WARNING: Improper installation, adjustment, alteration,
service or maintenance can
WARNING: Any change to
this rebox or its controls can
be dangerous.
cause injury or property damage.
Refer to this manual for correct
installation and operational
procedures. For assistance or
additional information consult
a qualified installer, service
agency or the gas supplier.
This appliance may be installed
in an aftermarket,* permanently
located, manufactured (mobile)
home, where not prohibited by
local codes.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer.
WARNING: This product
contains and/or generates
chemicals known to the state
of California to cause cancer or
birth defects or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble,
operate or service this heater.
Improper use of this replace
can cause serious injury or
death from burns, re, explosion, electrical shock and carbon
WARNING: Do not allow fans
to blow directly into the rebox.
Avoid any drafts that alter burner
ame patterns. Ceiling fans can
create drafts that alter burner
ame patterns. Altered burner
patterns can cause sooting.
WARNING: Do not use a
blower insert, heat exchanger
insert or other accessory not approved for use with this rebox.
Do not place clothing or other
ammable material on or near
the appliance. Never place any
objects in the rebox or on logs.
Firebox front and screen become
very hot when running heater.
Keep children and adults away
from hot surface to avoid burns
or clothing ignition. Firebox
will remain hot for a time after
shutdown. Allow surface to cool
before touching.
Carefully supervise young children when they are in the room
with rebox.
monoxide poisoning.
THE FIREBOX CANOPY (HOOD) MUST NOT BE MODIFIED OR REPLACED WITH A CANOPY (HOOD) THAT MAY BE PROVIDED WITH
THE UNVENTED DECORATIVE ROOM HEATER.
SAFETY
Continued
You must operate this replace
with the provided fireplace
screen, hood if provided, in
place. Make sure these parts
are in place and screens are
closed before running rebox.
The supplied hood may not be
replaced with a hood which may
be provided with a log heater.
Keep the replace area clear and
free from combustible materials,
gasoline and other ammable
vapors and liquids.
1. Do not use this rebox as a wood-burning
replace. Use only decorative unvented
room heaters (log sets).
2. Do not add extra logs or ornaments such as
pine cones, vermiculite or rock wool. Using
these added items can cause sooting.
LOCAL CODES
Install and use heater with care. Follow all
local codes. In the absence of local codes,
use the latest edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*. Firebox must
be electrically grounded in accordance with
the National Electrical Code, ANSI/NFPA70
(latest edition).
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
State of Massachusetts: The installation
must be made by a licensed plumber or
gas tter in the Commonwealth of Mas-
sachusetts.
Sellers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527
CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for
bedroom and bathroom installation in the
Commonwealth of Massachusetts.
3. Use only the provided hood or appropri-
ate hood accessory. See Accessories on
page 17.
4. Vent-free gas log heaters installed in these
reboxes require fresh air ventilation to
run properly. See Air for Combustion and
Ventilation, page 6.
5. Do not run rebox
• where ammable liquids or vapors are
used or stored
• under dusty conditions
6. Do not use this rebox to cook food or
burn paper or other objects.
7. Turn rebox off and let cool before servicing. Only a qualied service person should
service and repair rebox.
8. Operating rebox above elevations of
4,500 feet could cause pilot outage.
9. Do not use rebox if it has been under water
due to shock hazard that could result with
the blower accessary (if installed) in place.
to minimum rebox requirements supplied
with log heater.) It requires no outside vent-
ing or chimney making installation easy and
inexpensive. When used without the blower,
the rebox requires no electricity making it
ideal for emergency backup heat.
OUTSIDE AIR KIT ACCESSORY
The optional AK4 and AK4F air kit provides additional outdoor air to improve burner efciency
and reduce build-up of condensation in living
space. Follow instructions included with air kit.
REFRACTORY BRICK LINER
Your rebox may feature a concrete refractory
brick liner. As with all concrete liners, this liner
may develop slight cracks when exposed to
heat. These cracks will not affect the performance of the replace or vent-free gas logs.
OPTIONAL FIBER LINERS
For a vintage look, the ber panels give a old
masonry brick look and are light weight and
easy to install.
LOCATING FIREBOX
PLANNING
Plan where you will install the rebox. This will
save time and money later when you install
the rebox. Before installation, consider the
following:
1. Where the rebox will be located. Allow for
wall and ceiling clearances (see Installa-
tion Clearances, page 9).
2. Everything needed to complete installation.
3. These models CANNOT be installed in a
bedroom unless the maximum Btu rating
of the installed vent-free log set is less
than 10,000 Btu/hr.
4. Proper air for combustion and ventilation
(page 6).
36" MODELS
7.75622.605
PRODUCT SPECIFICATIONS
37.416
26.482
Firebox Top View
3.846
4.427
24.906
5.063
21.412
33.099
12.942
8.201
6.625
8.197
2.968
Electrical
Outlet
9.734
7.363
38.125
40.057
36.125
Right Side View Right Side View
Front View
Outside Air
Kit Location
(Optional)
Figure 1 - Firebox Dimensions 36'' Models
www.SuperiorFireplaces.US.com
9.256
9.734
126715-01A4
42" MODELS
PRODUCT SPECIFICATIONS
Continued
Firebox Top View
26.504
8.163
3.628
Electrical
Outlet
9.705
7.330
42.063
44.063
45.995
Right Side View Right Side View
Front View
7.76328.612
21.041
24.926
4.392
21.413
37.307
Outside Air
Kit Location
(Optional)
33.147
12.933
8.193
6.644
9.227
9.705
Figure 2 - Firebox Dimensions 42'' Models
126715-01A5
www.SuperiorFireplaces.US.com
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall
not be installed in a room or space
unless the required volume of indoor combustion air is provided
by the method described in the
National Fuel Gas Code, ANSI
Z223.1/NFPA 54, the International
Fuel Gas Code, or applicable
local codes. Read the following
instructions to insure proper fresh
air for this and other fuel-burning
appliances in your home.
Today’s homes are built more energy efcient
than ever. New materials, increased insulation
and new construction methods help reduce
heat loss in homes. Home owners weather
strip and caulk around windows and doors
to keep the cold air out and the warm air in.
During heating months, home owners want
their homes as airtight as possible.
While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning ap-
pliances need fresh air for proper combustion
and ventilation.
Exhaust fans, reboxes, clothes dryers and
fuel burning appliances draw air from the
house to operate. You must provide adequate
fresh air for these appliances. This will insure
proper venting of vented fuel-burning appli-
ances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on page 5 through 7 will help
you classify your space and provide adequate
ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of un-
usually tight construction, you must provide
additional fresh air.
Unusually tight construction is dened as
construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6 x 10
less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window
and door frames, between sole plates
and oors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical and gas lines
and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh
air. See Ventilation Air From Outdoors,
page 8.
If your home does not meet all of the three
criteria above, proceed to Determining Fresh-Air Flow for Firebox Location,
page 7.
Conned and Unconned Space
The National Fuel Gas Code, ANSI Z223.1/
NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed
in that space and an unconned space as a
space whose volume is not less than 50 cubic
feet per 1,000 Btu per hour (4.8 m3 per kw)
of the aggregate input rating of all appliances
installed in that space. Rooms communicating
directly with the space in which the appliances
are installed*, through openings not furnished
with doors, are considered a part of the unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.
-11
kg per pa-sec-m2) or
www.SuperiorFireplaces.US.com
126715-01A6
AIR FOR COMBUSTION AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Determining if You Have a Conned or
Unconned Space
Use this work sheet to determine if you have
a conned or unconned space.
Space: Includes the room in which you will
install heater plus any adjoining rooms with
doorless passageways or ventilation grills
between the rooms.
1. Determine the volume of the space (length
x width x height).
Length x Width x Height = ______cu. ft.
(volume of space)
Example: Space size 22 ft. (length) x 18
ft. (width) x 8 ft. (ceiling height) = 3168 cu.
ft. (volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can
support.
_____ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 3168 cu. ft. (volume of space) x
20 = 63,360 (maximum Btu/Hr the space
can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free heater _______ Btu/HrGas water heater* _______ Btu/Hr
Gas furnace _______ Btu/Hr
Vented gas heater _______ Btu/Hr
Gas replace logs _______ Btu/Hr
Other gas appliances* + ______ Btu/Hr
Total = ______ Btu/Hr
* Do not include direct-vent gas appli-
ances. Direct-vent draws combustion
air from the outdoors and vents to the
outdoors.
Example:
Gas water heater _________ Btu/HrVent-free heater + ________ Btu/Hr
Total = ________ Btu/Hr
40,000
39,000
79,000
4. Compare the maximum Btu/Hr the space
can support with the actual amount of
Btu/Hr used.
_________ Btu/Hr (maximum the space
can support)
_________ Btu/Hr (actual amount of
Btu/Hr used)
Example: 63,360 Btu/Hr (maximum the
space can support)
79,000 Btu/Hr (actual amount
of Btu/Hr used)
The space in the above example is a conned
space because the actual Btu/Hr used is more
than the maximum Btu/Hr the space can sup-
port. You must provide additional fresh air.
Your options are as follows:
A. Rework worksheet, adding the space
of an adjoining room. If the extra space
provides an unconned space, remove
door to adjoining room or add ventilation
grills between rooms. See Ventilation Air
From Inside Building, page 8.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 8.
C. Install a lower Btu/Hr heater, if lower
Btu/Hr size makes room unconned.
If the actual Btu/Hr used is less than the
maximum Btu/Hr the space can support, the
space is an unconned space. You will need
no additional fresh air ventilation.
WARNING: If the area in which
the heater may be operated does
not meet the required volume for
indoor combustion air, combustion and ventilation air shall be
provided by one of the methods
described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54,
the International Fuel Gas Code,
or applicable local codes.
126715-01A7
www.SuperiorFireplaces.US.com
AIR FOR COMBUSTION AND VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconned space. When ventilating to an
adjoining unconned space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the oor on the
wall connecting the two spaces (see options
1 and 2, Figure 3). You can also remove door
into adjoining room (see option 3, Figure 3).
Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and
Ventilation for required size of ventilation
grills or ducts.
12"
Ventilation
Grills
Into Adjoining
Room,
Option 1
Or
Remove
Door into
Adjoining
Room,
Option
3
Figure 3 - Ventilation Air from Inside
Ventilation Grills
Into Adjoining Room,
12"
Building
Option 2
INSTALLATION
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two permanent openings: one within 12" of the ceiling
and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermo-
stat-controlled power vent. Heated air entering
the attic will activate the power vent.
Ventilated
Attic
Crawl Space
Ventilated
To Attic
To
Crawl
Space
Outlet
Air
Inlet
Air
Outlet
Air
Inlet Air
Figure 4 - Ventilation Air from Outdoors
WARNING: A qualied service person must install rebox.
Follow all local codes.
WARNING: Never install the
rebox
• in a bedroom or bathroom*
• in a recreational vehicle
• where curtains, furniture, cloth-
ing or other ammable objects
are less than 42" from the front,
top or sides of the rebox
• in high trafc areas
• in windy or drafty areas
* Unless the installed log set is
rated at 10,000 Btu/Hr or less
in a bedroom or 6,000 Btu/Hr
or less in a bathroom.
www.SuperiorFireplaces.US.com
CAUTION: Log heaters
installed in this rebox create
warm air currents. These currents move heat to wall surfaces
next to rebox. Installing rebox
next to vinyl or cloth wall coverings or operating rebox where
impurities (such as, but not
limited to, tobacco smoke, aromatic candles, cleaning uids,
oil or kerosene lamps, etc.) in
the air exist, may discolor walls
or cause odors.