INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
This appliance may be installed in an aftermarket permanently located, manufactured (mobile) home,
where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the
rating plate. This appliance is not convertible for use with other gases.
WARNING: This appliance is for installation only in a solid-fuel burning masonry or UL127 factory-built
fi replace or in a listed ventless fi rebox enclosure. It is design-certifi ed for these installations in accordance
with ANSI Z21.11.2. Exception: DO NOT install this appliance in a factory-built fi replace that includes
instructions stating it has not been tested or should not be used with unvented gas logs.
This is an unvented gas-fi red heater. It uses air (oxygen) from the room in which it is installed. Provisions
for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation
section on Page 6 of this manual.
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
- Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other
appliance.
- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re department.
- Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
Improper adjustment, alteration, service, maintenance, or installation of this
heater or its controls can cause death or serious injury.
Read and follow instructions and precautions in User’s Information Manual
provided with this heater.
WARNING: This appliance is for
installation only in a solid-fuel burning masonry or UL127 factory-built
fi replace or in a listed ventless fi re-
box enclosure. It is design-certifi ed
for these installations in accordance
with ANSI Z21.11.2. Exception:
DO NOT install this appliance in a
factory-built fi replace that includes
instructions stating it has not been
tested or should not be used with
unvented gas logs.
WARNING: Vent-free products are
prohibited for bedroom and bathroom
installation in the Commonwealth of
Massachusetts.
WARNING: This product contains
and/or generates chemicals known
to the state of California to cause
cancer or birth defects or other reproductive harm.
WARNING: This is an unvented
gas-fi red heater. It uses air (oxygen)
from the room in which it is installed.
Provisions for adequate combustion
and ventilation air must be provided.
Refer to Air for Combustion and Ventilation section on Page 6 of
this manual.
This appliance may be installed in an
aftermarket,* permanently located,
manufactured (mobile) home, where
not prohibited by local codes.
This appliance is only for use with
the type of gas indicated on the
rating plate. This appliance is not
convertible for use with other gases.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
DANGER: Carbon monoxide
poisoning may lead to death!
SuperiorFireplaces.us.com
126817-01D2
SAFETY
Continued
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate
or service this appliance. Improper
use of this appliance can cause
serious injury or death from burns,
fi re, explosion, electrical shock and
carbon monoxide poisoning.
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning resemble the fl u,
with headaches, dizziness or nausea. If you
have these signs, the fi replace may not be
working properly. Get fresh air at once! Have
fi replace serviced. Some people are more affected by carbon monoxide than others. These
include pregnant women, people with heart
or lung disease or anemia, those under the
infl uence of alcohol and those at high altitudes.
Natural and Propane/LP
odor-making agent is added to these gases.
The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas
may be present even though no odor exists.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this appliance.
WARNING: Any change to this
gases are odorless. An
heater or its controls can be dangerous.
WARNING: Do not use a blower
insert, heat exchanger insert or other
accessory not approved for use with
this heater.
WARNING: Do not place log
scraps or volcanic stone on burner.
Due to high temperatures, the appliance should be located out of
traffi c and away from furniture and
draperies.
Do not place clothing or other
fl ammable material on or near the
appliance. Never place any objects
on the heater.
Appliance base assembly becomes
very hot when running appliance.
Children and adults should be
alerted to the hazard of high surface
temperature and should stay away
to avoid burns or clothing ignition.
Appliance will remain hot for a time
after shutdown. Allow surface to
cool before touching.
Young children should be carefully supervised when they are in
the same room with the appliance.
When using the hand-held remote
accessory, keep selector switch in
the OFF position to prevent children
from turning on burners with remote.
You must operate this appliance
with the fi replace screen and hood
in place. Make sure fi replace screen
and hood are in place before running
appliance. The fi replace screen shall
have openings for introduction of
combustion air.
WARNING: Do not allow fans to
blow directly into the heater. Avoid
any drafts that alter burner fl ame
patterns. Ceiling fans can create
drafts that alter burner fl ame pat-
terns. Altered burner patterns can
cause sooting.
126817-01D3
SuperiorFireplaces.us.com
Keep the appliance area clear and
free from combustible materials,
gasoline and other fl ammable va-
pors and liquids.
Solid-fuels shall not be burned in a
fi replace in which an unvented room
heater is installed.
SAFETY
Continued
Installation and repair should be
done by a qualifi ed service person.
The appliance should be inspected
before use and at least annually by
a professional service person. More
frequent cleaning may be required
due to excessive lint from carpeting,
bedding material, etc. It is imperative
that control compartments, burners,
and circulating air passageways of
the appliance be kept clean.
1. WARNING: This appliance is only for
use with the type of gas indicated on
the rating plate. This appliance is not
convertible for use with other gases.
2. Do not place propane/LP supply tank(s)
inside any structure. Locate propane/LP
supply tank(s) outdoors (propane/LP units
only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas supplier’s instructions
• if you cannot reach your gas supplier,
call the fi re department
4. This heater shall not be installed in a
bedroom or bathroom. This gas log set
may not be installed as a vented appliance in a bedroom or bathroom in the
Commonwealth of Massachusetts.
5. WARNING: Before installing in a solid
fuel-burning fi replace, the chimney fl ue
and fi rebox must be cleaned of soot,
creosote, ashes and loose paint by a
qualifi ed chimney cleaner. Creosote will
ignite if highly heated. A dirty chimney fl ue
may create and distribute soot within the
house. Inspect chimney fl ue for damage.
If damaged, repair fl ue and fi rebox before
operating appliance.
6. Do not burn solid-fuel in a fi replace in
which a vent-free appliance is installed.
7. If appliance has glass doors, never operate this appliance with glass doors closed.
Any glass doors shall be fully opened
when the appliance is in operation. If you
operate appliance with doors closed, heat
buildup inside fi replace will cause glass to
burst. Make sure there are no obstructions
across openings of fi replace.
8. T o prevent the creation of soot, follow the
instructions in Cleaning and Maintenance,
Page 30.
9. Before using furniture polish, wax, carpet
cleaner or similar products, turn appliance
off. If heated, the vapors from these products may create a white powder residue
within burner box or on adjacent walls and
furniture.
10. This appliance needs fresh, outside air
ventilation to run properly. This appliance
has an Oxygen Depletion Sensing (ODS)
safety shutoff system. The ODS shuts
down the appliance if enough fresh air is
not available. See Air for Combustion and Ventilation, Page 6. If appliance keeps
shutting off, see Troubleshooting, Page 31.
11. Do not run appliance
• where fl ammable liquids or vapors are
used or stored
• under dusty conditions
12. Do not use this appliance to cook food or
burn paper or other objects.
13. Do not use this room heater if any part
has been under water. Immediately call
a qualifi ed service technician to inspect
the room heater and to replace any part
of the control system and any gas control
which has been under water.
14. Do not operate appliance if any log is
broken. Do not operate appliance if a log
is chipped (dime-sized or larger).
15. Turn appliance off and let cool before
servicing, installing or repairing. Make
sure the selector switch is in the OFF
position. Only a qualifi ed service person
should install, service or repair appliance.
16. Make sure the selector switch is in the
OFF position when you are away from
home for long periods of time.
17. Remote-ready appliances must not be
connected to any external electrical
source.
18. Operating appliance above elevations of
4,500 feet may cause pilot outage.
19. To p revent performance problems, do
not use propane/LP fuel tank of less than
100 lb. capacity (propane/LP units only).
20. Provide adequate clearances around air
openings.
21. Follow the clearance requirements within
this manual to assure adequate clearances for accessibility for purposes of
servicing and proper operation.
4
SuperiorFireplaces.us.com
126817-01D
Left
Side
PRODUCT IDENTIFICATION
Chassis
Glowing
Embers
Front
Flame
Adjustment
Knob
Figure 1 - Product Identifi cation
LOCAL CODES
Install and use appliance with care. Follow all
local codes. In the absence of local codes, use
the latest edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
25 West 43rd Street, 4th fl oor
New York, NY 10036
National Fire Protection Association, Inc.
1 Batterymarch Park
Quincy, MA 02169-7471
UNPACKING
1. Remove logs and appliance base assembly from carton(s).
Right
Side
Control
Knob
NOTE: Do not pick up appliance base as-
sembly by burners. This could damage the
appliance. Always handle base assembly
by grate.
2. Remove all protective packaging applied
to logs and appliance for shipment.
3. Check appliance for any shipping damage. If appliance is damaged, promptly
inform dealer where you purchased the
appliance.
CAUTION: Do not remove
the data plates from the grate
assembly. The data plates
contain important warranty
and safety information.
COMMONWEALTH OF MASSACHUSETTS REQUIREMENTS
These appliances are approved for installation in the US state of Massachusetts if the following additional requirements are met:
• Un-vented Room Heaters shall be installed in accordance with 527 CMR 30.
• Installation and repair must be done by a plumber or gas fi tter licensed in the Common-
wealth of Massachusetts.
• The fl exible gas line connector used shall not exceed 36 inches (92 centimeters) in length.
• The individual manual shut-off must be a T-handle type valve.
• Unvented appliances may NOT be installed in bedrooms or bathrooms.
• A working smoke detector must be installed in the area where vent-free appliances are
installed.
Seller of unvented propane or natural gas-fi red supplemental room heaters shall provide
to each purchaser a copy of 527 CMR 30 upon sale of the unit.
126817-01D5
SuperiorFireplaces.us.com
PRODUCT FEATURES
OPERATION
This appliance is clean burning. It requires no
outside venting. There is no heat loss out a vent
or up a chimney. Heat is generated by both
realistic fl ames and glowing coals. This appli-
ance is designed for vent-free operation with fl ue
damper closed. It has been tested and approved
to the ANSI Z21.1 1.2 standard for unvented appliances. State and local codes in some areas
prohibit the use of vent-free appliances.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not
be installed in a room or space unless the required volume of indoor
combustion air is provided by the
method described in the National
Fuel Gas Code, ANSI Z223.1/NFPA
54, the International Fuel Gas Code,
or applicable local codes. Read the
following instructions to ensure
proper fresh air for this and other fuelburning appliances in your home.
Today’s homes are built more energy effi cient
than ever. New materials, increased insulation
and new construction methods help reduce
heat loss in homes. Homeowners apply
weather strip and caulk around windows and
doors to keep the cold air out and the warm air
in. During heating months, homeowners want
their homes as airtight as possible.
While it is good to make your home energy
effi cient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning appliances need fresh air for proper combustion
and ventilation.
Exhaust fans, some fi replaces, clothes dryers
and some fuel-burning appliances draw air
from the house to operate. You must provide
adequate fresh air for these appliances. That
will ensure proper venting of vented fuel-burning
appliances.
PROVIDING ADEQUA TE
VENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classifi cations:
SAFETY DEVICE
This appliance has a pilot with an Oxygen
Depletion Sensing (ODS) safety shutoff system.
The ODS/pilot is a required feature for vent-free
room appliances. The ODS/pilot shuts off the
appliance if there is not enough fresh air.
ELECTRONIC IGNITION SYSTEM
This appliance has an electronic Igniter to light
appliance fuel supply.
1. Unusually Tight Construction
2. Unconfi ned Space
3. Confi ned Space
The information on Pages6-8 will help you
classify your space and provide adequate
ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of unusually tight construction, you must provide
additional fresh air.
Unusually tight construction is defi ned as
construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6 x 10
less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window
and door frames, between sole plates
and fl oors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical and gas lines
and at other openings.
If your home meets all three criteria above,
you must provide additional fresh air. See
Ventilation Air From Outdoors, Page 8.
If your home does not meet all three criteria
above, proceed to Determining Fresh-Air Flow For Heater Location, Page 7.
Confi ned and Unconfi ned Space
The National Fuel Gas Code, ANSI Z223.1/
NFP A54 allows two methods for determining
whether the space in which the heater is being
installed is confi ned or unconfi ned space. The
-11
kg per pa-sec-m2) or
6
SuperiorFireplaces.us.com
126817-01D
AIR FOR COMBUSTION AND VENTILATION
Continued
standard method defi nes a confi ned space as
a space whose volume is less than 50 cubic
feet per 1,000 Btu/hr (4.8 m
gregate input rating of all appliances installed
in that space and an unconfi ned space as
a space whose volume is not less than 50
cubic feet per 1,000 Btu/hr (4.8 m
the aggregate input rating of all appliances
installed in that space. Rooms communicating
directly with the space in which the appliances
are installed*, through openings not furnished
with doors, are considered a part of the unconfi ned space.
Where the air infi ltration rate of a structure is
known, the Known Air Infi ltration Rate Method
may be used. Follow The National Fuel Gas
Code, ANSI Z223.1/NFPA 54 to use this
method to determine if the space is confi ned
or unconfi ned.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Determining if You Have a Confi ned or
Unconfi ned Space Using the Standard
Method
Use this work sheet to determine if you have
a confi ned or unconfi ned space.
Space: Includes the room in which you will install
fi replace plus any adjoining rooms with doorless passageways or ventilation grills between
the rooms.
1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20
= 51,200 (maximum Btu/Hr the space can
support)
3. Add the Btu/Hr of all fuel-burning appliances
in the space
3
per kw) of the ag-
3
per kw) of
Vent-free fi replace __________Btu/HrGas water heater* __________Btu/Hr
Gas furnace __________Btu/Hr
Vented gas heater __________Btu/Hr
Gas fi replace logs __________Btu/HrOther gas appliances* + _________ Btu/Hr
Total = _________Btu/Hr
* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
Example:Gas water heater __________Btu/Hr
Vent-free fi replace + _________Btu/Hr
Total = _________Btu/Hr
4. Compare the maximum Btu/Hr the space
can support with the actual amount of Btu/
Hr used.
______Btu/Hr (maximum the space can
support)
______Btu/Hr (actual amount used)
Example: 51,200 Btu/Hr (maximum the
space can support)
73,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the above example is a confi ned
space because the actual Btu/Hr used is more
than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your
options are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides
an unconfi ned space, remove door to adjoin-
ing room or add ventilation grills between
rooms. See Ventilation Air From Inside
Building, Page 8.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, Page 8.
C. Install a lower Btu/Hr heater , if lower Btu/Hr
size makes room unconfi ned.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is
an unconfi ned space. Y ou will need no additional
fresh air ventilation.
40,000
33,000
73,000
WARNING: If the area in which
the heater may be operated does not
meet the required volume for indoor
combustion air, combustion and
ventilation air shall be provided by
one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/
NFPA 54, the International Fuel Gas
Code, or applicable local codes.
126817-01D7
SuperiorFireplaces.us.com
AIR FOR COMBUSTION AND VENTILATION
A
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills Into
Adjoining
Room,
Option 1
12"
12"
Continued
VENTILA TION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconfi ned space. When ventilating to an
adjoining unconfi ned space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the fl oor on the
wall connecting the two spaces (see options 1 and 2, Figure 2). Y ou can also remove door
into adjoining room (see option 3, Figure 2).
Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and
Ventilation for required size of ventilation
grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two permanent openings: one within 12" of the ceiling
and one within 12" of the fl oor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings
for inlet or outlet air into attic if attic has a
thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.
Ventilated
Attic
Ventilated
Crawl Space
To Attic
To
Crawl
Space
Outlet
ir
Inlet
Air
Outlet
Air
Inlet Air
Figure 2 - Ventilation Air from Inside Building
INSTALLATION
NOTICE: This appliance is intended
for supplemental heating. Use this
appliance along with your primary
heating system. Do not install this appliance as your primary heat source.
If you have a central heating system,
you may run system’s circulating
blower while using appliance. This
will help circulate the heat throughout
the house. In the event of a power
outage, you can use this appliance
as your primary heat source.
person must install appliance. Follow all local codes.
NOTICE: State or local codes may only allow
operation of this appliance in a vented confi guration. Check your state or local codes.
WARNING: A qualifi ed service
Figure 3 - Ventilation Air from Outdoors
WARNING: Any outside air ducts
and/or ash dumps in the fi replace
shall be permanently closed at time
of appliance installation.
WARNING: Make sure the selector switch is in the OFF position
before installing appliance.
WARNING: Seal any fresh air
vents or ash clean-out doors located
on fl oor or wall of fi replace. If not,
drafting may cause pilot outage
or sooting. Use a heat-resistant
sealant. Do not seal chimney fl ue
damper.
8
SuperiorFireplaces.us.com
126817-01D
INSTALLATION
Continued
WARNING: Before installing in
a solid fuel-burning fi replace, the
chimney fl ue and fi rebox must be
cleaned of soot, creosote, ashes and
loose paint by a qualifi ed chimney
cleaner. Creosote will ignite if highly
heated. A dirty chimney fl ue may
create and distribute soot within the
house. Inspect chimney and fi rebox
fl ue for damage. If damaged, repair
fl ue and fi rebox before operating
appliance.
WARNING: Never install the
appliance
• in a bedroom or bathroom
• in a recreational vehicle
where curtains, furniture, clothing
•
or other fl ammable objects are less
than 36" from front, 42" from top of
appliance; for side clearances see
Figure 4, Page 10
• in high traffi c areas
• in windy or drafty areas
CHECK GAS TYPE
Use the correct type of gas (natural or propane/
LP). If your gas supply is not the correct gas
type, do not install appliance. Call dealer
where you purchased the appliance for proper
type appliance.
WARNING: This appliance is
equipped for either natural gas or
propane/LP gas but not both. Gas
type is indicated on the rating plate.
Field conversion is not permitte
d.
INST ALLATION AND CLEARANCES
FOR VENT-FREE OPERATION
WARNING: Maintain the
minimum clearances. If you can,
provide greater clearances from
fl oor, ceiling and adjoining wall.
MINIMUM FIREPLACE CLEARANCE
TO COMBUSTIBLE MATERIALS
Side Wall 16", Ceiling 42"
Floor 5", Front: 36"
CAUTION: This appliance creates
warm air currents. These currents
move heat to wall surfaces next
to appliance. Installing appliance next to vinyl or cloth wall
coverings or operating appliance
where impurities (such as, but
not limited to, tobacco smoke,
aromatic candles, cleaning fl uids,
oil or kerosene lamps, etc.) in the
air exist, may discolor walls or
cause odors.
IMPORTANT: Vent-free appliances add
moisture to the air. Although this is benefi cial,
installing appliance in rooms without enough
ventilation air may cause mildew to form from
too much moisture. See Air for Combustion and Ventilation, Page 6.
LOG SIZING REQUIREMENTS
Log
Size
18"20"14"28"20"
24"20"14"32"22"
30"20"14"40"30"
Carefully follow the instructions below. This
will ensure safe installation into a masonry,
UL127-listed manufactured fi replace or listed
vent-free fi rebox.
Minimum Clearances For Side Combustible
Material, Side Wall and Ceiling
A. Clearances from the side of the fi replace
cabinet to any combustible material and
wall should follow diagram in Figure 4, Page 10.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material
and protrudes 3-1/2" from the wall. This
combustible material must be 4" from the
side of the fi replace cabinet (see Figure 4, Page 10).
Minimum Firebox Size
HeightDepth
Front
Width
Rear*
Width
126817-01D9
SuperiorFireplaces.us.com
INSTALLATION
Heat Resistant
Material
(A)
Continued
NOTE: When installing your gas logs into
a manufactured firebox, follow firebox
manufacturer’s instructions for minimum
clearances to combustible materials.
B. Clearances from the top of the fi replace
opening to the ceiling should not be less
than 42".
Maintain adequate clearances for accessibility for purposes
of servicing and proper operation.
Example
*
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
Noncombustible
Material Distance
Requirements for
Safe Installation
(A)
1
2" or moreNoncombustible mate-
rial OK.
Between 8" and 12"
24" or 30" Models:
Install fi replace hood ac-
cessory (GA6050 - see
Accessories, Page 36).
18" Model: Noncombustible material OK.
Less than 8"
Noncombustible material must be extended
to at least 8". See
Between 8" and 12",
above. If you cannot
extend material, you
must operate appliance
with fl ue damper open.
Minimum Noncombustible Material
Clearances
If Not Using Mantel
NOTE: If using a mantel proceed to If Using
Mantel. If not using a mantel, follow these
instructions.
You must have noncombustible material(s)
above the fi replace opening. Noncombustible
materials (such as slate, marble, tile, etc.) must
be at least 1/2" thick. With sheet metal, you
must have noncombustible material behind
it. Noncombustible material must extend at
least 8" up (for all models). If noncombustible
material is less than 12", you must install the
fi replace hood accessory (24" and 30" Models
Only). See Figure 5 for minimum clearances.
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
If Using Mantel
You must have noncombustible material(s)
above the fi replace opening. Noncombus-
tible materials (such as slate, marble, tile,
etc.) must be at least 1/2" thick. With sheet
metal, you must have noncombustible material behind it. Noncombustible material
must extend at least 8" up (for all models). If
noncombustible material is less than 12", you
must install the fi replace hood accessory (24"
and 30" Models Only). Even if noncombustible
material is more than 12", you may need the
hood accessory to defl ect heat away from
your mantel shelf. See Figure 5 and Figures 6 and 7, Page 11, for minimum clearances.
10
SuperiorFireplaces.us.com
126817-01D
INSTALLATION
Minimum
Noncombustible
Material
8"
Min.
12" 15" 18" 20"
2
1
/2
"
6"
8"
10"
12"
Distances to
Underside of
Mantel
Hood (GA6050
or GA6053)
Top of
Fireplace
Opening
Underside
of Mantel
Shelf
Mantel Shelf
Continued
MANTEL CLEARANCES
In addition to meeting noncombustible material clearances, you must also meet required
clearances between fi replace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between
mantel shelf and top of fi replace opening, a
hood is not required (see Figure 6).
/2
(A)
12"
8"
Mantel Shelf
"
18"
20"
14"
22"
17"
19"
Distances to
Underside of
Mantel
Underside of
Mantel Shelf
24"
20"
Top of Fireplace
Opening
All minimum
distances are
in inches
Log Set
24"/30" Models
18" Model
Minimum NonCombustible
Material
10"
8"
6"
1
2
Minimum NonCombustible
Material Height
NOTICE: Surface temperatures
of adjacent walls and mantels become hot during operation. Walls
and mantels above the fi rebox
may become hot to the touch.
If installed properly, these temperatures meet the requirement
of the national product standard.
Follow all minimum clearances
shown in this manual.
NOTICE: If your installation does
not meet the minimum clearances shown, you must do one
of the following:
• operate the logs only with the
fl ue damper open
• raise the mantel to an acceptable height
• remove the mantel
Figure 6 - Minimum Mantel Clearances
Without Using Hood
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6 are not
met, you must have a hood. When using a
hood there are still certain minimum mantel
clearances required. Follow minimum clearances shown in Figure 7, when using hood.
FLOOR CLEARANCES
A. If installing appliance on the fl oor level,
you must maintain the minimum distance
of 14" to combustibles (see Figure 8).
B. If combustible materials are less than
14" to the fi replace, you must install ap-
pliance at least 5" above the top surface
of combustible fl ooring including tile and
carpet (see Figure 9).
Combustible
14"
Min.
Noncombustible Material
Material
Figure 8 - Minimum Fireplace Clearances
Figure 7 - Minimum Mantel Clearances
When Using Hood
If Installed at Floor Level
Hearth
5"
Min.
Combustible
Material
Minimum clearance requirements include any projections such
as shelves, window sills, mantels, etc. above the appliance.
126817-01D11
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
SuperiorFireplaces.us.com
INSTALLATION
Continued
INST ALLING APPLIANCE BASE
ASSEMBLY
WARNING: You must secure
this appliance to fi replace fl oor. If
not, appliance will move when you
adjust controls. Moving appliance
may cause a gas leak.
WARNING: If installing in a
sunken fireplace, special care
is needed. You must raise the
fi replace fl oor to allow access to
appliance control panel. This will
ensure adequate air fl ow and guard
against sooting and controls being
damaged. Raise fi replace fl oor with
noncombustible material. Make
sure material is secure.
CAUTION: Do not pick up
appliance base assembly by
burners. This could damage the
appliance. Only handle base assembly by grates.
IMPORTANT: Make sure the appliance burn-
ers are level. If appliance is not level, appliance will not work properly.
12
SuperiorFireplaces.us.com
126817-01D
INSTALLATION
Continued
Installation Items Needed
• hardware package (provided with appliance)
• approved fl exible gas hose and fi ttings
(provided) (if allowed by local codes)
• sealant (resistant to propane/LP gas, not
provided)
• electric drill with 3/16” masonry drill bit
1. Apply pipe joint sealant lightly to male
threads of the 1/2 NPT side of gas fi tting
elbow (provided) and connect to inlet
side of gas control. Remove gas fi tting
from fl exible gas hose (provided) before
connecting to elbow (see Figure 10).
2. Position appliance base assembly in
fi replace.
3. Mark screw locations through holes in
front panel of base (see Figure 11). If
installing in a brick-bottom fi replace, mark
screw locations in mortar joint of bricks.
4. Remove appliance base from fi replace.
5. Drill holes at marked locations using 3/16"
drill bit.
6. Attach base, through holes in back side pan-
els of base, to fi replace fl oor using masonry
screws provided in hardware package (see Figure 11).
7. Connect to gas supply. See Connecting
To Gas Supply.
Masonry Screw
Figure 11 - Attaching Base to Fireplace
Floor
CONNECTING TO GAS SUPPLY
WARNING: This appliance
requires a 3/8" NPT (National Pipe
Thread) inlet connection to the
pressure regulator.
WARNING: A qualifi ed service
person must connect appliance to
gas supply. Follow all local codes.
CAUTION: Never connect
propane/LP appliance directly
to the propane/LP supply. This
Flexible Gas Hose
(Install if allowed
by local codes)
appliance requires an external
regulator (not supplied). Install
the external regulator between the
appliance and propane/LP supply.
Elbow, 3/8 NPT x
3/8 Flare
Gas Control
Figure 10 - Attaching Flexible Gas Hose
to Appliance Gas Regulator
126817-01D13
SuperiorFireplaces.us.com
WARNING: Never connect
natural gas appliance to private
(non-utility) gas wells. This gas
is commonly known as wellhead
gas.
INSTALLATION
Continued
Installation Items Needed
Before installing appliance, make sure you
have the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved fl exible gas line with gas connec-
tor (if allowed by local codes) (not provided)
* An equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge
connection.
For propane/LP units, the installer must
supply an external regulator. The external
regulator will reduce incoming gas pressure.
You must reduce incoming gas pressure to
between 11" and 14" of water. If you do not
reduce incoming gas pressure, appliance
regulator damage could occur. Install external regulator with the vent pointing down as
shown in Figure 12. Pointing the vent down
protects it from freezing rain or sleet.
Check your building codes for any special
requirements for locating equipment shutoff
valve to appliances.
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could
result in clogged appliance valves.
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
Propane/LP
Supply Tank
Figure 12 - External Regulator With Vent
Pointing Down
External
Regulator
with Vent
Pointing
Down
CAUTION: Use only new,
black iron or steel pipe. Internally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of
1/2" diameter or greater to allow
proper gas volume to appliance.
If pipe is too small, undue loss
of volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up.
NPT tap must be upstream from appliance
(see Figure 13).
IMPORTANT: Install equipment shutoff valve
in an accessible location. The equipment
shutoff valve is for turning on or shutting off
the gas to the appliance.
PROPANE/LP
From External
Regulator
Approved Flexible
Gas Hose (if
allowed by local
codes)
3" Minimum
Pipe Cap Tee
Nipple Joint
Gas
Control
Figure 13 - Gas Connection (Remote-
Ready Models Only)
** Minimum inlet pressure for purpose of input
adjustment.
Sediment Trap
(11" W.C.**
to 14" W.C.
Pressure)
NATURAL
From Gas
Meter
(5" W.C.**
to 10.5"
W.C.
Pressure)
14
SuperiorFireplaces.us.com
126817-01D
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.