Superior VCM3026ZMP, VCM3026ZMN Installation And Operation Instructions Manual

Installation and Operation Instructions
Superior™ Unvented (Vent-Free) Gas Compact Classic Hearth Fireplace
P/N 126872-01 Rev.A 02/2014 Models
VCM3026ZMP VCM3026ZMN
P126872-01
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
This appliance may be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation section on page 6 of this manual.
causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a qualified installer, service agency or the gas supplier.
TABLE OF CONTENTS
Safety .................................................................. 2
Product Identication ........................................... 4
Optional Remote Control Accessories ................. 4
Local Codes......................................................... 4
Product Features ................................................. 5
Unpacking............................................................ 5
Assembly ............................................................. 5
Air For Combustion and Ventilation ..................... 6
Installation ........................................................... 9
Operation ........................................................... 22
Inspecting Burners............................................. 25
SAFETY
Cleaning and Maintenance ................................ 26
Wiring Diagram .................................................. 27
Troubleshooting ................................................. 28
Specications .................................................... 32
Replacement Parts ............................................ 32
Service Hints ..................................................... 32
Technical Service............................................... 32
Accessories ....................................................... 33
Parts .................................................................. 34
Warranty ............................................................ 36
WARNING: Improper instal­lation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.
WARNING: This is an un-
vented gas-red heater. It uses
air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation section on page 6 of this manual.
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
WARNING: This product contains and/or generates chemicals known to the State of California to cause cancer or birth defects, or other reproduc­tive harm.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, op-
erate, or service this replace. Improper use of this replace
can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
DANGER: Carbon monoxide poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the
u, with headaches, dizziness, or nausea. If you have these signs, the replace may not be working properly. Get fresh air at once! Have replace serviced. Some people are
more affected by carbon monoxide than oth-
ers. These include pregnant women, people with heart or lung disease or anemia, those under the inuence of alcohol, and those at
high altitudes. Natural and Propane/LP Gas: Natural and
propane/LP gases are odorless. An odor­making agent is added to the gas. The odor
helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be
present even though no odor exists.
www.SuperiorFireplaces.US.com
126872-01A2
SAFETY
Continued
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this replace.
WARNING: Any change to
this replace or its controls can
be dangerous.
Carefully supervise young chil­dren when they are in the room
with replace. When using the
hand-held remote accessory keep selector switch in the OFF position to prevent children from turning on burners with remote.
WARNING: Do not use a blower insert, heat exchanger insert, or other accessory not ap-
proved for use with this replace.
WARNING: Do not allow fans
to blow directly into the replace.
Avoid any drafts that alter burner
ame patterns. Ceiling fans can
create drafts that alter burner
ame patterns. Altered burner
patterns can cause sooting.
Due to high temperatures, the appliance should be located out
of trafc and away from furniture
and draperies.
Do not place clothing or other
ammable material on or near
the appliance. Never place any objects on the heater.
Fireplace front and screen be­come very hot when running heater. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Fire­place will remain hot for a time after shutdown. Allow surfaces to cool before touching.
You must operate this replace with the replace screen in place. Make sure replace screen is closed before running replace.
Keep the appliance area clear and free from combustible materials, gasoline, and other
ammable vapors and liquids.
1. This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors.
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas sup-
plier’s instructions
• if you cannot reach your gas supplier,
call the re department
4. This replace shall not be installed in a
bathroom or bedroom.
5. Do not use this replace as a wood-burn­ing replace. Use only the logs provided with the replace.
6. Do not add extra logs or ornaments such
as pine cones, vermiculite, or rock wool.
Using these added items can cause soot­ing. Do not add lava rock around base. Rock and debris could fall into the control
area of replace.
7. This replace is designed to be smokeless. If logs ever appear to smoke, turn off re­place and call a qualied service person.
126872-01A 3
www.SuperiorFireplaces.US.com
Note: During initial operation, slight smoking
O
N O
F
F R
E
M
O
T
E
could occur due to log curing and replace
burning manufacturing residues.
8. To prevent the creation of soot, follow
the instructions in Cleaning and Mainte­nance, page 26.
9. Before using furniture polish, wax, carpet cleaner, or similar products, turn replace off. If heated, the vapors from these prod­ucts may create a white powder residue within burner box or on adjacent walls or
furniture.
10. This replace needs fresh air ventilation to run properly. This replace has an Oxygen
Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the re­place if not enough fresh air is available. See Air for Combustion and Ventilation,
page 6. If replace keeps shutting off, see
Troubleshooting, page 28.
11. Do not run replace
• where ammable liquids or vapors are
used or stored.
• under dusty conditions.
12. Do not use this replace to cook food or burn paper or other objects.
PRODUCT
IDENTIFICATION
Fireplace Cabinet
Left Side
Selector
Switch
(Optional)
Figure 1 - Vent-Free Compact Classic
Control
Ignitor Button
Knob
Remote Control (Optional)
Hearth® Fireplace
www.SuperiorFireplaces.US.com
SAFETY
Continued
Screen
Right Side
Logs
Front
13. Do not use replace if any part has been under water. Immediately call a qualied
service technician to inspect the room
replace and to replace any part of the control system and any gas control which has been under water.
14. Turn off and unplug fireplace and let
cool before servicing. Only a qualied
service person should service and repair
replace.
15. Operating replace above elevations of 4,500 feet could cause pilot outage.
16. Do not operate fireplace if any log is
broken. Do not operate replace if a log is chipped (dime-sized or larger).
17. To prevent performance problems, do not
use propane/LP fuel tank of less than 100 lbs. capacity.
18. Provide adequate clearances around air openings.
19. The screen or any other part removed for servicing must be replaced prior to operating this heater.
OPTIONAL REMOTE
CONTROL ACCESSORIES
There are ve optional remote controls that
can be purchased separately:
• wall switch
• hand-held ON/OFF remote
• wall thermostat
• hand-held thermostat remote
• hand-held touch-screen thermostat remote
See Accessories, page 33.
LOCAL CODES
Install and use replace with care. Follow all local codes. In the absence of local codes,
use the latest edition of The National Fuel Gas Code ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
126872-01A4
LOCAL CODES
Continued
State of Massachusetts: The installation must be made by a licensed plumber or gas
tter in the Commonwealth of Massachusetts.
Sellers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for bedroom and bathroom installation in the
Commonwealth of Massachusetts.
UNPACKING
1. Remove replace and hood from carton. Log is wrapped and inside replace. Do
not remove at this time.
2. Remove all protective packaging applied
to replace for shipment.
3. Make sure your replace includes one hardware packet.
ASSEMBLY
WARNING: Always have
branch support and screen in
place before operating replace.
This prevents excessive tem-
peratures on replace surfaces.
WARNING: Failure to posi­tion the parts in accordance with these diagrams or failure
to use only parts specically approved with this replace
may result in property damage or personal injury.
ASSEMBLING FIREPLACE
Tools Required:
• Phillips screwdriver
• 5/16" hex wrench
• slotted screwdriver
• scissors
1. Remove two screws that hold replace screen in place for shipping. These screws
are located near top of screen. Discard
screws. Lift replace screen up and pull out
to remove. Set screen aside until installation has been completed.
PRODUCT FEATURES
SAFETY PILOT
This replace has a pilot with an Oxygen Deple­tion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent-free
room replaces. The ODS/pilot shuts off the replace if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This replace has a piezo ignitor. This sys­tem requires no matches, batteries, or other sources to light replace.
4. Check replace for any shipping dam-
age. If heater is damaged call INNOVA­TIVE HEARTH PRODUCTS at 1-800­655-2008 for replacement parts before returning to dealer.
2. Cut two plastic straps to remove the log from the rebox cavity.
3. An optional blower is available. See Ac- cessories, page 33. Install optional blower now. Follow installation instructions pro­vided with blower or (see page 14).
4. Locate four black phillips sheet metal
screws from the hardware packet.
5. Rotate hood as shown in Figure 3. Make sure hood tabs point toward replace.
6. Insert hood tabs between bafe and lou­vers (see Figure 3, page 6).
Shoulder
Screw
Burner Support With Log Locator Tabs
Screen
Branch Support
Figure 2 - Removing Screen
126872-01A 5
www.SuperiorFireplaces.US.com
ASSEMBLY
Continued
7. Gently rotate hood to upright position.
Make sure hood tabs are behind louvers
and hood is resting on rebox top (see Figure 3,).
8. Align screw holes on hood with screw holes on rebox top.
9. Insert screws as shown in Figure 3. Tighten screws rmly.
Hood Tabs
Figure 3 - Assembling Hood
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not be installed in a room or space unless the required vol­ume of indoor combustion air is provided by the method de­scribed in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code, or
applicable local codes. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy efcient than ever. New materials, increased insula­tion, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want
their homes as airtight as possible. While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning ap­pliances need fresh air for proper combustion and ventilation.
Exhaust fans, replaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh
www.SuperiorFireplaces.US.com
Louver
Hood
Sheet Metal
Screws
air for these appliances. This will insure proper
venting of vented fuel-burning appliances.
Hood Tab
Bafe
Firebox Top
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space The information on pages 6 through 8 will help
you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of un­usually tight construction, you must provide
additional fresh air.
Unusually tight construction is dened as
construction where: a. walls and ceilings exposed to the out-
side atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10 with openings gasketed or sealed and
b. weather stripping has been added on
openable windows and doors and
-11
kg per pa-sec-m2) or less
126872-01A6
AIR FOR COMBUSTION AND VENTILATION
Continued
c. caulking or sealants are applied to
areas such as joints around window and door frames, between sole plates
and oors, between wall-ceiling joints,
between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.
If your home meets all of these three crite­ria, you must provide additional fresh air. See Ventilation Air From Outdoors, page 8.
If your home does not meet all of the three criteria above, proceed to Determining Fresh-Air Flow For Fireplace Location, below.
Conned and Unconned Space
The National Fuel Gas Code, ANSI Z223.1/ NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the ag-
gregate input rating of all appliances installed
in that space and an unconned space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw)
of the aggregate input rating of all appliances installed in that space. Rooms communicating
directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the un­conned space.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION
Determining if You Have a Conned or Unconned Space
Use this work sheet to determine if you have a conned or unconned space.
Space: Includes the room in which you will
install replace plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 16 ft. (length) x 14 ft.
(width) x 8 ft. (ceiling height) = 1792 cu. ft.
(volume of space)
If additional ventilation to adjoining room
126872-01A 7
www.SuperiorFireplaces.US.com
is supplied with grills or openings, add the
volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to deter­mine the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 1792 cu. ft. (volume of space) x 20
= 35,840 (maximum Btu/Hr the space can
support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free replace ___________ Btu/Hr Gas water heater* ___________ Btu/Hr Gas furnace ___________ Btu/Hr
Vented gas heater ___________ Btu/Hr Gas replace logs ___________ Btu/Hr Other gas
appliances* + __________ Btu/Hr Total = __________ Btu/Hr * Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
Example:
Gas water heater ___________ Btu/Hr Vent-free replace + __________ Btu/Hr
Total = __________ Btu/Hr
4. Compare the maximum Btu/Hr the space
can support with the actual amount of Btu/
Hr used.
_______
support)
_______
us
Example: 35,840 Btu/Hr (maximum the
40,000 Btu/Hr (actual amount of
Btu/Hr (maximum the space can
Btu/Hr (actual amount of Btu/Hr
ed)
space can support)
Btu/Hr used)
30,000 10,000 40,000
The space in the example on the previous
page is a conned space because the actual
Btu/Hr used is more than the maximum Btu/Hr
the space can support. You must provide ad­ditional fresh air. Your options are as follows:
A. Rework worksheet, adding the space
of an adjoining room. If the extra space provides an unconned space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air
From Inside Building, page 8
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors.
AIR FOR COMBUSTION AND VENTILATION
Or Remove Door into
Adjoining
Room,
Option 3
Ventilation Grills
Into Adjoining Room,
Option 2
12"
12"
Ventilation
Grills
into
Adjoining
Room,
Option 1
Outlet Air
Ventilated Attic
Outlet
A
ir
Inlet Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
Continued
C. Install a lower Btu/Hr replace, if lower
Btu/Hr size makes room unconned.
If the actual Btu/Hr used is less than the
maximum Btu/Hr the space can support, the space is an unconned space. You will need
no additional fresh air ventilation.
WARNING: If the area in which the heater may be operated does not meet the required volume for indoor combustion air, combus­tion and ventilation air shall be provided by one of the methods described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code, or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconned space. When ventilating to an adjoining unconned space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the oor on the wall connecting the two spaces (see options 1 and 2, Figure 4). You can also remove door into adjoining room (see option 3, Figure 4). Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and Ventilation for required size of ventilation
grills or ducts.
Figure 4 - Ventilation Air from Inside
Building
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two perma­nent openings: one within 12" of the ceiling and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size
of ventilation grills or ducts. IMPORTANT: Do not provide openings
for inlet or outlet air into attic if attic has a
thermostat-controlled power vent. Heated air entering the attic will activate the power vent.
Figure 5 - Ventilation Air from Outdoors
www.SuperiorFireplaces.US.com
126872-01A8
INSTALLATION
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri­mary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualied ser-
vice person must install re-
place. Follow all local codes.
WARNING: Never install the
replace
• in a bathroom or bedroom
• in a recreational vehicle
• where curtains, furniture,
clothing, or other ammable
objects are less than 36" from the front, top, or sides of the
replace
• as a replace insert
• in high trafc areas
• in windy or drafty areas
CAUTION: This fireplace creates warm air currents. These currents move heat to
wall surfaces next to replace. Installing replace next to vinyl
or cloth wall coverings or oper-
ating replace where impurities
(such as, but not limited to, to­bacco smoke, aromatic candles,
cleaning uids, oil or kerosene
lamps, etc.) in the air exist, may discolor walls or cause odors.
IMPORTANT: Vent-free replaces add mois­ture to the air. Although this is benecial,
installing replace in rooms without enough ventilation air may cause mildew to form from
too much moisture. See Air for Combustion and Ventilation, page 6.
Note: Your replace is designed to be used in
zero clearance installations. Wall or framing ma­terial can be placed directly against any exterior
surface on the rear, sides, or top of your replace,
except where standoff spacers are integrally at­tached. If standoff spacers are attached to your
replace, these spacers can be placed directly
against wall or framing materials.
Note: When installing replace directly on
carpeting, tile or other combustible material,
other than wood ooring, the replace shall be
installed on a metal or wood panel extending
the full width and depth of the replace.
Use the dimensions shown for rough openings
to create the easiest installation (see Built-In Fireplace Installation, page 10).
CHECK GAS TYPE
Use the correct gas type (natural or propane/ LP) for your unit. If your gas supply is not cor-
rect, do not install replace. Call dealer where you bought replace for proper type replace.
WARNING: This appliance is equipped for either natural gas or propane/LP gas but not both. Gas type is indicated on the rating plate. Field conversion is not permitted.
INSTALLATION ITEMS
Before installing replace, make sure you have the items listed below.
• external regulator (supplied by installer, for
propane/LP units only)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection*
• ground joint union
• sediment trap
• tee joint
• pipe wrench * An equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge connection. Purchase the optional equipment shutoff valve from your dealer.
Note: If desired, purchase a three-sided trim kit for built-in installations. See Accessories, page 33.
126872-01A 9
www.SuperiorFireplaces.US.com
INSTALLATION
Continued
FIREPLACE CLEARANCES
WARNING: Maintain the minimum clearances shown in Figure 6. If you can, provide
greater clearances from oor,
ceiling, and joining wall.
If your replace is to be used with an optional mantel, the installation instructions included with your mantel shows an approved method of attaching the replace/mantel system to a wall. IMPORTANT: Only use optional cabinet or corner mantels specied in this manual.
Purchase the optional mantel from your dealer (see Accessories, page 33).
If your replace is to be recessed into the wall,
see Built-In Fireplace Installation to secure
your replace into the wall.
CAUTION: If you install the
replace in a home garage
• replace pilot and burner must
be at least 18" above oor.
• locate replace where moving
vehicle will not hit it.
For convenience and efficiency, install replace
• where there is easy access for operation, inspection, and service
• in coldest part of room
An optional blower kit is available from your dealer. See Accessories, page 33. If planning to use blower, follow instructions provided with blower for power source.
Example
Minimum Clearances For Side Combustible Material, Side Wall, and Ceiling
A. Clearances from the side of the replace
cabinet to any combustible material and
wall should follow diagram in Figure 6.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and protrudes 3 1/2" from the wall. This com-
bustible material must be 4" from the side of the replace opening (see Figure 6).
B. Clearances from the top of the replace
opening to the ceiling should not be less
than 36".
C.
For mantel clearances, see Figure 10
on page 12.
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
Top
36" 6" 0"
Left and
Right Sides
Bottom and
Rear
BUILT-IN FIREPLACE INSTALLATION
Built-in installation of this replace involves installing replace into a framed-in enclosure. This makes the front of replace ush with wall. An optional trim kit accessory is available (see Accessories, page 33). Trim will extend past sides of replace approximately 1/2". This will cover the rough edges of the wall
opening. If installing a built-in mantel above
the replace, you must follow the clearances shown in Figure 10, page 12. Follow the instructions below to install the replace in
this manner.
Actual Framing Height 26" 26 7/8" Front Width 26 3/4" 26 7/8" Depth 9 1/2" 10 1/2" Bottom 3/4" 3/4"
*Minimum 16" from Side Wall
Figure 6 - Minimum Clearance for
Combustible to Wall
www.SuperiorFireplaces.US.com
1. Frame in rough opening. Use dimensions
shown in Figure 7, page 11 for the rough opening. If installing in a corner, use di-
*
mensions shown in Figure 8, page 11 for the rough opening. The height is 26 7/8" which is the same as the wall opening
above.
2. If installing GA3450TA blower accessory, do so at this time. Follow instructions included with blower accessory.
126872-01A10
26
7
/
8
"
26
7
/
8
"
3/4" Off The Floo
r
Minimum
10
1
/
2
"
36
5
/
8
"
25
7
/
8
"
51
3
/
4
"
26
7
/
8
"
INSTALLATION
Wall Studs
Continued
Note: If not installing blower accessory,
you may wish to run electrical wiring to
your replace for future blower installation
(see Accessories, page 33). Use only ap­proved three-wire electrical wiring.
Note: A qualied installer should make all
electrical connections.
WARNING: If pre-wiring, do not connect wiring to any electri­cal source at this time.
Install replace electrical outlet
and connect wiring to outlet before connecting to electrical source. The replace electri­cal outlet is included with the GA3450TA blower accessory.
Only use the replace electri­cal outlet supplied with the GA3450TA blower accessory.
3. Install gas piping to replace location. This installation includes an approved exible gas line (if allowed by local codes) after the equipment shutoff valve. The exible
gas line must be the last item installed on the gas piping.
4. If you have not assembled rebox, follow
instructions beginning on page 5.
5. Carefully set replace in front of rough opening with back of replace inside wall
opening.
6. Attach exible gas line to replace gas
regulator. See Connecting Fireplace to Gas Supply, page 17.
7. Bend four nailing anges on outer casing with pliers (see Figure 9).
8. Attach replace to wall studs using nails or wood screws through holes in nailing ange.
9. Check all gas connections for leaks. See
Checking Gas Connections, page 19.
10. If using optional trim kit, install the trim after nal nishing and/or painting of wall. See instructions included with trim acces-
sory for attaching trim.
IMPORTANT: When nishing your rebox, combustible materials such as wall board, gypsum board, sheet rock, drywall, plywood,
etc. may be butted up next to the sides and
top edge of the rebox. Combustible materials should never overlap the rebox front facing.
WARNING: Do not allow any
combustible or noncombustible
materials to overlap the rebox
front facing.
Figure 7 - Rough Opening for Installing
in Wall
Nails or Wood Screws
Figure 8 - Rough Opening for Installing
126872-01A 11
in Corner
www.SuperiorFireplaces.US.com
Figure 9 - Attaching Fireplace to Wall Studs
Nailing Flanges
13" 16"
19"
21"
2 1/2"
6"
8"
10"
Note:
A
ll vertical measurements are from top of fireplace opening to bottom of mantel shelf. All measurements are in inches.
Mantel Clearances for Built-In Installation
If placing mantel above built-in replace, you must meet minimum clearance between man­tel shelf and top of replace opening.
INSTALLATION
Continued
WARNING: Do not allow noncombustible materials to cover any necessary openings like louvered slots.
WARNING: Never modify or cover the louvered slots on the
front of the rebox.
NOTICE: Surface temperatures of adjacent walls and mantels be­come hot during operation. Walls
and mantels above the rebox
may become hot to the touch. If installed properly, these tem­peratures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.
NOTICE: If your installation does not meet the minimum clear­ances shown in Figure 10, you must do one of the following:
• raise the mantel to an accept-
able height
• remove the mantel
Mantel Shelf
Side of Firebox
Figure 10 - Minimum Mantel Clearances
for Built-In Installation
OPTIONAL MANTEL INSTALLATION
Refer to instructions provided with the mantel for assembly instructions. Refer to the follow-
ing instructions for system installation. Refer to instructions on page 6 for hood assembly.
Blower accessory should be installed prior to
mantel if it is being used (see Installing Optional Blower Accessory GA3450TA, page 14).
1. Assemble cabinet mantel as shown in
accessory instruction sheet.
2. If blower is installed, install a properly grounded, 120 volt three-prong electrical outlet at replace location if an outlet is not there. If possible, locate outlet so cabinet mantel will cover it when installed (see
Figure 11).
3. Place hearth base against wall at installation
location. Cut an access hole in hearth base
to run gas line to replace (see Figure 11).
Make sure to locate access hole so cabinet
mantel will cover it when installed.
Note: You can secure base to oor using
wood screws. Countersink screw heads and putty over.
Hearth Base
Pipe and Gas
Shutoff Valve
Electrical Outlet
Figure 11 - Placing Hearth Base Against Wall
www.SuperiorFireplaces.US.com
126872-01A12
Loading...
+ 26 hidden pages