Superior Fireplaces VFGL-18MSP-4, VFGL-18VSN-4, VFGL-24VSN-4, VFGL-24MSN-4, VFGL-24VSP-4 Installation And Operating Instructions Manual

...
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
US
INSTALLATION AND OPERATING INSTRUCTIONS
STANDARD SERIES
Unvented Gas Log Room Heaters P/N 903623 REV. M 12/2007
MODELS
VFGL-18VSN-4 Series VFGL-18MSN-4 Series* VFGL-18VSP-4 Series VFGL-18MSP-4 Series* VFGL-24VSN-4 Series VFGL-24MSN-4 Series* VFGL-24VSP-4 Series VFGL-24MSP-4 Series* VFGL-28VSN-4 Series VFGL-28MSN-4 Series* VFGL-28VSP-4 Series VFGL-28MSP-4 Series*
WARNING: IMPROPER INSTALLATION, ADJUSTMENT, AL­TERATION, SERVICE OR MAINTENANCE CAN CAUSE IN­JURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL. FOR ASSISTANCE OR ADDITIONAL INFORMATION CON­SULT A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
FOR USE ONLY WITH DECORATIVE TYPE UNVENTED ROOM HEATERS.
WARNING: IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLO­SION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY: What to do if you smell gas:
• DO NOT light any appliance.
• DO NOT touch any electrical switches.
• DO NOT use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone.
Follow your gas suppliers instructions.
• If your gas supplier cannot be reached, call the fire department.
Installation and service must be performed by a quali­fied installer, service agency or the gas supplier.
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
WARNING: DO NOT BUILD A WOOD FIRE. DO NOT BURN WOOD OR OTHER MATERIAL IN THESE APPLIANCES.
CAREFULLY REVIEW THE INSTRUCTIONS SUPPLIED WITH THE DECORATIVE TYPE UNVENTED ROOM HEATER FOR THE MINIMUM FIREPLACE SIZE REQUIREMENT.
DO NOT INSTALL THE APPLIANCE IN THIS FIREBOX, UN­LESS THIS FIREBOX MEETS THE MINIMUM DIMENSIONS REQUIRED FOR THE INSTALLATIONS.
This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventila­tion air must be provided. Refer to Combustion and Ventilation Air Section, Page 3.
Due to high temperatures, the appliance should be located out of traffic and away from furniture or draperies.
Do not place clothing or other materials on or near this appliance.
IMPORTANT: READ AND UNDERSTAND THESE INSTRUCTIONS COMPLETELY BEFORE INSTALLING YOUR UNVENTED ROOM HEATER.
*Note: Manual control models are also design certified for use as vented
gas log sets.
1
TABLE OF CONTENTS
General Information......................... page 2
Inventory ......................................... page 2
Tools Required ................................ page 2
Important Safety Information .......... page 2
Codes .............................................. page 3
Combustion and Ventilation Air ....... page 3
Preinstallation.................................. page 4
Clearances ....................................... page 4
Installation....................................... page 6
Gas Pressure Check......................... page 7
Flame Appearance ........................... page 8
Operation......................................... page 8
Cleaning and Servicing .................... page 8
Replacement Parts .......................... page 8
Optional Equipment/Accessories ..... page 9
Heater Specification Chart ............... page 10
Heater Technical Detail Chart ........... page 10
Troubleshooting Guide .................... page 11
Operating Instructions – Manual ..... page 12
Operating Instructions – Millivolt .... page 14
Replacement Parts List.................... page 16
WARNING: THIS APPLIANCE IS FOR IN­STALLATION ONLY IN A SOLID FUEL BURNING FIREPLACE WITH A WORKING FLUE OR AN APPROVED VENTLESS FIRE­BOX ENCLOSURE.
Minimum Fireplace (Firebox) Size
Log Set Height Depth Width
18" Models 16" 14" 20" Front
19" Rear
24" Models 16" 14" 35" Front
27" Rear
28" Models 16" 14" 38" Front
30" Rear
Table 1
Do not install these Unvented Gas Log Room Heaters in a bedroom or a bathroom as all units exceed maximum allowable BTU/hr in­put of 10,000.
Check the inventory list to be sure that you have all the necessary parts in usable condition. Also check for concealed damage.
Inventory
WARNING: FAILURE TO COMPLY WITH THE INSTALLATION AND OPERATING IN­STRUCTIONS PROVIDED IN THIS DOCU­MENT WILL RESULT IN AN IMPROPERLY INSTALLED AND OPERATING APPLI­ANCE, VOIDING ITS WARRANTY. ANY CHANGE TO THIS APPLIANCE AND/OR ITS OPERATING CONTROLS IS DANGER­OUS. IMPROPER INSTALLATION OR USE OF THIS APPLIANCE CAN CAUSE SERI­OUS INJURY OR DEATH FROM FIRE, BURNS, EXPLOSION OF CARBON MON­OXIDE POISONING.
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning are similar to the flu with headaches, dizziness and/or nau­sea. If you have these signs, obtain fresh air immediately. Turn off the gas supply to the appliance and have it serviced by a qualified professional, as it may not be operating correctly.
Due to high temperatures, the heater should
be located out of traffic and away from furniture and draperies.
Children and adults should be alerted to the hazard of high surface temperature and should stay away to avoid burns or clothing ignition.
GENERAL INFORMATION
These Unvented Gas Log Room Heaters incor­porate unitized ceramic fiber logs which glow realistically when the heater is operating.
The log sets covered in this document are manually controlled heater rated units. These units are equipped with either a standard manual gas valve or a millivolt gas valve. The control knob is set to the desired position, which main­tains a continuous gas burning rate.
A spark ignition system (piezo) allows the gas pilot to be lit without the use of matches or batteries and permits operation of the heater during a power outage.
These heaters are fitted with a specially de­signed pilot utilizing an oxygen depletion sen­sor (ODS) which responds to the amount of oxygen available in the room and shuts the heater off before the oxygen level drops below 18%. The pilot can be relit only when fresh air is available. Refer to the Combustion and Ven­tilation Air section.
Unvented gas log room heater Two (2) screws Bag of decorative volcanic rock Ceramic fiber log set Installation and Operating Instructions
Tools and Supplies Normally Required
External regulator (Propane models only) Manual shut-off valve Sediment trap Piping complying with local codes Pipe compound Pipe wrench Tee joint Screwdriver
IMPORTANT SAFETY INFORMATION
INSTALLER: PLEASE LEAVE THESE INSTRUC­TIONS WITH THE OWNER.
OWNER: PLEASE RETAIN THESE INSTRUC­TION FOR FUTURE REFERENCE
IMPORTANT: READ THESE INSTALLATION IN­STRUCTIONS CAREFULLY BEFORE INSTALL­ING OR TRYING TO OPERATE THIS HEATER.
Young children should be carefully super-
vised when they are in the same room with the heater.
Do not place clothing or other flammable material on or near the heater.
Any safety screen or guard removed for servicing the heater must be replaced prior to operating the heater.
Installation and repair should be done by a qualified service person. The heater should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc.
It is important that control compartments, burn­ers and circulating air passageways of the heater be kept clean.
Allow the heater to cool before servicing.
Always shut off the gas to the heater while performing service work.
Do not install the heater in a bedroom or bathroom.
2
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
The installation must conform with local codes or, in the absence of local codes with the National Fuel Gas Code, ANSI Z223.1.
The heater and its individual shut-off valve must be disconnected from the gas supply piping system while performing any tests of the gas supply piping system at pressures in ex-
1/2 psig.
cess of
The heater must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure test­ing of the gas supply piping system at test pressures equal to or less than
1/2 psig.
Keep heater area clear and free from com­bustible materials, gasoline and other flam­mable vapors and liquids.
Do not use this heater if any part has been under water. Immediately call a qualified ser­vice technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water.
Input ratings are shown in BTU per hour and are for elevations up to 4,800 feet. Do not install this heater at an elevation above 4,800 feet if the gas supply has not been derated for that eleva­tion. Consult your local gas supplier. (For op­eration at elevations above 4,800 feet, equip­ment ratings shall be reduced at the rate of 4 percent for each 1,000 feet above sea level before selecting appropriately sized equipment.)
Ensure that the heater is clean when operat­ing. Excessive dust accumulation on the burner and/or logs will increase the amount of carbon monoxide formation and could lead to carbon monoxide poisoning and/or death.
CODES
Adhere to all local codes or in their absence the latest edition of The National Fuel Gas Code ANSI Z223.1 or NFPA54 which can be obtained from The American National Standards Insti­tute, Inc. (1430 Broadway, New York, NY,
10018) or National Fire Protection Association, Inc. (Batterymarch Park, Quincy, MA, 02269).
Massachusetts And New York Require­ments
These appliances are approved for installation in the following USA locations listed in the following:
Massachusetts:
These fireplaces are approved for installation in the US state of Massachusetts if the follow­ing additional requirements are met-
• Installation and repair must be done by a plumber or gas fitter licensed in the Common­wealth of Massachusetts.
• The flexible gas line connector used shall not exceed 36 inches (92 centimeters) in length.
• The individual manual shut-off must be a T­handle type valve.
• Vent-Free appliances may NOT be installed in bedrooms or bathrooms.
• A working smoke detector must be installed in the area where vent-free appliances are installed.
Seller of unvented propane or natural gas­fired supplemental room heaters shall pro­vide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
New York:
These fireplaces are approved for installation in the US state of New York, but not in New York city.
State or local codes may only allow operation of this appliance (manual version only) in a vented configuration. Check your state or local codes.
Superior Unvented Gas Log Room Heaters are certified by OMNI to ANSI Z21.11.2 standard. These gas log room heaters may be used as a space heat source for a room in conjunction with an approved unvented firebox. Additionally, manually controlled units are design certified by OMNI to ANSI 21.60 as a vented gas log set.
As such, manually controlled units may be used as a vented gas log set in any wood-burning fireplace that has been properly constructed to code, and in the case of factory built fireplaces, installed in compliance with manufacturers list­ing and installation instruction.
Use of the manually controlled log sets covered by this manual in a properly vented wood­burning fireplace which has had the damper blocked open as detailed in these installation instructions preclude consideration of the com­bustion and ventilation air and clearance to combustible restrictions discussed herein.
COMBUSTION AND VENTILATION AIR
These heaters shall not be installed in a con­fined space. The heater may be located in unusually tight construction provided the space is unconfined, or if confined, is pro­vided with two permanent openings commu­nicating directly with an additional room(s) of sufficient volume so that the combined volume of all connected spaces meets the criteria for an unconfined space, (National Fuel Gas Code ANSI Z223.1 (latest edition), Section 5.3). Generally 50 ft3 per 1,000 BTU input of all operating appliances in the space.
The National Fuel Gas Code defines a con­fined space as a space whose volume is less than 50 ft3 per 1,000 BTU/Hr (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 ft3 per 1,000 BTU/Hr (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicat­ing directly with the space in which the appli­ances are installed, through openings not furnished with doors, are considered a part of the unconfined space.
Unusually tight construction is defined as construction where:
a. wall and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating or one perm or less with openings gasketed or sealed, and
b. weather stripping has been added on oper­able windows and doors, and
c. caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall­ceiling joints, between wall panels, at penetra­tions for plumbing, electrical, and gas lines, and at other openings.
Use the following equations to determine if you have a confined or unconfined space.
1.Determine the volume of space — ft
Length x Width x Height = _____ ft (Include adjoining rooms with doorless pas­sageways or ventilation grills between rooms.)
Example: 24' (L) x 16' (W) x 8' (H) = 3072 ft
3
.
3
3
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
3
3
3
)/ 50 ft3 =
to
2.Divide the volume of space by 50 ft determine the maximum BTU/Hr the space can support.
______ (volume of space – ft (Maximum BTU/Hr the space can support)
Example: 3072 ft or 61,440 BTU/Hr the space can support.
3.Add the BTU/Hr of all the fuel burning appli­ances in the space.
Vent-Free heater _______ BTU/Hr Gas appliance #1* _______ BTU/Hr Gas appliance #2 + _______ BTU/Hr
Example:
Vent-free heater 32,000 BTU/Hr Gas appliance #1 35,000 BTU/Hr (water heater)
* Do not include direct-vent gas appliances. Direct-vent is sealed combustion and draws combustion air from the outdoors.
4. Compare the maximum BTU/Hr the space can support with the actual amount of BTU/ Hr used.
_________ BTU/Hr _________ BTU/Hr
Example:
61,440 BTU/Hr 67,000 BTU/Hr
The space in the previous example is a confined space because the actual BTU/Hr used is more than the maximum BTU/Hr the space can sup­port. You must provide additional fresh air.
Your options are: a.Rework equations adding the space of ad-
joining room(s). If the extra volume provides an unconfined space, then remove door or add ventilation grills between rooms. Refer to National Fuel Gas Code, ANSI Z223.1, Section 5.3.
3
/ 50 ft3 = 61.44
Total = _______ BTU/Hr
Total = 67,000 BTU/Hr
(max. the space can support) (actual amount of BTU/Hr used)
(max. the space can support) (actual amount of BTU/Hr used)
b.Vent room directly to the outdoors. Refer to
National Fuel Gas Code, ANSI Z223.1, Sec­tion 5.3.
c. Install a lower BTU/Hr heater, such as a
24,000 BTU/Hr, to make the area an uncon­fined space.
If the actual BTU/Hr used is less than the maximum BTU/Hr the space can support, then the space is an unconfined space. You will need no additional fresh air ventilation for an uncon­fined space.
WARNING: IF THE AREA IN WHICH THE HEATER MAY BE OPERATED IS SMALLER THAN THAT DEFINED AS AN UNCON­FINED SPACE, PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR BY ONE OF THE METHODS DESCRIBED IN THE NATIONAL FUEL GAS CODE, ANSI Z223.1, SECTION 5.3 OR APPLICABLE LOCAL CODES.
PREINSTALLATION
WARNING: BEFORE INSTALLING IN A SOLID FUEL BURNING FIREPLACE, THE CHIMNEY FLUE AND FIREBOX MUST BE CLEANED OF SOOT, CREOSOTE, ASHES AND LOOSE PAINT BY A QUALIFIED CHIM­NEY CLEANER.
Note: Illustrations shown in this manual reflect
“typical” installations with nominal dimensions and are for reference only. Actual installations may vary due to individual design preferences. However, always maintain minimum clearances to combustible materials and do not violate any specific installation requirements. Refer to Fig­ures 1 through 7 for clearances.
Note: The following steps represent the normal sequence of installation. Each installation is unique, however, and might require a different sequence.
When local codes require the damper to be fixed open, a damper stop must be installed to prevent full closure of the fireplace damper and provide a minimum 29 square inch flue opening at all times. Refer to accessories for damper clamp.
If damper clamp is not available, the damper may be fixed open in the following manner. Drill a hole in the end of the damper. Screw in a bolt of sufficient size and adjust to provide the minimum 29 square inches of flue opening.
CAUTION: HEATERS CREATE WARM AIR CUR­RENTS. THESE CURRENTS MOVE HEAT TO WALL SURFACES NEXT TO HEATER. INSTALL­ING HEATER NEXT TO VINYL OR CLOTH WALL COVERINGS OR OPERATING HEATER WHERE IMPURITIES IN THE AIR (SUCH AS TOBACCO SMOKE) EXISTS, MAY DISCOLOR WALLS.
Turn off gas supply to the fireplace or firebox.
Position heater in fireplace or firebox.
Connect gas line.
Secure heater.
Assemble logs and test flame.
Sprinkle volcanic rock over base plate in front
of and below the main burner.
Check Gas Type
This heater can only be connected to the gas type specified on the heater rating plate. This
heater can not be modified in the field for a different gas type. If the gas supply differs, DO NOT INSTALL the heater. Contact your dealer to
obtain the correct heater.
CLEARANCES
WARNING: DO NOT INSTALL THIS GAS HEATER:
• IN SLEEPING QUARTERS, BATH­ROOMS, A MOBILE HOME, OR A REC­REATIONAL VEHICLE.
• WHERE CURTAINS, FURNITURE, CLOTHING OR OTHER FLAMMABLE OB­JECTS ARE LESS THAN 42" FROM THE FRONT OF THE GAS HEATER.
• IN HIGH TRAFFIC AREAS.
• IN WINDY OR DRAFTY AREAS.
Ensure the minimum clearances shown in
ures 1 through 7
clearances are determined when facing the front of the heater.
are maintained. Left and right
Fig-
4
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
Noncombustible Material Requirements with No Mantel Installed
(A) Noncombustible Material Measurement Requirements for Safe Installation
12" or more Adjustable canopy not required. 8" minimum to 12" Install adjustable canopy, P/N 053752
(
Figure 3
Less than 8" Extend noncombustible material to at least
8" and install adjustable canopy ( or Extend noncombustible material to a height
of at least 12".
).
Figure 3
8" or More of
Noncombustible
Material
Adjustable Canopy
Heater in Fireplace
).
or Firebox
Figure 3
Table 2
Noncombustible Material Heights and Mantel Location
Requirements for Safe Installation
with Wood Mantel, Shelf or
Noncombustible Material Measurement Other Combustible Projection
12" or more Adjustable canopy not required. Observe pro-
Figure 4
Figure 5
.
.
Figure 4
Figure 2
A
files shown in
8" minimum to 12" Install adjustable canopy and observe pro-
files shown in or Extend heat resistant material to at least 12"
and observe profiles shown in
Table 3
Follow these instructions carefully to ensure safe installation. Failure to follow these require­ments may create a fire hazard.
Step 3. Noncombustible materials (minimum requirements): To install the room heater with-
out wood mantels, shelves or other combus-
tible projections directly above the opening of Step 1. Sidewall Clearances: The sides of the fireplace opening must be at least 16" from any combustible side wall (
Figure 1
).
the fireplace (firebox) refer to
Table 2.
Note that at least 8" of noncombustible material must be installed above the heaters described in this manual.
Noncombustible materials, such as slate and marble, must be at least 1/2" thick.
Noncombustible
Material
16"
Min.
42"
Min.
.
and
Step 4. Wood mantel, shelf or combustible projection requirements: To install a wood
mantel, shelf or other combustible projection directly above the fireplace (firebox), refer to
Table 3
and to
Figures 4 and 5
for installation
profiles. If your mantel profile is unsafe, you may either:
Raise the mantel to an acceptable height, or
Remove the mantel.
Example: The bottom of the mantel may project
from the wall a maximum of 2-1/2" at a mini­mum of 28" above the opening. The top shelf of the mantel may project a maximum of 6" at a minimum of 34-1/2" above the opening.
Heat Resistant Material
10"
8"
6"
2-1/2"
12"
Ceiling
42"
38-5/8"
34-1/2"
28"
Figure 1
Step 2. Ceiling Clearance: The ceiling must be
at least 42" from the top of the heater opening (
Figure 1
).
Heater in Fireplace or Firebox
Figure 2
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
Figure 4
5
Example: The bottom of the mantel may project
from the wall a maximum of 2-1/2" at a mini­mum of 8" above the opening. The top shelf of the mantel may project a maximum of 6" at a minimum of 14-1/2" above the opening.
12"
10"
2-1/2"
8"
6"
8"
Min.
18-5/8"
14-1/2"
Hood (Canopy) Heat Resistant
Material
26"
22-1/2"
Figure 5
Step 5. Floor clearance: If combustible floor-
ing materials, such as carpeting or asphalt tile, are to be located within 14" of the fireplace or firebox opening, the room heater base must be at least 5" above the combustible flooring ma­terial (
Figure 6
Combustible Material
).
Combustible Material
5" Min.
Figure 6
The room heater base may be lower than 5" above the combustible flooring materials if the combustible flooring materials are more than 14" from the fireplace or firebox opening (
Figure 7
).
(Both Sides Of Opening)
14" Min.
Combustible Material
Can be less than 5"
Figure 7
INSTALLATION
WARNING: DO NOT ALLOW FANS TO BLOW DIRECTLY INTO THE FIREPLACE. AVOID ANY DRAFTS THAT ALTER BURNER FLAME PATTERNS.
WARNING: DO NOT USE A BLOWER IN­SERT, HEAT EXCHANGER INSERT OR OTHER ACCESSORY NOT APPROVED FOR USE WITH THIS HEATER.
This appliance must not be operated without a fireplace screen installed. Fireplace screens must not impair the free flow of combustion air to the appliance.
Do not burn solid fuels in any fireplace equipped with this listed unvented gas room heater.
WARNING: INSTALLED DECORATIVE GLASS DOOR ENCLOSURES MUST BE FULLY OPENED WHEN OPERATING THIS LISTED UNVENTED GAS ROOM HEATER.
Any outside air ducts and/or ash dumps that are part of the original solid fuel burning fireplace system must be fully closed and sealed at the time of installation of this listed unvented gas room heater.
WARNING: SPECIAL CARE IS REQUIRED IF YOU ARE INSTALLING THE UNIT INTO A SUNKEN FIREPLACE. YOU MUST RAISE THE FIREPLACE FLOOR TO ALLOW AC­CESS TO GAS LOG CONTROLS. THIS WILL INSURE ADEQUATE AIR FLOW AND GUARD AGAINST SOOTING. RAISE THE FIREPLACE FLOOR USING NONCOMBUS­TIBLE MATERIALS.
A qualified gas appliance installer must install this heater.
Check gas type: The gas supply must be the same as stated on the heater’s rating plate. If the gas supply is different, DO NOT INSTALL the heater. Contact your dealer for the correct model.
Step 1. Placement of Heater – Center the
heater in the fireplace or firebox. Make certain the grate front feet sit inside the front edge of the fireplace or firebox.
To avoid any movement of the heater during operation, attach the grate to the floor of the fireplace or firebox using the screws provided. Slots along the back flange of the log set are provided. After centering the grate correctly, mark the positions of the bottom of the slots on the fireplace/firebox floor. Drill two (2) 9/64" diameter holes with masonry drill approximately 1/2" deep.
Preliminarily anchor the grate to the fireplace/ firebox floor with the two (2) screws provided
Figure 8
(
). Loosen screws and proceed with
the installation.
Alternate
Location
Anchor Screw
(Both Sides)
Figure 8
Step 2. Connecting Gas Line – A qualified gas
appliance installer must connect the gas room heater to the gas supply.
Consult all local codes. Route gas line using techniques and materials
prescribed by local and/or national codes. Only use pipe of ¹⁄₂" or greater diameter to allow full gas volume to the gas fireplace. Undue pres­sure loss will occur if the pipe is too small.
An ANSI approved manual shut-off valve and union must be installed upstream of the heater within the fireplace cavity when rigid pipe is used.
Ensure that a sediment trap is installed up­stream of the heater within the structures piping system to prevent moisture and con­taminants from passing through the pipe to the heater controls and burners (
Figure 9
Failure to do so could prevent the heater from operating reliably.
IMPORTANT: HOLD HEATER REGULATOR WITH A WRENCH TO PREVENT MOVEMENT WHEN CONNECTING TO INLET PIPING
An external regulator must be used on all pro­pane (L.P.G.) heaters, in addition to the regula­tor fitted to the heater, to reduce the supply tank pressure to 13" w.c. (maximum).
).
6
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
Regulator
Fireplace or
Firebox Wall
3"
Union
Sediment
Shut-Off
Fireplace or
Firebox Wall
Trap
Manual
Valve
Wall
Shut-Off
Key
Down
Figure 9
WARNING: CONNECTING DIRECTLY TO AN UNREGULATED PROPANE TANK MAY CAUSE AN EXPLOSION.
The heater gas inlet connection is 3/8" NPT at the regulator, located on the right side facing the heater. If a left side connection is required, the connection pipe may be piped under the rear of the appliance to end at the left hand side for connection to the inlet.
Gas Pressure Check
The heater regulator controls the burner pres­sure which should be checked at the pressure test point (1/8" NPT plugged tap) located at the bottom of the regulator (on manual mod­els) or on the control valve itself (on Millivolt models), identified A for the manifold side and E for inlet pressure. Ensure operatilng pressures are within the limits specified in the techinical chart on page 10.
Manual Valve Pressure Test Point
WARNING: DO NOT PLACE ANY LAVA ROCK ON LOGS OR BURNERS. THIS MAY CAUSE SOOTING. ONLY PLACE LAVA ROCK ON FLOOR OF FIREPLACE.
Each heater includes a unitized set of ceramic fiber logs. The heater and logs are assembled as shown in great care. The logs can be easily damaged, but when handled properly they can provide years of performance and enjoyment.
Figure 11
. Handle these logs with
When tightening up the joint to the regulator hold the regulator securely with a wrench to prevent the regulator from moving.
Checking Gas Connections: Turn on gas sup­ply and test for gas leaks using a gas leak test solution (also referred to as bubble leak solu­tion). NOTE: using a soapy water solution (50% dish soap, 50% water) is an effective leak test solution, but it is not recommended, be­cause the soap residue that is left on the pipes/ fittings can result in corrosion over time.
A. Light the appliance (refer to the lighting instructions label in the control compartment or on pages 12 or 14).
B. Brush all joints and connections with the gas leak test solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob (off/pilot/on) to the “OFF” position. Either tighten or refasten the leaking connection, then retest as described above.
C. When the gas lines are tested and leak free, be sure to rinse off the leak testing solution.
D. Observe the individual tongues of flame on the burner. Make sure all ports are open and producing flame evenly across the burner. If any ports are blocked, or partially blocked, clean out the ports.
Millivolt Valve Pressure Test Point On Front Of Valve
Figure 10
The pressure should be checked with the gas heater burning and the control set to high (3).
The pressure regulator on manual models is preset and locked to avoid tampering. If the pressure is not as specified in the Technical Details Chart on page 10, replace the regulator with P/N 110351 for natural gas and P/N 110352 for propane (L.P.G.) heaters.
Replace the test point plug after pressure measurement ensuring no gas leaks.
Step 3. Secure the log set within the firebox using the screws and drilled holes discussed in Step 2.
Step 4. Assembling the Logs
WARNING: DO NOT ADD EXTRA LOGS OR ORNAMENTS SUCH AS PINE CONES, VER­MICULITE OR ROCK WOOL. USING THESE ADDED ITEMS CAN CAUSE SOOTING.
Millivolt Log Set Shown, Manual Similar
Figure 11
WARNING: FAILURE TO POSITION THE PARTS IN ACCORDANCE ITH THESE DIA­GRAMS OR FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED WITH THIS HEATER MAY RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY.
Periodically verify proper positioning of all logs.
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
7
Flame Appearance
REFER TO THE OPERATING INSTRUCTIONS LOCATED AT THE BACK OF THIS MANUAL BEFORE LIGHTING THE HEATER TO OBSERVE THE FLAMES.
Flames from the pilot, front and rear burner should be visually checked as soon as the heater is installed. In addition a periodic visual check of the flames should be made. The pilot flame should always be present when the heater is in operation (
Figure 12
).
WARNING: NO ADJUSTMENTS ARE TO BE MADE TO THE ODS PILOT SYSTEM. TAMPERING WITH THIS SYSTEM CAN BE EXTREMELY HAZARDOUS.
Figure 12
An incorrect pilot flame pattern is shown in
Figure 13
thermocouple to cool. When the thermocouple cools, the log set will shut off. If pilot flame pattern is incorrect, or if log set shuts off, contact your service representative.
Figure 13
In normal operation, at full rate, after 15 min­utes the following flame appearance should be observed:
. This pilot flame will cause the
Rear Burner Characteristics– The rear flames should be yellow. The flames should extend about 3 – 4" above the front log for natural gas and 2 – 3" above for propane (L.P.G.) gas
Figure 14
(
).
Figure 14
Main Burner Characteristics – The flames at
the front burner holes will be blue becoming orange as they hit the bark-like texture of the base and front face of the log.
OPERATION AND CARE OF YOUR APPLIANCE
1. Appliance operation may be controlled
through the ON/OFF unit rocker switch, located in the control compartment, or through a re­motely located optional wall switch or wall thermostat.
2. Thermostat units are equipped with a two stage (HI, LOW) gas control valve. To cycle the burner between the HI and LOW settings, rotate the control knob clockwise and counterclock­wise respectively.
3. When lit for the first time, the appliance will emit a slight odor for an hour or two. This is due to the “burn-in” of the internal paints and lubricants used in the manufacturing process. For the first few hours, operate the appliance with doors and windows open to encourage the dissipation of odor.
CLEANING AND SERVICING
WARNING: TURN OFF THE UNVENTED GAS ROOM HEATER AND ALLOW TO COOL BEFORE CLEANING.
CAUTION: YOU MUST KEEP CONTROL AR­EAS, BURNERS AND CIRCULATING AIR PAS­SAGEWAYS OF FIREPLACE CLEAN. INSPECT THESE AREAS OF FIREPLACE BEFORE EACH USE. HAVE FIREPLACE AND CHIMNEY (IF APPLICABLE) INSPECTED YEARLY BY A QUALIFIED SERVICE PERSON. FIREPLACE MAY NEED MORE FREQUENT CLEANING DUE TO EXCESSIVE LINT FORM CARPETING, BED­DING MATERIAL, ETC.
Only limited cleaning will be required under the normal use of the heater. Dust the front grate, the top of the piezo cover and the control knob occasionally. Do not use cleaning fluids to clean the logs or any other part of the room heater.
Remove the logs, gently handling at each end. Use a vacuum cleaner to remove loose particles from the base and from around the burners. Gloves are recommended to prevent the fibers from pricking your skin. If the skin is pricked, wash gently with soap and water. Replace the logs as detailed in Step 4 Assembling the Logs.
If, after a period of use, the flames start to exhibit unusual shapes and behavior, or the burners fail to ignite smoothly, then the burner holes may require some cleaning. If this hap­pens, contact your nearest dealer to get the appliance serviced.
REPLACEMENT PARTS
An exploded view of the room heater with numbered parts and a parts list can be found on pages 16 and 17. All parts should be or­dered through your Lennox distributor or dealer. Parts will be shipped at prevailing prices at time of order.
When ordering repair parts, always give the following information:
1. The model number of the heater.
2. The serial number of the heater.
3. The part number.
4. The description of the part.
5. The quantity required.
6. The installation date of the heater.
If you encounter any problems or have any questions concerning the installation of this heater, please contact your distributor. For the name of your nearest distributor contact:
LHP 1110 West Taft Avenue Orange, CA 92865
8
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
OPTIONAL EQUIPMENT
Wall Thermostat Kit*
All options are available in kit form, are easy to install and are packaged complete with all re­quired parts and instructions. Some of the option kits need to be fitted prior to completing the installation of the appliance. The following paragraphs detail the kit options available.
The appliances covered in this manual are heater rated and produce a great deal of heat. Decorative brass trim pieces and hoods may tarnish because of their proximity to the heater opening and front face. Tarnishing of these pieces is normal, unavoidable and should be expected.
Remote Control Kits
Models RCL and RCL-STAT add the conve­nience of remote control for your appliance. The kits include a wireless, hand held trans­mitter and a receiver. This special receiver permits either manual or remote control modes. Both receiver and transmitter operate on standard 9 volt batteries (not included). Refer to the RCL and RCL-STAT installation instructions for specific details.
Damper Clamp Kit
A wall thermostat kit is available for use with these appliances. The wall thermostat is de­signed to be wired directly to the appliance millivolt gas control circuit and provide auto­matic On/Off control of the appliance to main­tain a desired temperature within the room.
Decorative Volcanic Stone
The decorative volcanic stone, Model FDVS, can be used to enhance the look of your appli­ance. Spread the decorative volcanic stone evenly around the bottom of the firebox.
Adjustable Canopy
An attractive black canopy kit is available for use with these VF appliances. The canopy kit is designed to be fitted to the wall above the firebox opening. In addition to providing an aesthetically pleasing appearance, the canopy reduces heat effects to decorative mantles and finish materials located directly above the fire­place opening. The canopy kit includes the necessary attaching hardware.
*Use 18GA, solid two conductor wire to connect these kits to the appliance.
Damper Clamp P/N 110701 DCK
Thermostat P/N 064248 WTK
A Damper Clamp Kit is available for use when required by local codes. Using the damper clamp to fix open the fireplace damper will allow this vent free product to be utilized as a vented decorative gas log set, (see details on pages 3 and 4).
Wall Switch Kit*
An optional wall switch kit can be installed along with all vent-free appliances. The kit consists of a standard UL wall switch with cover plate. This kit provides for remote (wall) operation of the appliance. Replace the wall switch and cover plate of this kit with the components of the FWSK and you can have true remote control of your vent-free appliance, turning it on and off from your favorite easy chair. The wall switch kit should be installed along with the appliance.
ACCESSORIES
Remote Control Kit (Standard) P/N H0249 RCL
Wall Switch Kit P/N 064035 FWSK
Decorative Volcanic Stone P/N 110791 FDVS
Adjustable Canopy Black P/N 053752 AC - BLK
Remote Control Kit (Deluxe) P/N H0251 RCL-STAT
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
9
UNVENTED GAS LOG ROOM HEATER SPECIFICATION CHART
Model No. Valve Operation BTU/hr Input Gas Type
VFGL - 18 MSN-4 Manual* 14,000 - 25,000 Natural VFGL - 18 MSP-4 Manual* 14,000 - 25,000 Propane/LPG VFGL - 24 MSN-4 Manual* 17,000 - 32,000 Natural VFGL - 24 MSP-4 Manual* 17,000 - 32,000 Propane/LPG VFGL - 28 MSN-4 Manual* 17,000 - 32,000 Natural VFGL - 28 MSP-4 Manual* 17,000 - 32,000 Propane/LPG
VFGL - 18 VSN-4 Millivolt 19,500 - 25,000 Natural VFGL - 18 VSP-4 Millivolt 19,500 - 25,000 Propane/LPG VFGL - 24 VSN-4 Millivolt 25,000 - 32,000 Natural VFGL - 24 VSP-4 Millivolt 25,000 - 32,000 Propane/LPG VFGL - 28 VSN-4 Millivolt 25,000 - 32,000 Natural VFGL - 28 VSP-4 Millivolt 25,000 - 32,000 Propane/LPG
* Manual control models are also design certified for use as vented gas log sets.
UNVENTED GAS LOG ROOM HEATER TECHNICAL CHART
BTU/HR Regulator Gas Inlet Valve
Model No. High Gas Type Ignition Pres. Setting Pressure** Operation
VFGL - 18N 25,000 Natural Piezo 5" w.c. Max. 10.5" w.c. Manual*/Millivolt
Min. 6" w.c.
VFGL - 18P 25,000 Propane/LPG Piezo 10" w.c. Max. 13" w.c. Manual*/Millivolt
Min. 11" w.c.
VFGL - 24N 32,000 Natural Piezo 5" w.c. Max. 10.5" w.c. Manual*/Millivolt
Min. 6" w.c.
VFGL - 24P 32,000 Propane/LPG Piezo 10" w.c. Max. 13" w.c. Manual*/Millivolt
Min. 11" w.c.
VFGL - 28N 32,000 Natural Piezo 5" w.c. Max. 10.5" w.c. Manual*/Millivolt
Min. 6" w.c.
VFGL - 28P 32,000 Propane/LPG Piezo 10" w.c. Max. 13" w.c. Manual*/Millivolt
Min. 11" w.c.
* Manual control models are also design certified for use as vented gas log sets. ** For the purpose of input adjustment.
10
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
TROUBLESHOOTING GUIDE FOR VENT-FREE GAS PRODUCTS
OBSERVED PROBLEM POSSIBLE CAUSE REMEDY
1. When igniter button is
pressed, there is no spark at ODS/pilot.
2. Heater produces unwanted odors.
3. Heater shuts off in use (ODS operates).
4. Gas odor even when control knob is in “OFF” position.
5. When igniter button is pressed, there is spark at ODS/pilot, but no ignition.
6. ODS/pilot lights, but flame goes out when control knob is released.
7. Burner does not light after ODS/pilot is lit.
8. Delayed ignition of burner.
9. Burner backfiring during
combustion.
10. Slight smoke or odor during initial operation.
11. Heater produces a whistling noise when burner is lit.
A. Igniter electrode positioned wrong. B. Igniter electrode broken. C. Igniter electrode not connected to igniter cable. D. Igniter cable pinched or wet. E. Piezo igniter nut is loose. F. Broken igniter cable. G. Bad piezo igniter. A. Heater burning vapors from paint, hair spray, glues, etc. B. Gas leak. See Warning statement on the front page. A. Not enough fresh air is available. B. Low line pressure. C. ODS/pilot is partially clogged. A. Gas leak. See Warning statement on the front page. B. Control valve defective. A. Gas supply turned off or manual shut-off valve closed. B. Control knob not in “PILOT” position. C. Control knob not pressed in while in “PILOT” position. D. Air in gas lines when installed.
E. ODS/pilot is clogged. F. Gas regulator setting is not correct. A. Control knob not fully pressed in. B. Control knob not pressed in long enough. C. Manual shut-off valve not fully open. D. Thermocouple connection loose at control valve. E. Pilot flame not touching thermocouple, which allows
thermocouple to cool, causing pilot flame to go out. This problem could be caused by one or both of the following:
1). Low gas pressure
2). Dirty or partially clogged ODS/pilot
F. Thermocouple damaged. G. Control valve damaged. A. Burner orifice is clogged. B. Burner orifice diameter is too small. C. Inlet gas pressure is too low. A. Manifold pressure is too low. B. Burner orifice is clogged. A. Burner orifice is clogged or damaged. B. Burner damaged. C. Gas regulator defective. A. Vapors from paint or curing process of logs.
A. Turning control knob to “HI” position when burner is cold. B. Air in gas line.
C. Dirty or partially clogged burner orifice.
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
Replace igniter. Replace igniter. Reconnect igniter cable. Free igniter cable if pinched by any metal or tubing. Keep igniter cable dry. Tighten nut. Replace igniter cable. Replace piezo igniter. Ventilate room. Stop using odor-causing products while fireplace is running. Locate and correct all leaks. Open window and/or door for ventilation. Contact local gas company. Clean ODS/pilot. Locate and correct all leaks (see Checking Gas Connections, page 6). Replace control valve. Turn on gas supply or open manual shut-off valve. Turn control knob to pilot position. Press in control knob while in pilot position. Continue holding down control knob. Repeat igniting operation until air is
removed. Replace ODS/pilot assembly or get it serviced. Replace gas regulator. Press in control knob fully. After ODS/pilot lights, keep control knob pressed in 30 seconds. Fully open manual shut-off valve. Hand tighten until snug, then tighten ¹⁄₄ turn more.
1). Contact local gas company.
2). Replace ODS/pilot assembly or get pilot serviced. Replace thermocouple. Replace control valve. Clean burner or replace burner orifice. Replace burner orifice. Contact local gas company. Contact local gas company. Clean burner or replace burner orifice. Clean burner or replace burner orifice. Replace burner. Replace gas regulator. Problem will stop after a few hours of operation. Superior recommends
running the heater with the excess ventilation for the first few hours. Turn control knob to “LO” position and let warm up for a minute. Operate burner until air is removed from line. Have gas line checked by local gas
company. Clean burner or replace burner orifice.
11
OPERATING INSTRUCTIONS — MANUAL CONTROL MODELS
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY
RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
A. This heater has a pilot which must be lit by hand. When
lighting the pilot, follow these instructions exactly.
B. BEFORE OPERATING smell all around the heater area for gas.
Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone
in your building.
LIGHTING INSTRUCTIONS
1. Stop! Read the safety information above.
2. Make sure manual shut-off valve is fully open.
3. Refer to
4. Depress control knob in and turn clockwise to the
“OFF” position (
5. Wait 5 minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information above. If you do not smell gas, go to the next step.
6. The pilot is located on the right side in front of the burner (
7. Depress control knob in and turn counterclockwise to the “IGN” position ( the way in for 5 seconds.
Figure 15
Figure 17
to locate gas control knob and piezo.
Figure 16
).
).
Figure 18
). Press the control knob all
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob.
Never use tools. If the knob will not push in or turn by hand, do not try to repair it, call a qualified service technician. Forced or attempted repair may result in a fire or explosion.
D. Do not use this heater if any part has been under water.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
8. With the control knob pressed in, push in and release the piezo igniter button to light the pilot.
9. Hold the control knob in for a further 10 seconds to prevent the flame failure detector from shutting off the gas while the probe is warming up.
10. Release the control knob while turning counterclockwise to the preferred setting.
If the knob does not pop out when released, stop and
immediately call your service technician or gas supplier.
If the pilot will not stay lit after several tries, depress and
turn the gas control knob clockwise to “OFF” and wait 30 seconds. Depress and turn knob counter­clockwise to “IGN” and press igniter button again. If your pilot does not relight depress and turn control knob clockwise to “OFF” and call your service technician or gas supplier.
Note: If you are running the heater for the first time it will be necessary to press the control knob all the way in for 30 seconds to allow air to bleed out of the gas piping.
1. Depress and turn control knob clockwise to the “OFF” position (
1. If the pilot cannot be lit with the piezo igniter, the heater can be manually lit with a match.
2. With the right hand, depress and turn the control knob counterclockwise to the “IGN” position. Hold in the knob.
12
Figure 18
).
MANUAL MATCH LIGHTING PROCEDURE — EMERGENCY ONLY
11. Wait 30 seconds before readjusting the heater when the
control knob has been turned down to a lower setting.
TO TURN OFF GAS TO APPLIANCE
3. Light the match and hold the flame to the end of the pilot and
ignite the pilot.
4. Continue to hold control knob for an additional 10 seconds to insure pilot remains lit.
5. Release the control while turning control knob to desired setting.
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
Millivolt Model
Pilot
Figure 15
Figure 16
Piezo
Flame Adjustment Knob
Control Knob Locations Pilot Location
Gas Control Knob
Figure 17
O
F
O
F
F
N
W
O
G
I
I
H
L
Turn Control Knob to “OFF” Position (Manual) Turn Control Knob to “IGN” Position (Manual)
Figure 18
F
I
H
N
W
O
G
I
L
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
13
OPERATING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY
RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
A. This heater has a pilot which must be lit by hand. When
lighting the pilot, follow these instructions exactly.
B. BEFORE OPERATING smell all around the heater area for gas.
Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone
in your building.
LIGHTING INSTRUCTIONS
1. Stop! Read the safety information above.
2. Make sure manual shut-off valve is fully open.
3. Locate gas control knob and piezo.
4. Depress control knob in and turn clockwise to the
“OFF” position (
5. Wait 5 minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information above. If you do not smell gas, go to the next step.
6. The pilot is located on the right side in front of the burner (
Figure 20
7. Depress control knob in and turn counterclockwise to the “PILOT” position ( the way in for 5 seconds.
).
Figure 19
).
Figure 21
). Press the control knob all
Note: If you are running the heater for the first time it will be necessary to press the control knob all the way in for 30 seconds to allow air to bleed out of the gas piping.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob.
Never use tools. If the knob will not push in or turn by hand, do not try to repair it, call a qualified service technician. Forced or attempted repair may result in a fire or explosion.
D. Do not use this heater if any part has been under water.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
8. With the control knob pressed in, push in and release the piezo igniter button to light the pilot.
9. Hold the control knob in for a further 10 seconds to prevent the flame failure detector from shutting off the gas while the probe is warming up.
10. Release the control knob while turning counterclockwise to the "ON" Position ( "HI"-"LOW" knob to prefered setting.
If the knob does not pop out when released, stop and
immediately call your service technician or gas supplier.
If the pilot will not stay lit after several tries, depress and
turn the gas control knob clockwise to “OFF” and wait 30 seconds. Depress and turn knob counterclockwise to “IGN” and press igniter button again. If your pilot does not relight depress and turn control knob clockwise to “OFF” and call your service technician or gas supplier.
11. Wait 30 seconds before readjusting the heater when the control knob has been turned down to a lower setting.
Figure 22
). Then adjust
1. Depress and turn control knob clockwise to the “OFF” position (
1. If the pilot cannot be lit with the piezo igniter, the heater can be manually lit with a match.
2. With the right hand, depress and turn the control knob counterclockwise to the “ON” position. Hold in the knob.
14
Figure 19
).
MANUAL MATCH LIGHTING PROCEDURE — EMERGENCY ONLY
TO TURN OFF GAS TO APPLIANCE
3. Light the match and hold the flame to the end of the pilot and
ignite the pilot.
4. Continue to hold control knob for an additional 10 seconds to insure pilot remains lit.
5. Release the control while turning control knob to desired
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
setting.
Note: Knob cannot be turned from “PILOT” to “OFF”
EA
TPTH TP TH
P
I
L
O
T
H
I
L
O
W
P
I
L
O
T
O
N
it
O
F
F
EA
TPTH TP TH
P
I
L
O
T
H
I
L
O
W
P
I
L
O
T
O
N
it
O
F
F
EA
TPTH TP TH
P
I
L
O
T
H
I
L
O
W
P
I
L
O
T
O
N
it
O
F
F
unless the knob is pushed in slightly. Do not force.
Figure 19
Figure 20
Turn Control Knob to “OFF” Position
Pilot
Pilot Location
Turn Control Knob to “PILOT” Position
Figure 21
Turn Control Knob to “ON” Position
Figure 22
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
15
REPLACEMENT PARTS LIST
18N/18P 24N/24P 28N/28P
No. Description Part No. Part No. Part No.
1. Valve - Manual (Natural) 110331 110331 110331
Valve - Manual (Propane, L.P.G.) 110331 110331 110331
2. Valve, Millivolt (Natural) 903489 903489 903489 Valve, Millivolt (Propane, L.P.G.) 901917 901917 901917
3. Pilot (Natural) 110345 110345 110345 Pilot (Propane, L.P.G.) 110341 110341 110341
4. Pilot, Millivolt (Natural) 110344 110344 110344 Pilot, Millivolt (Propane, L.P.G.) 901915 901915 901915
5. Regulator (Natural) 110351 110351 110351 Regulator (Propane, L.P.G.) 110352 110352 110352
6. Front Burner 110281 110282 110282
7. Rear Burner (Natural) 113301 110302 110302
Rear Burner (Propane, L.P.G.) 113301 110302 110302
8. Crossover Burner 110321 110321 110321
9. Piezo 111061 111061 111061
10. Piezo Wire 110361 110361 110361
11. Log Assembly – Split Oak 100104 100105 100106
12. Control Knob - Manual 110401 110401 110401
13. Injector, Burner (Natural) 110381 110383 110383
Injector, Burner (Propane, L.P.G.) 110382 110384 110384
14. Injector, Crossover Burner (Natural) 110387 110387 110387 Injector, Crossover Burner (Propane, L.P.G.) 110388 110388 110388
16
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
REPLACEMENT PARTS
14
11
1
2
5
13
10
9
8
7
12
4
6
3
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
17
18
NOTE: THIS PAGE INTENTIONALLY LEFT BLANK.
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
NOTE: THIS PAGE INTENTIONALLY LEFT BLANK.
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
19
The manufacturer reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
Printed in U.S.A. © 1997 by Lennox Hearth Products
P/N 903623 REV. M 12/2007
LHP
1110 West Taft Avenue Orange, CA 92865
Loading...