children or inrm persons without supervision. Please ensure that young children are supervised to ensure that they do not play with the appliance.
AquaGen 5
Controller
3
Operating Instructions
Mode Button
Pressing this button changes to the next mode of operation in the following order; Heating / Manual / Standby.
Once the mode button is no longer being pressed then the selected mode of operation is automatically saved.
Heating mode (Auto) is the normal operating mode for heating the pool.
Manual mode is for testing the pump installation on a cold or cloudy day. Once manual mode is
selected the pump will start. After manual mode time-outs, unit will return to the previous mode.
Standby mode of operation is for o-season maintenance or if pool heating is not required. This is a better option than turning o the controller as it will ush treated pool water through the solar system as well as prolong pump bearing and mechanical seal life. The pump will run for 3 minutes each day at 10am.
The factory default for SOLAR MODE is Heating MODE
Temperature Setting (Up and Down Buttons)
Adjusting the temperature limit will allow the controller to heat the pool until the temperature limit +½°C is achieved. Heating will then remain o until the sample wait period expires, if no sample wait period is active the heating will remain o until the pool temperature drops ½°C below the temperature limit setting. Due to rounding the actual heat may vary by up to ±½°C.
The ability to solar heat the pool will depend on weather conditions.
The factory default for SOL. LIMIT is 30°C
Loading...
+ 5 hidden pages