Superior TF18NV, TF18PV, TF2430PV, TF2430NV Installation And Operation Instructions Manual

Installation and Operation Instructions
Superior™ Unvented (Vent-Free) Gas Log Heater
P/N 126817-01 Rev. A 01/2014 Models
TF18NV TF18PV TF2430NV TF2430PV
P126817-01
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
This appliance may be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
WARNING: This appliance is for installation only in a solid-fuel burning masonry or UL127 factory-built fireplace or in a listed ventless firebox enclosure. It is design-certified for these installations in accordance with ANSI Z21.11.2. Exception: DO NOT install this appliance in a factory-built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs.
This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation section on page 6 of this manual.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a qualified installer, service agency or the gas supplier.
SAFETY
WARNING: Improper installation, adjustment, alteration, service or main­tenance can cause injury or property damage. Refer to this manual for correct installation and operation­al procedures. For assis­tance or additional infor-
mation consult a qualied
installer, service agency or the gas supplier.
WARNING: This ap­pliance is for installation only in a solid-fuel burning masonry or UL127 factory-
built replace or in a listed ventless rebox enclosure.
It is design-certified for these installations in accor­dance with ANSI Z21.11.2.
Exception: DO NOT install
this appliance in a factory-
built replace that includes
instructions stating it has not been tested or should not be used with unvented gas logs.
WARNING: This is an
unvented gas-red heat­er. It uses air (oxygen)
from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air
for Combustion and Ven­tilation section on page 6
of this manual.
This appliance may be in­stalled in an aftermarket,* permanently located,
manufactured (mobile)
home, where not prohib­ited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
TABLE OF CONTENTS
Safety .................................................................. 2
Product Identication ........................................... 5
Local Codes......................................................... 5
Unpacking............................................................ 5
Product Features ................................................. 6
Air For Combustion and Ventilation ..................... 6
Installation ........................................................... 9
Operation ........................................................... 23
Inspecting Burners............................................. 27
Cleaning and Maintenance ................................ 27
Specications .................................................... 29
Wiring Diagram .................................................. 29
Troubleshooting ................................................. 30
Parts .................................................................. 38
Replacement Parts ............................................ 38
Service Hints ..................................................... 38
Technical Service............................................... 38
Accessories ....................................................... 38
Warranty ............................................................ 42
WARNING: Do not allow fans
to blow directly into the replace.
Avoid any drafts that alter burner
ame patterns. Ceiling fans can create drafts that alter burner ame
patterns. Altered burner patterns can cause sooting.
Due to high temperatures, the ap­pliance should be located out of
trafc and away from furniture and
draperies.
Do not place clothing or other ammable material on or near the
appliance. Never place any objects on the heater.
Heater base assembly becomes very hot when running heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater will remain hot for a time after shutdown. Allow surface to cool before touching.
Carefully supervise young children when they are in the room with heater. When using the hand-held remote accessory, keep selector switch in
the OFF position to prevent children
from turning on burners with remote.
You must operate this heater with
the replace screen and hood in place. Make sure replace screen
and hood are in place before running
heater. The replace screen shall
have openings for introduction of combustion air.
Keep the appliance area clear and free from combustible materials, gasoline and other ammable va­pors and liquids.
WARNING: This product con­tains and/or generates chemicals known to the state of California to cause cancer or birth defects or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely before trying to assemble, op-
erate or service this replace. Improper use of this replace
can cause serious injury or death from burns, re, explo­sion, electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning resemble the u, with headaches, dizziness or nausea. If you have these signs, the replace may not be
working properly. Get fresh air at once! Have replace serviced. Some people are more af­fected by carbon monoxide than others. These
include pregnant women, people with heart or lung disease or anemia, those under the inu-
ence of alcohol and those at high altitudes. Natural and Propane/LP
gases are odorless. An odor-making agent is added to these gases. The odor helps you detect a gas leak. How-
ever, the odor added to the gas can fade. Gas
may be present even though no odor exists. Make certain you read and understand all
warnings. Keep this manual for reference. It is your guide to safe and proper operation of
this replace.
WARNING: Any change to this heater or its controls can be dangerous.
WARNING: Do not use a blower insert, heat exchanger
insert or other accessory not ap­proved for use with this heater.
SAFETY
Continued
www.SuperiorFireplaces.US.com
126817-01A4
SAFETY
Continued
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors (propane/LP units only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas sup­plier’s instructions
• if you cannot reach your gas supplier,
call the re department
4. This heater shall not be installed in a bedroom or bathroom. This gas log set may not be installed as a vented appli­ance in a bedroom or bathroom in the Commonwealth of Massachusetts.
5. Before installing in a solid fuel burning re­place, the chimney ue and rebox must be cleaned of soot, creosote, ashes and loose paint by a qualied chimney cleaner.
Creosote will ignite if highly heated. A dirty
chimney ue may create and distribute
soot within the house. Inspect chimney
ue for damage. If damaged, repair ue and rebox before operating heater.
6. Do not burn solid-fuel in a replace in
which a vent-free room heater is installed.
7. If replace has glass doors, never operate
this heater with glass doors closed. Any glass doors shall be fully opened when the appliance is in operation. If you operate
heater with doors closed, heat buildup inside replace will cause glass to burst.
Make sure there are no obstructions
across openings of replace.
8. To prevent the creation of soot, follow the
instructions in Cleaning and Maintenance, page 27.
9. Before using furniture polish, wax, carpet cleaner or similar products, turn heater off. If heated, the vapors from these products may
create a white powder residue within burner box or on adjacent walls and furniture.
10. This heater needs fresh, outside air ven­tilation to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if enough fresh air is not available. See Air for Combustion and Ventilation,
page 6. If heater keeps shutting off, see Troubleshooting, page 30.
11. Do not run heater
• where ammable liquids or vapors are
used or stored
• under dusty conditions
12. Do not use this heater to cook food or burn paper or other objects.
13. Do not use heater if any part has been ex­posed to or under water. Immediately call
a qualied service technician to inspect
the room heater and to replace any part of the control system and any gas control which has been under water.
14. Do not operate heater if any log is broken. Do not operate heater if a log is chipped
(dime-sized or larger).
15. Turn heater off and let cool before servic-
ing, installing or repairing. Make sure the
selector switch is in the OFF position. Only
a qualied service person should install,
service or repair heater.
16. Make sure the selector switch is in the OFF position when you are away from home for long periods of time.
17. Remote-ready heaters must not be con­nected to any external electrical source.
18. Operating heater above elevations of
4,500 feet may cause pilot outage.
19. To prevent performance problems, do
not use propane/LP fuel tank of less than 100 lb. capacity (propane/LP units only).
20. Provide adequate clearances around air openings.
Young children should be carefully supervised when they are in the same
room as the appliance. Toddlers, young children and others may be
susceptible to accidental burns.A physical barrier is recommended if there
are at-risk individuals in the house. To restrict access to a replace or
stove, install an adjustable safety gate to keep toddlers, young children and
other at-risk individuals out of the room and away from hot surfaces.
www.SuperiorFireplaces.US.com
126817-01A 5
PRODUCT IDENTIFICATION
LOCAL CODES
State of Massachusetts: The installa­tion must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts.
Sellers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for bedroom and bathroom installation in the Commonwealth of Massachusetts.
UNPACKING
Install and use heater with care. Follow all
local codes. In the absence of local codes,
use the latest edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
CAUTION: Do not remove the
data plates from the grate as­sembly. The data plates contain important warranty and safety information.
1. Remove logs and heater base assembly from carton(s).
Note: Do not pick up heater base assem-
bly by burners. This could damage heater. Always handle base assembly by grate.
2. Remove all protective packaging applied to logs and heater for shipment.
3. Check heater for any shipping damage. If heater is damaged call INNOVATIVE HEARTH PRODUCTS at 1-800-655-2008 for replacement parts before returning to dealer.
Figure 1 - Product Identication
Glowing
Embers
Chassis
Control Knob
Flame Adjustment Knob
Left Side
Right Side
Front
www.SuperiorFireplaces.US.com
126817-01A6
OPERATION
This heater is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by
both realistic ames and glowing coals. This
heater is designed for vent-free operation with ue damper closed. It has been tested and ap­proved to ANSI Z21.11.2 standard for unvented heaters. State and local codes in some areas prohibit the use of vent-free heaters.
PRODUCT FEATURES
SAFETY DEVICE
This heater has a pilot with an Oxygen Deple­tion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent-free room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.
ELECTRONIC IGNITION SYSTEM
This heater has an electronic ignitor to light heater fuel supply.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not be installed in a room or space unless the required volume of indoor combustion air is provided by the method described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code, or applicable
local codes. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy efcient than ever. New materials, increased insulation
and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. Dur-
ing heating months, home owners want their
homes as airtight as possible. While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning ap­pliances need fresh air for proper combustion and ventilation.
Exhaust fans, replaces, clothes dryers and
fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 6 through 8 will help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion
and ventilation. However, in buildings of un­usually tight construction, you must provide
additional fresh air.
Unusually tight construction is dened as
construction where: a. walls and ceilings exposed to the out-
side atmosphere have a continuous water vapor retarder with a rating of
one perm (6 x 10
-11
kg per pa-sec-m2) or less with openings gasketed or sealed and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window and door frames, between sole plates
and oors, between wall-ceiling joints,
between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh air.
See Ventilation Air From Outdoors, page 8. If your home does not meet all of the three
criteria above, proceed to Determining Fresh­Air Flow For Heater Location, page 7.
www.SuperiorFireplaces.US.com
126817-01A 7
AIR FOR COMBUSTION AND VENTILATION
Continued
Conned and Unconned Space
The National Fuel Gas Code, ANSI Z223.1/ NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu/hr (4.8 m3 per kw) of the aggregate
input rating of all appliances installed in that
space and an unconned space as a space
whose volume is not less than 50 cubic feet
per 1,000 Btu/hr (4.8 m3 per kw) of the ag-
gregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are
installed*, through openings not furnished with doors, are considered a part of the un­conned space.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Conned or Unconned Space
Use this work sheet to determine if you have
a conned or unconned space.
Space: Includes the room in which you will install
replace plus any adjoining rooms with door­less passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support) Example: 2560 cu. ft. (volume of space) x 20
= 51,200 (maximum Btu/Hr the space can
support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free replace __________ Btu/Hr Gas water heater* __________ Btu/Hr Gas furnace __________ Btu/Hr
Vented gas heater __________ Btu/Hr Gas replace logs __________ Btu/Hr Other gas appliances* + _________ Btu/Hr Total = _________ Btu/Hr * Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater __________ Btu/Hr Vent-free replace + _________ Btu/Hr
Total = _________ Btu/Hr
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/ Hr used.
______Btu/Hr (maximum the space can
support)
______Btu/Hr (actual amount used) Example: 51,200 Btu/Hr (maximum the
space can support)
73,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the above example is a conned
space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can sup­port. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides an unconned space, remove door to adjoin­ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 8.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 8.
C. Install a lower Btu/Hr replace, if lower Btu/
Hr size makes room unconned.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is an unconned space. You will need no additional
fresh air ventilation.
40,000 33,000 73,000
www.SuperiorFireplaces.US.com
126817-01A8
AIR FOR COMBUSTION AND VENTILATION
Continued
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two perma­nent openings: one within 12" of the ceiling
and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size
of ventilation grills or ducts. IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermo­stat-controlled power vent. Heated air entering the attic will activate the power vent.
Figure 3 - Ventilation Air from Outdoors
Outlet Air
Ventilated Attic
Outlet
A
ir
Inlet Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
WARNING: If the area in which the heater may be operated does not meet the required volume for indoor combustion air, combus­tion and ventilation air shall be provided by one of the methods described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54,
the International Fuel Gas Code, or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconned space. When ventilating to an adjoining unconned space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the oor on the
wall connecting the two spaces (see options
1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2).
Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size of ventilation
grills or ducts.
Figure 2 - Ventilation Air from Inside Building
Or
Remove Door into Adjoining
Room, Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills Into Adjoining
Room,
Option 1
12"
12"
www.SuperiorFireplaces.US.com
126817-01A 9
WARNING: Never install the
heater
• in a bedroom or bathroom unless
installed as a vented appliance, see page 12
• in a recreational vehicle
where curtains, furniture, clothing
or other ammable objects are less
than 36" from front, 42" from top of heater; for side clearances see
Figure 4, page 10
• in high trafc areas
• in windy or drafty areas
CAUTION: This heater creates
warm air currents. These currents
move heat to wall surfaces next to heater. Installing heater next
to vinyl or cloth wall coverings or operating heater where impurities (such as, but not limited to, to­bacco smoke, aromatic candles,
cleaning uids, oil or kerosene lamps, etc.) in the air exist, may
discolor walls or cause odors.
IMPORTANT: Vent-free heaters add moisture
to the air. Although this is benecial, installing
heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventila-
tion, page 6.
CHECK GAS TYPE
Use the correct type of gas (natural or propane/ LP). If your gas supply is not the correct gas
type, do not install heater. Call dealer where
you bought heater for proper type heater.
WARNING: This appliance is equipped for either natural gas or propane/LP gas but not both. Gas type is indicated on the rating plate.
Field conversion is not permitted.
NOTICE: This heater is intended
for use as supplemental heat. Use this heater along with your primary
heating system. Do not install this
heater as your primary heat source. If you have a central heating system,
you may run system’s circulating
blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualied service
person must install heater. Follow all local codes.
WARNING: Make sure the se-
lector switch is in the OFF position
before installing heater.
WARNING: Any outside air ducts
and/or ash dumps in the replace
shall be permanently closed at time of appliance installation.
WARNING: Seal any fresh air
vents or ash clean-out doors located
on oor or wall of replace. If not,
drafting may cause pilot outage or sooting. Use a heat-resistant
sealant. Do not seal chimney ue
damper.
WARNING: Before installing in a solid fuel burning replace, the chimney ue and rebox must be
cleaned of soot, creosote, ashes and
loose paint by a qualied chimney
cleaner. Creosote will ignite if highly
heated. A dirty chimney ue may
create and distribute soot within the
house. Inspect chimney and rebox ue for damage. If damaged, repair ue and rebox before operating
heater.
INSTALLATION
www.SuperiorFireplaces.US.com
126817-01A10
INSTALLATION
Continued
Noncombustible
Material Distance (A)
Requirements for Safe Installation
1
2" or more Noncombustible mate-
rial OK.
Between 8" and 12"
24" or 30" Models:
Install replace hood accessory (GA6050 or GA6053 see Accesso- ries, page 44).
18" Model: Noncom­bustible material OK.
Less than 8"
Noncombustible mate­rial must be extended to at least 8". See
Between 8" and 12",
above. If you cannot
extend material, you
must operate heater
with ue damper open.
Figure 4 - Minimum Clearance for
Combustible to Wall
*Minimum 16" from Side Wall
*
Example
Minimum Noncombustible Material Clearances
If Not Using Mantel
Note: If using a mantel proceed to If Using Mantel. If not using a mantel, follow these instructions.
You must have noncombustible material(s)
above the replace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2" thick. With sheet metal, you
must have noncombustible material behind it. Noncombustible material must extend at least 8" up (for all models). If noncombustible
material is less than 12", you must install the replace hood accessory (24" and 30"
Models Only). See Figure 5 for minimum clearances.
LOG SIZING REQUIREMENTS
Log
Size
Minimum Firebox Size
Height Depth
Front Width
Rear*
Width
18" 20" 14" 28" 20" 24" 20" 14" 32" 22" 30" 20" 14" 40" 30"
Carefully follow the instructions below. This
will ensure safe installation into a masonry, UL127-listed manufactured replace or listed vent-free rebox.
Minimum Clearances For Side Combustible Material, Side Wall and Ceiling
A. Clearances from the side of the replace
cabinet to any combustible material and
wall should follow diagram in Figure 4,
page 10.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and protrudes 3 1/2" from the wall. This combustible material must be 4" from the
side of the replace cabinet (see Figure 4, page 10).
Note: When installing your gas logs into
a manufactured rebox, follow rebox
manufacturer’s instructions for minimum clearances to combustible materials.
B. Clearances from the top of the replace
opening to the ceiling should not be less than 42".
INSTALLATION AND CLEARANCES FOR VENT-FREE OPERATION
WARNING: Maintain the minimum clearances. If you can, provide greater clearances from
oor, ceiling and adjoining wall.
MINIMUM FIREPLACE CLEARANCE TO
COMBUSTIBLE MATERIALS
Side Wall 16", Ceiling 42"
Floor 5", Front: 36"
www.SuperiorFireplaces.US.com
126817-01A 11
INSTALLATION
Continued
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required clearances between replace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between
mantel shelf and top of replace opening, a
hood is not required (see Figure 6).
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6, are not met, you must have a hood. When using a
hood there are still certain minimum mantel clearances required. Follow minimum clear-
ances shown in Figure 7, when using hood.
Figure 6 - Minimum Mantel Clearances
Without Using Hood
Figure 7 - Minimum Mantel Clearances
When Using Hood
Minimum Non­Combustible Material
Minimum Non­Combustible Material Height
Distances to Underside of Mantel
Top of Fireplace Opening
Underside of Mantel Shelf
12"
8"
(A)
18"
14"
20"
17"
22"
19"
24"
20"
All minimum distances are in inches
Log Set 24"/30" Models
18" Model
2
1
/2
"
6"
8"
10"
Mantel Shelf
If Using Mantel
You must have noncombustible material(s)
above the replace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2" thick. With sheet metal,
you must have noncombustible material be­hind it. Noncombustible material must extend at least 8" up (for all models). If noncombus-
tible material is less than 12", you must install the replace hood accessory (24" and 30"
Models Only). Even if noncombustible mate-
rial is more than 12", you may need the hood accessory to deect heat away from your
mantel shelf. See Figure 5 and Figures 6 and
7, page 11, for minimum clearances.
Minimum Noncombustible Material
8" Min.
12" 15" 18" 20"
2
1
/2
"
6"
8"
10"
12"
Distances to Underside of
Mantel
Hood (GA6050
or GA6053)
Top of Fireplace Opening
Underside
of Mantel
Shelf
Mantel Shelf
Heat Resistant Material
(A)
www.SuperiorFireplaces.US.com
126817-01A12
INSTALLATION
Continued
INSTALLING HEATER BASE ASSEMBLY
WARNING: You must secure
this heater to replace oor. If
not, heater will move when you adjust controls. Moving heater may cause a gas leak.
WARNING: If installing in a
sunken replace, special care
is needed. You must raise the
replace oor to allow access to
heater control panel. This will in-
sure adequate air ow and guard
against sooting and controls be-
ing damaged. Raise replace oor
with noncombustible material. Make sure material is secure.
CAUTION: Do not pick up
heater base assembly by burn­ers. This could damage heater.
Only handle base assembly by
grates.
IMPORTANT: Make sure the heater burners are level.
Installation Items Needed
• hardware package (provided with heater)
• approved exible gas hose and ttings
(provided) (if allowed by local codes)
• sealant (resistant to propane/LP gas, not
provided)
• electric drill with 3/16” masonry drill bit
1. Apply pipe joint sealant lightly to male
threads of the 1/2 NPT side of gas tting
elbow (provided) and connect to inlet
side of gas control. Remove gas tting from exible gas hose (provided) before
connecting to elbow (see Figure 10).
NOTICE: Surface temperatures
of adjacent walls and mantels be­come hot during operation. Walls
and mantels above the rebox
may become hot to the touch. If installed properly, these tem­peratures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.
NOTICE: If your installation does not meet the minimum clear­ances shown, you must do one of the following:
• operate the logs only with the ue damper open
• raise the mantel to an accept-
able height
• remove the mantel
FLOOR CLEARANCES
A. If installing appliance on the oor level,
you must maintain the minimum distance of 14" to combustibles (see Figure 8).
B. If combustible materials are less than
14" to the replace, you must install ap­pliance at least 5" above the top surface
of combustible ooring including tile and
carpet.(see Figure 9).
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
14" Min.
Combustible Material
Noncombustible Material
Hearth
5" Min.
Combustible Material
www.SuperiorFireplaces.US.com
126817-01A 13
INSTALLATION
Continued
2. Position heater base assembly in re­place.
3. Mark screw locations through holes in front panel of base (see Figure 11). If
installing in a brick-bottom replace, mark
screw locations in mortar joint of bricks.
4. Remove heater base from replace.
5. Drill holes at marked locations using 3/16" drill bit.
6. Attach base, through holes in back side pan­els of base, to replace oor using masonry
screws provided in hardware package (see Figure 11).
7. Connect to gas supply. See Connecting To Gas Supply.
Figure 10 - Attaching Flexible Gas Hose
to Heater Gas Regulator
Gas Control
Flexible Gas Hose
(Install if allowed by local codes)
Figure 11 - Attaching Base to Fireplace
Floor
Masonry Screw
CONNECTING TO GAS SUPPLY
WARNING: This appliance
requires a 3/8" NPT (National
Pipe Thread) inlet connection to
the pressure regulator.
WARNING: A qualied ser­vice person must connect heater to gas supply. Follow all local codes.
CAUTION: Never connect propane/LP replace directly
to the propane/LP supply. This
heater requires an external regu­lator (not supplied). Install the external regulator between the
heater and propane/LP supply.
WARNING: Never connect
natural gas replace to private (non-utility) gas wells. This
gas is commonly known as wellhead gas.
Installation Items Needed
Before installing heater, make sure you have
the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved exible gas line with gas con-
nector (if allowed by local codes) (not provided)
* An equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional equipment shutoff valve from your dealer.
Elbow, 3/8 NPT x
3/8 Flare
www.SuperiorFireplaces.US.com
126817-01A14
Pipe Cap Tee Nipple Joint
For propane/LP units, the installer must
supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11" and 14" of water. If you do not re-
duce incoming gas pressure, heater regulator
damage could occur. Install external regulator with the vent pointing down as shown in Figure
13. Pointing the vent down protects it from
freezing rain or sleet.
CAUTION: Use only new,
black iron or steel pipe. In­ternally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to heater. If pipe is too small, undue loss of volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 13).
IMPORTANT: Install equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
Check your building codes for any special requirements for locating equipment shutoff
valve to replaces.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
Propane/LP Supply Tank
External Regulator with Vent Pointing Down
Figure 12 - External Regulator With Vent
Pointing Down
INSTALLATION
Continued
* Purchase the optional equipment shutoff
valve from your dealer.
**Minimum inlet pressure for purpose of input
adjustment.
Figure 13 - Gas Connection (Remote-
Ready Models Only)
Gas
Control
3" Minimum
Sediment Trap
Equipment Shutoff Valve With 1/8" NPT Tap*
Approved Flexible
Gas Hose (if
allowed by local codes)
PROPANE/LP
From External
Regulator
(11" W.C.**
to 14" W.C.
Pressure)
NATURAL
From Gas
Meter
(5" W.C.**
to 10.5"
W.C.
Pressure)
We recommend that you install a sediment trap in supply line as shown in Figure 13. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to
freeze. A sediment trap traps moisture and
contaminants. This keeps them from going into heater controls. If sediment trap is not
installed or is installed wrong, heater may
not run properly.
Loading...
+ 30 hidden pages