Ce manuel est disponible en francais,
simplement en faire la demande. Numéro
de la pièce 127029-02.
P127029-01
PFS
®
USC
Report No. F09-130
Models
VRE4536WS
VRE4536WH
VRE4542WS
VRE4542WH
VRE4550WS
VRE4550WH
SAVE THIS BOOK
This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information
that will enable you to obtain replacement parts or accessory items when needed. Keep it with your other important papers.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information
consult a qualifi ed installer, service agency or the gas supplier.
This fi replace is approved for use on an outdoor application provided that a certifi ed gas log set approved under the
With Refractory Panels
ANSI Z21.97 standard with a maximum input rate of 40,000 BTU's is used.
a vent-free log heater (see Parts, Page 17).
An IHP hood must be installed when using
DO NOT INSTALL THE APPLIANCE IN THIS FIREBOX, UNLESS THIS FIREBOX MEETS THE MINIMUM DIMENSIONS
REQUIRED FOR THE INSTALLATION.
WARNING: FOR USE ONLY WITH A LISTED, GAS-FIRED UNVENTED DECORATIVE ROOM HEATER NOT TO EXCEED
40,000 BTU/H.
DO NOT BUILD A WOOD FIRE.
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could
result in serious injury, death, or property damage.
AVERTISSEMENT:
RISQUED’INDENDIE OU D’EXPLOSION
Le non-respect Des avertissements de sécurité pourrait
d’entraîner des blessures graves, la mort ou des dommages matériels.
- Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any
other appliance.
- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the
fi re department.
- Installation and service must be performed by
a qualifi ed installer, service agency or the gas
supplier.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs
ou liquides infl ammables dans le voisinage de cet appareil
ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Sortez immédiatement de bâtiment.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez
le service des incindies.
- L’installation et l’entretien doivent être assurés par un
installateur ou un service d’entretien qualifi é ou par le
fournisseur de gaz.
Page 2
Thank you for your purchase. We appreciate your
business!
Please carefully read and follow all instructions in this manual. Pay
special attention to all warnings and safety information.
Following these safety, care, and operation instructions will help
ensure many years of dependable and enjoyable service from your
fi replace.
Please read and understand these instructions before installing
or operating.
NOTICE: The fi rebox canopy must not be modifi ed or
replaced with a canopy that may be provided with the
unvented decorative room heater.
IMPORTANT: Read this owner’s manual carefully and
completely before trying to assemble, operate or
service this fi replace. Improper use of this fi replace
can cause serious injury or death from burns, fi re,
explosion, electrical shock and carbon monoxide
poisoning.
DANGER: Carbon monoxide poisoning may lead
to death!
WARNING: Any change to this heater or its controls
can be dangerous.”
WARNING: Do not allow fans to blow directly into
the fi rebox. Avoid any drafts that alter burner fl ame
patterns. Ceiling fans can create drafts that alter
burner fl ame patterns. Altered burner patterns can
cause sooting.
WARNING: Do not use a blower insert, heat
exchanger insert or other accessory not approved for
use with this fi rebox.
Due to high temperatures, the appliance should be
located out of traffi c and away from furniture and
draperies.
Do not place clothing or other fl ammable material on
or near the appliance. Never place any objects in the
fi rebox or on logs.
Firebox front and screen becomes very hot when
running fi rebox. Keep children and adults away from
hot surfaces to avoid burns or clothing ignition.
Firebox will remain hot for a time after shutdown.
Allow surfaces to cool before touching.
Keep the fi replace area clear and free from combustible
materials, gasoline, and other fl ammable vapors and
liquids.
You must operate this fi replace with the provided
fi replace screen and hood in place. Make sure these
parts are in place and screens are closed before
running installed gas log heater. Replace hood with
IHP catalog no. (J4353) 50", (J4354) 42", or (J4355)
36" only. This hood has been designed to keep the
operation of your fi replace safe and effi cient.
WARNING: If the information in this manual is not
followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of live
Children and adults should be alerted to the hazard
of high surface temperature and should stay away to
avoid burns or clothing ignition.
Young children should be carefully supervised when
they are in the same room with the appliance.
SuperiorFireplaces.US.com127029-01D2
Page 3
SAFETY Continued
Installation and repair should be done by a qualifi ed
service person. The appliance should be inspected
before use and at least annually by a professional
service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding
material, etc. It is imperative that control compartments, burners and circulating air passageways of
the appliance be kept clean.
1. Do not use this fi rebox as a wood burning fi replace. Use only
decorative unvented room heaters (log sets).
2. Do not add extra logs or ornaments such as pine cones, vermiculite
or rock wool. Using these added items can cause sooting.
3. Use only the provided hood. See Parts, Page 15.
4. Vent-free gas log heaters installed in these fi reboxes require
fresh air ventilation to run properly. See Air for Combustion and
Ventilation, Page 7.
5. Do not run vent-free heaters installed in these fi reboxes
• where fl ammable liquids or vapors are used or stored
• under dusty conditions
6. Do not use this fi rebox to cook food or burn paper or other objects.
7. Turn unit off and let cool before servicing. Only a qualifi ed service
person should service and repair fi rebox.
8. Operating vent-free heaters installed in these fi reboxes above
elevations of 4,500 feet could cause pilot outage.
9. Do not use the fi rebox if it has been under water.
10. Before using furniture polish, wax, carpet cleaner or similar
products, turn heater off. If heated, the vapors from these
products may create a white powder residue within burner box
or on adjacent walls and furniture.
11. Provide adequate clearances around air openings.
LOCAL CODES
Install and use fi rebox with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas
Code ANSI Z223.1/NFPA 54*; National Fuel Gas Code; Natural Gas
and Propane Installation Code, CSA B149.1; or Propane Storage and
Handling Code, CSA B149.2, as applicable. Firebox must be electrically grounded in accordance with the National Electrical Code, ANSI/
NFPA 70 (latest edition).
*Available from:
American National Standards Institute, Inc.
25 West 43rd Street, 4th fl oor
New York, NY 10036
National Fire Protection Association, Inc.
1 Batterymarch Park
Quincy, MA 02169-7471
PRODUCT FEATURES
OPERATION
This fi rebox is designed for use with approved ANSI Z21.11.2 decorative type unvented room heaters. (Physical size limitations apply.
Refer to minimum fi rebox requirements supplied with log heater.)
It requires no outside venting or chimney making installation easy
and inexpensive.
COMMONWEALTH OF MASSACHUSETTS REQUIREMENTS
These appliances are approved for installation in the US state of
Massachusetts if the following additional requirements are met:
• Un-vented Room Heaters shall be installed in accordance with
527 CMR 30.
• Installation and repair must be done by a plumber or gas fi tter
licensed in the Commonwealth of Massachusetts.
• The fl exible gas line connector used shall not exceed 36 inches
(92 centimeters) in length.
• The individual manual shut-off must be a T-handle type valve.
• Unvented appliances may NOT be installed in bedrooms or
bathrooms.
• A working smoke detector must be installed in the area where
vent-free appliances are installed.
Seller of unvented propane or natural gas-fi red supplemental room
heaters shall provide to each purchaser a copy of 527 CMR 30 upon
sale of the unit.
LOCATING FIREBOX
PLANNING
Plan where you will install the fi rebox. This will save time and money
later when you install the fi rebox. Before installation, consider the
following:
1. Where fi rebox will be located. Allow for wall and ceiling clearances
(see Installation Clearances, Page 9).
2. Everything needed to complete installation.
3. These models CANNOT be installed in a bedroom unless maximum
Btu rating of installed vent-free log set is less than 10,000 Btu/hr.
4. Proper air for combustion and ventilation (Page 7).
OUTDOOR ENCLOSURE REQUIREMENTS
Must conform to one of the following conditions:
• With walls on all sides, but with no overhead cover;
• Within a partial enclosure which includes an overhead cover and
no more than two side walls. These side walls may be parallel,
as in breezeway or at right angles to each side; or
• Within a partial enclosure which includes an overhead cover
and three sidewalls, as long as 30% or more of the horizontal
periphery of the enclosure is permanently open.
WARNING: This fi rebox shall not be installed in a
room or space unless the required volume of indoor
combustion air is provided by the method described in
the National Fuel Gas Code, ANSI Z223.1/NFPA 54, the
International Fuel Gas Code, or applicable local codes.
Read the following instructions to ensure proper fresh air
for this and other fuel-burning appliances in your home.
Today’s homes are built more energy effi cient than ever. New materials,
increased insulation and new construction methods help reduce heat
loss in homes. Homeowners apply weather strip and caulk around
windows and doors to keep the cold air out and the warm air in. During
heating months, homeowners want their homes as airtight as possible.
While it is good to make your home energy effi cient, your home needs
to breathe. Fresh air must enter your home. All fuel-burning appliances
need fresh air for proper combustion and ventilation.
Exhaust fans, some fi replaces, clothes dryers and some fuel-burning
appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will ensure proper venting
of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/
NFPA 54, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation
classifi cations:
1. Unusually Tight Construction
2. Unconfi ned Space
3. Confi ned Space
The information on Pages 7 through 8 will help you classify your space
and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough
fresh air for combustion and ventilation. However, in buildings of
unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defi ned as construction where:
a. walls and ceilings exposed to the outside atmosphere have a
continuous water vapor retarder with a rating of one perm (6 x
-11
10
kg per pa-sec-m2) or less with openings gasketed or sealed
and
b. weather stripping has been added on openable windows and
doors and
c. caulking or sealants are applied to areas such as joints around
window and door frames, between sole plates and fl oors, between wall-ceiling joints, between wall panels, at penetrations
for plumbing, electrical and gas lines and at other openings.
If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, Page 8.
If your home does not meet all of the three criteria above, proceed
to Determining Fresh-Air Flow For Firebox Location.
Confi ned and Unconfi ned Space
The National Fuel Gas Code, ANSI Z223.1/ NFPA54 allows two methods for determining whether the space in which the heater is being
installed is confi ned or unconfi ned space. The standard method
defi nes a confi ned space as a space whose volume is less than 50
SuperiorFireplaces.US.com127029-01D7
cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate
input rating of all appliances installed in that space and an unconfi ned
space as a space whose volume is not less than 50 cubic feet per
1,000 Btu per hour (4.8 m
appliances installed in that space. Rooms communicating directly with
the space in which the appliances are installed*, through openings not
furnished with doors, are considered a part of the unconfi ned space.
Where the air infi ltration rate of a structure is known, the Known Air
Infi ltration Rate Method may be used. Follow The National Fuel Gas
Code, ANSI Z223.1/NFPA 54 to use this method to determine if the
space is confi ned or unconfi ned.
* Adjoining rooms are communicating only if there are doorless
passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR FIREBOX LOCATION
Determining if You Have a Confi ned or Unconfi ned Space Using
the Standard Method
Use this work sheet to determine if you have a confi ned or unconfi ned space.
Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between
the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height =__________cu. ft. (volume of space)
Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling
height) = 3,168 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills
or openings, add the volume of these rooms to the total volume
of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr
the space can support.
_______ (volume of space) x 20 = (Maximum Btu/Hr the space
can support)
Example: 3,168 cu. ft. (volume of space) x 20 = 63,360 (maximum
Btu/Hr space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free fi replace ________ Btu/Hr
Gas water heater* ________ Btu/Hr
Gas furnace ________ Btu/Hr
Vented gas heater ________ Btu/Hr
Gas fi replace logs ________ Btu/Hr
Other gas appliances*+ _____ Btu/Hr
Total = _______ Btu/Hr
* Do not include direct-vent gas appliances. Direct-vent draws
combustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater 40,000 Btu/Hr
Vent-free fi replace + 39,000 Btu/Hr
Total = 79,000 Btu/Hr
4. Compare the maximum Btu/Hr the space can support with the
actual amount of Btu/Hr used.
______ Btu/Hr (maximum the space can support)
______ Btu/Hr (actual amount of Btu/Hr used)
Example: 63,360 Btu/Hr (maximum the space can support)
79,000 Btu/Hr (actual amount of Btu/Hr used)
3
per kw) of the aggregate input rating of all
Page 8
AIR FOR COMBUSTION AND VENTILATION continued
A
The space in the example is a confi ned space because the actual Btu/
Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the
extra space provides an unconfi ned space, remove door to adjoining
room or add ventilation grills between rooms. See Ventilation Air
From Inside Building.
B. Vent room directly to the outdoors. See Ventilation Air From
Outdoors.
C. Install a lower Btu/Hr fi replace, if lower Btu/Hr size makes room
unconfi ned.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space
can support, the space is an unconfi ned space. You will need no additional fresh air ventilation.
WARNING: If the area in which the heater may be
operated does not meet the required volume for indoor
combustion air, combustion and ventilation air shall
be provided by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, the
International Fuel Gas Code, or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfi ned space. When
ventilating to an adjoining unconfi ned space, you must provide two
permanent openings: one within 12" of the ceiling and one within 12"
of the fl oor on the wall connecting the two spaces (see options 1 and
2, Figure 4). You can also remove door into adjoining room (see option
3, Figure 4). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA
54, Air for Combustion and Ventilation for required size of ventilation
grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the fl oor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, Air for Combustion and Ventilation for required size of
ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet or outlet air
into attic if attic has a thermostat-controlled power vent.
Heated air entering the attic will activate the power vent.
Outlet
Air
Outlet
ir
Inlet
Air
Inlet Air
Figure 5 - Ventilation Air from Outdoors
Ventilated
Attic
To Attic
To
Crawl
Space
Ventilated
Crawl Space
12"
Ventilation
Grills Into
Adjoining
Room,
Option 1
Or
Remove
Door into
Adjoining
Room,
Option
3
Figure 4 - Ventilation Air from Inside Building
Ventilation Grills
Into Adjoining Room,
Option 2
12"
SuperiorFireplaces.US.com127029-01D8
Page 9
INSTALLATION
WARNING: A qualifi ed service person must install
fi rebox. Follow all local codes.
WARNING: Never install fi rebox
• in a bedroom or bathroom*
• in a recreational vehicle
• where curtains, furniture, clothing, or other fl ammable objects are less than 36" from front or 42"
from top of fi rebox; for side clearances see Figure 6
• in high traffi c areas
• in windy or drafty areas
* Unless installed log set is rated at 10,000 Btu/Hr or
less, 6,000 for bathrooms
CAUTION: Log heaters installed in this fi rebox create warm air currents. These currents move heat to
wall surfaces next to fi rebox. Installing fi rebox next to
vinyl or cloth wall coverings or operating fi rebox where
impurities (such as, but not limited to, tobacco smoke,
aromatic candles, cleaning fl uids, oil or kerosene lamps,
etc.) in the air exist, may discolor walls or cause odors.
NOTICE: The fi rebox identifi cation label (including
model number, serial number, clearances, etc.) is
located on a chain under the bottom refractory.
INSTALLATION CLEARANCES
WARNING: Maintain the minimum clearances. If
you can, provide greater clearances from fl oor, ceiling, and adjoining wall.
Carefully follow the instructions below. This will ensure safe installation.
Minimum Wall and Ceiling Clearances (see Figure 6)
A. Clearances from the side of the fi replace cabinet to any combus-
tible material and wall should follow diagram in Figure 6.
Example: The face of a mantel, bookshelf, etc. is made of combus-
tible material and protrudes 3-1/2" from the wall. This combustible
material must be 4" from the side of the fi replace cabinet (see
Figure 4, Page 8).
B. Clearances from the top of the fi rebox opening to the ceiling should
not be less than 42".
C. When fi rebox is installed on carpeting, tile (vinyl) or other com-
bustible material, other than wood fl ooring, the fi rebox should be
installed on a metal or wood panel extending the full width and
depth of the enclosure.
D. Clearances from the bottom of fi rebox to the fl oor is 0".
These fi reboxes can be installed as freestanding units against a
wall with approved cabinet mantels that may be available from your
retailer or supplier, or as a built-in unit. The clearances are the same
for either installation method.
IMPORTANT: Vent-free gas log heaters add moisture to the air. Although this is benefi cial, installing fi rebox in rooms without enough
ventilation air may cause mildew to form from too much moisture.
See, Page 7.
IMPORTANT: Make sure the fi rebox is level. If fi rebox is not level, log
set will not work properly.
NOTE: Your fi rebox is designed to be used in zero clearance installations. Wall or framing material can be placed against any exterior
surface on the rear, sides, top or bottom of your fi rebox, except
where standoff spacers are integrally attached. If standoff spacers
are attached to your fi rebox, these spacers can be placed directly
against wall or framing materials. Use the dimensions shown for
rough opening to create the easiest installation.
Use dimensions shown for rough openings to create the easiest
installation (see Built-In Firebox Installation, Page 10).
Example
*
*Minimum 16" from Side Wall
Figure 6 - Minimum Clearance for Combustible to Wall
SuperiorFireplaces.US.com127029-01D9
Page 10
2
INSTALLATION continued
Mantel Clearances for Built-In Installation
If placing custom mantel above built-in fi rebox, you must meet
the minimum allowable clearance between mantel shelf and top of
fi rebox opening shown in Figure 7. These are the minimum allowable mantel clearances for a safe installation. Use larger clearances
wherever possible to minimize the heating of objects and materials
placed on the mantel.
CAUTION: Do not allow the vent-free gas log heater
to touch or extend beyond the fi replace screen.
NOTICE: Surface temperatures of adjacent walls and
mantels become hot during operation. Walls and
mantels above the fi rebox may become hot to the
touch. If installed properly, these temperatures meet
the requirement of the national product standard. Follow all minimum clearances shown in this manual.
Wall board or facing
material (above
firebox) may be of
combustible material,
including decorative
mantel ornaments or
other similar projections off of the facing
material.
Framing
Material
Firebox
Wire-mesh
Screen
12"
6
1
Supplied
Firebox Hood
Must Be Used
at All Times
Mantel Shelf
Note: Any portion of the
mantel shelf must NOT
extend beyond this profile.
3
/
4
"
1
/
2
"
Noncombustible
Material May
Project Off this
Surface above
the Firebox Hood
Note: All vertical
measurements are
from top of fireplace
hood opening to
bottom of mantel shelf.
These minimum
clearances replace any
other recommended
clearances supplied
with your ANSI Z21.11.
approved gas logs.
12" 16" 20"
BUILT-IN FIREBOX INSTALLATION
Built-in installation of this fi rebox involves installing fi rebox into a
framed-in enclosure. This makes the front of fi rebox fl ush with wall. If
installing a mantel above the fi rebox, you must follow the clearances
shown in Figure 7. Follow these instructions to install the fi rebox in
this manner.
1. Frame in rough opening. The fi rebox framing should be constructed
of 2 x 4 lumber or heavier. Use dimensions and rough opening layout
in Figure 8. Adjust framing so that fi rebox fl ushes with fi nished
wall surface. If installing in a corner, use dimensions in Figure 9,
for rough opening.
2. Install gas piping to fi rebox location. See Gas Line Installation on
Page 13 and Connecting to Gas Supply in log set owner’s manual.
54-5/8"
1
/8"
3
45-
/8" (36" Models)
3
/8" (42" Models)
51-
3
/8" (50" Models)
59-
30-
1
/4"
28-
(36" Models)
Figure 8 - Framing Dimensions
Maintain 1-1/2"
Clearance at Sides
and Back of Fireplace
Figure 7 - Minimum Mantel Clearances for Built-In Installation
NOTICE: If your installation does not meet the minimum
clearances shown, you must do one of the following:
• raise the mantel to an acceptable height
• remove the mantel
SuperiorFireplaces.US.com127029-01D10
1
/2" (36" Models)
8692" (42" Models)
100" (50" Models)
Figure 9 - Corner Installation
3. Carefully set fi rebox in front of rough opening with back of fi rebox
inside wall opening.
4. Carefully insert fi rebox into rough opening.
5. Attach fi rebox to wall studs using nails or wood screws through
holes in nailing fl ange (see Figure 10, Page 11).
6. Install and properly test gas log heater. Follow installation instructions included with the vent-free gas log heater that is being
installed.
Page 11
INSTALLATION continued
IMPORTANT: When fi nishing your fi rebox, combustible materials such
as wall board, gypsum board, sheet rock, drywall, plywood, etc. may
be butted up next to the sides and top of the fi rebox. Combustible
materials should never overlap the fi rebox front facing.
WARNING: Do not allow any combustible materials
to overlap the fi rebox front facing.
IMPORTANT: Noncombustible materials such as brick, tile, etc.
may overlap the front facing, but should never cover any necessary
openings.
WARNING: Do not allow noncombustible materials
to cover any necessary openings.
Nails or
Wood
Screws
1. Assemble cabinet mantel as instructed.
2. Install gas piping to fi rebox location. See Gas Line Installation on
Page 11. You may have to cut an access hole in the fl oor or wall to
run gas line to fi rebox. Make sure to locate access hole so cabinet
mantel will cover it when installed (see Figure 11).
3. Place fi rebox on fl oor in desired location. Make sure mantel will
be fl ush against wall when installed.
4. Carefully slide cabinet mantel over fi rebox. Be careful not to
scratch fi rebox, cabinet mantel, fl ooring, etc., when installing
(see Figure 12).
5. Install and properly test gas log heater. Follow installation instructions included with the vent-free gas log heater that is being
installed.
Cabinet
Mantel
Gas Line Access
Hole (Either Side
of Firebox)
Gas
Piping
Nailing
Flanges
Figure 10 - Attaching Firebox to Wall Studs
WARNING: Use only noncombustible mortar or
adhesives when overlapping the front facing with
noncombustible facing material.
INSTALLING FIREBOX USING OPTIONAL CUSTOM
BUILT MANTELS
WARNING: A qualifi ed service person must install
fi rebox. Follow all local codes.
This fi rebox may be installed using a cabinet mantel against a wall in
your home. The fi rebox and cabinet mantel can be installed directly
on the fl oor. Mantels may be available from your retailer or custom
built for your home.
Figure 11 - Installing Cabinet Mantel (Mantel May Vary From
Illustration)
Figure 12 - Inserting Firebox Into Cabinet Mantel (Mantel May Vary
From Illustration)
SuperiorFireplaces.US.com127029-01D11
Page 12
INSTALLATION Continued
K
REFRACTORY PANEL INSTALLATION
IMPORTANT: Installation of brick should be done after
the fi replace is placed in a permanent location.
1. Remove screen assemblies and all hardware components out of
the fi rebox. The bottom panel is preinstalled in the fi rebox. Make
sure the bottom refractory panels is centered in the fi rebox and
fl ush with the front of the fi replace.
2. Place cardboard on top of bottom refractory panel as a protection
to prevent shipping and scratching during installation of the other
panels.
3. Install rear refractory panel. This panel has a top and bottom. To
determine which is which, match up the pattern on the rear panel
with the left and right sides before installing the rear panel. Make
sure panel is center before continuing.
4. Install the right and left refractory panels with the gas line knockouts orientated down toward the bottom refractory. Align the left
and right panels with the rear panel so the grout lines line up.
5. Install the upper corner brackets and tighten set screws (Figure
13).
UPPER CORNER
LEFT BRICK
PANEL
BRACKET (2x)
REAR BRICK
PANEL
INSTALLING FIREPLACE HOOD AND SCREENS
1. Attach hood to fi rebox using screws provided (see Figure 14).
1. Slide round end of screen rod into rings at top of screen. Attach one
push-on nut to end of rod before attaching last ring of screen.
2. Insert the round end screen rod into hole on the left and right side
of smoke shelf (Figure 15).
3. Mount fl at end of screen rod with #10 x 5/8" to center of smoke
shelf.
4. Install other screen rod in same manner.
Screws
Figure 14 - Screw and Hood Placement
Rating
Plate
Hole for Screen
Rod
Leading
Bricks
ASH PANEL
Figure 15 - Installing Fireplace Screen
RIGHT BRIC
PANEL
BOTTOM
BRICK PANEL
Figure 13 - Installing Refractory Panels
SuperiorFireplaces.US.com127029-01D12
Page 13
INSTALLATION Continued
GAS LINE INSTALLATION
WARNING: A qualifi ed service person must connect
heater to gas supply. Follow all local codes.
IMPORTANT: See Connecting to Gas Supply in your log set owner’s
manual for details on gas hookup.
NOTE: Before you proceed, make sure your gas supply is turned off.
Use only a 1/2" black iron pipe and appropriate fi ttings.
1. Remove knockout indentation on refractory or fi rebrick wall located above refractory hearth fl oor. Knockout indentation must be
fi rmly tapped with any solid object such as a 1/2" dowel until it is
released. Remove fragmented portions of refractory (see Figure
16).
2. Remove gas line cover plate located on either side of fi replace and
pull out insulation from gas line conduit sleeve. Save insulation for
reuse. Replace screws.
3. Run a 1/2" black iron gas line into fi replace through the rear at gas
line conduit sleeve (if using a raised platform, add height). Provide
suffi cient gas line into fi replace chamber for fi tting connection (see Figure 17).
NOTE: Secure incoming gas line to wood framing to provide rigidity
for threaded end.
4. Repack insulation around gas line and into sleeve opening. Seal any
gaps between gas line and refractory knockout hole with refractory
cement or commercial furnace cement, Install the gas appliance or
cap-off gas line if desired.
A gas line or gas log lighter may be installed for the purpose of installing
a vent-free decorative gas appliance incorporating an automatic shutoff
device and complying with the Standard for Decorative Gas Appliances
for Installation in Vented Fireplaces, ANSI Z21.60 or American Gas Association draft requirements for Gas Fired Log Lighters for Wood Burning
Fireplaces, Draft No. 4 dated August, 1993.
When installing an unvented (vent-free) gas log set, only unvented
gas log sets which have been found to comply with the standard for
unvented room heaters, ANSI Z21.11.2 are to be installed in this
fi replace.
CAUTION: All gas piping and connections must be
tested for leaks after the installation is completed.
After ensuring that the gas valve is on, apply soap and
water solution to all connections and joints. Bubbles
forming show a leak. Correct all leaks at once. DO NOT
USE AN OPEN FLAME FOR LEAK TESTING AND DO NOT
OPERATE ANY APPLIANCE IF A LEAK IS DETECTED.
LEAK TESTING SHOULD BE DONE BY A QUALIFIED
SERVICE PERSON.
Outside of
Fireplace
Gas Line
Conduit
Insulation
Gas
Conduit
Cover
Outside of
Fireplace
Gas Line
Conduit
Repack
Insulation
Remove
Knockout
Figure 16 - Gas Line Access
Incoming
1/2" Black
Iron Pipe
Seal Opening
with
Refractory
Cement
Side Firebrick
Finished Side
1/2" Dowel
Brick with
Access Hole
Side Firebrick
Finished Side
Provide Enough
Threaded End for
Fitting Connection
This list contains replaceable parts used in your fi rebox. When ordering parts, follow the instructions listed under Replacement Parts on
Page 18 of this manual.
WARNING: Contact an IHP dealer to obtain any of these parts. Never use substitute materials not approved
by IHP. Use of non-approved parts can result in poor performance and safety hazards.
WARNING: Contact an IHP dealer to obtain any of these parts. Never use substitute materials not approved
by IHP. Use of non-approved parts can result in poor performance and safety hazards.
WARNING
LIFTING HAZARD
SINGLE -PERSON LIFT COULD
CAUSE INJURY.
USE ASSISTANCE WHEN MOVING
OR LIFTING.
4
5
7
6
IMPORTANT: Installation of brick panels should be
done after the fireplace is placed in a permanent
location.
6
7
3
2
4
3
5
6
1
2
1
SuperiorFireplaces.US.com127029-01D16
Page 17
PARTS
This list contains replaceable parts used in your fi rebox. When ordering parts, follow the instructions listed under Replacement Parts on
Page 18 of this manual.
KEY
NO. CAT. NO. DESCRIPTION
1F3242 WHITE STACK REFRACTORY SET, 36"•1
F3244 WHITE STACK REFRACTORY SET, 42"1
F3246 WHITE STACK REFRACTORY SET, 50"1
F3243 WHITE HERRINGBONE REFRACTORY SET, 36"1
F3245 WHITE HERRINGBONE REFRACTORY SET, 42"1
F3247 WHITE HERRINGBONE REFRACTORY SET, 50"1
2---REFRACTORY, HEARTH 36 STD WHITE••1
---REFRACTORY, HEARTH 42 STK WHITE••1
---REFRACTORY, HEARTH 50 STK WHITE••1
3---REFRACTORY, RIGHT 36" STK WHITE•1
---REFRACTORY, RIGHT 36 HER WHITE•1
---REFRACTORY, RT 42" STK WHITE•1
---REFRACTORY, RT 42 HER WHITE•1
---REFRACTORY, RT 50" STK WHITE•1
---REFRACTORY, RT 50" HER WHITE•1
4---REFRACTORY, LEFT 36 STK WHITE•1
---REFRACTORY, LEFT 36 HER WHITE•1
---REFRACTORY, LT 42" STK WHITE•1
---REFRACTORY, LT 42" HER WHITE•1
---REFRACTORY, LT 50" STK WHITE•1
---REFRACTORY, LT 50" HER WHITE•1
5---REFRACTORY, REAR 36" STK WHITE•1
---REFRACTORY, REAR 36 HER WHITE•1
---REFRACTORY REAR 42" STK WHITE•1
---REFRACTORY, REAR 42 HER WHITE•1
---REFRACTORY REAR 50" STK WHITE•1
---REFRACTORY, REAR 50 HER WHITE•1
6J5108 ASSY, ASH REFRACTORY 36 WHITE••1
J4583 REFRACTORY, ASH 42 STK WHITE••1
J4593 REFRACTORY, ASH 50" STK WHITE••1
7J4466 RETAINER ASSY., REF. CORNER••••••2
VRE4536WS
(F0474)
VRE4536WH
(F0476)
VRE4542WS
(F0478)
VRE4542WH
(F0480)
VRE4550WS
(F0482)
VRE4550WH
(F0484)QTY.
SuperiorFireplaces.US.com127029-01D17
Page 18
SERVICE HINTS
REPLACEMENT PARTS
When Gas Pressure Is Too Low
• pilot will not stay lit
• burner will have delayed ignition
• fi replace will not produce specifi ed heat
• for propane/LP unit, propane/LP gas supply may be low
You may feel your gas pressure is too low. If so, contact your local
gas supplier.
TECHNICAL SERVICE
You may have further questions about installation, operation, or
troubleshooting. Please contact your IHP dealer for any questions
or concerns a. When contacting your dealer please have your model
and serial numbers of your fi replace ready. You can also visit our web
site at SuperiorFireplaces.US.com.
See Pages 14 to 17 for a complete replacement parts list. Use only
parts supplied from the manufacturer.
Normally, all parts should be ordered through your IHP distributor
or dealer. Parts will be shipped at prevailing prices at time of order.
When ordering repair parts, always give the following information:
1. The model number of the fi replace.
2. The serial number of the fi replace.
3. The part number.
4. The description of the part.
5. The quantity required.
6. The installation date of the fi replace.
If you encounter any problems or have any questions concerning the
installation or application of this fi replace, please contact your dealer.
IHP
1508 Elm Hill Pike, Suite 108
Nashville, TN 37210
Visit us at SuperiorFireplaces.US.com
ACCESSORIES
Purchase these appliance accessories from your local dealer. If they can not supply these accessories, contact IHP at SuperiorFireplaces.
US.com for referral information. You can also write to the address listed on the back of this manual.
Only kits supplied by IHP shall be used in the installation of this appliance. Use of non-approved accessory/part kit(s) can result in
poor performance and safety hazards.
CAT NO.MODELDESCRIPTION
OPTIONAL AIR KITS
F1091AK4FOutside Air Kit For Floor Installation
F1094AK4Outside Air Kit For Sidewall Installation
REFRACTORY STAIN KITS
Use the Refractory Stain Kits to give white refractory panels a new look.
Kit includes foam roller, roller handle, paint tray, and one can of stain. Available stain colors
are Creamer (ivory), Rust (terra cotta), and Cappuccino (rosy taupe).
H8176BSK-CR Refractory Stain Kit, Creamer
H8177BSK-RT Refractory Stain Kit, Rust
H8178BSK-CP Refractory Stain Kit, Cappuccino
SuperiorFireplaces.US.com127029-01D18
CreamerRustCappuccino
Page 19
Innovative Hearth Products
®
Superior
Brand Gas Fireplaces, Stoves and Inserts
20 Year Limited Warranty
THE WARRANTY
Innovative Hearth Products ("IHP") 20 Year Limited Warranty warrants your Superior® Brand gas fi replace, Stove or Insert ("Product") to be free from defects in materials
and workmanship at the time of manufacture. The product body, fi rebox and barrier carry the 20 Year Limited Warranty. Ceramic glass carries the 20 Year Limited Warranty
against thermal breakage only. After installation, if covered components manufactured by IHP are found to be defective in materials or workmanship during the 20 Year
Limited Warranty period and while the Product remains at the site of the original installation, IHP will, at its option, repair or replace the covered components. If repair or
replacement is not commercially practical, IHP will, at its option, refund the purchase price or wholesale price of the IHP product, whichever is applicable. IHP will also
pay IHP prevailing labor rates, as determined in its sole discretion, incurred in repairing or replacing such components for up to fi ve years. THERE ARE EXCLUSIONS AND
LIMITATIONS to this 20 Year Limited Warranty as described herein.
COVERAGE COMMENCEMENT DATE
Warranty coverage begins on the date of purchase. In the case of new home construction, warranty coverage begins on the date of fi rst occupancy of the dwelling or six
months after the sale of the Product by an independent IHP dealer/distributor, whichever occurs earlier. The warranty shall commence no later than 24 months following
the date of product shipment from IHP, regardless of the installation or occupancy date.
EXCLUSIONS AND LIMITATIONS
This 20 Year Limited Warranty applies only if the Product is installed in the United States or Canada and only if operated and maintained in accordance with the printed
instructions accompanying the Product and in compliance with all applicable installation and building codes and good trade practices.
This warranty is non-transferable and extends to the original owner only. The Product must be purchased through a listed supplier of IHP and proof of purchase must be
provided. The product body, fi rebox and barrier carry the 20 Year Limited Warranty from the date of installation. Vent components, trim components and paint are excluded
from this 20 Year Limited Warranty. The following do not carry the 20 Year Limited Warranty but are warranted as follows:
Burner – Repair or replacement for one year from the date of installation
Gas components – Repair or replacement for one year from the date of installation
Gaskets – Repair or replacement for one year from the date of installation
Logs – Replacement for one year from the date of installation against thermal breakage only
Optional blowers & remote controls – Repair or replacement for one year from the date of installation
Optional glass doors – Repair or replacement for 90 days from the date of installation
Tempered glass - Replacement for one year from the date of installation
Labor coverage – Prevailing IHP labor rates apply for the warranty period of the component
Parts not otherwise listed carry a 90 day warranty from the date of installation.
Whenever practicable, IHP will provide replacement parts, if available, for a period of 10 years from the last date of manufacture of the Product.
IHP will not be responsible for: (a) damages caused by normal wear and tear, accident, riot, fi re, fl ood or acts of God; (b) damages caused by abuse, negligence, misuse, or
unauthorized alteration or repair of the Product affecting its stability or performance (The Product must be subjected to normal use. The Product is designed to burn either
natural or propane gas only. Burning conventional fuels such as wood, coal or any other solid fuel will cause damage to the Product, will produce excessive temperatures
and could result in a fi re hazard.); (c) damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product;
(d) damages, repairs or ineffi ciency resulting from faulty installation or application of the Product.
IHP is not responsible for inadequate fi replace system draft caused by air conditioning and heating systems, mechanical ventilation systems, or general construction conditions which may generate negative pressure in the room in which the appliance is installed. Additionally IHP assumes no responsibility for drafting conditions caused by
venting confi gurations, adjoining trees or buildings, adverse wind conditions or unusual environmental factors and conditions that affect the operation of the unit.
This 20 Year Limited Warranty covers only parts and labor as provided herein. In no case shall IHP be responsible for materials, components or construction, which are not
manufactured or supplied by IHP or for the labor necessary to install, repair or remove such materials, components or construction. Additional utility bills incurred due to
any malfunction or defect in equipment are not covered by this warranty. All replacement or repair components will be shipped F.O.B. from the nearest stocking IHP factory.
LIMITATION ON LIABILITY
It is expressly agreed and understood that IHP’s sole obligation and the purchaser’s exclusive remedy under this warranty, under any other warranty, expressed or implied,
or in contract, tort or otherwise, shall be limited to replacement, repair, or refund, as specifi ed herein.
In no event shall IHP be liable for any incidental or consequential damages caused by defects in the Product, whether such damage occurs or is discovered before or
after repair or replacement, and whether such damage is caused by IHP’s negligence. IHP has not made and does not make any representation or warranty of fi tness for a
particular use or purpose, and there is no implied condition of fi tness for a particular use or purpose.
IHP makes no expressed warranties except as stated in this 20 Year Limited Warranty. The duration of any implied warranty is limited to the duration of this expressed warranty.
No one is authorized to change this 20 Year Limited Warranty or to create for IHP any other obligation or liability in connection with the Product. Some states and provinces
do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. The provisions of this 20 Year
Limited Warranty are in addition to and not a modifi cation of or subtraction from any statutory warranties and other rights and remedies provided by law.
INVESTIGATION OF CLAIMS AGAINST WARRANTY
IHP reserves the right to investigate any and all claims against this 20 Year Limited Warranty and to decide, in its sole discretion, upon the method of settlement.
To receive the benefi ts and advantages described in this 20 Year Limited Warranty, the appliance must be installed and repaired by a licensed contractor approved by IHP.
Contact IHP at the address provided herein to obtain a listing of approved dealers/distributors. IHP shall in no event be responsible for any warranty work done by a
contractor that is not approved without fi rst obtaining IHP's prior written consent.
HOW TO REGISTER A CLAIM AGAINST WARRANTY
In order for any claim under this warranty to be valid, you must contact the IHP dealer/distributor from which you purchased the product. If you cannot locate the dealer/
distributor, then you must notify IHP in writing. IHP must be notifi ed of the claimed defect in writing within 90 days of the date of failure. Notices should be directed to the
IHP Warranty Department at 1508 Elm Hill Pike, Suite 108; Nashville, TN 37210 or visit our website at WWW.SUPERIORFIREPLACES.US.COM.
Innovative Hearth Products
1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210
19
Page 20
SuperiorFireplaces.US.com
Record the following important information about your appliance:
Appliance model number
Appliance serial number
Date appliance was Installed
Type of gas appliance uses
Dealer name
IHP reserves the right to make changes at any time, without notice, in design,
materials, specifi cations, prices and also to discontinue colors, styles and
products. Consult your local distributor for fi replace code information.