Supero 1027R-WRF4, SuperServer 1027RWRFT+, SuperServer 1027R-WRF4+ User Manual

SUPERSERVER
1027R-WRFT+
1027R-WRF4+
SUPER
®
USER’S MANUAL
1.0
The information in this User’s Manual has been carefully reviewed and is believed to be accurate. The vendor assumes no responsibility for any inaccuracies that may be contained in this document, makes no commitment to update or to keep current the information in this manual, or to notify any person or organization of the updates. Please Note: For the most up-to-date version of this
manual, please see our web site at www.supermicro.com.
Super Micro Computer, Inc. ("Supermicro") reserves the right to make changes to the product described in this manual at any time and without notice. This product, including software and docu­mentation, is the property of Supermicro and/or its licensors, and is supplied only under a license. Any use or reproduction of this product is not allowed, except as expressly permitted by the terms of said license.
IN NO EVENT WILL SUPERMICRO BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, SPECULATIVE OR CONSEQUENTIAL DAMAGES ARISING FROM THE USE OR INABILITY TO USE THIS PRODUCT OR DOCUMENTATION, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. IN PARTICULAR, SUPERMICRO SHALL NOT HAVE LIABILITY FOR ANY HARDWARE, SOFTWARE, OR DATA STORED OR USED WITH THE PRODUCT, INCLUDING THE COSTS OF REPAIRING, REPLACING, INTEGRATING, INSTALLING OR RECOVERING SUCH HARDWARE, SOFTWARE, OR DATA.
Any disputes arising between manufacturer and customer shall be governed by the laws of Santa Clara County in the State of California, USA. The State of California, County of Santa Clara shall be the exclusive venue for the resolution of any such disputes. Super Micro's total liability for all claims will not exceed the price paid for the hardware product.
FCC Statement: This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environ­ment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the manufacturer’s instruction manual, may cause harmful interference with radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case you will be required to correct the interference at your own expense.
California Best Management Practices Regulations for Perchlorate Materials: This Perchlorate warn­ing applies only to products containing CR (Manganese Dioxide) Lithium coin cells. “Perchlorate Material-special handling may apply. See www.dtsc.ca.gov/hazardouswaste/perchlorate”
WARNING: Handling of lead solder materials used in this product may expose you to lead, a chemical known to the State of California to cause birth defects and other repro­ductive harm.
Manual Revision 1.0 Release Date: August 8, 2012
Unless you request and receive written permission from Super Micro Computer, Inc., you may not copy any part of this document.
Information in this document is subject to change without notice. Other products and companies referred to herein are trademarks or registered trademarks of their respective companies or mark holders.
Copyright © 2012 by Super Micro Computer, Inc. All rights reserved.
Printed in the United States of America
iii
Preface
Preface
About This Manual
This manual is written for professional system integrators and PC technicians.
It provides information for the installation and use of the SuperServer 1027R-
WRFT+/1027R-WRF4+. Installation and maintenance should be performed by
experienced technicians only.
Manual Organization
Chapter 1: Introduction
The rst chapter provides a checklist of the main components included with the
server system and describes the main features of the X9DRW-3TF+/X9DRW-
3LN4F+ serverboard and the SC119TQ-R700WB chassis, which comprise the
SuperServer 1027R-WRFT+/1027R-WRF4+.
Chapter 2: Server Installation
This chapter describes the steps necessary to install the SuperServer into a rack and
check out the server conguration prior to powering up the system. If your server
was ordered without processor and memory components, this chapter will refer you
to the appropriate sections of the manual for their installation.
Chapter 3: System Interface
Refer here for details on the system interface, which includes the functions and
information provided by the control panel on the chassis as well as other LEDs
located throughout the system.
Chapter 4: System Safety
You should thoroughly familiarize yourself with this chapter for a general overview
of safety precautions that should be followed when installing and servicing the
SuperServer 1027R-WRFT+/1027R-WRF4+.
SUPERSERVER 1027R-WRFT+/1027R-WRF4+ User's Manual
iv
Chapter 5: Advanced Serverboard Setup
Chapter 5 provides detailed information on the X9DRW-3TF+/X9DRW-3LN4F+
serverboard, including the locations and functions of connections, headers and
jumpers. Refer to this chapter when adding or removing processors or main memory
and when reconguring the serverboard.
Chapter 6: Advanced Chassis Setup
Refer to Chapter 6 for detailed information on the SC119TQ-R700WB server chas-
sis. You should follow the procedures given in this chapter when installing, removing
or reconguring SAS or peripheral drives and when replacing system power supply
modules and cooling fans.
Chapter 7: BIOS
The BIOS chapter includes an introduction to BIOS and provides detailed informa-
tion on running the CMOS Setup Utility.
Appendix A: BIOS Error Beep Codes
Appendix B: System Specications
v
Preface
Notes
vi
SUPERSERVER 1027R-WRFT+/1027R-WRF4+ User's Manual
Table of Contents
Chapter 1 Introduction
1-1 Overview ......................................................................................................... 1-1
1-2 Serverboard Features ..................................................................................... 1-2
Processors ...................................................................................................... 1-2
Memory ........................................................................................................... 1-2
Onboard SAS .................................................................................................. 1-2
Onboard Serial ATA ........................................................................................ 1-2
Rear I/O Ports ................................................................................................. 1-2
1-3 Server Chassis Features ................................................................................ 1-3
System Power ................................................................................................. 1-3
Hard Drives ..................................................................................................... 1-3
PCI Expansion Slots ....................................................................................... 1-3
Front Control Panel ......................................................................................... 1-3
Cooling System ............................................................................................... 1-3
1-4 Contacting Supermicro .................................................................................... 1-5
Chapter 2 Server Installation
2-1 Overview ......................................................................................................... 2-1
2-2 Unpacking the System .................................................................................... 2-1
2-3 Preparing for Setup ......................................................................................... 2-1
Choosing a Setup Location ............................................................................. 2-1
Rack Precautions ............................................................................................ 2-2
Server Precautions .......................................................................................... 2-2
Rack Mounting Considerations ....................................................................... 2-3
Ambient Operating Temperature ................................................................ 2-3
Reduced Airow ......................................................................................... 2-3
Mechanical Loading ................................................................................... 2-3
Circuit Overloading ..................................................................................... 2-3
Reliable Ground ......................................................................................... 2-3
2-4 Installing the System into a Rack ................................................................... 2-4
Identifying the Sections of the Rack Rails ...................................................... 2-4
Inner Rails ....................................................................................................... 2-5
Outer Rails ...................................................................................................... 2-6
Installing the Server into a Telco Rack ........................................................... 2-8
Chapter 3 System Interface
3-1 Overview ......................................................................................................... 3-1
3-2 Control Panel Buttons ..................................................................................... 3-1
vii
Table of Contents
UID .................................................................................................................. 3-1
Reset ............................................................................................................... 3-1
Power .............................................................................................................. 3-1
3-3 Control Panel LEDs ........................................................................................ 3-2
Information LED .............................................................................................. 3-2
NIC2 ................................................................................................................ 3-2
NIC1 ................................................................................................................ 3-2
HDD ................................................................................................................. 3-3
Power .............................................................................................................. 3-3
3-4 Drive Carrier LEDs .......................................................................................... 3-3
Chapter 4 System Safety
4-1 Electrical Safety Precautions .......................................................................... 4-1
4-2 General Safety Precautions ............................................................................ 4-2
4-3 ESD Precautions ............................................................................................. 4-3
4-4 Operating Precautions .................................................................................... 4-4
Chapter 5 Advanced Serverboard Setup
5-1 Handling the Serverboard ............................................................................... 5-1
Precautions ..................................................................................................... 5-1
Unpacking ....................................................................................................... 5-1
5-5 Processor and Heatsink Installation................................................................ 5-2
Installing an LGA 2011 Processor ................................................................... 5-2
Removing the Heatsink ................................................................................... 5-5
5-3 Connecting Cables .......................................................................................... 5-6
Connecting Data Cables ................................................................................. 5-6
Connecting Power Cables .............................................................................. 5-6
Connecting the Control Panel ......................................................................... 5-6
5-4 I/O Ports .......................................................................................................... 5-7
5-5 Installing Memory ............................................................................................ 5-8
5-6 Adding PCI Cards ......................................................................................... 5-10
5-7 Serverboard Details .......................................................................................5-11
X9DRW-3TF+/X9DRW-3LN4F+ Quick Reference ........................................ 5-12
5-8 Connector Denitions .................................................................................... 5-13
5-9 Jumper Settings ............................................................................................ 5-21
5-10 Onboard Indicators ........................................................................................ 5-24
5-11 SAS/SATA Port Connections ......................................................................... 5-26
5-12 Installing Software ......................................................................................... 5-27
SuperDoctor III .............................................................................................. 5-28
viii
SUPERSERVER 1027R-WRFT+/1027R-WRF4+ User's Manual
Chapter 6 Advanced Chassis Setup
6-1 Static-Sensitive Devices .................................................................................. 6-1
Precautions ..................................................................................................... 6-1
6-2 Control Panel .................................................................................................. 6-2
6-3 System Fans ................................................................................................... 6-2
System Fan Failure ......................................................................................... 6-3
Air Shroud ....................................................................................................... 6-4
Hard Drive Installation ..................................................................................... 6-6
Hard Drive Backplane ..................................................................................... 6-8
DVD-ROM Drive Installation ........................................................................... 6-8
6-4 Power Supply .................................................................................................. 6-9
Power Supply Failure ...................................................................................... 6-9
Chapter 7 BIOS
7-1 Introduction ...................................................................................................... 7-1
Starting BIOS Setup Utility .............................................................................. 7-1
How To Change the Conguration Data ......................................................... 7-2
Starting the Setup Utility ................................................................................. 7-2
7-2 Main Setup ...................................................................................................... 7-2
7-3 Advanced Setup Congurations...................................................................... 7-4
7-4 Event Logs .................................................................................................... 7-25
7-5 IPMI ............................................................................................................... 7-27
7-6 Boot ............................................................................................................... 7-29
7-7 Security ......................................................................................................... 7-30
7-8 Save & Exit ................................................................................................... 7-31
Appendix A BIOS Error Beep Codes
Appendix B System Specications
Chapter 1
Introduction
1-1 Overview
The SuperServer 1027R-WRFT+/1027R-WRF4+ is a high-end server comprised of
two main subsystems: the SC119TQ-R700WB 1U server chassis and the X9DRW-
3TF+/X9DRW-3LN4F+ dual processor serverboard. Please refer to our web site for
information on operating systems that have been certied for use with the system
(www.supermicro.com).
In addition to the serverboard and chassis, various hardware components have been
included with the 1027R-WRFT+/1027R-WRF4+, as listed below:
•Six sets of 4-cm counter-rotating fans (FAN-0101L4)
•One air shroud (MCP-310-19003-0N)
•Two passive CPU heatsinks (SNK-P0047PS)
•Riser Cards
One RSC-R1UW-2E16
One RSC-R1UW-E8R
•SAS Accessories
One SAS backplane (BPN-SAS-113TQ)
Eight drive carriers (MCP-220-00047-0B)
•One CD containing drivers and utilities
•SuperServer 1027R-WRFT+/1027R-WRF4+ User's Manual
Chapter 1: Introduction
1-1
1-2
SUPERSERVER 1027R-WRFT+/1027R-WRF4+ User's Manual
1-2 Serverboard Features
At the heart of the SuperServer 1027R-WRFT+/1027R-WRF4+ lies the X9DRW-
3TF+/X9DRW-3LN4F+, a dual processor serverboard based on the Intel® C606
chipset. Below are the main features of the serverboard. (See Figure 1-1 for a
block diagram of the chipset).
Processors
The X9DRW-3TF+/X9DRW-3LN4F+ supports single or dual Intel® E5-2600 Series
(Socket R) processors in LGA 2011 sockets. Please refer to our web site for a
complete listing of supported processors (www.supermicro.com).
Memory
The X9DRW-3TF+/X9DRW-3LN4F+ features 24 DIMM slots that can support up
to 768 GB of registered/unbuffered ECC DDR3-1600/1333/1066/800 SDRAM or
LRDIMM type memory. Please refer to Chapter 5 for installing memory.
Onboard SAS
A SAS controller is integrated into the chipset to support eight SAS 2.0 ports. The
hot-swap SAS drives are connected to a backplane that provides power, bus ter-
mination and conguration settings.
Note: RAID 0, 1, 5, 6, 10, 50 and 60 is supported. Refer to the following ftp site
for setup guidelines:
<ftp://ftp.supermicro.com/driver/SAS/LSI/LSI_SAS_EmbMRAID_SWUG.pdf>.
Onboard Serial ATA
An on-chip SATA controller is integrated into the X9DRW-3TF+/X9DRW-3LN4F+ to
provide a six-port, SATA subsystem (two SATA 3.0 ports and four SATA 2.0 ports),
which is RAID 0, 1, 5 and 10 supported (RAID 5 is supported with Windows OS
only). The SATA drives are hot-swappable units.
Note: You must have RAID set up to enable the hot-swap capability of the SATA
drives. Documentation on RAID setup guidelines can be found on our web site.
Rear I/O Ports
The color-coded I/O ports include one COM port, a VGA (monitor) port, two USB
2.0 ports, PS/2 mouse and keyboard ports and one dedicated IPMI LAN port. In
addition, the X9DRW-3TF+ has two 1 Gb LAN (Ethernet) ports and two 10 Gb LAN
ports and the X9DRW-3LN4F+ has four 1 Gb LAN ports.
1-3
Chapter 1: Introduction
1-3 Server Chassis Features
The 1027R-WRFT+/1027R-WRF4+ is built upon the SC119TQ-R700WB chassis.
Details on the chassis and on servicing procedures can be found in Chapter 6.The
following is a general outline of the main features of the chassis.
System Power
The SC119TQ-R700WB features a redundant 700W power supply consisting of
two power modules. The system does not need to be shut down when replacing or
removing a single power supply module.
Hard Drives
The chassis was designed to support eight hot-swap SAS or SATA hard drives.
PCI Expansion Slots
Two riser cards are included. The RSC-R1UW-E8R is located on the right side of the
chassis and supports one low-prole (max. length = 4.1") PCI-E x8 card. The RSC-
R1UW-2E16 is located on the left side of the chassis and supports two full-height,
half-length PCI-E x16 add-on cards. See section 5-6 of this manual for details.
Front Control Panel
The chassis' control panel provides you with system monitoring and control. LEDs
indicate system power, HDD activity, network activity (2), system information and
UID (Unit Identication). A main power button and a UID button is also included.
Cooling System
The system has an innovative cooling design that features six sets of 4-cm counter-
rotating fans located in the middle section of the chassis. Fan speed may be varied
by IPMI to respond to uctuations in system temperature. The power supply module
also includes a cooling fan.
1-4
SUPERSERVER 1027R-WRFT+/1027R-WRF4+ User's Manual
Figure 1-1. Intel C606 Chipset:
System Block Diagram
Note: This is a general block diagram. Please see Chapter 5 for details.
1-5
Chapter 1: Introduction
1-4 Contacting Supermicro
Headquarters
Address: Super Micro Computer, Inc.
980 Rock Ave.
San Jose, CA 95131 U.S.A.
Tel: +1 (408) 503-8000
Fax: +1 (408) 503-8008
Email: marketing@supermicro.com (General Information)
support@supermicro.com (Technical Support)
Web Site: www.supermicro.com
Europe
Address: Super Micro Computer B.V.
Het Sterrenbeeld 28, 5215 ML
's-Hertogenbosch, The Netherlands
Tel: +31 (0) 73-6400390
Fax: +31 (0) 73-6416525
Email: sales@supermicro.nl (General Information)
support@supermicro.nl (Technical Support)
rma@supermicro.nl (Customer Support)
Asia-Pacic
Address: Super Micro Computer, Inc.
4F, No. 232-1, Liancheng Rd.
Chung-Ho Dist., New Taipei City 235
Taiwan
Tel: +886-(2) 8226-3990
Fax: +886-(2) 8226-3991
Web Site: www.supermicro.com.tw
Technical Support:
Email: support@supermicro.com.tw
Tel: 886-2-8228-1366, ext.132 or 139
1-6
SUPERSERVER 1027R-WRFT+/1027R-WRF4+ User's Manual
Notes
Chapter 2: Server Installation
2-1
Chapter 2
Server Installation
2-1 Overview
This chapter provides a quick setup checklist to get your 1027R-WRFT+/1027R-
WRF4+ up and running. Following these steps in the order given should enable
you to have the system operational within a minimum amount of time. This quick
setup assumes that your system has come to you with the processors and memory
pre-installed. If your system is not already fully integrated with a serverboard, pro-
cessors, system memory etc., please turn to the chapter or section noted in each
step for details on installing specic components.
2-2 Unpacking the System
You should inspect the box the 1027R-WRFT+/1027R-WRF4+ was shipped in and
note if it was damaged in any way. If the server itself shows damage you should
le a damage claim with the carrier who delivered it.
Decide on a suitable location for the rack unit that will hold the server. It should be
situated in a clean, dust-free area that is well ventilated. Avoid areas where heat,
electrical noise and electromagnetic elds are generated. You will also need it placed
near a grounded power outlet. Be sure to read the Rack and Server Precautions
in the next section.
2-3 Preparing for Setup
The box the server was shipped in should include two sets of rail assemblies, two
rail mounting brackets and the mounting screws you will need to install the system
into the rack. Follow the steps in the order given to complete the installation process
in a minimum amount of time. Please read this section in its entirety before you
begin the installation procedure outlined in the sections that follow.
Choosing a Setup Location
•Leave enough clearance in front of the rack to enable you to open the front door
completely (~25 inches) and approximately 30 inches of clearance in the back
of the rack to allow for sufcient airow and ease in servicing.This product is for
2-2
SUPERSERVER 1027R-WRFT+/1027R-WRF4+ User's Manual
!
!
Warnings and Precautions!
installation only in a Restricted Access Location (dedicated equipment rooms,
service closets and the like).
•This product is not suitable for use with visual display work place devices
acccording to §2 of the the German Ordinance for Work with Visual Display
Units.
Rack Precautions
•Ensure that the leveling jacks on the bottom of the rack are fully extended to
the oor with the full weight of the rack resting on them.
•In single rack installation, stabilizers should be attached to the rack. In multiple
rack installations, the racks should be coupled together.
•Always make sure the rack is stable before extending a component from the
rack.
•You should extend only one component at a time - extending two or more si-
multaneously may cause the rack to become unstable.
Server Precautions
•Review the electrical and general safety precautions in Chapter 4.
•Determine the placement of each component in the rack before you install the
rails.
•Install the heaviest server components on the bottom of the rack rst, and then
work up.
•Use a regulating uninterruptible power supply (UPS) to protect the server from
power surges, voltage spikes and to keep your system operating in case of a
power failure.
•Allow the hot plug SAS drives and power supply modules to cool before touch-
ing them.
•Always keep the rack's front door and all panels and components on the servers
closed when not servicing to maintain proper cooling.
Chapter 2: Server Installation
2-3
Rack Mounting Considerations
Ambient Operating Temperature
If installed in a closed or multi-unit rack assembly, the ambient operating tempera-
ture of the rack environment may be greater than the ambient temperature of the
room. Therefore, consideration should be given to installing the equipment in an
environment compatible with the manufacturer’s maximum rated ambient tempera-
ture (Tmra).
Reduced Airow
Equipment should be mounted into a rack so that the amount of airow required
for safe operation is not compromised.
Mechanical Loading
Equipment should be mounted into a rack so that a hazardous condition does not
arise due to uneven mechanical loading.
Circuit Overloading
Consideration should be given to the connection of the equipment to the power
supply circuitry and the effect that any possible overloading of circuits might have
on overcurrent protection and power supply wiring. Appropriate consideration of
equipment nameplate ratings should be used when addressing this concern.
Reliable Ground
A reliable ground must be maintained at all times. To ensure this, the rack itself
should be grounded. Particular attention should be given to power supply connec-
tions other than the direct connections to the branch circuit (i.e. the use of power
strips, etc.).
2-4
SUPERSERVER 1027R-WRFT+/1027R-WRF4+ User's Manual
2-4 Installing the System into a Rack
This section provides information on installing the server into a rack unit with the
rack rails provided. If the system has already been mounted into a rack, you can
skip ahead to Sections 2-5 and 2-6. There are a variety of rack units on the market,
which may mean the assembly procedure will differ slightly. You should also refer to
the installation instructions that came with the rack unit you are using.
Identifying the Sections of the Rack Rails
You should have received two rack rail assemblies in the rack mounting kit. Each
assembly consists of two sections: an inner xed chassis rail that secures directly
to the server chassis and an outer xed rack rail that secures directly to the rack
itself (see Figure 2-1).
Note: The rails will t a rack between 26" and 33.5" deep.
Figure 2-1. Identifying the Inner Rails and Inner Rail Extensions
Inner Rails
(Inner rails are pre-installed
on the chassis)
Inner Rail
Extensions
Chapter 2: Server Installation
2-5
Inner Rails
The SC119 chassis inner rails are composed of two sections: inner rails and inner
rail extensions. The inner rails are pre-attached and do not interfere with normal use
of the chassis if you decide not to use a server rack. Attach the inner rail extension
to stabilize the chassis within the rack.
Installing the Inner Rails
1. Place the inner rail extensions on the side of the chassis aligning the hooks
of the chassis with the rail extension holes. Make sure the extension faces
"outward" just like the pre-attached inner rail.
2. Slide the extension toward the front of the chassis.
3. Secure the chassis with 2 screws as illustrated.
4. Repeat steps 1-3 for the other inner rail extension.
1
1
1
2
1
3
Figure 2-2: Identifying the Sections of the Rack Rails
(right side rail shown)
2-6
SUPERSERVER 1027R-WRFT+/1027R-WRF4+ User's Manual
Outer Rails
Installing the Outer Rails to the Rack
1. Attach the shorter outer rail to the outside of the longer outer rail. You must
align the pins with the slides. Both bracket ends must face the same direction.
2. Adjust the outer rails so that they t snugly within the rack.
3. Secure the longer outer rail to the front of the rackl with two screws
4. Secire the shorter outer rail to the rear rack with three screws.
5. Repeat steps 1-4 for the remaining outer rail.
Locking Tabs
Both chassis rails have a locking tab, which serves two functions. The rst is to
lock the server into place when installed and pushed fully into the rack, which is
its normal position. Secondly, these tabs also lock the server in place when fully
extended from the rack. This prevents the server from coming completely out of
the rack when you pull it out for servicing.
Secure to the
Front of the
Rack
Secure to the
Rear of the Rack
Figure 2-3. Assembling the Outer Rails
Attach Outer Rails
Together
Chapter 2: Server Installation
2-7
Installing the Server into the Rack
Installing the Chassis into a Rack (Figure 2-4)
1. Conrm that the chassis includes the inner rails and rail extensions, and
conrm that the outer rails are installed on the rack.
2. Align the inner rails on the chassis with the front of the outer rails on the rack.
3. Slide the inner rails into the outer rails, keeping the pressure even on both
sides (it may be necessary to depress the locking tabs when inserting). When
the server has been pushed completely into the rack, you should hear the
locking tabs click into the locked position.
4. (Optional) Insert and tighten the thumbscrews that hold the front of the chas-
sis to the rack.
Figure 2-4. Installing the Server into a Rack
2-8
SUPERSERVER 1027R-WRFT+/1027R-WRF4+ User's Manual
Installing the Server into a Telco Rack
To install the chassis into a Telco type rack, use two L-shaped brackets on either
side of the chassis (four total). First, determine how far the server will extend out the
front of the rack. Larger chassis should be positioned to balance the weight between
front and back. If a bezel is included on your server, remove it. Then attach the two
front brackets to each side of the chassis, then the two rear brackets positioned with
just enough space to accommodate the width of the telco rack. Finish by sliding the
chassis into the rack and tightening the brackets to the rack.
Figure 2-5: Installing the Server into a Telco Rack
Chapter 3: System Interface
3-1
Chapter 3
System Interface
3-1 Overview
There are several LEDs on the control panel as well as others on the hard drive
carriers to keep you constantly informed of the overall status of the system as well
as the activity and health of specic components. There are also three buttons on
the chassis control panel and an on/off switch on the power supply. This chapter
explains the meanings of all LED indicators and the appropriate response you may
need to take.
3-2 Control Panel Buttons
There are three push-buttons located on the front of the chassis: UID button, a reset
button and a power on/off button.
UID
Depressing the UID (unit identier) button illuminates an LED on both the front and
rear of the chassis for easy system location in large stack congurations. The LED
will remain on until the button is pushed a second time. Another UID button on the
rear of the chassis serves the same function.
Reset
The reset button is used to reboot the system.
Power
The main power switch is used to apply or remove power from the power supply
to the server system. Turning off system power with this button removes the main
power but keeps standby power supplied to the system.
3-2
SUPERSERVER 1027R-WRFT+/1027R-WRF4+ User's Manual
Universal Information LED States
State Indication
Fast Blinking Red (1x/sec) Fan Fail
Solid Red CPU Overheat
Slow Blinking Red (1x/4 sec) Power Fail
Solid Blue Local UID Button Depressed
Blinking Blue IPMI-Activated UID
2
1
3-3 Control Panel LEDs
The control panel located on the front of the SC119TQ chassis has ve LEDs. These
LEDs provide you with critical information related to different parts of the system.
This section explains what each LED indicates when illuminated and any corrective
action you may need to take.
Information LED
This LED will be blue when the UID function has been activated. When this LED
ashes red, it indicates a fan failure. When red continuously it indicates an overheat
condition, which may be caused by cables obstructing the airow in the system or
the ambient room temperature being too warm. Check the routing of the cables
and make sure all fans are present and operating normally. You should also check
to make sure that the chassis covers are installed. Finally, verify that the heatsinks
are installed properly (see Chapter 5). This LED will remain ashing or on as long
as the indicated condition exists.
NIC2
Indicates network activity on GLAN2 when ashing .
NIC1
Indicates network activity on GLAN1 when ashing.
Chapter 3: System Interface
3-3
HDD
Indicates IDE channel activity. On the 6016T-6RFT+/6016T-6F+ this light indicates
HDD and/or DVD-ROM drive activity when ashing.
Power
Indicates power is being supplied to the system's power supply units. This LED
should normally be illuminated when the system is operating.
3-4 Drive Carrier LEDs
 Green: Each hard drive carrier has a green LED. When illuminated, this
green LED indicates drive activity. A connection to the SAS backplane enables
this LED to blink on and off when that particular drive is being accessed. Please
refer to Chapter 6 for instructions on replacing failed hard drives.
 Red: The red LED to indicate a hard drive failure. If one of the drives fail, you
should be notied by your system management software. Please refer to Chapter
6 for instructions on replacing failed hard drives.
3-4
SUPERSERVER 1027R-WRFT+/1027R-WRF4+ User's Manual
Notes
Chapter 4: System Safety
4-1
Chapter 4
System Safety
4-1 Electrical Safety Precautions
!
Basic electrical safety precautions should be followed to protect yourself from harm
and the SuperServer 1027R-WRFT+/1027R-WRF4+ from damage:
•Be aware of the locations of the power on/off switch on the chassis as well
as the room's emergency power-off switch, disconnection switch or electrical
outlet. If an electrical accident occurs, you can then quickly remove power from
the system.
•Do not work alone when working with high voltage components.
•Power should always be disconnected from the system when removing or in-
stalling main system components, such as the serverboard, memory modules
and oppy drive. When disconnecting power, you should rst power down the
system with the operating system rst and then unplug the power cords of all
the power supply units in the system.
•When working around exposed electrical circuits, another person who is familiar
with the power-off controls should be nearby to switch off the power if neces-
sary.
•Use only one hand when working with powered-on electrical equipment. This
is to avoid making a complete circuit, which will cause electrical shock. Use
extreme caution when using metal tools, which can easily damage any electrical
components or circuit boards they come into contact with.
•Do not use mats designed to decrease static electrical discharge as protection
from electrical shock. Instead, use rubber mats that have been specically
designed as electrical insulators.
•The power supply power cords must include a grounding plug and must be
plugged into grounded electrical outlets. The unit has more than one power
4-2
SUPERSERVER 1027R-WRFT+/1027R-WRF4+ User's Manual
4-2 General Safety Precautions
Follow these rules to ensure general safety:
•Keep the area around the system clean and free of clutter.
•The 1027R-WRFT+/1027R-WRF4+ weighs approximately 46 lbs. (20.9 kg.).
When lifting the system, two people at either end should lift slowly with their
feet spread out to distribute the weight. Always keep your back straight and lift
with your legs.
•Place the chassis top cover and any system components that have been re-
moved away from the system or on a table so that they won't accidentally be
stepped on.
•While working on the system, do not wear loose clothing such as neckties and
unbuttoned shirt sleeves, which can come into contact with electrical circuits or
be pulled into a cooling fan.
!
supply cord. Disconnect both power supply cords before servicing to avoid
electrical shock
•Serverboard Battery: CAUTION - There is a danger of explosion if the onboard
battery is installed upside down, which will reverse its polarites (see Figure 4-1).
This battery must be replaced only with the same or an equivalent type recom-
mended by the manufacturer (CR2032). Dispose of used batteries according to
the manufacturer's instructions.
•DVD-ROM Laser: CAUTION - this server may have come equipped with a
DVD-ROM drive. To prevent direct exposure to the laser beam and hazardous
radiation exposure, do not open the enclosure or use the unit in any uncon-
ventional way.
•Mainboard replaceable soldered-in fuses: Self-resetting PTC (Positive Tempera-
ture Coefcient) fuses on the mainboard must be replaced by trained service
technicians only. The new fuse must be the same or equivalent as the one
replaced. Contact technical support for details and support.
Chapter 4: System Safety
4-3
4-3 ESD Precautions
Electrostatic Discharge (ESD) is generated by two objects with different electrical
charges coming into contact with each other. An electrical discharge is created to
neutralize this difference, which can damage electronic com ponents and printed
circuit boards. The following measures are generally sufcient to neutralize this
difference before contact is made to protect your equipment from ESD:
•Use a grounded wrist strap designed to prevent static discharge.
•Keep all components and printed circuit boards (PCBs) in their antistatic bags
until ready for use.
•Touch a grounded metal object before removing the board from the antistatic
bag.
•Do not let components or PCBs come into contact with your clothing, which may
retain a charge even if you are wearing a wrist strap.
•Handle a board by its edges only; do not touch its components, peripheral chips,
memory modules or contacts.
•When handling chips or modules, avoid touching their pins.
•Put the serverboard and peripherals back into their antistatic bags when not
in use.
•For grounding purposes, make sure your computer chassis provides excellent
conductivity between the power supply, the case, the mounting fasteners and
the serverboard.
!
•Remove any jewelry or metal objects from your body, which are excellent metal
conductors that can create short circuits and harm you if they come into contact
with printed circuit boards or areas where power is present.
•After accessing the inside of the system, close the system back up and secure
it to the rack unit after ensuring that all connections have been made.
4-4
SUPERSERVER 1027R-WRFT+/1027R-WRF4+ User's Manual
4-4 Operating Precautions
Care must be taken to assure that the chassis cover is in place when the 1027R-
WRFT+/1027R-WRF4+ is operating to assure proper cooling. Out of warranty dam-
age to the system can occur if this practice is not strictly followed.
!
Figure 4-1. Installing the Onboard Battery
LITHIUM BATTERY
BATTERY HOLDER
BATTERY HOLDER
LITHIUM BATTERY
OR
!
Please handle used batteries carefully. Do not damage the battery in any way; a
damaged battery may release hazardous materials into the environment. Do not
discard a used battery in the garbage or a public landll. Please comply with the
regulations set up by your local hazardous waste management agency to dispose
of your used battery properly.