Superior Installation And Operation Instructions Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
Installation and Operation Instructions
Superior™ Unvented (Vent-Free) Gas Log Heater
P/N 126838-01 Rev. A 01/2014Models
VD1824NMVD1824PM
P126838-01
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
This appliance may be installed in an aftermarket permanently located, manufactured (mobile) home, where not
prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This
appliance is not convertible for use with other gases.
WARNING: This appliance is for installation only in a solid-fuel burning masonry or UL127 factory-built
fireplace or in a listed ventless firebox enclosure. It is design-certified for these installations in accordance
with ANSI Z21.11.2. Exception: DO NOT install this appliance in a factory-built fireplace that includes
instructions stating it has not been tested or should not be used with unvented gas logs.
This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions
for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation
section on page 6 of this manual.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a qualified installer, service agency or the gas supplier.
WARNING: Improper installation, adjustment, alteration, service
or maintenance can cause
injury or property damage. Refer to this manual
for correct installation and
operational procedures.
For assistance or additional information consult
a qualied installer, service agency or the gas
supplier.
WARNING: This ap-
pliance is for installation
only in a solid-fuel burning
masonry or UL127 factory-
built replace or in a listed
ventless rebox enclosure.
It is design-certified for
these installations in accordance with ANSI Z21.11.2.
Exception: DO NOT install
this appliance in a factory-
built replace that includes
instructions stating it has
not been tested or should
not be used with unvented
gas logs.
WARNING: This is an
unvented gas-red heater. It uses air (oxygen)
from the room in which
it is installed. Provisions
for adequate combustion
and ventilation air must
be provided. Refer to Air
for Combustion and Ventilation section on page 6
of this manual.
This appliance may be installed in an aftermarket,*
permanently located,
manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for
use with the type of gas
indicated on the rating
plate. This appliance is
not convertible for use
with other gases.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
SAFETY
Continued
WARNING: This product
contains and/or generates
chemicals known to the State
of California to cause cancer or
birth defects or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, op-
erate or service this replace.
Improper use of this replace
can cause serious injury or
death from burns, re, explosion, electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the
u, with headaches, dizziness or nausea. If
you have these signs, the replace may not
be working properly. Get fresh air at once!
Have replace serviced. Some people are
more affected by carbon monoxide than oth-
ers. These include pregnant women, people
with heart or lung disease or anemia, those
under the inuence of alcohol and those at
high altitudes.
Natural and Propane/LP Gas: Natural and
propane/LP gases are odorless. An odormaking agent is added to these gases. The
odor helps you detect a gas leak. However,
the odor added to the gas can fade. Gas may
be present even though no odor exists.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this replace.
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not allow fans
to blow directly into the replace.
Avoid any drafts that alter burner
ame patterns. Ceiling fans can
create drafts that alter burner ame
patterns. Altered burner patterns
can cause sooting.
Due to high temperatures, the appliance should be located out of
trafc and away from furniture and
draperies.
Do not place clothing or other
ammable material on or near the
appliance. Never place any objects
on the heater.
Heater base assembly becomes
very hot when running heater. Keep
children and adults away from hot
surface to avoid burns or clothing
ignition. Heater will remain hot for a
time after shutdown. Allow surface
to cool before touching.
Carefully supervise young children
when they are in the room with heater.
When using the hand-held remote
accessory, keep selector switch in
the OFF position to prevent children
from turning on burners with remote.
You must operate this heater with
the replace screen and hood in
place. Make sure replace screen
and hood are in place before running
heater. The replace screen shall
have openings for introduction of
combustion air.
Keep the appliance area clear and
free from combustible materials,
gasoline and other ammable vapors and liquids.
SAFETY
Continued
1. This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases.
2. Do not place propane/LP supply tank(s)
inside any structure. Locate propane/LP
supply tank(s) outdoors (propane/LP units
only).
3. To prevent performance problems, the use
of a propane/LP tank of less than 100 lbs.
capacity is not recommended (propane/
LP units only).
4. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas sup-
plier’s instructions
• if you cannot reach your gas supplier,
call the re department
5. This heater shall not be installed in a
bedroom or bathroom.
6. Do not burn solid-fuel in a replace in
which a vent-free room heater is installed.
7. Before installing in a solid fuel burning replace, the chimney ue and rebox must
be cleaned of soot, creosote, ashes and
loose paint by a qualied chimney cleaner.
Creosote will ignite if highly heated. A dirty
chimney ue may create and distribute
soot within the house. Inspect chimney
ue and rebox for damage. If damaged,
repair ue before operating heater.
8. If replace has glass doors, never operate
this heater with glass doors closed. Any
glass doors shall be fully opened when the
appliance is in operation. If you operate
heater with doors closed, heat buildup
inside replace will cause glass to burst.
Make sure there are no obstructions
across openings of replace.
9. This log heater is designed to be smoke-
less. If logs ever appear to smoke, turn off
heater and call a qualied service person.
Note: During initial operation, slight smoking could occur due to log curing and
heater burning manufacturing residues.
10. To prevent the creation of soot, follow the
instructions in Cleaning and Maintenance,
page 23.
www.SuperiorFireplaces.US.com
11. Before using furniture polish, wax, carpet
cleaner or similar products, turn heater off.
If heated, the vapors from these products
may create a white powder residue within
burner box or on adjacent walls or furniture.
12. This heater needs fresh, outside air ven-
tilation to run properly. This heater has an
Oxygen Depletion Sensing (ODS) safety
shutoff system. The ODS shuts down the
heater if not enough fresh air is available.
See Air for Combustion and Ventilation,
page 6. If heater keeps shutting off, see
Troubleshooting, page 24.
13. Do not run heater
• where ammable liquids or vapors are
used or stored
• under dusty conditions
14. Do not use this heater to cook food or burn
paper or other objects.
15. Do not use heater if any part has been ex-
posed to or under water. Immediately call
a qualied service technician to inspect
the room heater and to replace any part
of the control system and any gas control
which has been under water.
16. Do not operate heater if any log is broken.
Do not operate heater if a log is chipped
(dime-sized or larger).
17. Turn heater off and let cool before servic-
ing. Only a qualied service person should
service and repair heater.
18. Operating heater above elevations of
4,500 feet could cause pilot outage.
19. Provide adequate clearances around air
openings.
20. Solid fuels shall not be burned in a replace in which an unvented room heater
is installed.
21. Installation and the provisions for combustion and ventilation air must conform
with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54.
22. When installing as a vented appliance in a
manufactured home or mobile home, the
installation must conform with the Manu-
factured Home Construction and Safety
Standard, Title 24 CFR, Part 3280, or
when applicable, with Manufacture Home
Install and use heater with care. Follow all
local codes. In the absence of local codes,
use the latest edition of The National Fuel
Gas Code ANSI Z223/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269
Log Set
Right
Side
State of Massachusetts: The installation must be made by a licensed plumber
or gas fitter in the Commonwealth of
Massachusetts.
Sellers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527
CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for
bedroom and bathroom installation in the
Commonwealth of Massachusetts.
UNPACKING
Note: Do not pick up heater base assem-
CAUTION: Do not remove the
data plates from the grate assembly. The data plates contain
important warranty and safety
information.
1. Remove logs and heater base assembly
from cartons.
bly by burners. This could damage heater.
Always handle base assembly by grate.
2. Remove all protective packaging applied
to logs and heater for shipment.
3. Check heater for any shipping damage.
If heater is damaged call INNOVATIVE
HEARTH PRODUCTS at 1-800-655-2008
for replacement parts before returning to
dealer.
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no
outside venting. There is no heat loss out a
vent or up a chimney. Heat is generated by
realistic, dancing yellow ames. This heater
is designed for vent-free operation with ue
damper closed. It has been tested and approved to ANSI Z21.11.2 standard for unvented heaters. State and local codes in some
areas prohibit the use of vent-free heaters.
126838-01A5
www.SuperiorFireplaces.US.com
SAFETY PILOT
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS/pilot is a required feature for vent-free
room heaters. The ODS/pilot shuts off the
heater if there is not enough fresh air.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall
not be installed in a room or space
unless the required volume of indoor combustion air is provided
by the method described in the
National Fuel Gas Code, ANSI
Z223.1/NFPA 54, the International
Fuel Gas Code, or applicable
local codes. Read the following
instructions to insure proper
fresh air for this and other fuelburning appliances in your home.
Today’s homes are built more energy efcient
than ever. New materials, increased insulation
and new construction methods help reduce
heat loss in homes. Home owners weather
strip and caulk around windows and doors
to keep the cold air out and the warm air in.
During heating months, home owners want
their homes as airtight as possible.
While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning appliances need fresh air for proper combustion
and ventilation.
Exhaust fans, replaces, clothes dryers and
fuel burning appliances draw air from the house
to operate. You must provide adequate fresh
air for these appliances. This will insure proper
venting of vented fuel-burning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code. ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 6 through 8 will help
you classify your space and provide adequate
ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of unusually tight construction, you must provide
additional fresh air.
www.SuperiorFireplaces.US.com
Unusually tight construction is dened as
construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6x10
less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window
and door frames, between sole plates
and oors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical and gas lines
and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh air.
See Ventilation Air From Outdoors, page 8.
If your home does not meet all of the three
criteria above, proceed to Determining Fresh-Air Flow For Heater Location.
Conned Space and Unconned Space
The National Fuel Gas Code ANSI Z223.1/
NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu per hour (4.8 m3 per kw) of the ag-
gregate input rating of all appliances installed
in that space and an unconned space as a
space whose volume is not less than 50 cubic
feet per 1,000 Btu per hour (4.8 m3 per kw)
of the aggregate input rating of all appliances
installed in that space. Rooms communicating
directly with the space in which the appliances
are installed*, through openings not furnished
with doors, are considered a part of the unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.
-11
kg per pa-sec-m2) or
DETERMINING FRESH-AIR FLOW
FOR FIREPLACE LOCATION
Determining if You Have a Conned or
Unconned Space
Use this work sheet to determine if you have
a conned or unconned space.
Space: Includes the room in which you will
install replace plus any adjoining rooms with
doorless passageways or ventilation grills
between the rooms.
126838-01A6
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills Into
Adjoining
Room,
Option 1
12"
12"
AIR FOR COMBUSTION AND VENTILATION
1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2,560 cu. ft.
(volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2,560 cu. ft. (volume of space) x
20 = 51,200 (maximum Btu/Hr the space can
support)
3. Add the Btu/Hr of all fuel burning appliances
in the space.
Vent-free replace __________ Btu/HrGas water heater* __________ Btu/Hr
Gas furnace __________ Btu/Hr
Vented gas heater __________ Btu/Hr
Gas replace logs __________ Btu/Hr
Other gas appliances* + __________ Btu/Hr
Total = __________ Btu/Hr
* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
Example:
Gas water heater __________ Btu/HrVent-free replace __________ Btu/Hr
Total = __________ Btu/Hr
4. Compare the maximum Btu/Hr the space
can support with the actual amount of Btu/
Hr used.
_______
support)
_______ Btu/Hr (actual amount of Btu/Hr
used)
Example: 51,200 Btu/Hr (maximum the
71,500 Btu/Hr (actual amount of
The space in the example is a conned space
because the actual Btu/Hr used is more than the
maximum Btu/Hr the space can support. You
must provide additional fresh air. Your options
are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides an
unconned space, remove door to adjoining
126838-01A7
Btu/Hr (maximum the space can
space can support)
Btu/Hr used)
40,000
31,500
71,500
www.SuperiorFireplaces.US.com
Continued
room or add ventilation grills between rooms.
See Ventilation Air From Inside Building.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 8.
C. Install a lower Btu/Hr replace, if lower Btu/
Hr size makes room unconned.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is
an unconned space. You will need no additional
fresh air ventilation.
WARNING: If the area in which
the heater may be operated does
not meet the required volume for
indoor combustion air, combustion and ventilation air shall be
provided by one of the methods
described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54,
the International Fuel Gas Code,
or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconned space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the oor on the
wall connecting the two spaces (see options 1
and 2, Figure 2). You can also remove door into
adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code ANSI Z223.1/
NFPA 54 Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
Figure 2 - Ventilation Air from Inside Building
Outlet
Air
Ventilated
Attic
Outlet
A
ir
Inlet
Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
AIR FOR COMBUSTION AND VENTILATION
Continued
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two permanent openings: one within 12" of the ceiling
and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermo-
stat-controlled power vent. Heated air entering
the attic will activate the power vent.
NOTICE: State or local codes may
only allow operation of this appliance
in a vented conguration. Check your
state or local codes.
WARNING: Before installing in
a solid fuel burning replace, the
chimney ue and rebox must be
cleaned of soot, creosote, ashes and
loose paint by a qualied chimney
cleaner. Creosote will ignite if highly
heated. A dirty chimney ue may
create and distribute soot within
the house. Inspect chimney ue
and rebox for damage. If damaged,
repair ue before operating heater.
WARNING: Any outside air ducts
and/or ash dumps in the replace
shall be permanently closed at time
of appliance installation.
Figure 3 - Ventilation Air from Outdoors
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your primary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
vice person must install heater.
Follow all local codes.
WARNING: A qualied ser-
www.SuperiorFireplaces.US.com
WARNING: Seal any fresh air
vents or ash clean-out doors located
on oor or wall of replace. If not,
drafting may cause pilot outage
or sooting. Use a heat-resistant
sealant. Do not seal chimney ue
damper.
WARNING: Never install the
heater
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture, cloth-
ing or other ammable objects
are less than 36" from front or
42" from top of heater. For side
clearances see Figure 4, page 9
• in high trafc areas
• in windy or drafty areas
126838-01A8
INSTALLATION
Continued
CAUTION: This heater creates warm air currents. These
currents move heat to wall sur-
faces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities (such as, but
not limited to, tobacco smoke,
aromatic candles, cleaning uids, oil or kerosene lamps, etc.) in
the air exist, may discolor walls
or cause odors.
IMPORTANT: Vent-free heaters add moisture
to the air. Although this is benecial, installing
heater in rooms without enough ventilation
air may cause mildew to form from too much
moisture. See Air for Combustion and Ventilation, page 6.
CHECK GAS TYPE
Use only the correct gas type (natural or propane/LP) for your unit. If your gas supply is not
correct, do not install heater. Call dealer where
you bought heater for proper type heater.
WARNING: This appliance is
equipped for either natural gas
or propane/LP gas but not both.
Gas type is indicated on the rating plate. Field conversion is not
permitted.
INSTALLATION AND CLEARANCES
(Vent-Free Operation Only)
MINIMUM FIREPLACE CLEARANCE
TO COMBUSTIBLE MATERIALS
Side Wall 16", Ceiling 42", Front 36"
WARNING: Maintain the
minimum clearances. If you can,
provide greater clearances from
oor, ceiling and adjoining wall.
Carefully follow the instructions below. This
will ensure safe installation into a masonry,
UL127-listed manufactured replace or certied vent-free rebox.
MINIMUM CLEARANCES FOR SIDE
COMBUSTIBLE MATERIAL, SIDE WALL
AND CEILING
A. Clearances from the side of the replace
cabinet to any combustible material and
wall should follow diagram in Figure 4.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and
protrudes 3 1/2" from the wall. This com-
bustible material must be 4" from the side
of the replace cabinet (see Figure 4).
Note: When installing your gas logs into
a manufactured rebox, follow rebox
manufacturer’s instructions for minimum
clearances to combustible materials.
B. Clearances from the top of the replace
opening to the ceiling should not be less
than 42".
NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney ue damper open.
If running heater with damper
open, noncombustible material
above replace opening is not
needed. Go to Installing Damper
Clamp Accessory for Vented
Operation, page 11.
LOG SIZING REQUIREMENTS
Minimum Firebox
Log
Size
Height Depth
18"17"13.5"24"20.5"
24"17"13.5"28"20.5"
* Measured at 13.5" depth.
126838-01A9
Front
Width
Rear *
Width
*Minimum 16" from Side Wall
www.SuperiorFireplaces.US.com
Example
*
Figure 4 - Minimum Clearance for
Combustible to Wall
Minimum
Noncombustible
Material
Minimum
Noncombustible
Material Height
Distances to
Underside of
Mantel
Top of
Fireplace
Opening
Underside
of Mantel
Shelf
Mantel Shelf
12"
(A)
18" 20" 22" 24"
All
minimum
distances
are in
inches
2
1
/2"
6"
8"
10"
INSTALLATION
Heat Resistant
Material
(A)
Continued
MINIMUM NONCOMBUSTIBLE
MATERIAL CLEARANCES
If Not Using Mantel
Note: If using a mantel, proceed to If Using
Mantel. If not using a mantel, follow the information below.
You must have noncombustible material(s)
above the replace opening. Noncombustible
materials (such as slate, marble, tile, etc.)
must be at least 1/2" thick. With sheet metal,
you must have noncombustible material behind it. Noncombustible material must extend
at least 12" up (for all models). See Figure 5
for minimum clearances.
Noncombustible
Material Distance (A)
12" or moreNoncombustible mate-
Between 8"
and 12"
Less than 8"Noncombustible material
Requirements for Safe
Installation
rial OK.
Install fireplace hood
accessory (GA6050 or
GA6053, see Accessories, page 34).
must be extended to at
least 8". See Between
8" and 12", above. If you
cannot extend material,
you must operate heater
with ue damper open and
damper clamp installed.
If Using Mantel
You must have noncombustible material(s)
above the replace opening. Noncombustible
materials (such as slate, marble, tile, etc.) must
be at least 1/2" thick. With sheet metal, you
must have noncombustible material behind it.
Noncombustible material must extend at least
8 inches up (for all models). If noncombustible
material is less than 12", you must install the
replace hood accessory. Even if noncombustible material is more than 12", you may need
the hood accessory to deect heat away from
your mantel shelf. See Figure 5, and Figures
6 and 7 (page 11) for minimum clearances.
IMPORTANT: If you cannot meet these mini-
mum clearances, you must operate heater
with chimney ue damper open. Go to Install-
ing Damper Clamp Accessory for Vented
Operation, page 11.
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required
clearances between replace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between
mantel shelf and top of replace opening, a
hood is not required (see Figure 6).
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
www.SuperiorFireplaces.US.com
Figure 6 - Minimum Mantel Clearances
Without Using Hood
126838-01A10
INSTALLATION
Minimum
Noncombustible
Material
8"
Min.
12" 15" 18" 20"
2½"
6"
8"
10"
12"
Distances to
Underside of
Mantel
Hood
(GA6050 or
GA6053)
Top of
Fireplace
Opening
Underside
of Mantel
Shelf
Mantel Shelf
14"
Min.
Combustible
Material
Noncombustible Material
Hearth
5"
Min.
Combustible
Material
Continued
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6, page 10, are
not met, you must have a hood. When using
a hood there are still certain minimum mantel
clearances required. Follow minimum clearances shown in Figure 7 when using hood.
FLOOR CLEARANCES
A. If installing appliance on the oor level,
you must maintain the minimum distance
of 14" to combustibles (see Figure 8).
B. If combustible materials are less than
14" to the replace, you must install appliance at least 5" above the top surface
of combustible ooring including tile and
carpet. (see Figure 9).
126838-01A11
Figure 7 - Minimum Mantel Clearances
When Using Hood
NOTICE: Surface temperatures
of adjacent walls and mantels become hot during operation. Walls
and mantels above the rebox
may become hot to the touch.
If installed properly, these temperatures meet the requirement
of the national product standard.
Follow all minimum clearances
shown in this manual.
NOTICE: If your installation does
not meet the minimum clearances shown, you must do one
of the following:
• raise the mantel to an acceptable height
www.SuperiorFireplaces.US.com
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
INSTALLING DAMPER CLAMP
ACCESSORY FOR VENTED
OPERATION
Note: When used as a vented heater, appliance must be installed only in a solid-fuel
burning replace with a working ue and constructed of noncombustible material.
For Massachusetts Residents Only: Installation of this vented gas log set in the Com-
monwealth of Massachusetts requires the
damper be permanently removed or welded
in the fully open position.
If your heater is a manually-controlled model,
you may use this heater as a vented product.
There are three reasons for operating your
heater in the vented mode.
1. The replace does not meet the clearance
to combustibles requirements for vent-free
operation.
2. State or local codes do not permit ventfree operation.
3. You prefer vented operation.
INSTALLATION
Continued
If reasons number 1 or 2 apply to you,
you must permanently open chimney ue
damper. You must install the damper clamp
accessory (to order, see Accessories, page
34). This will insure vented operation (see Figure 10). The damper clamp will keep damper
open. Installation instructions are included
with clamp accessory.
Damper
Clamp
Damper
Masonry Fireplace
Figure 10 - Attaching Damper Clamp
See chart for minimum permanent ue opening you must provide. Attach damper clamp so
the minimum permanent ue opening will be
maintained at all times.
Area of Various Standard
DiameterArea
5"20 sq. in.
6"29 sq. in.
7"39 sq. in.
8"51 sq. in.
Chimney
Height
6' to 15'39 sq. in.
15' to 30'29 sq. in.
INSTALLING HEATER BASE
ASSEMBLY
WARNING: You must secure
this heater to replace oor. If
not, heater will move when you
adjust controls. Moving heater
may cause a gas leak or log
misplacement.
Damper
Damper
Clamp
Manufactured Fireplace
Round Flues
Minimum Permanent
Flue Opening
www.SuperiorFireplaces.US.com
Damper
WARNING: If installing in a
sunken replace, special care
is needed. You must raise the
replace oor to allow access to
heater control panel. This will in-
sure adequate air ow and guard
against sooting and controls
being damaged. Raise replace
oor with noncombustible mate-
rial. Make sure material is secure.
CAUTION: Do not pick up
heater base assembly by burners. This could damage heater.
Only handle base assembly by
grates.
IMPORTANT: Make sure the heater burners
are level. If heater is not level, heater will not
work properly.
Installation Items Needed
• hardware package (provided with heater)
• approved exible gas hose and ttings (if
allowed by local codes)
• sealant (resistant to propane/LP gas, not
provided)
• electric drill with 3/16" drill bit (metal or
masonry as applicable)
• athead screwdriver
• pipe wrench
1. Connect approved exible gas hose to
gas control tting in heater (see Figure
11, page 13).
IMPORTANT: Hold gas tting with wrench
when connecting exible gas hose.
2. Locate two masonry screws in hardware
package.
3. Place heater base in replace.
4. Place logs in their proper position on heater
base (see Installing Logs, page 16).
5. Center heater base and logs front-to-back
and side-to-side in replace.
6. Carefully remove logs without moving
heater base.
7. Mark screw locations through one hole on
each side of the mounting bracket (see
Figure 12, page13). If installing in a brickbottom replace, mark screw locations in
mortar joint of bricks.
126838-01A12
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.