Superior Fireplaces VS1824NM, VS1824PM, LVS18VO, LVS24VO Installation And Operation Instructions Manual

Page 1
Installation and Operation Instructions
Unvented (Vent-Free) Gas Log Heater
P/N 126842-01 REV. B 05/2017
PFS
®
Models
VS1824NM
VS1824PM
US
P126842-01
Report No. F09-129
For use with log sets
LVS18VO
LVS24VO
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
This appliance may be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
WARNING: This appliance is for installation only in a solid-fuel burning masonry or UL127 factory-built fi replace or in a listed ventless fi rebox enclosure. It is design-certifi ed for these installations in accordance with ANSI Z21.11.2. Exception: DO NOT install this appliance in a factory-built fi replace that includes instructions stating it has not been tested or should not be used with unvented gas logs.
This is an unvented gas-fi red heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation section on Page 6 of this manual.
WARNING:
FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
- Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re department.
- Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
Page 2
TABLE OF CONTENTS
Safety .................................................................. 2
Product Identifi cation ........................................... 5
Local Codes......................................................... 5
Unpacking............................................................ 5
Product Features ................................................. 6
Air For Combustion and Ventilation ..................... 6
Installation ........................................................... 9
Operation .......................................................... 18
Inspecting Burners............................................. 20
Cleaning and Maintenance ................................ 20
Troubleshooting .................................................22
Parts .................................................................. 26
Specifi cations ....................................................29
Replacement Parts ............................................ 29
Service Hints .....................................................29
Technical Service............................................... 29
Accessories ....................................................... 30
Warranty ............................................................35
SAFETY
WARNING: FIRE, EXPLOSION, AND ASPHYXIATION HAZARD
Improper adjustment, alteration, service, maintenance, or installation of this heater or its controls can cause death or serious injury.
Read and follow instructions and precautions in User’s Information Manual provided with this heater.
WARNING: This appliance is for installation only in a solid-fuel burn­ing masonry or UL127 factory-built replace or in a listed ventless fi re- box enclosure. It is design-certifi ed for these installations in accordance with ANSI Z21.11.2. Exception: DO NOT install this appliance in a factory-built fi replace that includes instructions stating it has not been tested or should not be used with unvented gas logs.
WARNING: Vent-free products are prohibited for bedroom and bathroom installation in the Commonwealth of Massachusetts.
WARNING: This product contains and/or generates chemicals known to the state of California to cause cancer or birth defects or other re­productive harm.
WARNING: This is an unvented gas-fi red heater . It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation section on Page 6 of this manual.
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
DANGER: Carbon monoxide
poisoning may lead to death!
SuperiorFireplaces.us.com
126842-01B2
Page 3
SAFETY
Continued
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, operate or service this fi replace. Improper use of this fi replace can cause serious injury or death from burns, fi re, ex- plosion, electrical shock and carbon monoxide poisoning.
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning resemble the fl u, with headaches, dizziness or nausea. If you have these signs, the fi replace may not be working properly . Get fresh air at once! Have replace serviced. Some people are more af­fected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the infl uence of alcohol and those at high altitudes.
Natural and Propane/LP gases are odorless. An odor-making agent is added to these gases. The odor helps you detect a gas leak. How­ever, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this fi replace.
WARNING: Do not place log
scraps or volcanic stone on burner.
Due to high temperatures, the ap­pliance should be located out of traffi c and away from furniture and draperies.
Do not place clothing or other fl am- mable material on or near the appli­ance. Never place any objects on the heater.
Heater base assembly becomes very hot when running heater. Children and adults should be alerted to the hazard of high surface temperature and should stay away to avoid burns or clothing ignition. Heater will remain hot for a time after shut­down. Allow surface to cool before touching.
Young children should be carefully supervised when they are in the same room with the appliance.
WARNING: Any change to this heater or its controls can be dan­gerous.
You must operate this heater with the fi replace screen and hood in place. Make sure fi replace screen and hood are in place before running heater. The fi replace screen shall
WARNING: Do not use a blower
insert, heat exchanger insert or other
have openings for introduction of combustion air.
accessory not approved for use with this heater.
Keep the appliance area clear and free from combustible materials, gasoline and other fl ammable vapors
WARNING: Do not allow fans
and liquids. to blow directly into the fi replace. Avoid any drafts that alter burner ame patterns. Ceiling fans can create drafts that alter burner fl ame
Solid-fuels shall not be burned in a
replace in which an unvented room
heater is installed. patterns. Altered burner patterns can
cause sooting.
126842-01B 3
SuperiorFireplaces.us.com
Page 4
SAFETY
Continued
Installation and repair should be done by a qualifi ed service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments, burners, and circulating air passageways of the appliance be kept clean.
1. WARNING: This appliance is only for
use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors (propane/LP units only).
3. T o prevent performance problems, the use of a propane/LP tank of less than 100 lbs. capacity is not recommended (propane/LP units only).
4. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas sup­plier’s instructions
• if you cannot reach your gas supplier, call
the fi re department
5. This heater shall not be installed in a bedroom or bathroom unless installed as a vented appliance (see Installing Damper
Clamp Accessory for Vented Operation,
Page 12). This gas log set may not be installed as a vented appliance in a bed­room or bathroom in the Commonwealth of Massachusetts.
6. Do not burn solid-fuel in a fi replace in which a vent-free room heater is installed.
7. WARNING: Before installing in a solid
fuel burning fi replace, the chimney fl ue and fi rebox must be cleaned of soot, creosote, ashes and loose paint by a qualifi ed chimney cleaner. Creosote will
ignite if highly heated. A dirty chimney fl ue may create and distribute soot within the house. Inspect chimney fl ue and fi rebox for damage. If damaged, repair fl ue before operating heater.
8. If fi replace has glass doors, never oper- ate this heater with glass doors closed. Any glass doors shall be fully opened
SuperiorFireplaces.us.com
when the appliance is in operation. If you operate heater with doors closed, heat
buildup inside fi replace will cause glass to burst. Make sure there are no obstructions across openings of fi replace.
9. This log heater is designed to be smoke­less. If logs ever appear to smoke, turn off heater and call a qualifi ed service person.
NOTE: During initial operation, slight
smoking could occur due to log curing and heater burning manufacturing residues.
10. To prevent the creation of soot, follow the instructions in Cleaning and Maintenance, Page 20.
11. Before using furniture polish, wax, carpet cleaner or similar products, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
12. This heater needs fresh, outside air ven­tilation to run properly . This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if not enough fresh air is available. See Air for Combustion and Ventilation, Page 6. If heater keeps shutting off, see Troubleshooting, Page 22.
13. Do not run heater
• where fl ammable liquids or vapors are
used or stored
• under dusty conditions
14. Do not use this heater to cook food or burn paper or other objects.
15. Do not use this room heater if any part has been under water. Immediately call a qualifi ed service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water.
16. Do not operate heater if any log is broken. Do not operate heater if a log is chipped (dime-sized or larger).
17. Turn heater off and let cool before servic­ing. Only a qualifi ed service person should service and repair heater.
18. Operating heater above elevations of 4,500 feet could cause pilot outage.
19. Provide adequate clearances around air openings.
20. Solid fuels shall not be burned in a fi re- place in which an unvented room heater or decorative appliance is installed.
21. When installing as a vented appliance in a manufactured home , the installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280 or when standard is not applicable, with Manufactured Home
Installations Standard, ANSI/NCSBCS A225.1/NFPZ 501A.
126842-01B4
Page 5
PRODUCT IDENTIFICATION
Left Side
Grate
Heater Base
Front
Figure 1 - Product Identifi cation
Control Knob
LOCAL CODES
Install and use appliance with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
25 West 43rd Street, 4th fl oor
New York, NY 10036
National Fire Protection Association, Inc.
1 Batterymarch Park
Quincy, MA 02169-7471
UNPACKING
1. Remove logs and appliance base assem­bly from carton(s).
Right Side
NOTE: Do not pick up appliance base as-
sembly by burners. This could damage the appliance. Always handle base assembly by grate.
2. Remove all protective packaging applied to logs and appliance for shipment.
3. Check appliance for any shipping dam­age. If appliance is damaged, promptly inform dealer where you purchased the appliance.
CAUTION: Do not remove the data plates from the grate as­sembly . The data plates contain important warranty and safety information.
COMMONWEALTH OF MASSACHUSETTS REQUIREMENTS
These appliances are approved for installation in the US state of Massachusetts if the fol­lowing additional requirements are met:
• Un-vented Room Heaters shall be installed in accordance with 527 CMR 30.
• Installation and repair must be done by a plumber or gas fi tter licensed in the Common- wealth of Massachusetts.
• The fl exible gas line connector used shall not exceed 36 inches (92 centimeters) in length.
• The individual manual shut-off must be a T-handle type valve.
• Unvented appliances may NOT be installed in bedrooms or bathrooms.
• A working smoke detector must be installed in the area where vent-free appliances are installed.
Seller of unvented propane or natural gas-fi red supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
126842-01B 5
SuperiorFireplaces.us.com
Page 6
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by realistic, dancing yellow fl ames. This heater is designed for vent-free operation with fl ue damper closed. It has been tested and ap­proved to ANSI Z21.11.2 standard for un­vented heaters. State and local codes in some areas prohibit the use of vent-free heaters.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not
be installed in a room or space un­less the required volume of indoor combustion air is provided by the method described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code, or applicable local codes. Read the following instructions to ensure proper fresh air for this and other fuel­burning appliances in your home.
T oday’s homes are built more energy effi cient than ever. New materials, increased insulation and new construction methods help reduce heat loss in homes. Homeowners apply weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, homeowners want their homes as airtight as possible.
While it is good to make your home energy effi cient, your home needs to breathe. Fresh air must enter your home. All fuel-burning ap­pliances need fresh air for proper combustion and ventilation.
Exhaust fans, some fi replaces, clothes dryers and some fuel-burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will ensure proper venting of vented fuel­burning appliances.
PROVIDING ADEQUA TE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classifi cations:
Non-thermostat models may also be operated as a vented decorative (ANSI Z21.60) product by opening fl ue damper.
SAFETY PILOT
This heater has a pilot with an Oxygen Deple­tion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent-free room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.
1. Unusually Tight Construction
2. Unconfi ned Space
3. Confi ned Space The information on Pages 6-8 will help you
classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of un­usually tight construction, you must provide additional fresh air.
Unusually tight construction is defi ned as construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10 less with openings gasketed or sealed and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window and door frames, between sole plates and fl oors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings.
If your home meets all three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, Page 8.
If your home does not meet all three criteria above, proceed to Determining Fresh-Air Flow For Heater Location, below.
Confi ned and Unconfi ned Space
The National Fuel Gas Code, ANSI Z223.1/ NFPA54 allows two methods for determining
whether the space in which the heater is being
-11
kg per pa-sec-m2) or
SuperiorFireplaces.us.com
126842-01B6
Page 7
AIR FOR COMBUSTION AND VENTILATION
Continued
installed is confi ned or unconfi ned space. The standard method defi nes a confi ned space as a space whose volume is less than 50 cubic feet per 1,000 Btu/hr (4.8 m gregate input rating of all appliances installed in that space and an unconfi ned space as a space whose volume is not less than 50 cubic feet per 1,000 Btu/hr (4.8 m the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the un­confi ned space.
Where the air infi ltration rate of a structure is known, the Known Air Infi ltration Rate Method may be used. Follow The National Fuel Gas Code, ANSI Z223.1/NFPA 54 to use this method to determine if the space is confi ned or unconfi ned.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confi ned or Unconfi ned Space Using the Standard Method
Use this work sheet to determine if you have a confi ned or unconfi ned space.
Space: Includes the room in which you will install replace plus any adjoining rooms with door­less passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2,560 cu. ft. (volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
3
per kw) of the ag-
3
per kw) of
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2,560 cu. ft. (volume of space) x
20 = 51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free fi replace _________Btu/Hr Gas water heater* _________Btu/Hr Gas furnace _________Btu/Hr Vented gas heater _________Btu/Hr Gas fi replace logs _________Btu/Hr Other gas appliances* + _________ Btu/Hr Total = _________Btu/Hr * Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the outdoors and vents to the outdoors.
Example: Gas water heater __________Btu/Hr Vent-free fi replace + _________Btu/Hr Total = _________Btu/Hr
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/ Hr used.
_______ Btu/Hr (maximum the space can support) _______ Btu/Hr (actual amount of Btu/Hr used) Example: 51,200 Btu/Hr (maximum the
space can support)
71,500 Btu/Hr (actual amount of
Btu/Hr used)
The space in the example is a confi ned space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides an unconfi ned space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, Page 8.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, Page 8.
C. Install a lower Btu/Hr fi replace, if lower Btu/
Hr size makes room unconfi ned.
If the actual Btu/Hr used is less than the maxi­mum Btu/Hr the space can support, the space is an unconfi ned space. Y ou will need no additional fresh air ventilation.
40,000 31,500 71,500
126842-01B 7
SuperiorFireplaces.us.com
Page 8
AIR FOR COMBUSTION AND VENTILATION
A
Continued
WARNING: If the area in which the heater may be operated does not meet the required volume for indoor combustion air, combus­tion and ventilation air shall be provided by one of the methods described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code, or applicable local codes.
VENTILA TION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfi ned space. When ventilating to an adjoining unconfi ned space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the fl oor on the wall connecting the two spaces (see options 1 and 2, Figure 2). Y ou can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code ANSI
Z223.1/NFPA 54, Air for Combustion and Ventilation for required size of ventilation
grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two perma­nent openings: one within 12" of the ceiling and one within 12" of the fl oor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel
Gas Code ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size
of ventilation grills or ducts. IMPORTANT: Do not provide openings
for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.
Ventilated Attic
Crawl Space
Ventilated
To Attic
To
Crawl
Space
Outlet
ir
Inlet Air
Outlet Air
Inlet Air
Figure 3 - Ventilation Air from Outdoors
12"
Ventilation
Grills Into Adjoining
Room,
Option 1
Or
Remove Door into Adjoining
Room, Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
12"
Figure 2 - Ventilation Air from Inside
Building
SuperiorFireplaces.us.com
126842-01B8
Page 9
INSTALLATION
NOTICE: This appliance is intended for supplemental heating. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualifi ed service person must install heater. Follow all local codes.
NOTICE: State or local codes may only allow operation of this appli­ance in a vented confi guration. Check your state or local codes.
WARNING: Before installing in a solid fuel burning fi replace, the chimney fl ue and fi rebox must be cleaned of soot, creosote, ashes and loose paint by a qualifi ed chimney cleaner. Creosote will ignite if highly heated. A dirty chimney fl ue may create and distribute soot within the house. Inspect chimney and fi rebox
ue for damage. If damaged, repair ue and fi rebox before operating
heater.
WARNING: Any outside air ducts and/or ash dumps in the fi replace shall be permanently closed at time of appliance installation.
WARNING: Seal any fresh air
vents or ash clean-out doors located on fl oor or wall of fi replace. If not, drafting may cause pilot outage or sooting. Use a heat-resistant sealant. Do not seal chimney fl ue damper.
WARNING: Never install the
heater
in a bedroom or bathroom unless installed as a vented appliance
(see Page 12)
• in a recreational vehicle where curtains, furniture, clothing
• or other fl ammable objects are less than 36" from front and 42" from top of heater; for side clearances see Figure 4, Page 10
• in high traffi c areas
• in windy or drafty areas
CAUTION: This heater creates
warm air currents. These currents move heat to wall surfaces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as, but not limited to, tobacco smoke, aromatic candles, cleaning fl uids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
IMPORTANT: Vent-free heaters add moisture to the air. Although this is ben­efi cial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, Page 6.
CHECK GAS TYPE
Use only the correct gas type (natural or propane/LP) for your unit. If your gas supply is not correct, do not install heater. Call dealer where you bought heater for proper type heater.
WARNING: This appliance is equipped for either natural gas or propane/LP gas but not both. Gas type is indicated on the rating plate. Field conversion is not permitted.
126842-01B 9
SuperiorFireplaces.us.com
Page 10
INSTALLATION
Continued
INST ALLATION AND CLEARANCES (Vent-Free Operation Only)
WARNING: Maintain the minimum clearances. If you can, provide greater clearances from oor , ceiling and adjoining wall.
Minimum Fireplace Clearance to
Combustible Materials
Side Wall 16", Ceiling 42", Front 36"
Minimum Firebox Size
Height 17", Depth 14", Front Width 24",
Rear Width 20" (measured at 14" depth)
Carefully follow instructions below. This will ensure safe installation into a masonry, UL127-listed manufactured fi replace or certi- ed vent-free fi rebox.
Minimum Clearances For Side Combustible Material, Side Wall and Ceiling
A. Clearances from side of fi replace cabinet
to any combustible material and wall should follow diagram in Figure 4.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and protrudes 3-1/2" from the wall. This com­bustible material must be 4" from the side of the fi replace cabinet (see Figure 4).
NOTE: When installing your gas logs into
a manufactured firebox, follow firebox manufacturer’s instructions for minimum clearances to combustible materials.
B. Clearances from the top of the fi replace
opening to the ceiling should not be less than 42".
Maintain adequate clearances for accessibility for purposes of servicing and proper operation.
Example
NOTICE: Manual control heaters may be used as a vented product. If so, you must always run heater with chimney fl ue damper open. If running heater with damper open, noncombustible material above replace opening is not needed. Go to Installing Damper Clamp Acces- sory for Vented Operation, Page 12.
Minimum Noncombustible Material Clearances
If Not Using Mantel
NOTE: If using a mantel, proceed to If Using Mantel, Page 10. If not using a mantel, follow the information below.
You must have noncombustible material(s) above the fi replace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible material must extend at least 8" up (for all models). If noncombustible material is less than 12", you must install the replace hood accessory (for all models). See Figure 5 on Page 1 1 for minimum clearances.
If Using Mantel
Noncombustible
Material Distance
(A)
12" or more Noncombustible material Between 8" and
12"
Less than 8"
Requirements for Safe
Installation
okay. Install fi replace hood
accessory (GA6050 - see
Accessories, Page 30).
Noncombustible material must be extended to at least 8". See Between 8" and 12", above. If you cannot extend material, you must operate heater with fl ue damper open.
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
Minimum clearance requirements include any projections such as shelves, window sills, mantels, etc. above the appliance.
*
SuperiorFireplaces.us.com
126842-01B10
Page 11
INSTALLATION
Continued
MANTEL CLEARANCES
Heat Resistant Material
(A)
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
You must have noncombustible material(s) above the fi replace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2" thick. With sheet metal, you must have noncombustible material behind it. Noncombustible material must extend at least 8" up. See Figure 5 and 6 for minimum clearances.
IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney fl ue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, Page 12.
Mantel Shelf
8" 14" 17" 20"
Distances to Underside of Mantel
Underside of Mantel Shelf
All minimum distances are in inches
Log Set All Models
Top of Fireplace Opening
Minimum Noncombustible Material
10"
8"
6"
2 1/2"
(A)
8"
Minimum Noncombustible Material Height
Figure 6 - Minimum Mantel Clearances
Without Using Hood
126842-01B 11
SuperiorFireplaces.us.com
In addition to meeting noncombustible mate­rial clearances, you must also meet required clearances between fi replace opening and mantel shelf. If you do not meet the clearances listed below, you will need a hood.
You must meet the minimum clearances between the mantel shelf and the top of the replace opening as shown in Figure 6.
Determining Minimum Mantel Clearance When Using a Hood
If minimum clearances in Figure 6, are not met, you must have a hood. When using a hood there are still certain minimum mantel clear­ances required. Follow minimum clearances shown in Figure 7, Page 12 when using hood.
NOTICE: Surface temperatures of adjacent walls and mantels become hot during operation. Walls and mantels above the firebox may become hot to the touch. If installed properly, these temperatures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.
Notice: If your installation does not meet the minimum clear­ances shown, you must do one of the following:
• operate the logs only with the fl ue damper open
• raise the mantel to an ac­ceptable height
• remove the mantel
FLOOR CLEARANCES
A. If installing appliance on fl oor level, you
must maintain the minimum distance of 14" to combustibles (see Figure 8, Page
12).
B. If combustible materials are less than 14"
to fi replace, you must install appliance at least 5" above the top surface of combus­tible fl ooring including tile and carpet (see
Figure 9, Page 12).
Page 12
INSTALLATION
Minimum Noncombustible Material
8" Min.
12" 15" 18" 20"
2½"
6"
8"
10"
12"
Distances to Underside of Mantel
Hood (GA6050)
Top of Fireplace Opening
Underside of Mantel Shelf
Mantel Shelf
Continued
Figure 7 - Minimum Mantel Clearances
When Using Hood
1. The fi replace does not meet the clear- ance to combustibles requirements for vent-free operation.
2. State or local codes do not permit vent­free operation.
3. You prefer vented operation.
If reasons number 1 or 2 apply to you, you must permanently open chimney fl ue damper. You must install the damper clamp accessory (to order, see Accessories, Page 30). This will ensure vented operation (see Figure 10). The damper clamp will keep damper open. Installation instructions are included with clamp accessory.
See chart below for minimum permanent fl ue opening you must provide. Attach damper clamp so the minimum permanent fl ue open- ing will be maintained at all times.
14" Min.
Noncombustible Material
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Hearth
5" Min.
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED OPERATION
NOTE: When used as a vented heater, ap­pliance must be installed only in a solid-fuel burning fi replace with a working fl ue and con- structed of noncombustible material.
Y ou may use this heater as a vented product. There are three reasons for operating your heater in the vented mode.
SuperiorFireplaces.us.com
Combustible Material
Combustible Material
Chimney
Height
Minimum Permanent
Flue Opening
6' to 15' 39 sq. inches
15' to 30' 29 sq. inches
Area of Various Standard Round Flues
Diameter Area
5" 20 sq. inches 6" 29 sq. inches 7" 39 sq. inches 8" 51 sq. inches
Damper
Damper Clamp
Damper
Masonry Fireplace
Manufactured
Fireplace
Figure 10 - Attaching Damper
Damper
126842-01B12
Page 13
INSTALLATION
Continued
INSTALLING HEATER BASE ASSEMBLY
CAUTION: Do not remove the data plates from the grate as­sembly . The data plates contain important warranty and safety information.
W ARNING: Y ou must secure this heater to fi replace fl oor. If not, heater will move when you adjust controls. Moving heater may cause a gas leak.
WARNING: If installing in a sunken fi replace, special care is needed. You must raise the replace fl oor to allow access to heater control panel. This will ensure adequate air fl ow and guard against sooting and controls being damaged. Raise replace fl oor with noncombus- tible material. Make sure material is secure.
gas hose to gas regulator of heater (see
Figure 11).
IMPORTANT: Hold gas regulator with
wrench when connecting fl exible gas hose.
2. Locate masonry screws in hardware package.
3. Position heater base assembly in fi replace.
4. Place log in proper position on heater base
(see Installing Logs, Page 16).
5. Center heater base and logs front-to-front and side-to-side in fi replace.
6. Carefully remove log without moving heater base.
7. Mark screw locations through holes in mounting brackets (see Figure 12). If installing in a brick-bottom fi replace, mark screw locations in mortar joint of bricks.
8. Remove heater base from fi replace.
9. Drill holes at marked locations using 3/16" drill bit.
10. Attach base assembly to fi replace fl oor using two masonry screws (in hardware package) (see Figure 12).
Fitting
Heater Gas Regulator
CAUTION: Do not pick up
Flexible Gas Hose (if allowed by local codes)
heater base assembly by burn­ers. This could damage heater. Only handle base assembly by grates.
IMPORTANT: Make sure heater burners are level. If heater is not level, heater will not work properly.
Installation Items Needed
• hardware package (provided with heater)
• approved fl exible gas hose (if allowed by local codes)
sealant (resistant to propane/LP gas, not
• provided)
• electric drill with 3/16" drill bit
fl athead screwdriver
1. Apply pipe joint sealant lightly to male
threads of the fi tting to be threaded into gas regulator. Connect approved fl exible
126842-01B 13
SuperiorFireplaces.us.com
Figure 11 - Attaching Flexible Gas Hose
to Heater Gas Regulator
Masonry Screw
Mounting Bracket
Figure 11 - Attaching Base Assembly to
Fireplace Floor
Page 14
INSTALLATION
Continued
CONNECTING TO GAS SUPPLY
WARNING: This appliance requires a 3/8" NPT (National Pipe Thread) inlet connection to the pressure regulator.
WARNING: A qualifi ed ser- vice person must connect heater to gas supply. Follow all local codes.
CAUTION: Never connect propane/LP fi replace directly to the propane/LP supply. This heater requires an external regu­lator (not supplied). Install the external regulator between the heater and propane/LP supply.
WARNING: Never connect natural gas fi replace to private (non-utility) gas wells. This gas is commonly known as wellhead gas.
Installation Items Needed
Before installing heater, make sure you have the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve
• test gauge connection
• sediment trap
• tee joint
• pipe wrench For propane/LP gas, the installer must supply
an external regulator. An external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 1 1" and 14" of water.
If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with vent pointing down as shown in Figure 13. Pointing vent down protects it from freezing rain or sleet.
CAUTION: Use only new, black iron or steel pipe. Inter­nally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to heater. If pipe is too small, undue loss of volume will occur.
Installation must include an equipment shutoff valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see
Figure 14, Page 15). IMPORTANT: Install equipment shutoff valve
in an accessible location. Main gas valve is for turning on or shutting off gas to the appliance.
Check your building codes for any special requirements for locating equipment shutoff valve to fi replaces.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
Propane/LP Supply Tank
External Regulator with Vent Pointing Down
Figure 13 - External Regulator With Vent
SuperiorFireplaces.us.com
Pointing Down
126842-01B14
Page 15
INSTALLATION
Continued
We recommend that you install sediment trap in supply line as shown in Figure 14. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contami­nants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.
CAUTION: A void damage to regulator. Hold gas regulator with wrench when connecting it to gas piping and/or fi ttings.
Natural
From Gas Meter (5" W.C.** to
10.5" W.C. Pressure)
Propane/LP
From External Regulator (11" W.C.** to 14" W.C. Pressure
** Min. inlet pressure for purpose of input adjustment.
Tee Cap Pipe Joint Nipple
Sediment Trap
Figure 14 - Gas Connection
3" Min.
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.
Gas Regulator
Approved Flexible Gas Hose (if allowed by local codes)
CAUTION: For propane/LP units, make sure external regula­tor has been installed between propane/LP supply and heater. See guidelines under Connect­ing to Gas Supply, Page 14.
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1. Disconnect appliance with its appliance main gas valve (control valve) and equip­ment shutoff valve from gas supply piping. Pressures in excess of 1/2 psig (3.5 kPa) will damage heater regulator.
2. Cap off open end of gas pipe where equip­ment shutoff valve was connected.
3. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.
4. Check all joints of gas supply piping system. Apply a commercial leak detection solution to all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff valve to gas supply. Check reconnected ttings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig- ure 15).
2. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.
Equipment Shutoff Valve
Open
WARNING: Never use an open fl ame to check for a leak. Apply a noncorrosive leak detec­tion fl uid to all joints. Bubbles
Figure 15 - Equipment Shutoff Valve
Closed
forming show a leak. Correct all leaks at once.
126842-01B 15
SuperiorFireplaces.us.com
Page 16
INSTALLATION
Continued
3. Check all joints from gas meter (natural gas) or propane/LP supply to equipment shutoff valve (see Figure 16 or 17). Apply a commercial leak detection solution to all joints. Bubbles forming show a leak.
4. Correct all leaks at once.
Propane/LP Supply Tank
Figure 16 - Checking Gas Joints
(Propane/LP Gas Only)
Equipment Shutoff Valve
Gas Meter
Figure 17 - Checking Gas Joints
(Natural Gas Only)
PRESSURE TESTING HEATER GAS CONNECTIONS
1. Open equipment shutoff valve (see Figure 15, Page 15).
2. Open main gas valve located on or near gas meter for natural gas or open pro­pane/LP supply tank valve.
3. Make sure control knob of heater is in the OFF position.
4. Check all joints from gas meter (natural gas) or propane/LP supply to equipment shutoff valve (see Figure 16 or 17). Apply a commercial leak detection solution to all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light heater (see Operation Page 18). Check all other internal joints for leaks.
7. Turn off heater (see To Turn Off Gas to
Appliance, Page 19).
Equipment Shutoff Valve
Control Valve Location
Control Valve Location
INSTALLING LOGS
WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts specifi cally approved with this heater may result in property damage or personal injury.
CAUTION: After installation and periodically thereafter, check to ensure that no fl ame comes in contact with any log. With the heater set to High, check to see if fl ames contact any log. If so, reposition log according to the log installation instructions in this manual. Flames contacting log will create soot.
MODELS LVS18-VO AND LVS24-VO
It is very important to install these logs exactly as instructed. Do not modify logs. Only use logs supplied with heater.
1. Place grate into square holes on heater base as shown in Figure 18.
2. Place front log on burner so that it sits between grate fi ngers and burner (see
Figure 18).
The Front Log Should Be Centered Left To Right.
Front Log
Grate
Heater Base
Figure 18 - Installing Grate and Logs
SuperiorFireplaces.us.com
126842-01B16
Page 17
INSTALLATION
Continued
3. Place rear log on heater base behind the metal burner. The bottom of the rear log has recess areas on the left and right side for the base to set into. Pull the rear log forward until it touches the front log (see
Figure 18, Page 16).
4. Place the left crossover log as shown in Figure 19. The bottom of the log is marked with a “L” for left. Match round peg on left side of top of rear log with round hole in bottom of left crossover. Match square peg on left side of top of front log with square hole in bottom of left crossover log.
Left Crossover Log
Center Crossover Log
Figure 20 - Installing Center Crossover Log
Right Crossover Log
Figure 19 - Installing Left Crossover Log
5. Place the center crossover log as shown in Figure 20. The bottom of the log is marked with a “C” for center. Match square peg on center of rear log with square hole in bottom of center cross­over. Match round peg on center of front log with round hole in bottom of center crossover log.
6. Place the right crossover log as shown in Figure 21. The bottom of the log is marked with a “R” for right. Match square peg on right side of rear log with square hole in bottom of right crossover. Match round peg on right side of front log with round hole in bottom of right crossover log.
7. Add volcanic stone around base of heater if desired. Do not place any volcanic stone on logs or burner.
126842-01B 17
SuperiorFireplaces.us.com
Figure 21 - Installing Left Crossover Log
Page 18
OPERATION
FOR YOUR SAFETY
READ BEFORE LIGHTING
W ARNING: If you do not fol­low these instructions exactly, a fi re or explosion may result causing property damage, per­sonal injury or loss of life.
A. This appliance has a pilot which must
be lighted by hand. When lighting the pilot, follow these instructions exactly .
B. BEFORE LIGHTING smell all around
the appliance area for gas. Be sure to smell next to the fl oor because some gas is heavier than air and will settle on the fl oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re department.
C. Use only your hand to push in or turn
the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a quali­ ed service technician or gas supplier. Force or attempted repair may result in a fi re or explosion.
Do not use this appliance if any part has
D.
been under water. Immediately call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
LIGHTING
INSTRUCTIONS
WARNING:
• If fi replace has glass doors, never operate this heater with glass doors closed. If you op­erate heater with doors closed, heat buildup inside fi replace will cause glass to burst. Make sure there are no obstructions across openings of fi replace.
• You must operate this heater with a fireplace screen in place. Make sure fireplace screen is closed before run­ning heater.
NOTICE: During initial operation of new heater , burning logs will give off a paper-burning smell. Orange fl ame will also be pres- ent. Open damper or window to vent smell. This will only last a few hours.
NOTE: Homeowners generally prefer to op­erate their heater with the chimney damper closed. This will put all the heat into the room. However, there may be times you will desire the full fl ames of the HI heat setting but will nd the heat output excessive. You can open the chimney damper (if you have one) fully or partially to release some of the heat.
WARNING: Damper handle will be hot if heater has been running.
SuperiorFireplaces.us.com
126842-01B18
Page 19
OPERATION
Continued
1. STOP! Read the safety information in column 1.
2. Make sure equipment shutoff valve is fully open.
3. Press in and turn control knob clockwise
to the OFF position.
4. Wait fi ve (5) minutes to clear out any gas. Then smell for gas, including near the oor. If you smell gas, STOP! Follow “B” in the safety information, Page 18. If you don’t smell gas, go to the next step.
5. Press in control knob and turn counterclock­wise
to the PILOT position. The igniter will spark once. Keep control knob pressed in for 5 seconds. If control knob does not pop up when released, contact a qualifi ed service person or gas supplier for repairs.
NOTE: You may be running this heater for
the fi rst time after hooking up to gas sup- ply . If so, the control knob may need to be pressed in for 30 seconds or more. This will allow air to bleed from the gas system.
6. Turn control knob clockwise
to OFF position. Press in control knob and turn counterclockwise
to PILOT position. This will light pilot. Pilot is at­tached to rear of burner. If needed, repeat this process until pilot lights.
NOTE: If pilot does not stay lit, contact a
qualifi ed service person or gas supplier for repairs. Until repairs are made, light pilot with match. T o light pilot with match, see Manual Lighting Procedure.
7. Keep control knob pressed in for 30 sec­onds after lighting pilot. After 30 seconds, release control knob.
NOTE: If pilot goes out, repeat steps 3
through 7.
• If control knob does not pop out when
released, contact a qualified service person or gas supplier for repairs.
8. Slightly press and turn control knob coun­terclockwise
to desired heating level. The burner should light. Set control knob to HI or LO.
HI
PILOT
OFF
LO
Control Knob
Figure 22 - Control Knob and Igniter
Button Location
126842-01B 19
SuperiorFireplaces.us.com
WARNING: Do not operate heater between PILOT and HIGH positions.
9. T o leave pilot lit and shut off burners only , turn control knob clockwise
to the
PILOT position.
Thermocouple
Igniter Electrode
Pilot Burner
Figure 23 - Pilot
VARIABLE CONTROL
OPERATION
The variable control valve can be set to high or low, by simply turning the control knob until that setting is attained. Even the low­est setting provides realistic, dancing yellow ames. Selecting higher settings produces greater heat output. This results in increased heating comfort.
CAUTION: Do not try to ad­just heating levels by using the equipment shutoff valve.
TO TURN OFF GAS
TO APPLIANCE
1. Press in and turn control knob clockwise to the OFF position.
2. Close equipment shutoff valve (see Fig-
ure 15, Page 15).
MANUAL LIGHTING
PROCEDURE
1. Follow steps 1 through 5 under Lighting
Instructions, Page 19.
2. Depress control knob and light pilot
with match.
3. Keep control knob pressed in for 30 sec-
onds after lighting pilot. After 30 seconds, release control knob. Now follow step 8 under Lighting Instructions, Page 19.
Page 20
INSPECTING BURNERS
Check pilot fl ame pattern and burner fl ame patterns often.
PILOT FLAME PATTERN
Figure 24 shows a correct pilot ame pattern. Figure 25 shows an incorrect pilot ame pat-
tern. The incorrect pilot fl ame is not touching the thermocouple. This will cause the thermocouple to cool. When the thermocouple cools, the heater will shut down.
If pilot fl ame pattern is incorrect, as shown in Figure 25
• turn heater off (see To Turn Off Gas to Ap-
pliance, Page 19)
• see Troubleshooting, Page 22 NOTE: The pilot ame on natural gas units will
have a slight curve, but fl ame should be blue and have no yellow or orange color.
Pilot Burner
Thermocouple
Figure 24 - Correct Pilot Flame Pattern
Thermocouple
Pilot Burner
Figure 25 - Incorrect Pilot Flame Pattern
BURNER PRIMARY AIR HOLES
Air is drawn into the burner through the holes in the fi tting at the entrance to the burner. These holes may become blocked with dust or lint. Periodically inspect these holes for any blockage and clean as necessary . Blocked air holes will create soot.
MAIN BURNER
Periodically inspect all burner fl ame holes with the heater running. All slotted burner fl ame holes should be open with yellow fl ame pres- ent. All round burner fl ame holes should be open with a small blue fl ame present. Some burner fl ame holes may become blocked by debris or rust, with no fl ame present. If so, turn off heater and let cool. Remove blockage, blocked burner fl ame holes will create soot.
CLEANING AND MAINTENANCE
WARNING: Turn off heater
and let cool before cleaning.
CAUTION: You must keep control areas, burner and circu­lating air passageways of heater clean. Inspect these areas of heater before each use. Have heater inspected yearly by a qualifi ed service person. Heater may need more frequent clean­ing due to excessive lint from carpeting, bedding material, pet hair, etc.
SuperiorFireplaces.us.com
WARNING: Failure to keep the primary air opening(s) of the burner(s) clean may result in sooting and property damage.
ODS/PILOT AND BURNER
Use a vacuum cleaner or small, soft bristled brush to clean.
BURNER ORIFICE HOLDER AND PILOT AIR INLET HOLE
The primary air inlet holes allow the proper amount of air to mix with the gas. This pro­vides a clean burning fl ame. Keep these holes clear of dust, dirt and lint. Clean these air inlet holes prior to each heating season. Blocked air holes will create soot. We recommend that you clean the unit every three months during operation and have heater inspected yearly by a qualifi ed service person.
126842-01B20
Page 21
CLEANING AND MAINTENANCE
Continued
We also recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt. To clean these parts we recommend using compressed air no greater than 30 PSI. Your local computer store, hardware store or home center may carry compressed air in a can. If using compressed air in a can, please follow the directions on the can. If you don’t follow directions on the can, you could dam­age the pilot assembly.
1. Shut off unit, including pilot. Allow unit to cool for at least thirty minutes.
2. Inspect burner, pilot and primary air inlet holes on orifi ce holder for dust and dirt
(see Figure 26).
3. Blow air through the ports/slots and holes in the burner.
4. Check orifi ce holder located at the end of the burner tube again. Remove any large particles of dust, dirt, lint or pet hair with a soft cloth or vacuum cleaner nozzle.
Burner Tube
Orifi ce Holder (May Be Brass or Aluminum Depending on Model)
5. Blow air into the primary air holes on the orifi ce holder.
6. In case any large clumps of dust have now been pushed into the burner repeat steps 3 and 4.
Clean pilot assembly also. A yellow tip on the pilot fl ame indicates dust and dirt in the pilot assembly. There is a small pilot air inlet hole about 2" from where the pilot fl ame comes out of the pilot assembly (see Figure 27). With the unit off, lightly blow air through the air inlet hole. You may blow through a drinking straw if compressed air is not available.
Pilot Assembly
Pilot Air Inlet Hole
Figure 27 - Pilot Inlet Air Hole
Primary Air Inlet Holes
Figure 26 - Orifi ce Holder On Outlet
Burner Tube
126842-01B 21
SuperiorFireplaces.us.com
Page 22
TROUBLESHOOTING
W ARNING: Turn off heater and let cool before servicing. Only a
qualifi ed service person should service and repair heater.
CAUTION: Never use a wire, needle or similar object to clean
ODS/pilot. This can damage ODS/pilot unit.
NOTE: All troubleshooting items are listed in order of operation.
OBSERVED PROBLEM POSSIBLE CAUSE REMEDY
When control knob is pressed in and turned to PILOT , there is not spark at ODS/pilot
When control knob is pressed in and turned to PILOT , there is spark at ODS/pilot but no ignition
1. Igniter electrode not con­nected to igniter cable
2. Igniter cable pinched or wet
3. Broken igniter cable
4. Bad piezo igniter
5. Igniter electrode broken
6. Igniter electrode posi­tioned wrong
1. Gas supply turned off or equipment shutoff valve closed
2. Control knob not in PILOT position
3. Control knob not pressed in while in PILOT position
4. Air in gas lines when in­stalled
5. Depleted gas supply (pro­pane/LP only)
6. ODS/pilot is clogged
7. Gas regulator setting is not correct
1. Reconnect igniter cable
2. Free igniter cable if pinched by any metal or tubing. Keep igniter cable dry
3. Replace valve
4. Replace valve
5. Replace pilot
6. Reposition igniter elec­trode
1. Turn on gas supply or open equipment shutoff valve
2. Turn control knob to PILOT position
3. Press in control knob while in PILOT position
4. Continue holding down control knob. Repeat ig­niting operation until air is removed
5. Contact local propane/LP gas company
6. Clean ODS/pilot (see
Cleaning and Mainte­nance, Page 20) or re-
place ODS/pilot assembly
7. Replace gas regulator
SuperiorFireplaces.us.com
126842-01B22
Page 23
TROUBLESHOOTING
Continued
OBSERVED PROBLEM POSSIBLE CAUSE REMEDY
ODS/pilot lights but fl ame goes out when control knob is released
Burner does not light after ODS/pilot is lit
1. Control knob not fully pressed in
2. Control knob not pressed in long enough
3. Equipment shutoff valve not fully open
4. Pilot flame not touching thermocouple, which al­lows thermocouple to cool, causing pilot fl ame to go out. This problem could be caused by one or both of the following:
A) Low gas pressure B) Dirty or partially clogged
ODS/pilot
5. Thermocouple connection loose at control valve
6. Thermocouple damaged
7. Control valve damaged
1. Burner orifi ce clogged
2. Inlet gas pressure is too low
1. Press in control knob fully
2. After ODS/pilot lights, keep control knob pressed in 30 seconds
3. Fully open equipment shutoff valve
4. A) Contact local natural or propane/LP gas com­pany
B) Clean ODS/pilot (see
Cleaning and Mainte­nance, Page 20) or re-
place ODS/pilot assembly
5. Hand tighten until snug, then tighten 1/4 turn more
6. Replace pilot assembly
7. Replace control valve
1. Clean burner (see Clean-
ing and Maintenance,
Page 20) or replace burner orifi ce
2. Contact local natural or propane/LP gas company
Delayed ignition of burner 1. Manifold pressure is too
low
2. Burner orifi ce clogged
Burner backfiring during combustion
1. Burner orifi ce is clogged or damaged
2. Damaged burner
3. Gas regulator defective
1. Contact local natural or propane/LP gas company
2. Clean burner (see Clean-
ing and Maintenance,
Page 20) or replace burner orifi ce
1. Clean burner (see Clean-
ing and Maintenance,
Page 20) or replace burner orifi ce
2. Replace damaged burner
3. Replace gas regulator
126842-01B 23
SuperiorFireplaces.us.com
Page 24
TROUBLESHOOTING
Continued
OBSERVED PROBLEM POSSIBLE CAUSE REMEDY
Slight smoke or odor during initial operation
Moisture/condensation no­ticed on windows
Heater produces a whistling noise when burner is lit
1. Not enough air
2. Gas regulator defective
3. Residues from manufac­turing processes and log curing
1. Not enough combustion/ ventilation air
1. Turning control knob to HI position when burner is cold
2. Air in gas line
3. Air passageways on heat­er blocked
4. Dirty or partially clogged burner orifi ce
1. Check burner for dirt and debris. If found, clean burner (see Cleaning and
Maintenance, Page 20)
2. Replace gas regulator
3. Problem will stop after a few hours of operation
1. Refer to Air for Combus- tion and Ventilation re­quirements (Page 6)
1. Turn control knob to LO position and let warm up for a minute
2. Operate burner until air is removed from line. Have gas line checked by local natural or propane/LP gas company
3. Observe minimum instal­lation clearances (see
Page 10)
4. Clean burner (see Clean­ing and Maintenance,
Page 20) or replace burn- er orifi ce
White powder residue form­ing within burner box or on adjacent walls or furniture
Heater produces a clicking/ ticking noise just after burner is lit or shut off
1. When heated, vapors from furniture polish, wax, carpet cleaners, etc. may turn into a white powder residue
1. Metal expanding while heating or contracting while cooling
1. Turn heater off when us­ing furniture polish, wax, carpet cleaners or similar products
1. This is normal with most heaters. If noise is exces­sive, contact qualifi ed ser- vice person
SuperiorFireplaces.us.com
126842-01B24
Page 25
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re department.
IMPORTANT: Operating heater where impurities in air exist may create odors. Cleaning sup- plies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These fumes may mix with combustion air and create odors. These odors will disappear over time.
OBSERVED PROBLEM POSSIBLE CAUSE REMEDY
Heater produces unwanted odors
Heater shuts off in use (ODS operates)
Gas odor even when control knob is in OFF position
Gas odor during combustion 1. Foreign matter between
1. Heater burning vapors from paint, hair spray, glues, cleaners, chemi­cals, new carpet, etc. (See IMPORTANT statement above)
2. Low fuel supply (propane/ LP only)
3. Gas leak. See Warning
statement above
1. Not enough fresh air is available
2. Low line pressure
3. ODS/pilot is partially clogged
1. Gas leak. See Warning
statement above
2. Control valve defective
control valve and burner
2. Gas leak. See Warning
statement above
1.
Open window and ven­tilate room. Stop using odor causing products while heater is running
2. Refill supply tank (pro­pane/LP only)
3. Locate and correct all leaks (see Checking Gas
Connections, Page 15)
1. Open window and/or door for ventilation
2. Contact local natural or propane/LP gas company
3. Clean ODS/pilot (see
Cleaning and Mainte­nance, Page 20)
1. Locate and correct all leaks
(see Checking Gas Con­nections, Page 15)
2. Replace control valve
1. Take apart gas tubing and remove foreign matter
2. Locate and correct all leaks
(see Checking Gas Con­nections, Page 15)
126842-01B 25
SuperiorFireplaces.us.com
Page 26
PARTS
VARIABLE MANUALLY-CONTROLLED BURNER SYSTEMS VS1824NM AND VS1824PM
CAT. NO. MODEL
F0069 VS1824NM F0070 VS1824PM
4
1
WARNING: Failure to position the parts in ac­cordance with these diagrams or failure to use only parts specifi cally approved with this heater may result in property damage or personal injury.
15
3
8
14
5
13
7
15
10
14
16
11
12
15
9
2
SuperiorFireplaces.us.com
126842-01B26
Page 27
PARTS
This list contains replaceable parts used in your heater. When ordering parts, follow the in­structions listed under Replacement Parts on Page 29 of this manual.
KEY
NO. PART NO. DESCRIPTION QTY.
1 ** Log Base 1 2 J5536 Cast Iron Grate 1 3 J5523 Pilot Bracket 1 4 J5963 Single Yellow Flame Burner 1 5 J5529 ODS Pilot, NG 1
J5527 ODS Pilot, LP 1 6 J5521 Regulator Bracket 1 7 J3652 Gas Regulator, NG 1
J3653 Gas Regulator, LP 1 8 J5768 Manual Valve with Igniter, NG 1
J5769 Manual Valve with Igniter, LP 1 9 J5767 Manual Valve Outlet Tube 1
10 J5770 Natural Gas Plate 1 11 J4015 Orifi ce 0.099 1
J4016 Orifi ce 0.057 1
12 J3579 Control Knob 1 13 J3634 Pilot Tube 1 14 J1958 HWH AB 8-18 x 0.38 Screw 1 15 F3327 HWH AB 10-16 x 0.38 Screw 8 16 J3573 HWH AB 6-20 x 0.25 Screw 2
PARTS AVAILABLE — NOT SHOWN
J3658 Warning Plate 1
J3688
Lighting Instructions Plate J3662 Caution Decal 1 J3719 Control Position Decal 1 J3689 Hardware Kit 1 80L42 Volcanic stone 1
** Not a fi eld replaceable part.
VS1824NM
VS1824PM
•• 1
126842-01B 27
SuperiorFireplaces.us.com
Page 28
LVS18-VO AND LVS24-VO LOGS
PARTS
4
(24" Models)
3
4
(18" Models)
2
5
1
KEY
NO. PART NO. DESCRIPTION QTY.
LVS18-VO
LVS24-VO
1 F3329 Front Log 1
J6081 Front Log 1
2 J6080 Rear Log 1
F3333 Rear Log 1
3 F3330 Left Crossover Log 1
F3334 Left Crossover Log 1
4 F3331 Center Crossover Log 1
F3335 Center Crossover Log 1
5 F3332 Right Crossover Log 1
F3336 Right Crossover Log 1
SuperiorFireplaces.us.com
126842-01B28
Page 29
SPECIFICATIONS
Models VS1824PM
• Rating (Variable): 16,000/23,000 Btu/Hr
• Gas Type: Propane/LP
• Ignition: Piezo
• Manifold Pressure: 8.0" W.C.
• Inlet Gas Pressure (in. of water): Maximum 14" W.C., Minimum 11"* W.C.
• Shipping Weight: 27 lbs. *For purpose of input adjustment
REPLACEMENT PARTS
See Pages 26-28 for a complete replacement parts list. Use only parts supplied from the manufacturer.
Normally, all parts should be ordered through your IHP distributor or dealer. Parts will be shipped at prevailing prices at time of order.
NEVER USE SUBSTITUTE MATERIALS. USE OF NON-APPROVED PARTS CAN RESULT IN POOR PERFORMANCE AND SAFETY HAZARDS.
Models VS1824NM
• Rating (Variable): 16,000/26,000 Btu/Hr
• Gas Type: Propane/LP
• Ignition: Piezo
• Manifold Pressure: 8.0" W.C.
• Inlet Gas Pressure (in. of water): Maximum 14" W.C., Minimum 11"* W.C.
• Shipping Weight: 27 lbs.
When ordering repair parts, always give the follow­ing information:
1. The model number of the appliance.
2. The serial number of the appliance.
3. The part number.
4. The description of the part.
5. The quantity required.
6. The installation date of the appliance. If you encounter any problems or have any ques­tions concerning the installation or application of this appliance, please contact your dealer.
SERVICE HINTS
When Gas Pressure Is Too Low
• pilot will not stay lit
• burners will have delayed ignition
• appliance will not produce specifi ed heat
• propane/LP gas supply may be low You may feel your gas pressure is too low. If
so, contact your local propane/LP or natural gas supplier.
TECHNICAL SERVICE
You may have further questions about instal­lation, operation, or troubleshooting. Please contact your IHP dealer for any questions or concerns. When contacting your dealer please have your model and serial numbers of your appliance ready. You can also visit our web site at SuperiorFireplaces.us.com.
126842-01B 29
SuperiorFireplaces.us.com
Page 30
ACCESSORIES
Purchase these appliance accessories from your local dealer. If they can not supply these accessories, contact IHP at SuperiorFire­places.us.com for referral information. You can also write to the address listed on the back page of this manual.
Only kits supplied by IHP shall be used in the installation of this appliance. Use of non-approved accessory/part kit(s) can result in poor performance and safety hazards.
FIREPLACE HOOD, BLACK
Cat. No. F1764, Model GA6050 For all models. Helps de ect heat away from
mantel or wall above fi replace. Fits openings 28" to 48" wide.
VOLCANIC STONE
Cat. No. 80L42, Model FDVS For all models. Order when additional volca-
nic stone is desired.
FLOOR MEDIA KIT
Cat. No. F1762, Model FM100 For all models. Includes volcanic stone,
burner embers, and burner cinders
DECORATIVE ASH BED / CONTROL COVER KIT (SIX PACK)
Cat. No. F1759, Model CDABKA-6
DECORATIVE ASH BED / CONTROL COVER KIT
Cat. No. F0246, Model CDABKA
Damper Clamp
Damper
DAMPER CLAMP
(Required in vented applications) Cat. No. F1760, Model GA6080 For all models. Per ma nent ly opens chim ney
ue damper for vent ed operation. This is included with all models.
GAS APPLIANCE INSTALLATION KIT
Cat. No. F0249, Model CIKA
SuperiorFireplaces.us.com
126842-01B30
Page 31
ACCESSORIES
Continued
LOG SCRAPS / FLOOR MEDIA KIT-1
Cat. No. F0250, Model VTA-LS5-1
WALL-MOUNT THERMOST A T SWITCH
Cat. No. F2040, Model GWMT1 For all models. The desired comfort setting
can be selected on the wall thermostat and the log heater will automatically cycle from pilot to the heat setting selected. Includes thermostat assembly, 25' of wire and two mounting screws.
LOG SCRAPS / FLOOR MEDIA KIT-2
Cat. No. F0251, Model VTA-LS5-2
WALL-MOUNT ON/OFF SWITCH
Cat. No. F0245, Model GWMS2 For all models. Allows the gas log heater to
be turned on and off with a wall switch.
126842-01B 31
SuperiorFireplaces.us.com
Page 32
NOTES
______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
32
Page 33
NOTES
______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
33
Page 34
NOTES
______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
34
Page 35
Innovative Hearth Products
Superior
®
Brand Gas Log Set
Limited Three Year Warranty
THE WARRANTY
Innovative Hearth Products Limited Three Year Warranty ("IHP") warrants your Superior® brand Gas Log Set ("Product") to be free from defects in materials and workmanship at the time of manufacture. The logs and grate carry the Limited Three Year Warranty. After installation, if covered components manufactured by IHP are found to be defec­tive in materials or workmanship during the Limited Three Year Warranty period and while the Product remains at the site of the original installation, IHP will, at its option, repair or replace the covered components. If repair or replacement is not commercially practical, IHP will, at its option, refund the purchase price or wholesale price of the IHP product, whichever is applicable. IHP will also pay IHP prevailing labor rates, as determined in its sole discretion, incurred in repairing or replacing such components. THERE ARE EXCLUSIONS AND LIMITATIONS to this Limited Three Year Warranty as described herein.
COVERAGE COMMENCEMENT DATE
Warranty coverage begins on the date of purchase. In the case of new home construction, warranty coverage begins on the date of fi rst occupancy of the dwelling or six months after the sale of the Product by an independent IHP dealer, whichever occurs earlier. The warranty shall commence no later than 24 months following the date of product shipment from IHP, regardless of the installation or occupancy date.
EXCLUSIONS AND LIMITATIONS
This Limited Three Year Warranty applies only if the Product is installed in the United States or Canada and only if operated and maintained in accordance with the printed instructions accompanying the Product and in compliance with all applicable installation and building codes and good trade practices.
This warranty is non-transferable and extends to the original owner only. The Product must be purchased through a listed supplier of IHP and proof of purchase must be provided. The following do not carry the Limited Three Year Warranty but are warranted as follows:
Gas components – Repair or replacement for one year from the date of installation. Remote control – Repair or replacement for one year from the date of installation. Labor coverage – Prevailing IHP labor rates apply for the warranty period of the component.
Parts not otherwise listed carry a 90 day warranty from the date of installation.
Whenever practicable, IHP will provide replacement parts, if available, for a period of 10 years from the last date of manufacture of the product.
IHP will not be responsible for: (a) damages caused by normal wear and tear, accident, riot, fi re, fl ood or acts of God; (b) damages caused by abuse, negligence, misuse, or unauthorized alteration or repair of the Product affecting its stability or performance (The Product must be subjected to normal use. The Product is designed to burn either natural or propane gas only. Burning conventional fuels such as wood, coal or any other solid fuel will cause damage to the Product, will produce excessive temperatures and could result in a fi re hazard.); (c) damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product; (d) damages, repairs or ineffi ciency resulting from faulty installation or application of the Product.
This Limited Three Year Warranty covers only parts and labor as provided herein. In no case shall IHP be responsible for materials, components or construction which are not manufactured or supplied by IHP or for the labor necessary to install, repair or remove such materials, components or construction. Additional utility bills incurred due to any malfunction or defect in equipment are not covered by this warranty. All replacement or repair components will be shipped F.O.B. from the nearest stocking IHP factory.
LIMITATION ON LIABILITY
It is expressly agreed and understood that IHP’s sole obligation and the purchaser’s exclusive remedy under this warranty, under any other warranty, expressed or implied, or in contract, tort or otherwise, shall be limited to replacement, repair, or refund, as specifi ed herein.
In no event shall IHP be liable for any incidental or consequential damages caused by defects in the Product, whether such damage occurs or is discovered before or after replacement or repair, and whether such damage is caused by IHP’s negligence. IHP has not made and does not make any representation or warranty of fi tness for a particular use or purpose, and there is no implied condition of fi tness for a particular use or purpose.
IHP makes no expressed warranties except as stated in this Limited Three Year Warranty. The duration of any implied warranty is limited to the duration of this expressed warranty.
No one is authorized to change this Limited Three Year Warranty or to create for IHP any other obligation or liability in connection with the Product. Some states and provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. The provisions of this Limited Three Year Warranty are in addition to and not a modifi cation of or subtraction from any statutory warranties and other rights and remedies provided by law.
INVESTIGATION OF CLAIMS AGAINST WARRANTY
IHP reserves the right to investigate any and all claims against this Limited Three Year Warranty and to decide, in its sole discretion, upon the method of settlement.
To receive the benefi ts and advantages described in this Limited Three Year Warranty, the appliance must be installed and repaired by a licensed contractor approved by IHP.
Contact IHP at the address provided herein to obtain a listing of approved dealers/distributors. IHP shall in no event be responsible for any warranty work done by a
contractor that is not approved without fi rst obtaining LHP's prior written consent.
HOW TO REGISTER A CLAIM AGAINST WARRANTY
In order for any claim under this warranty to be valid, you must contact the IHP dealer/distributor from which you purchased the product. If you cannot locate the dealer/ distributor, then you must notify IHP in writing. IHP must be notifi ed of the claimed defect in writing within 90 days of the date of failure. Notices should be directed to the IHP Warranty Department at 1508 Elm Hill Pike, Suite 108; Nashville, TN 37210 or visit our website at WWW.SUPERIORFIREPLACES.US.COM.
Printed in U.S.A. © 2014 Innovative Hearth Products
P/N 900247-00, Rev. A, 10/2015
Innovative Hearth Products 1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210
35
Page 36
SuperiorFireplaces.us.com
Record the following important information about your appliance:
Appliance model number
Appliance serial number
Date appliance was Installed
Type of gas appliance uses
Dealer name
IHP reserves the right to make changes at any time, without notice, in design, materials, specifi cations, prices and also to discontinue colors, styles and products. Consult your local distributor for fi replace code information.
Printed in U.S.A. © 2014 Innovative Hearth Products P/N 126842-01 Rev. B 05/2017
P126842-01
1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210
Loading...