INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
This appliance may be installed in an aftermarket permanently located, manufactured (mobile) home, where not
prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This
appliance is not convertible for use with other gases.
WARNING: This appliance is for installation only in a solid-fuel burning masonry or UL127 factory-built
fireplace or in a listed ventless firebox enclosure. It is design-certified for these installations in accordance
with ANSI Z21.11.2. Exception: DO NOT install this appliance in a factory-built fireplace that includes
instructions stating it has not been tested or should not be used with unvented gas logs.
This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions
for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation
section on page 6 of this manual.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a qualified installer, service agency or the gas supplier.
WARNING: Improper installation, adjustment, alteration, service
or maintenance can cause
injury or property damage. Refer to this manual
for correct installation and
operational procedures.
For assistance or additional information consult
a qualied installer, service agency or the gas
supplier.
WARNING: This ap-
pliance is for installation
only in a solid-fuel burning
masonry or UL127 factory-
built replace or in a listed
ventless rebox enclosure.
It is design-certified for
these installations in accordance with ANSI Z21.11.2.
Exception: DO NOT install
this appliance in a factory-
built replace that includes
instructions stating it has
not been tested or should
not be used with unvented
gas logs.
WARNING: This is an
unvented gas-red heater. It uses air (oxygen)
from the room in which
it is installed. Provisions
for adequate combustion
and ventilation air must
be provided. Refer to Air
for Combustion and Ventilation section on page 6
of this manual.
This appliance may be installed in an aftermarket,*
permanently located,
manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for
use with the type of gas
indicated on the rating
plate. This appliance is
not convertible for use
with other gases.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
Page 3
SAFETY
Continued
WARNING: This product
contains and/or generates
chemicals known to the State
of California to cause cancer or
birth defects or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, op-
erate or service this replace.
Improper use of this replace
can cause serious injury or
death from burns, re, explosion, electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the
u, with headaches, dizziness or nausea. If
you have these signs, the replace may not
be working properly. Get fresh air at once!
Have replace serviced. Some people are
more affected by carbon monoxide than oth-
ers. These include pregnant women, people
with heart or lung disease or anemia, those
under the inuence of alcohol and those at
high altitudes.
Natural and Propane/LP Gas: Natural and
propane/LP gases are odorless. An odormaking agent is added to these gases. The
odor helps you detect a gas leak. However,
the odor added to the gas can fade. Gas may
be present even though no odor exists.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this replace.
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not allow fans
to blow directly into the replace.
Avoid any drafts that alter burner
ame patterns. Ceiling fans can
create drafts that alter burner ame
patterns. Altered burner patterns
can cause sooting.
Due to high temperatures, the appliance should be located out of
trafc and away from furniture and
draperies.
Do not place clothing or other
ammable material on or near the
appliance. Never place any objects
on the heater.
Heater base assembly becomes
very hot when running heater. Keep
children and adults away from hot
surface to avoid burns or clothing
ignition. Heater will remain hot for a
time after shutdown. Allow surface
to cool before touching.
Carefully supervise young children
when they are in the room with heater.
When using the hand-held remote
accessory, keep selector switch in
the OFF position to prevent children
from turning on burners with remote.
You must operate this heater with
the replace screen and hood in
place. Make sure replace screen
and hood are in place before running
heater. The replace screen shall
have openings for introduction of
combustion air.
Keep the appliance area clear and
free from combustible materials,
gasoline and other ammable vapors and liquids.
Page 4
SAFETY
Continued
1. This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases.
2. Do not place propane/LP supply tank(s)
inside any structure. Locate propane/LP
supply tank(s) outdoors (propane/LP units
only).
3. To prevent performance problems, the use
of a propane/LP tank of less than 100 lbs.
capacity is not recommended (propane/
LP units only).
4. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas sup-
plier’s instructions
• if you cannot reach your gas supplier,
call the re department
5. This heater shall not be installed in a
bedroom or bathroom.
6. Do not burn solid-fuel in a replace in
which a vent-free room heater is installed.
7. Before installing in a solid fuel burning replace, the chimney ue and rebox must
be cleaned of soot, creosote, ashes and
loose paint by a qualied chimney cleaner.
Creosote will ignite if highly heated. A dirty
chimney ue may create and distribute
soot within the house. Inspect chimney
ue and rebox for damage. If damaged,
repair ue before operating heater.
8. If replace has glass doors, never operate
this heater with glass doors closed. Any
glass doors shall be fully opened when the
appliance is in operation. If you operate
heater with doors closed, heat buildup
inside replace will cause glass to burst.
Make sure there are no obstructions
across openings of replace.
9. This log heater is designed to be smoke-
less. If logs ever appear to smoke, turn off
heater and call a qualied service person.
Note: During initial operation, slight smoking could occur due to log curing and
heater burning manufacturing residues.
10. To prevent the creation of soot, follow the
instructions in Cleaning and Maintenance,
page 23.
www.SuperiorFireplaces.US.com
11. Before using furniture polish, wax, carpet
cleaner or similar products, turn heater off.
If heated, the vapors from these products
may create a white powder residue within
burner box or on adjacent walls or furniture.
12. This heater needs fresh, outside air ven-
tilation to run properly. This heater has an
Oxygen Depletion Sensing (ODS) safety
shutoff system. The ODS shuts down the
heater if not enough fresh air is available.
See Air for Combustion and Ventilation,
page 6. If heater keeps shutting off, see
Troubleshooting, page 24.
13. Do not run heater
• where ammable liquids or vapors are
used or stored
• under dusty conditions
14. Do not use this heater to cook food or burn
paper or other objects.
15. Do not use heater if any part has been ex-
posed to or under water. Immediately call
a qualied service technician to inspect
the room heater and to replace any part
of the control system and any gas control
which has been under water.
16. Do not operate heater if any log is broken.
Do not operate heater if a log is chipped
(dime-sized or larger).
17. Turn heater off and let cool before servic-
ing. Only a qualied service person should
service and repair heater.
18. Operating heater above elevations of
4,500 feet could cause pilot outage.
19. Provide adequate clearances around air
openings.
20. Solid fuels shall not be burned in a replace in which an unvented room heater
is installed.
21. Installation and the provisions for combustion and ventilation air must conform
with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54.
22. When installing as a vented appliance in a
manufactured home or mobile home, the
installation must conform with the Manu-
factured Home Construction and Safety
Standard, Title 24 CFR, Part 3280, or
when applicable, with Manufacture Home
Install and use heater with care. Follow all
local codes. In the absence of local codes,
use the latest edition of The National Fuel
Gas Code ANSI Z223/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269
Log Set
Right
Side
State of Massachusetts: The installation must be made by a licensed plumber
or gas fitter in the Commonwealth of
Massachusetts.
Sellers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527
CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for
bedroom and bathroom installation in the
Commonwealth of Massachusetts.
UNPACKING
Note: Do not pick up heater base assem-
CAUTION: Do not remove the
data plates from the grate assembly. The data plates contain
important warranty and safety
information.
1. Remove logs and heater base assembly
from cartons.
bly by burners. This could damage heater.
Always handle base assembly by grate.
2. Remove all protective packaging applied
to logs and heater for shipment.
3. Check heater for any shipping damage.
If heater is damaged call INNOVATIVE
HEARTH PRODUCTS at 1-800-655-2008
for replacement parts before returning to
dealer.
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no
outside venting. There is no heat loss out a
vent or up a chimney. Heat is generated by
realistic, dancing yellow ames. This heater
is designed for vent-free operation with ue
damper closed. It has been tested and approved to ANSI Z21.11.2 standard for unvented heaters. State and local codes in some
areas prohibit the use of vent-free heaters.
126838-01A5
www.SuperiorFireplaces.US.com
SAFETY PILOT
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS/pilot is a required feature for vent-free
room heaters. The ODS/pilot shuts off the
heater if there is not enough fresh air.
Page 6
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall
not be installed in a room or space
unless the required volume of indoor combustion air is provided
by the method described in the
National Fuel Gas Code, ANSI
Z223.1/NFPA 54, the International
Fuel Gas Code, or applicable
local codes. Read the following
instructions to insure proper
fresh air for this and other fuelburning appliances in your home.
Today’s homes are built more energy efcient
than ever. New materials, increased insulation
and new construction methods help reduce
heat loss in homes. Home owners weather
strip and caulk around windows and doors
to keep the cold air out and the warm air in.
During heating months, home owners want
their homes as airtight as possible.
While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning appliances need fresh air for proper combustion
and ventilation.
Exhaust fans, replaces, clothes dryers and
fuel burning appliances draw air from the house
to operate. You must provide adequate fresh
air for these appliances. This will insure proper
venting of vented fuel-burning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code. ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 6 through 8 will help
you classify your space and provide adequate
ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of unusually tight construction, you must provide
additional fresh air.
www.SuperiorFireplaces.US.com
Unusually tight construction is dened as
construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6x10
less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window
and door frames, between sole plates
and oors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical and gas lines
and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh air.
See Ventilation Air From Outdoors, page 8.
If your home does not meet all of the three
criteria above, proceed to Determining Fresh-Air Flow For Heater Location.
Conned Space and Unconned Space
The National Fuel Gas Code ANSI Z223.1/
NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu per hour (4.8 m3 per kw) of the ag-
gregate input rating of all appliances installed
in that space and an unconned space as a
space whose volume is not less than 50 cubic
feet per 1,000 Btu per hour (4.8 m3 per kw)
of the aggregate input rating of all appliances
installed in that space. Rooms communicating
directly with the space in which the appliances
are installed*, through openings not furnished
with doors, are considered a part of the unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.
-11
kg per pa-sec-m2) or
DETERMINING FRESH-AIR FLOW
FOR FIREPLACE LOCATION
Determining if You Have a Conned or
Unconned Space
Use this work sheet to determine if you have
a conned or unconned space.
Space: Includes the room in which you will
install replace plus any adjoining rooms with
doorless passageways or ventilation grills
between the rooms.
126838-01A6
Page 7
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills Into
Adjoining
Room,
Option 1
12"
12"
AIR FOR COMBUSTION AND VENTILATION
1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2,560 cu. ft.
(volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2,560 cu. ft. (volume of space) x
20 = 51,200 (maximum Btu/Hr the space can
support)
3. Add the Btu/Hr of all fuel burning appliances
in the space.
Vent-free replace __________ Btu/HrGas water heater* __________ Btu/Hr
Gas furnace __________ Btu/Hr
Vented gas heater __________ Btu/Hr
Gas replace logs __________ Btu/Hr
Other gas appliances* + __________ Btu/Hr
Total = __________ Btu/Hr
* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
Example:
Gas water heater __________ Btu/HrVent-free replace __________ Btu/Hr
Total = __________ Btu/Hr
4. Compare the maximum Btu/Hr the space
can support with the actual amount of Btu/
Hr used.
_______
support)
_______ Btu/Hr (actual amount of Btu/Hr
used)
Example: 51,200 Btu/Hr (maximum the
71,500 Btu/Hr (actual amount of
The space in the example is a conned space
because the actual Btu/Hr used is more than the
maximum Btu/Hr the space can support. You
must provide additional fresh air. Your options
are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides an
unconned space, remove door to adjoining
126838-01A7
Btu/Hr (maximum the space can
space can support)
Btu/Hr used)
40,000
31,500
71,500
www.SuperiorFireplaces.US.com
Continued
room or add ventilation grills between rooms.
See Ventilation Air From Inside Building.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 8.
C. Install a lower Btu/Hr replace, if lower Btu/
Hr size makes room unconned.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is
an unconned space. You will need no additional
fresh air ventilation.
WARNING: If the area in which
the heater may be operated does
not meet the required volume for
indoor combustion air, combustion and ventilation air shall be
provided by one of the methods
described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54,
the International Fuel Gas Code,
or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconned space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the oor on the
wall connecting the two spaces (see options 1
and 2, Figure 2). You can also remove door into
adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code ANSI Z223.1/
NFPA 54 Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
Figure 2 - Ventilation Air from Inside Building
Page 8
Outlet
Air
Ventilated
Attic
Outlet
A
ir
Inlet
Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
AIR FOR COMBUSTION AND VENTILATION
Continued
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two permanent openings: one within 12" of the ceiling
and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermo-
stat-controlled power vent. Heated air entering
the attic will activate the power vent.
NOTICE: State or local codes may
only allow operation of this appliance
in a vented conguration. Check your
state or local codes.
WARNING: Before installing in
a solid fuel burning replace, the
chimney ue and rebox must be
cleaned of soot, creosote, ashes and
loose paint by a qualied chimney
cleaner. Creosote will ignite if highly
heated. A dirty chimney ue may
create and distribute soot within
the house. Inspect chimney ue
and rebox for damage. If damaged,
repair ue before operating heater.
WARNING: Any outside air ducts
and/or ash dumps in the replace
shall be permanently closed at time
of appliance installation.
Figure 3 - Ventilation Air from Outdoors
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your primary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
vice person must install heater.
Follow all local codes.
WARNING: A qualied ser-
www.SuperiorFireplaces.US.com
WARNING: Seal any fresh air
vents or ash clean-out doors located
on oor or wall of replace. If not,
drafting may cause pilot outage
or sooting. Use a heat-resistant
sealant. Do not seal chimney ue
damper.
WARNING: Never install the
heater
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture, cloth-
ing or other ammable objects
are less than 36" from front or
42" from top of heater. For side
clearances see Figure 4, page 9
• in high trafc areas
• in windy or drafty areas
126838-01A8
Page 9
INSTALLATION
Continued
CAUTION: This heater creates warm air currents. These
currents move heat to wall sur-
faces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities (such as, but
not limited to, tobacco smoke,
aromatic candles, cleaning uids, oil or kerosene lamps, etc.) in
the air exist, may discolor walls
or cause odors.
IMPORTANT: Vent-free heaters add moisture
to the air. Although this is benecial, installing
heater in rooms without enough ventilation
air may cause mildew to form from too much
moisture. See Air for Combustion and Ventilation, page 6.
CHECK GAS TYPE
Use only the correct gas type (natural or propane/LP) for your unit. If your gas supply is not
correct, do not install heater. Call dealer where
you bought heater for proper type heater.
WARNING: This appliance is
equipped for either natural gas
or propane/LP gas but not both.
Gas type is indicated on the rating plate. Field conversion is not
permitted.
INSTALLATION AND CLEARANCES
(Vent-Free Operation Only)
MINIMUM FIREPLACE CLEARANCE
TO COMBUSTIBLE MATERIALS
Side Wall 16", Ceiling 42", Front 36"
WARNING: Maintain the
minimum clearances. If you can,
provide greater clearances from
oor, ceiling and adjoining wall.
Carefully follow the instructions below. This
will ensure safe installation into a masonry,
UL127-listed manufactured replace or certied vent-free rebox.
MINIMUM CLEARANCES FOR SIDE
COMBUSTIBLE MATERIAL, SIDE WALL
AND CEILING
A. Clearances from the side of the replace
cabinet to any combustible material and
wall should follow diagram in Figure 4.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and
protrudes 3 1/2" from the wall. This com-
bustible material must be 4" from the side
of the replace cabinet (see Figure 4).
Note: When installing your gas logs into
a manufactured rebox, follow rebox
manufacturer’s instructions for minimum
clearances to combustible materials.
B. Clearances from the top of the replace
opening to the ceiling should not be less
than 42".
NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney ue damper open.
If running heater with damper
open, noncombustible material
above replace opening is not
needed. Go to Installing Damper
Clamp Accessory for Vented
Operation, page 11.
LOG SIZING REQUIREMENTS
Minimum Firebox
Log
Size
Height Depth
18"17"13.5"24"20.5"
24"17"13.5"28"20.5"
* Measured at 13.5" depth.
126838-01A9
Front
Width
Rear *
Width
*Minimum 16" from Side Wall
www.SuperiorFireplaces.US.com
Example
*
Figure 4 - Minimum Clearance for
Combustible to Wall
Page 10
Minimum
Noncombustible
Material
Minimum
Noncombustible
Material Height
Distances to
Underside of
Mantel
Top of
Fireplace
Opening
Underside
of Mantel
Shelf
Mantel Shelf
12"
(A)
18" 20" 22" 24"
All
minimum
distances
are in
inches
2
1
/2"
6"
8"
10"
INSTALLATION
Heat Resistant
Material
(A)
Continued
MINIMUM NONCOMBUSTIBLE
MATERIAL CLEARANCES
If Not Using Mantel
Note: If using a mantel, proceed to If Using
Mantel. If not using a mantel, follow the information below.
You must have noncombustible material(s)
above the replace opening. Noncombustible
materials (such as slate, marble, tile, etc.)
must be at least 1/2" thick. With sheet metal,
you must have noncombustible material behind it. Noncombustible material must extend
at least 12" up (for all models). See Figure 5
for minimum clearances.
Noncombustible
Material Distance (A)
12" or moreNoncombustible mate-
Between 8"
and 12"
Less than 8"Noncombustible material
Requirements for Safe
Installation
rial OK.
Install fireplace hood
accessory (GA6050 or
GA6053, see Accessories, page 34).
must be extended to at
least 8". See Between
8" and 12", above. If you
cannot extend material,
you must operate heater
with ue damper open and
damper clamp installed.
If Using Mantel
You must have noncombustible material(s)
above the replace opening. Noncombustible
materials (such as slate, marble, tile, etc.) must
be at least 1/2" thick. With sheet metal, you
must have noncombustible material behind it.
Noncombustible material must extend at least
8 inches up (for all models). If noncombustible
material is less than 12", you must install the
replace hood accessory. Even if noncombustible material is more than 12", you may need
the hood accessory to deect heat away from
your mantel shelf. See Figure 5, and Figures
6 and 7 (page 11) for minimum clearances.
IMPORTANT: If you cannot meet these mini-
mum clearances, you must operate heater
with chimney ue damper open. Go to Install-
ing Damper Clamp Accessory for Vented
Operation, page 11.
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required
clearances between replace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between
mantel shelf and top of replace opening, a
hood is not required (see Figure 6).
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
www.SuperiorFireplaces.US.com
Figure 6 - Minimum Mantel Clearances
Without Using Hood
126838-01A10
Page 11
INSTALLATION
Minimum
Noncombustible
Material
8"
Min.
12" 15" 18" 20"
2½"
6"
8"
10"
12"
Distances to
Underside of
Mantel
Hood
(GA6050 or
GA6053)
Top of
Fireplace
Opening
Underside
of Mantel
Shelf
Mantel Shelf
14"
Min.
Combustible
Material
Noncombustible Material
Hearth
5"
Min.
Combustible
Material
Continued
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6, page 10, are
not met, you must have a hood. When using
a hood there are still certain minimum mantel
clearances required. Follow minimum clearances shown in Figure 7 when using hood.
FLOOR CLEARANCES
A. If installing appliance on the oor level,
you must maintain the minimum distance
of 14" to combustibles (see Figure 8).
B. If combustible materials are less than
14" to the replace, you must install appliance at least 5" above the top surface
of combustible ooring including tile and
carpet. (see Figure 9).
126838-01A11
Figure 7 - Minimum Mantel Clearances
When Using Hood
NOTICE: Surface temperatures
of adjacent walls and mantels become hot during operation. Walls
and mantels above the rebox
may become hot to the touch.
If installed properly, these temperatures meet the requirement
of the national product standard.
Follow all minimum clearances
shown in this manual.
NOTICE: If your installation does
not meet the minimum clearances shown, you must do one
of the following:
• raise the mantel to an acceptable height
www.SuperiorFireplaces.US.com
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
INSTALLING DAMPER CLAMP
ACCESSORY FOR VENTED
OPERATION
Note: When used as a vented heater, appliance must be installed only in a solid-fuel
burning replace with a working ue and constructed of noncombustible material.
For Massachusetts Residents Only: Installation of this vented gas log set in the Com-
monwealth of Massachusetts requires the
damper be permanently removed or welded
in the fully open position.
If your heater is a manually-controlled model,
you may use this heater as a vented product.
There are three reasons for operating your
heater in the vented mode.
1. The replace does not meet the clearance
to combustibles requirements for vent-free
operation.
2. State or local codes do not permit ventfree operation.
3. You prefer vented operation.
Page 12
INSTALLATION
Continued
If reasons number 1 or 2 apply to you,
you must permanently open chimney ue
damper. You must install the damper clamp
accessory (to order, see Accessories, page
34). This will insure vented operation (see Figure 10). The damper clamp will keep damper
open. Installation instructions are included
with clamp accessory.
Damper
Clamp
Damper
Masonry Fireplace
Figure 10 - Attaching Damper Clamp
See chart for minimum permanent ue opening you must provide. Attach damper clamp so
the minimum permanent ue opening will be
maintained at all times.
Area of Various Standard
DiameterArea
5"20 sq. in.
6"29 sq. in.
7"39 sq. in.
8"51 sq. in.
Chimney
Height
6' to 15'39 sq. in.
15' to 30'29 sq. in.
INSTALLING HEATER BASE
ASSEMBLY
WARNING: You must secure
this heater to replace oor. If
not, heater will move when you
adjust controls. Moving heater
may cause a gas leak or log
misplacement.
Damper
Damper
Clamp
Manufactured Fireplace
Round Flues
Minimum Permanent
Flue Opening
www.SuperiorFireplaces.US.com
Damper
WARNING: If installing in a
sunken replace, special care
is needed. You must raise the
replace oor to allow access to
heater control panel. This will in-
sure adequate air ow and guard
against sooting and controls
being damaged. Raise replace
oor with noncombustible mate-
rial. Make sure material is secure.
CAUTION: Do not pick up
heater base assembly by burners. This could damage heater.
Only handle base assembly by
grates.
IMPORTANT: Make sure the heater burners
are level. If heater is not level, heater will not
work properly.
Installation Items Needed
• hardware package (provided with heater)
• approved exible gas hose and ttings (if
allowed by local codes)
• sealant (resistant to propane/LP gas, not
provided)
• electric drill with 3/16" drill bit (metal or
masonry as applicable)
• athead screwdriver
• pipe wrench
1. Connect approved exible gas hose to
gas control tting in heater (see Figure
11, page 13).
IMPORTANT: Hold gas tting with wrench
when connecting exible gas hose.
2. Locate two masonry screws in hardware
package.
3. Place heater base in replace.
4. Place logs in their proper position on heater
base (see Installing Logs, page 16).
5. Center heater base and logs front-to-back
and side-to-side in replace.
6. Carefully remove logs without moving
heater base.
7. Mark screw locations through one hole on
each side of the mounting bracket (see
Figure 12, page13). If installing in a brickbottom replace, mark screw locations in
mortar joint of bricks.
126838-01A12
Page 13
INSTALLATION
Continued
Flexible Gas
Hose (if allowed
by local codes)
Fitting
Figure 11 - Attaching Flexible Gas Hose
to Heater
8. Remove heater base from replace. If
installing optional control accessories,
do so at this time. Follow all directions
provided with accessory.
9. Drill holes at marked locations using 3/16"
drill bit.
10. Attach base assembly to replace oor
using two masonry screws (in hardware
package).
Masonry
Screw
Mounting
Bracket
Figure 12 - Attaching Base to Fireplace
Floor
CONNECTING TO GAS SUPPLY
WARNING: This appliance
requires a 1/2" NPT (National
Pipe Thread) inlet connection
to the pressure regulator.
WARNING: A qualied service
person must connect heater to
gas supply. Follow all local codes.
CAUTION: Never connect
propane/LP replace directly
to the propane/LP supply. This
heater requires an external regulator (not supplied). Install the
external regulator between the
heater and propane/LP supply.
Installation Items Needed
Before installing heater, make sure you have
the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
* A equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge
connection. Purchase the optional equipment
shutoff valve from your dealer.
For propane/LP units, the installer must
supply an external regulator. The external
regulator will reduce incoming gas pressure.
You must reduce incoming gas pressure to
between 11" and 14" of water. If you do not reduce incoming gas pressure, heater regulator
damage could occur. Install external regulator
with the vent pointing down as shown in Figure
13. Pointing the vent down protects it from
freezing rain or sleet.
Propane/LP
Supply Tank
Figure 13 - External Regulator With Vent
Pointing Down
External
Regulator
Vent
Pointing
Down
126838-01A13
www.SuperiorFireplaces.US.com
Page 14
INSTALLATION
Continued
WARNING: Never connect
natural gas replace to private
(non-utility) gas wells. This gas
is commonly known as wellhead
gas.
CAUTION: Use only new,
black iron or steel pipe. Internally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of
1/2" diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up.
NPT tap must be upstream from heater (see
Figure 14).
IMPORTANT: Install equipment shutoff valve
in an accessible location. The equipment
shutoff valve is for turning on or shutting off
the gas to the appliance.
Check your building codes for any special
requirements for locating equipment shutoff
valve to replaces.
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could
result in clogged heater valves.
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
We recommend that you install a sediment trap
in supply line as shown in Figure 14. Locate
sediment trap where it is within reach for
cleaning. Install in piping system between
fuel supply and heater. Locate sediment trap
where trapped matter is not likely to freeze.
A sediment trap traps moisture and contaminants. This keeps them from going into heater
controls. If sediment trap is not installed or is
installed wrong, heater may not run properly.
PROPANE/LP
Equipment Shutoff
Valve With 1/8"
NPT Tap*
Approved
Flexible
Gas Hose (if
allowed by
local codes)
3” Minimum
Gas
Control
Figure 14 - Gas Connection
* Purchase the optional equipment shutoff
valve from your dealer.
** Minimum inlet pressure for purpose of input
adjustment.
From External
Regulator (11"
W.C.** to 14" W.C.
Pressure)
NATURAL
From Gas Meter
(5" W.C.** to
10.5" W.C.
Pressure)
Cap Pipe Tee
Nipple Joint
Sediment Trap
CAUTION: Avoid damage to
gas control. Hold gas tting with
wrench when connecting it to
gas piping and/or ttings.
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
WARNING: Never use an
open ame to check for a leak.
Apply a noncorrosive leak detec-
tion uid to all joints. Bubbles
forming show a leak. Correct all
leaks at once.
www.SuperiorFireplaces.US.com
126838-01A14
Page 15
INSTALLATION
Continued
3. Make sure control knob of heater is in the
CAUTION: Make sure external regulator has been installed
between propane/LP supply
and heater. See guidelines under Connecting to Gas Supply,
page 13.
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance
main gas valve (control valve) and equipment shutoff valve from gas supply piping
system. Pressures in excess of 1/2 psig
(3.5 kPa) will damage heater regulator.
2. Cap off open end of gas pipe where equipment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
4. Check all joints of gas supply piping system.
Apply noncorrosive leak detection uid to
all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff
valve to gas supply. Check reconnected
ttings for leaks.
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see
Figure 15).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
3. Check all joints from gas meter to equipment
shutoff valve for natural gas or propane/
LP supply to equipment shutoff valve for
propane/LP (see Figures 16 and 17). Ap-
ply noncorrosive leak detection uid to all
joints. Bubbles forming show a leak.
4. Correct all leaks at once.
PRESSURE TESTING HEATER GAS
CONNECTIONS
1. Open equipment shutoff valve (see
Figure 17).
2. Open main gas valve located on or near
gas meter for natural gas or open propane/LP supply tank valve.
126838-01A15
www.SuperiorFireplaces.US.com
OFF position.
4. Check all joints from equipment shutoff
valve to gas control (see Figures 16 and
17). Apply noncorrosive leak detection
uid to all joints. Bubbles forming show a
leak.
5. Correct all leaks at once.
6. Light heater (see Operation, page 20).
Check all other internal joints for leaks.
7. Turn off heater (see To Turn Off Gas to
Appliance, page 21).
Equipment
Shutoff
Valve
Figure 15 - Equipment Shutoff Valve
Propane/LP
Supply Tank
Figure 16 - Checking Gas Joints
(Propane/LP Model Shown)
Gas Meter
Figure 17 - Checking Gas Joints (Natural
Equipment
Shutoff Valve
Gas Control
Valve Location
Equipment
Shutoff Valve
Gas Control Valve
Location
Gas Only)
Open
Closed
Page 16
INSTALLATION
Continued
INSTALLING LOGS
WARNING: Failure to position
the parts in accordance with these
diagrams or failure to use only
parts specically approved with
this heater may result in property
damage or personal injury.
CAUTION: After installation and periodically thereafter,
check to ensure that no ame
comes in contact with any log.
With the heater set to HI, check
to see if ames contact any log. If
so, reposition logs according to
the log installation instructions
in this manual. Flames contacting logs will create soot.
LVD18-GO AND LVD24-GO
It is very important to install these logs exactly
as instructed. Do not modify logs. Only use
logs supplied with heater.
1. Place rear log onto base. Holes in bottom
of log must seat over pins on base as
shown in Figure 18.
2. Place center log onto base. Holes in bottom of log must seat over pins on base
as shown in Figure 18.
Center Log
Pin for
Hole in
Bottom
of Log
Rear Log
3. Place front log onto grate as shown in
Figure 19. Front log has cut outs for the
ngers of the grate to t into.
Front Log
Grate
Figure 19 - Installing Front Log
(Picture may vary from actual)
4. Place left crossover log as shown in Figure 20, page 17. Match square peg on top
of center log with square hole on bottom
of left crossover log. Match pin on top of
front log with round hole on bottom of left
crossover log.
5. Place center crossover log as shown in
Figure 20, page 17. Match square peg on
top of rear log with square hole on bottom
of center crossover log. Match pin on top
of center log with round hole on bottom
of center crossover log.
6. Place left front crossover log as shown in
Figure 20, page 17. Log should rest on the
grate and t into recess area on the center
log.
Burner
Figure 18 - Installing Rear and Middle Logs
(Picture may vary from actual)
www.SuperiorFireplaces.US.com
126838-01A16
Page 17
INSTALLATION
Continued
Center
Crossover
Log
Left
Crossover
Log
Square
Peg on
Middle
Log
Round
Peg on
Front Log
Figure 20 - Installing Left, Center and
Right Crossover Logs
(Picture may vary from actual)
Right
Crossover
Log
Square Peg
on Rear Log
Round Peg
on Center
Log
LVD18-PP AND LVD24-PP
1. Place rear log (#1) onto base. Holes in
bottom of log must seat over pins on base
as shown in Figure 21.
2. Place middle log (#2) onto base. Holes in
bottom of log must seat over pins on base
as shown in Figure 21.
3. Place front log (#3) onto grate as shown
in Figure 22.
Middle Log
Rear Log
Pin for
Hole in
Bottom
of Log
Front Log
Grate
Figure 22 - Installing Front Log
(Picture may vary from actual)
4. Place left top log (#4) as shown in Figure
23. Match square peg on top of rear log
(#1) with square hole on bottom of left top
log (#4). Match round peg on top of middle
log (#2) with round hole on bottom of left
top log (#4).
5. Place right top log (#5) as shown in Figure
23. Match square peg on top of rear log
(#1) with square hole on bottom of right
top log (#5). Match round peg on top of
front log (#3) with round hole on bottom
of right top log (#5).
Left Top
Log
Round
Peg on
Middle
Log
Square Peg
on Rear Log
Right
Top
Log
Round
Burner
Figure 21 - Installing Rear and Middle
Logs (Picture may vary from actual)
126838-01A17
www.SuperiorFireplaces.US.com
Figure 23 - Installing Left and Right Logs
(Picture may vary from actual)
Peg on
Front Log
Page 18
INSTALLATION
Continued
LVD18-CH AND LVD24-CH
It is very important to install these logs exactly
as instructed. Do not modify logs. Only use
logs supplied with heater.
1. Place the rear log onto base. Notches
in the back of the log must seat over
the pins on base as shown in Figure 24.
Make sure the rear log is pushed back
as far as it will go.
Rear Log
Middle Log
Pin for
Hole in
Bottom of
Log
Pin for Hole
in Bottom of
Log
Burner
Figure 24 - Installing Rear Log
(Picture may vary from actual)
2. Place the middle log on base. Holes in
bottom of log must seat over pins on
base as shown in Figure 25.
3. Place the front log onto grate as shown
in Figure 26.
Burner
Figure 25 - Installing Middle Log
(Picture may vary from actual)
Middle Log
Grate
Figure 26 - Installing Front Log
(Picture may vary from actual)
4. Place the top right log onto the rear,
middle and front logs as shown in Figure
27 (page 19). The rear, middle and front
logs has notches for the top right log to
set into. You may have to move the front
log from left to right to get it to line up
with the top right log.
www.SuperiorFireplaces.US.com
126838-01A18
Page 19
Rear Log
Middle
Log
Top Right Log
Front Log
INSTALLATION
Continued
6. Place the top left log onto the middle and
front logs as shown in Figure 29. Make
sure to match up the shape on the bot-
tom of the top left log with the notches
in the middle and front logs.
7. Final assembly is shown in Figure 30.
Log
Notch
Log Notch
Top Left Log
Middle Log
Figure 27 - Installing Top Right Log
(Picture may vary from actual)
5. Place the top middle log onto the rear
& middle logs as shown in Figure 28.
Make sure to match up the shape on
the bottom of the top middle log with
the notches in the rear and middle logs.
Top Middle
Log
Rear Log
Middle
Log
Figure 28 - Installing Middle Log
(Picture may vary from actual)
Log
Notch
Front Log
Notch
Figure 29 - Installing Top Left Log
(Picture may vary from actual)
Figure 30 - Final assembly
(Picture may vary from actual)
126838-01A19
www.SuperiorFireplaces.US.com
Page 20
FOR YOUR SAFETY
READ BEFORE LIGHTING
OPERATION
LIGHTING
INSTRUCTIONS
WARNING: If you do not fol-
low these instructions exactly,
a re or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must
be lighted by hand. When lighting
the pilot, follow these instructions
exactly.
B. BEFORE LIGHTING smell all around
the appliance area for gas. Be sure to
smell next to the oor because some
gas is heavier than air and will settle
on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the re department.
C. Use only your hand to push in or turn
the gas control knob. Never use tools.
If the knob will not push in or turn by
hand, don’t try to repair it, call a qualied service technician or gas supplier.
Force or attempted repair may result in
a re or explosion.
D. Do not use this appliance if any part
has been under water. Immediately call
a qualied service technician to inspect
the appliance and to replace any part of
the control system and any gas control
which has been under water.
WARNING
• If replace has glass doors,
never operate this heater with
glass doors closed. If you operate heater with doors closed,
heat buildup inside replace
will cause glass to burst. Make
sure there are no obstructions
across openings of replace.
• You must operate this heater
with a replace screen in place.
Make sure replace screen is
closed before running heater.
NOTICE: During initial operation
of new heater, burning logs will
give off a paper-burning smell.
Orange ame will also be present. Open damper or window to
vent smell. This will only last a
few hours.
Note: Home owners generally prefer to operate their heater with chimney damper closed.
This will put all of the heat into room. However,
there may be times you will desire full ames
of HI heat setting but will nd heat output
excessive. You can open chimney damper
(if you have one) fully or partially to release
some heat.
WARNING: Damper handle
will be hot if heater has been
running.
1. STOP! Read the safety information,
column 1.
2. Make sure equipment shutoff valve is fully
open.
3. Press in and turn control knob clockwise
to the OFF position.
4. Wait ve (5) minutes to clear out any gas.
Then smell for gas, including near the
oor. If you smell gas, STOP! Follow “B”
in the safety information, column 1. If you
don’t smell gas, go to the next step.
www.SuperiorFireplaces.US.com
126838-01A20
Page 21
OPERATION
PILOT
OFF
LO
HI
Continued
5. Press in control knob and turn counter-
clockwise to the PILOT position
(see Figure 31). The ignitor will spark
once. Keep control knob pressed in for 5
seconds. If control knob does not pop up
when released, contact a qualied service
person or gas supplier for repairs.
Note: You may be running this heater for
the rst time after hooking up to gas supply. If so, the control knob may need to be
pressed in for 30 seconds or more. This
will allow air to bleed from the gas system.
6. Turn control knob clockwise to
OFF position. Press in control knob and
turn counterclockwise to PILOT
position. This will light pilot. Pilot is attached to rear of burner. If needed, repeat
this process until pilot lights.
Note: If pilot does not stay lit, contact a
qualied service person or gas supplier
for repairs. Until repairs are made, light
pilot with match. To light pilot with match,
see Manual Lighting Procedure.
7. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds,
release control knob.
Note: If pilot goes out, repeat steps 3
through 7.
Control Knob
Figure 31 - Control Knob and Ignitor
Button Location
• If control knob does not pop out when
released, contact a qualified service
person or gas supplier for repairs.
8. Slightly press and turn control knob counterclockwise to desired heating
level. The burner should light. Set control
knob to HI or LO.
WARNING: Do not operate
heater between PILOT and HIGH
positions.
9. To leave pilot lit and shut off burners only,
turn control knob clockwise to the
PILOT position.
CAUTION: Do not try to adjust heating levels by using the
equipment shutoff valve.
TO TURN OFF GAS
TO APPLIANCE
1. Turn control knob clockwise to OFF
position.
2. Close equipment shutoff valve (see Figure
15, page 15).
MANUAL LIGHTING
PROCEDURE
1. Follow steps 1 through 5 under Lighting
Instructions beginning on page 20.
2. Press control knob and light pilot with
match.
3. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds,
release control knob. Now follow step 8
under Lighting Instructions, above.
126838-01A21
www.SuperiorFireplaces.US.com
Page 22
INSPECTING BURNERS
Check pilot ame pattern and burner ame
patterns often.
PILOT FLAME PATTERN
Figure 32 shows a correct pilot ame pattern.
Figure 33 shows an incorrect pilot ame pattern. Incorrect pilot ame is not touching thermocouple. This will cause the thermocouple
to cool. When thermocouple cools, heater
will shut down.
If pilot ame pattern is incorrect, as shown
in Figure 33
• turn heater off (see To Turn Off Gas to
Appliance, page 21.
• see Troubleshooting, page 24
Pilot Burner
Thermocouple
Figure 32 - Correct Pilot Flame Pattern
Thermocouple
Figure 33 - Incorrect Pilot Flame Pattern
Pilot Burner
Note: Pilot ame on natural gas units will have
a slight curve, but ame should be blue and
have no yellow or orange color.
BURNER PRIMARY AIR HOLES
Air is drawn into burner through holes in tting at entrance to burner. These holes may
become blocked with dust or lint. Periodically
inspect these holes for any blockage and
clean as necessary. Blocked air holes will
create soot.
MAIN BURNER
Periodically inspect all burner ame holes
with heater running. All slotted burner ame
holes should be open with yellow ame present. All round burner ame holes should be
open with a small blue ame present. Some
burner ame holes may become blocked by
debris or rust, with no ame present. If so,
turn off heater and let cool. Remove blockage,
blocked burner ame holes will create soot.
www.SuperiorFireplaces.US.com
126838-01A22
Page 23
CLEANING AND MAINTENANCE
WARNING: Turn off heater
and let cool before cleaning.
CAUTION: You must keep control areas, burner and circulating
air passageways of heater clean.
Inspect these areas of heater
before each use. Have heater
inspected yearly by a qualied
service person. Heater may need
more frequent cleaning due to
excessive lint from carpeting,
bedding material, pet hair, etc.
WARNING: Failure to keep
the primary air opening(s) of
the burner(s) clean may result
in sooting and property damage.
Once every year a qualied agency or certied
chimney sweep should examine and clean the
venting system of replace.
ODS/PILOT AND BURNER
Use a vacuum cleaner or small, soft bristled
brush to clean.
BURNER ORIFICE HOLDER AND
PILOT AIR INLET HOLE
The primary air inlet holes allow the proper
amount of air to mix with the gas. This provides a clean burning ame. Keep these holes
clear of dust, dirt and lint. Clean these air inlet
holes prior to each heating season. Blocked
air holes will create soot. We recommend that
you clean the unit every three months during
operation and have heater inspected yearly
by a qualied service person.
We also recommend that you keep burner tube
and pilot assembly clean and free of dust and
dirt. To clean these parts we recommend using
compressed air no greater than 30 PSI. Your
local computer store, hardware store or home
center may carry compressed air in a can. If
using compressed air in a can, please follow
directions on can. If you don’t follow directions
on can, you could damage pilot assembly.
1. Shut off unit, including pilot. Allow unit to
cool for at least thirty minutes.
2. Inspect burner, pilot and primary air inlet
holes on orice holder for dust and dirt
(see Figure 34).
126838-01A23
www.SuperiorFireplaces.US.com
3. Blow air through ports/slots and holes in
burner.
4. Check orice holder located at end of
burner tube again. Remove any large
particles of dust, dirt, lint or pet hair with
a soft cloth or vacuum cleaner nozzle.
5. Blow air into primary air holes on orice
holder.
6. In case any large clumps of dust have now
been pushed into burner, repeat steps 3
and 4.
Clean pilot assembly also. A yellow tip on pilot
ame indicates dust and dirt in pilot assembly.
There is a small pilot air inlet hole about 2"
from where pilot ame comes out of pilot assembly (see Figure 35). With unit off, lightly
blow air through air inlet hole. You may blow
through a drinking straw if compressed air is
not available.
Orice Holder (May Be Brass or
Aluminum Depending on Model)
Burner Tube
Primary Air Inlet
Holes (Shape of
Holes May Vary
by Model)
Figure 34 - Orice Holder On Outlet
Burner Tube
Pilot
Assembly
Pilot Air Inlet Hole
Figure 35 - Pilot Inlet Air Hole
LOGS
• If you remove logs for cleaning, refer to Install-
ing Logs, page 16, to properly replace logs.
• Replace log(s) if broken or chipped (dime-
sized or larger).
BURNER PRIMARY AIR HOLES
Air is drawn into burner through the 8 holes
in brass tting at entrance to burner. These
holes may become blocked with dust or lint.
Periodically inspect these holes for any blockage and clean as necessary. Blocked air holes
will create soot.
Page 24
TROUBLESHOOTING
WARNING: Turn off and unplug heater and let cool before servic-
ing. Only a qualied service person should service and repair heater.
CAUTION: Never use a wire, needle or similar object to clean
ODS/pilot. This can damage ODS/pilot unit.
Note: All troubleshooting items are listed in order of operation.
OBSERVED PROBLEM
When control knob is pressed
in and turned to PILOT, there
is not spark at ODS/pilot
POSSIBLE CAUSE
1. Ignitor electrode not connected to ignitor cable
2. Ignitor cable pinched or
wet
3. Broken ignitor cable
4. Bad piezo ignitor
5. Ignitor electrode broken
6. Ignitor electrode positioned
wrong
REMEDY
1. Reconnect ignitor cable
2. Free ignitor cable if pinched
by any metal or tubing.
Keep ignitor cable dry
3. Replace valve
4. Replace valve
5. Replace valve
6. Replace valve
When control knob is pressed
in and turned to PILOT, there
is spark at ODS/pilot but no
ignition
1. Gas supply turned off or
equipment shutoff valve
closed
2. Control knob not in PILOT
position
3. Control knob not pressed in
while in PILOT position
4. Air in gas lines when in-
stalled
5. Depleted gas supply (propane/LP only)
6. ODS/pilot is clogged
7. Gas regulator setting is not
correct
1. Turn on gas supply or open
equipment shutoff valve
2. Turn control knob to PILOT
position
3. Press in control knob while
in PILOT position
4. Continue holding down control knob. Repeat igniting operation until air is removed
5. Contact local propane/LP
gas company
6. Clean ODS/pilot (see
Cleaning and Maintenance,
page 23) or replace ODS/
pilot assembly
7. Replace gas regulator
www.SuperiorFireplaces.US.com
126838-01A24
Page 25
OBSERVED PROBLEM
ODS/pilot lights but flame
goes out when control knob
is released
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Control knob not fully
pressed in
2. Control knob not pressed in
long enough
3. Equipment shutoff valve not
fully open
4. Pilot flame not touching
thermocouple, which allows thermocouple to cool,
causing pilot ame to go
out. This problem could be
caused by one or both of
the following:
A) Low gas pressure
B) Dirty or partially clogged
ODS/pilot
5. Thermocouple connection
loose at control valve
6. Thermocouple damaged
7. Control valve damaged
REMEDY
1. Press in control knob fully
2. After ODS/pilot lights, keep
control knob pressed in 30
seconds
3. Fully open equipment shutoff valve
4. A) Contact local natural or
propane/LP gas company
B) Clean ODS/pilot (see
Cleaning and Maintenance,
page 23) or replace ODS/
pilot assembly
5. Hand tighten until snug,
then tighten 1/4 turn more
6. Replace pilot assembly
7. Replace control valve
Burner does not light after
ODS/pilot is lit
Delayed ignition of burner
Burner backring during combustion
1. Burner orice clogged
2. Inlet gas pressure is too
low
1. Manifold pressure is too
low
2. Burner orice clogged
1. Burner orice is clogged or
damaged
2. Damaged burner
3. Gas regulator defective
1. Clean burner (see Cleaning
and Maintenance, page 23)
or replace burner orice
2. Contact local natural or
propane/LP gas company
1. Contact local natural or
propane/LP gas company
2. Clean burner (see Cleaning
and Maintenance, page 23)
or replace burner orice
1. Clean burner (see Cleaning
and Maintenance, page 23)
or replace burner orice
2. Replace damaged burner
3. Replace gas regulator
126838-01A25
www.SuperiorFireplaces.US.com
Page 26
OBSERVED PROBLEM
Slight smoke or odor during
initial operation
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Not enough air
2. Gas regulator defective
3. Residues from manufacturing processes and logs
curing
REMEDY
1. Check burner for dirt and
debris. If found, clean
burner (see Cleaning and
Maintenance, page 23)
2. Replace gas regulator
3. Problem will stop after a few
hours of operation
Moisture/condensation no-
ticed on windows
Heater produces a whistling
noise when burner is lit
White powder residue forming
within burner box or on adjacent walls or furniture
Heater produces a clicking/
ticking noise just after burner
is lit or shut off
1. Not enough combustion/
ventilation air
1. Turning control knob to HI
position when burner is
cold
2. Air in gas line
3. Air passageways on heater
blocked
4. Dirty or partially clogged
burner orice
1. When heated, vapors from
furniture polish, wax, carpet
cleaners, etc. may turn into
a white powder residue
1. Metal expanding while
heating or contracting while
cooling
1. Refer to Air for Combustion and Ventilation requirements (page 6)
1. Turn control knob to LO
position and let warm up
for a minute
2. Operate burner until air is
removed from line. Have
gas line checked by local
natural or propane/LP gas
company
3. Observe minimum installation clearances (see
page 9)
4. Clean burner (see Cleaning
and Maintenance, page 23)
or replace burner orice
1. Turn heater off when using furniture polish, wax,
carpet cleaners or similar
products
1. This is normal with most
heaters. If noise is excessive, contact qualied service person
www.SuperiorFireplaces.US.com
126838-01A26
Page 27
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
Operating heater where impurities in air exist may create odors. Cleaning supplies, paint, paint
remover, cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These
fumes may mix with combustion air and create odors. These odors will disappear over time.
OBSERVED PROBLEM
Heater produces unwanted
odors
Heater shuts off in use (ODS
operates)
Gas odor even when control
knob is in OFF position
Gas odor during combustion
POSSIBLE CAUSE
1. Heater burning vapors from
paint, hair spray, glues,
cleaners, chemicals, new
carpet, etc. (See IMPOR-
TANT statement above)
2. Low fuel supply (propane/
LP only)
3. Gas leak. See Warning
statement above
1. Not enough fresh air is
available
2. Low line pressure
3. ODS/pilot is partially
clogged
1. Gas leak. See Warning
statement above
2. Control valve defective
1. Foreign matter between
control valve and burner
2. Gas leak. See Warning
statement above
REMEDY
1. Open window and ventilate room. Stop using odor
causing products while
heater is running
2. Rell supply tank (propane/
LP only)
3. Locate and correct all leaks
(see Checking Gas Con-
nections, page 14)
1. Open window and/or door
for ventilation
2. Contact local natural or
propane/LP gas company
3. Clean ODS/pilot (see
Cleaning and Maintenance,
page 23)
1. Locate and correct all leaks
(see Checking Gas Con-nections, page 14)
2. Replace control valve
1. Take apart gas tubing and
remove foreign matter
2. Locate and correct all leaks
(see Checking Gas Con-nections, page 14)
126838-01A27
www.SuperiorFireplaces.US.com
Page 28
PARTS
11
BURNER SYSTEMS VD1824NM AND VD1824PM
5
12
3
13
7
6
1
8
2
4
9
14
10
9
www.SuperiorFireplaces.US.com
126838-01A28
Page 29
This list contains replaceable parts used in your heater. When ordering parts, follow the
PARTS
instructions listed under Replacement Parts on page 33 of this manual.
120630-02 ODS Pilot, LP•1
6098867-20 Gas Regulator, NG•1
098867-21 Gas Regulator, LP•1
7122142-01 Manual Valve with Ignitor, NG•1
122142-02 Manual Valve with Ignitor, LP•1
8123483-01 Inlet Tube Assembly•1
122484-01 Burner Inlet Tube•1
9M11084-26 Screw, HWH AB 10-16 x 0.38• •7
10 098354-01 Control Knob• •1
11099056-26 Orice 0.1070•1
099056-19 Orice 0.0670•1
12 099387-08 Pilot Tube• •1
13 098249-01 ODS Nut• •2
14 M11084-38 Screw, HWH AB 8-18 x 0.38• •2
PARTS AVAILABLE — NOT SHOWN
100563-01 Warning Plate• •1
101055-08 Lighting Instructions Plate• •1
100639-01 Caution Decal• •1
101137-02 Hardware Kit• •1
GA6060Lava Rock• •1
** Not a eld replaceable part.
VD1824NM
VD1824PM
126838-01A29
www.SuperiorFireplaces.US.com
Page 30
LVD18-GO AND LVD24-GO LOGS
3
PARTS
2
1
5
4
KEY
NO. PART NO.DESCRIPTIONQTY.
LVD18-GO
6
LVD24-GO
1124673-01 Front Log•1
124674-01 Front Log•1
2124673-02 Center Log•1
124674-02 Center Log•1
3124673-03 Rear Log•1
124674-03 Rear Log•1
4124673-04 Left Crossover Log•1
124674-04 Left Crossover Log•1
5124673-05 Center Crossover Log•1
124674-05 Center Crossover Log•1
6124673-06 Right Front Crossover Log•1
124674-06 Right Front Crossover Log•1
www.SuperiorFireplaces.US.com
126838-01A30
Page 31
LVD18-PP AND LVD24-PP LOGS
PARTS
2
3
5
KEY
NO. PART NO.DESCRIPTIONQTY.
1
4
LVD18-PP
LVD24-PP
1123190-01 Rear Log•1
123190-06 Rear Log•1
2123190-02 Middle Log•1
123190-07 Center Log•1
3123190-03 Front Log•1
123190-08 Front Log•1
4123190-04 Top Right Log•1
123190-09 Top Right Log•1
5123190-10 Top Left Log•1
123190-05 Top Left Log•1
126838-01A31
www.SuperiorFireplaces.US.com
Page 32
LVD18-CH AND LVD24-CH LOGS
5
6
PARTS
4
1
2
KEY
NO.
1125959-04125959-05 Rear Log (#1)1
2125959-03125959-03 Middle Log (#2)1
3125959-01125959-02 Front Log (#3)1
4125959-08125959-08 Top Right Log (#4)1
5125959-07125959-07 Top Middle Log (#5)1
6125959-06125959-06 Top Left Log (#6)1
PART NUMBERS
DESCRIPTIONQTYLVD18-CHLVD24-CH
www.SuperiorFireplaces.US.com
3
126838-01A32
Page 33
SPECIFICATIONS
VD1824PM
• Rating (Variable): 19,000/36,000 Btu/Hr
• Type Gas: Propane/LP
• Ignition: Piezo
• Pressure Manifold: 10.0" W.C.
• Inlet Gas Pressure (in. of water):
Maximum 14" W.C., Minimum* 11" W.C.
• Shipping Weight: 27 lbs.
* For input adjustment
REPLACEMENT PARTS
Note: Use only original replacement parts.
This will protect your warranty coverage for
parts replaced under warranty.
Contact authorized dealers of this product.
If they can’t supply original replacement
part(s), call INNOVATIVE HEARTH PRODUCTS at 1-800-655-2008.
VD1824NM
• Rating (Variable): 19,000/36,000 Btu/Hr
• Type Gas : Natural Gas
• Ignition: Piezo
• Pressure Manifold: 4.5" W.C.
• Inlet Gas Pressure (in. of water):
Maximum 10.5" W.C., Minimum* 5" W.C.
• Shipping Weight: 29 lbs.
* For input adjustment
When calling, have ready
• your name
• your address
• model and serial numbers of your heater
• how heater was malfunctioning
• type of gas used (propane/LP or natural
gas)
• purchase date
Usually, we will ask you to return the part to
the factory.
TECHNICAL SERVICE
You may have further questions about installation, operation or troubleshooting. If so,
contact INNOVATIVE HEARTH PRODUCTS
at 1-800-655-2008. When calling please
have your model and serial numbers of your
heater ready.
You can also visit our web site atwww.IHP.US.com.
126838-01A33
www.SuperiorFireplaces.US.com
When Gas Pressure Is Too Low
• pilot will not stay lit
• burners will have delayed ignition
• heater will not produce specied heat
• propane/LP gas supply may be low
You may feel your gas pressure is too low. If
so, contact your local natural or propane/LP
gas supplier.
SERVICE HINTS
Page 34
ACCESSORIES
Purchase these accessories from your local
dealer. If they can not supply these accesso-
ries, either contact your nearest Parts Central
or call INNOVATIVE HEARTH PRODUCTS
at 1-800-655-2008 for information. You can
also write to the address listed on the back
page of this manual.
FIREPLACE HOOD
Black - GA6050
Antique Brass - GA6053
For all models. Helps deect heat away from
mantel or wall above replace. Fits openings
28" to 48" wide.
DAMPER CLAMP - GA6080
For all models. Permanently opens chimney
ue damper for vented operation.
LAVA ROCK - GA6060
For all models. Order when additional rock
is desired.
FLOOR MEDIA KIT - FM100
For all models. Includes lava rock, burner
embers, and burner cinders
Innovative Hearth Products Limited Three Year Warranty ("IHP") warrants your Superior™ brand Gas Log Set ("Product") to be free from defects in materials and workmanship
at the time of manufacture. The logs and grate carry the Limited Three Year Warranty. After installation, if covered components manufactured by IHP are found to be defective in materials or workmanship during the Limited Three Year Warranty period and while the Product remains at the site of the original installation, IHP will, at its option,
repair or replace the covered components. If repair or replacement is not commercially practical, IHP will, at its option, refund the purchase price or wholesale price of the
IHP product, whichever is applicable. IHP will also pay IHP prevailing labor rates, as determined in its sole discretion, incurred in repairing or replacing such components.
THERE ARE EXCLUSIONS AND LIMITATIONS to this Limited Three Year Warranty as described herein.
COVERAGE COMMENCEMENT DATE
Warranty coverage begins on the date of installation. In the case of new home construction, warranty coverage begins on the date of first occupancy of the dwelling or six
months after the sale of the Product by an independent IHP dealer, whichever occurs earlier. The warranty shall commence no later than 24 months following the date of
product shipment from IHP, regardless of the installation or occupancy date.
EXCLUSIONS AND LIMITATIONS
This Limited Three Year Warranty applies only if the Product is installed in the United States or Canada and only if operated and maintained in accordance with the printed
instructions accompanying the Product and in compliance with all applicable installation and building codes and good trade practices.
This warranty is non-transferable and extends to the original owner only. The Product must be purchased through a listed supplier of IHP and proof of purchase must be
provided. The following do not carry the Limited Three Year Warranty but are warranted as follows:
Gas components – Repair or replacement for one year from the date of installation.
Remote control – Repair or replacement for one year from the date of installation.
Labor coverage – Prevailing IHP labor rates apply for the warranty period of the component.
Parts not otherwise listed carry a 90 day warranty from the date of installation.
Whenever practicable, IHP will provide replacement parts, if available, for a period of 10 years from the last date of manufacture of the product.
IHP will not be responsible for: (a) damages caused by normal wear and tear, accident, riot, fire, flood or acts of God; (b) damages caused by abuse, negligence, misuse, or
unauthorized alteration or repair of the Product affecting its stability or performance (The Product must be subjected to normal use. The Product is designed to burn either
natural or propane gas only. Burning conventional fuels such as wood, coal or any other solid fuel will cause damage to the Product, will produce excessive temperatures
and could result in a fire hazard.); (c) damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product;
(d) damages, repairs or inefficiency resulting from faulty installation or application of the Product.
This Limited Three Year Warranty covers only parts and labor as provided herein. In no case shall IHP be responsible for materials, components or construction which are
not manufactured or supplied by IHP or for the labor necessary to install, repair or remove such materials, components or construction. Additional utility bills incurred due to
any malfunction or defect in equipment are not covered by this warranty. All replacement or repair components will be shipped F.O.B. from the nearest stocking IHP factory.
LIMITATION ON LIABILITY
It is expressly agreed and understood that IHP’s sole obligation and the purchaser’s exclusive remedy under this warranty, under any other warranty, expressed or implied,
or in contract, tort or otherwise, shall be limited to replacement, repair, or refund, as specified herein.
In no event shall IHP be liable for any incidental or consequential damages caused by defects in the Product, whether such damage occurs or is discovered before or after
replacement or repair, and whether such damage is caused by IHP’s negligence. IHP has not made and does not make any representation or warranty of fitness for a particular
use or purpose, and there is no implied condition of fitness for a particular use or purpose.
IHP makes no expressed warranties except as stated in this Limited Three Year Warranty. The duration of any implied warranty is limited to the duration of this expressed
warranty.
No one is authorized to change this Limited Three Year Warranty or to create for IHP any other obligation or liability in connection with the Product. Some states and
provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. The provisions of
this Limited Three Year Warranty are in addition to and not a modification of or subtraction from any statutory warranties and other rights and remedies provided by law.
INVESTIGATION OF CLAIMS AGAINST WARRANTY
IHP reserves the right to investigate any and all claims against this Limited Three Year Warranty and to decide, in its sole discretion, upon the method of settlement.
To receive the benefits and advantages described in this Limited Three Year Warranty, the appliance must be installed and repaired by a licensed contractor approved by IHP.
Contact IHP at the address provided herein to obtain a listing of approved dealers/distributors. IHP shall in no event be responsible for any warranty work done by a
contractor that is not approved without first obtaining LHP's prior written consent.
HOW TO REGISTER A CLAIM AGAINST WARRANTY
In order for any claim under this warranty to be valid, you must contact the IHP dealer/distributor from which you purchased the product. If you cannot locate the dealer/
distributor, then you must notify IHP in writing. IHP must be notified of the claimed defect in writing within 90 days of the date of failure. Notices should be directed to the
IHP Warranty Department at 1508 Elm Hill Pike, Suite 108; Nashville, TN 37210 or visit our website at WWW.SUPERIORFIREPLACES.US.COM.