This appliance may be installed in an aftermarket permanently located, manufactured (mobile) home, where not
prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This
appliance is not convertible for use with other gases.
WARNING: This appliance is for installation only in a solid-fuel burning masonry or UL127 factory-built
fi replace or in a listed ventless fi rebox enclosure. It is design-certifi ed for these installations in accordance
with ANSI Z21.11.2. Exception: DO NOT install this appliance in a factory-built fi replace that includes
instructions stating it has not been tested or should not be used with unvented gas logs.
This is an unvented gas-fi red heater. It uses air (oxygen) from the room in which it is installed. Provisions
for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation
section on Page 6 of this manual.
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
- Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re department.
- Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
installation, adjustment,
alteration, service or maintenance can cause injury or
property damage. Refer to
this manual for correct installation and operational
procedures. For assistance or additional information consult a qualifi ed
installer , service agency or
the gas supplier .
WARNING: This appliance is for installation
only in a solid-fuel-burning
masonry or UL127 factorybuilt fi replace or in a listed
unvented gas-fi red appli-
ance. It uses air (oxygen)
from the room in which
it is installed. Provisions
for adequate combustion
and ventilation air must
be provided. Refer to Air
for Combustion and Ventilation section on Page 6
of this manual.
This appliance may be in-
stalled in an aftermarket,*
permanently located,
manufactured (mobile)
home, where not prohib-
ited by local codes.
ventless fi rebox enclosure.
It is design-certified for
these installations in accordance with ANSI Z21.11.2.
Exception: DO NOT install
this appliance in a factorybuilt fi replace that includes
instructions stating it has
not been tested or should
not be used with unvented
gas logs.
2
SuperiorFireplaces.us.com
This appliance is only for
use with the type of gas
indicated on the rating
plate. This appliance is
not convertible for use
with other gases.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
900463-01A
SAFETY
Continued
WARNING: This product contains and/or generates chemicals
known to the state of California
to cause cancer or birth defects
or other reproductive harm.
IMPORT ANT: Read this owner’ s
manual carefully and completely
before trying to assemble, operate or service this appliance.
Improper use of this appliance
can cause serious injury or
death from burns, fi re, explo-
sion, electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning resemble the fl u,
with headaches, dizziness or nausea. If you
have these signs, the fi replace may not be
working properly. Get fresh air at once! Have
fi replace serviced. Some people are more affected by carbon monoxide than others. These
include pregnant women, people with heart
or lung disease or anemia, those under the
infl uence of alcohol and those at high altitudes.
Natural and Propane/LP
odor-making agent is added to these gases.
The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas
may be present even though no odor exists.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this fi replace.
gases are odorless. An
WARNING: Any change to
this appliance or its controls can
be dangerous.
WARNING: Do not allow fans
to blow directly into the appliance.
Avoid any drafts that alter burner
fl ame patterns. Ceiling fans can
create drafts that alter burner fl ame
patterns. Altered burner patterns
can cause sooting.
Due to high temperatures, the appliance should be located out of
traffi c and away from furniture and
draperies.
Do not place clothing or other
fl ammable material on or near the
appliance. Never place any objects
on the appliance.
Appliance base assembly becomes
very hot when running appliance.
Keep children and adults away from
hot surface to avoid burns or clothing ignition. Appliance will remain
hot for a time after shutdown. Allow
surface to cool before touching.
Carefully supervise young children
when they are in the room with appliance. When using the hand-held remote accessory , keep selector switch
in the OFF position to prevent children
from turning on burners with remote.
You must operate this appliance
with the fi replace screen and hood
in place. Make sure fi replace screen
and hood are in place before running
appliance. The fi replace screen shall
have openings for introduction of
combustion air.
WARNING: Do not use a blower
insert, heat exchanger insert or
other accessory not approved for
use with this appliance.
900463-01A
SuperiorFireplaces.us.com
Keep the appliance area clear and
free from combustible materials,
gasoline and other fl ammable va-
pors and liquids.
3
SAFETY
Continued
1. This appliance is only for use with the type
of gas indicated on the rating plate. This appliance is not convertible for use with other
gases.
2. Do not place propane/LP supply tank(s)
inside any structure. Locate propane/LP
supply tank(s) outdoors (propane/LP units
only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions
• if you cannot reach your gas supplier , call
the fi re department
4. This appliance shall not be installed in a
bedroom or bathroom, unless installed as
a vented appliance. See Installing Damper Clamp Accessory for Vented Operation,
Page 12. This gas log set may not be installed as a vented appliance in a bedroom
or bathroom in the Commonwealth of Massachusetts.
5. Before installing in a solid fuel-burning fi re-
place, the chimney fl ue and fi rebox must
be cleaned of soot, creosote, ashes and
loose paint by a qualifi ed chimney cleaner.
Creosote will ignite if highly heated. A dirty
chimney fl ue may create and distribute soot
within the house. Inspect chimney fl ue for
damage. If damaged, repair fl ue and fi rebox
before operating appliance.
6. Do not burn solid-fuel in a fi replace in which
a vent-free room appliance is installed.
7. If fi replace has glass doors, never operate
this appliance with glass doors closed. Any
glass doors shall be fully opened when the
appliance is in operation. If you operate
appliance with doors closed, heat buildup
inside fi replace will cause glass to burst.
Make sure there are no obstructions across
openings of fi replace.
8. To prevent the creation of soot, follow the
instructions in Cleaning and Maintenance,
Page 30.
9. Before using furniture polish, wax, carpet
cleaner or similar products, turn appliance
off. If heated, the vapors from these products may create a white powder residue
within burner box or on adjacent walls and
furniture.
10. This appliance needs fresh, outside air
ventilation to run properly. This appliance
has an Oxygen Depletion Sensing (ODS)
safety shutoff system. The ODS shuts down
the appliance if enough fresh air is not available. See Air for Combustion and Ventilation,
Page 6. If appliance keeps shutting off, see
T roubleshooting, Page 32.
1 1. Do not run appliance
• where fl ammable liquids or vapors are
used or stored
• under dusty conditions
12. Do not use this appliance to cook food or
burn paper or other objects.
13. Do not use appliance if any part has been
exposed to or under water. Immediately call
a qualifi ed service technician to inspect the
room appliance and to replace any part of
the control system and any gas control which
has been under water.
14. Do not operate appliance if any log is broken.
Do not operate appliance if a log is chipped
(dime-sized or larger).
15. Turn appliance off and let cool before servicing, installing or repairing. Make sure the
selector switch is in the OFF position. Only
a qualifi ed service person should install,
service or repair appliance.
16. Make sure the selector switch is in the OFF
position when you are away from home for
long periods of time.
17. Remote-ready appliances must not be connected to any external electrical source.
18. Operating appliance above elevations of
4,500 feet may cause pilot outage.
19. To prevent performance problems, do not
use propane/LP fuel tank of less than 100 lb.
capacity (propane/LP units only).
20. Provide adequate clearances around air
openings.
Young children should be carefully supervised when they are in the same room as
the appliance. Toddlers, young children and others may be susceptible to accidental
burns.A physical barrier is recommended if there are at-risk individuals in the house.
To restrict access to a fi replace or stove, install an adjustable safety gate to keep
toddlers, young children and other at-risk individuals out of the room and away from
hot surfaces.
SuperiorFireplaces.us.com
900463-01A4
PRODUCT IDENTIFICATION
Left
Side
ChassisControl
Glowing
Embers
Front
Figure 1 - Product Identifi cation
LOCAL CODES
Install and use appliance with care. Follow all
local codes. In the absence of local codes, use
the latest edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
25 West 43rd Street, 4th fl oor
New York, NY 10036
National Fire Protection Association, Inc.
1 Batterymarch Park
Quincy, MA 02169-7471
Right
Side
Knob
Flame
Adjustment Knob
State of Massachusetts: The installation must be made by a licensed plumber
or gas fitter in the Commonwealth of
Massachusetts.
Sellers of unvented propane or natural
gas-fi red supplemental room heaters shall
provide to each purchaser a copy of 527
CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for
bedroom and bathroom installation in the
Commonwealth of Massachusetts.
OPTIONAL REMOTE
UNPACKING
CONTROL ACCESSORIES
There are fi ve optional remote controls that
can be purchased separately for RemoteReady Models Only:
• wall switch
• hand-held ON/OFF remote
• wall thermostat
• hand-held thermostat remote
• TSRC hand-held remote
See Accessories, Page 41.
The wall thermostat or hand-held thermostat
may not be used where vented decorative listing is required.
Variable remote control models include a thermostat remote control.
900463-01A5
SuperiorFireplaces.us.com
CAUTION: Do not remove the
data plates from the grate assembly . The data plates contain
important warranty and safety
information.
1. Remove logs and appliance base assembly from carton(s).
NOTE: Do not pick up appliance base
assembly by burners. This could damage
appliance. Always handle base assembly
by grate.
2. Remove all protective packaging applied
to logs and appliance for shipment.
3. Check appliance for any shipping damage. If appliance is damaged, promptly
inform dealer where you purchased the
appliance.
PRODUCT FEATURES
OPERATION
This appliance is clean burning. It requires
no outside venting. There is no heat loss out
a vent or up a chimney. Heat is generated by
both realistic fl ames and glowing coals. This
appliance is designed for vent-free operation
with fl ue damper closed. It has been tested
and approved to the ANSI Z21.11.2 standard
for unvented appliances. State and local codes
in some areas prohibit the use of vent-free appliances. This appliance may also be operated
as a vented decorative (ANSI Z21.60) product
by opening the fl ue damper.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not
be installed in a room or space unless the required volume of indoor
combustion air is provided by the
method described in the National
Fuel Gas Code, ANSI Z223.1/NFPA
54, the International Fuel Gas Code,
or applicable local codes. Read the
following instructions to ensure
proper fresh air for this and other fuelburning appliances in your home.
Today’s homes are built more energy effi cient
than ever. New materials, increased insulation
and new construction methods help reduce
heat loss in homes. Homeowners apply
weather strip and caulk around windows and
doors to keep the cold air out and the warm air
in. During heating months, homeowners want
their homes as airtight as possible.
While it is good to make your home energy
effi cient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning appliances need fresh air for proper combustion
and ventilation.
Exhaust fans, some fi replaces, clothes dryers
and some fuel-burning appliances draw air
from the house to operate. You must provide
adequate fresh air for these appliances. That
will ensure proper venting of vented fuel-burning
appliances.
PROVIDING ADEQUA TE
VENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation.
All spaces in homes fall into one of the three
SuperiorFireplaces.us.com
SAFETY DEVICE
This appliance has a pilot with an Oxygen
Depletion Sensing (ODS) safety shutoff
system. The ODS/pilot is a required feature
for vent-free room appliances. The ODS/pilot
shuts off the appliance if there is not enough
fresh air.
ELECTRONIC IGNITION SYSTEM
This appliance has an electronic igniter to light
appliance fuel supply.
following ventilation classifi cations:
1. Unusually Tight Construction
2. Unconfi ned Space
3. Confi ned Space
The information on Pages 6 through 8 will
help you classify your space and provide
adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of unusually tight construction, you must provide
additional fresh air.
Unusually tight construction is defi ned as
construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6 x 10
less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window
and door frames, between sole plates
and fl oors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical and gas lines
and at other openings.
If your home meets all three criteria above,
you must provide additional fresh air. See
Ventilation Air From Outdoors, Page 8.
If your home does not meet all three criteria
above, proceed to Determining Fresh-Air Flow
For Heater Location, Page 7.
Confi ned and Unconfi ned Space
The National Fuel Gas Code, ANSI Z223.1/
NFP A54 allows two methods for determining
-11
kg per pa-sec-m2) or
900463-01A6
AIR FOR COMBUSTION AND VENTILATION
Continued
whether the space in which the heater is being
installed is confi ned or unconfi ned space. The
standard method defi nes a confi ned space as
a space whose volume is less than 50 cubic
3
feet per 1,000 Btu/hr (4.8 m
per kw) of the aggregate input rating of all appliances installed
in that space and an unconfi ned space as
a space whose volume is not less than 50
3
cubic feet per 1,000 Btu/hr (4.8 m
per kw) of
the aggregate input rating of all appliances
installed in that space. Rooms communicating
directly with the space in which the appliances
are installed*, through openings not furnished
with doors, are considered a part of the unconfi ned space.
Where the air infi ltration rate of a structure is
known, the Known Air Infi ltration Rate Method
may be used. Follow The National Fuel Gas
Code, ANSI Z223.1/NFPA 54 to use this
method to determine if the space is confi ned
or unconfi ned.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Determining if You Have a Confi ned or
Unconfi ned Space Using the Standard
Method
Use this work sheet to determine if you have
a confi ned or unconfi ned space.
Space: Includes the room in which you will install
fi replace plus any adjoining rooms with doorless passageways or ventilation grills between
the rooms.
1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20 =
51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel-burning appliances
in the space.
900463-01A7
SuperiorFireplaces.us.com
Vent-free fi replace __________Btu/HrGas water heater* __________Btu/Hr
Gas furnace __________Btu/Hr
Vented gas heater __________Btu/Hr
Gas fi replace logs __________Btu/HrOther gas appliances* + _________ Btu/Hr
Total = _________Btu/Hr
* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
Example:Gas water heater __________Btu/Hr
Vent-free fi replace + _________Btu/Hr
Total = _________Btu/Hr
4. Compare the maximum Btu/Hr the space
can support with the actual amount of Btu/
Hr used.
______Btu/Hr (maximum the space can
support)
______Btu/Hr (actual amount used)
Example: 51,200 Btu/Hr (maximum the
space can support)
73,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the above example is a confi ned
space because the actual Btu/Hr used is more
than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your
options are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides
an unconfi ned space, remove door to adjoin-
ing room or add ventilation grills between
rooms. See Ventilation Air From Inside
Building, Page 8.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, Page 8.
C. Install a lower Btu/Hr appliance, if lower Btu/
Hr size makes room unconfi ned.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is
an unconfi ned space. Y ou will need no additional
fresh air ventilation.
40,000
33,000
73,000
WARNING: If the area in which
the appliance may be operated does
not meet the required volume for
indoor combustion air, combustion
and ventilation air shall be provided
by one of the methods described in
the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, the International
Fuel Gas Code, or applicable local
codes.
AIR FOR COMBUSTION AND VENTILATION
A
Continued
VENTILA TION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconfi ned space. When ventilating to an
adjoining unconfi ned space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the fl oor on the
wall connecting the two spaces (see options 1 and 2, Figure 2). Y ou can also remove door
into adjoining room (see option 3, Figure 2).
Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and
Ventilation for required size of ventilation
grills or ducts.
12"
Ventilation
Grills Into
Adjoining
Room,
Option 1
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
12"
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two permanent openings: one within 12" of the ceiling
and one within 12" of the fl oor . Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings
for inlet or outlet air into attic if attic has a
thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.
Ventilated
Attic
Ventilated
Crawl Space
To Attic
To
Crawl
Space
Outlet
ir
Inlet
Air
Outlet
Air
Inlet Air
Figure 3 - Ventilation Air from Outdoors
Figure 2 - Ventilation Air from Inside
Building
INSTALLATION
NOTICE: This appliance is intended
for use as supplemental heat. Use
this appliance along with your primary
heating system. Do not install this appliance as your primary heat source.
If you have a central heating system,
you may run system’s circulating
blower while using appliance. This will
help circulate the heat throughout the
house. In the event of a power outage,
you can use this appliance as your
primary heat source.
WARNING: A qualifi ed service
person must install appliance. Follow
all local codes.
NOTICE: State or local codes may
only allow operation of this appliance
in a vented confi guration. Check your
state or local codes.
WARNING: Make sure the selector
switch is in the OFF position before
installing appliance.
WARNING: Any outside air ducts
and/or ash dumps in the fi replace
shall be permanently closed at time
of appliance installation.
WARNING: Seal any fresh air vents
or ash clean-out doors located on fl oor
or wall of fi replace. If not, drafting may
cause pilot outage or sooting. Use a
heat-resistant sealant. Do not seal
chimney fl ue damper.
SuperiorFireplaces.us.com
900463-01A8
INSTALLATION
Continued
W ARNING: Before installing
CHECK GAS TYPE
Use the correct type of gas (natural or propane/
LP). If your gas supply is not the correct gas
type, do not install appliance. Call dealer where
you bought appliance for proper type appliance.
in a solid fuel-burning fi replace,
the chimney fl ue and fi rebox
must be cleaned of soot, creosote, ashes and loose paint by
a qualified chimney cleaner.
Creosote will ignite if highly
heated. A dirty chimney fl ue may
WARNING: This appliance is
equipped for either natural gas
or propane/LP gas but not both.
Gas type is indicated on the rating plate. Field conversion is not
permitted.
create and distribute soot within
the house. Inspect chimney and
fi rebox fl ue for damage. If dam-
INST ALLATION AND CLEARANCES
FOR VENT-FREE OPERATION
aged, repair fl ue and fi rebox
before operating appliance.
WARNING: Maintain the
minimum clearances. If you can,
W ARNING: Never install the
appliance
• in a bedroom or bathroom
unless installed as a vented
appliance, see Page 12
• in a recreational vehicle
where curtains, furniture, cloth-
•
ing or other fl ammable objects
are less than 36" from front, 42"
from top of appliance; for side
clearances see Figure 4, Page 10
• in high traffi c areas
• in windy or drafty areas
CAUTION: This appliance
creates warm air currents. These
currents move heat to wall surfaces
next to appliance. Installing appliance next to vinyl or cloth wall
coverings or operating appliance
where impurities (such as, but
not limited to, tobacco smoke,
aromatic candles, cleaning fl uids,
oil or kerosene lamps, etc.) in the
air exist, may discolor walls or
cause odors.
IMPORTANT: Vent-free appliances add
moisture to the air. Although this is benefi cial,
installing appliance in rooms without enough
ventilation air may cause mildew to form from
too much moisture. See Air for Combustion and Ventilation, Page 6.
900463-01A9
SuperiorFireplaces.us.com
provide greater clearances from
fl oor, ceiling and adjoining wall.
MINIMUM FIREPLACE CLEARANCE TO
COMBUSTIBLE MATERIALS
Side Wall 16", Ceiling 42"
Floor 5", Front: 36"
LOG SIZING REQUIREMENTS
Log
Size
LMF24GTA/B
LMF24MOA/B
LMF30GTA/B
LMF30MOA/B
LMF36GTA/B
LMF36MOA/B
* Also approved for use in VEGA42 and V ALIANT42
Series fi replaces.
Carefully follow the instructions below. This
will ensure safe installation into a masonry,
UL127-listed manufactured fi replace or listed
vent-free fi rebox.
Minimum Clearances For Side Combustible
Material, Side Wall and Ceiling
A. Clearances from the side of the fi replace
cabinet to any combustible material and
wall should follow diagram in Figure 4, Page 10.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material
and protrudes 3-1/2" from the wall. This
combustible material must be 4" from the
side of the fi replace cabinet (see Figure
4, Page 10).
Minimum Firebox Size
Height Depth
29"15.5"32.5"22.75"
29"15.5"39"26.75"
29''20''47''33''
Front
Width
Rear*
Width
INSTALLATION
Continued
NOTE: When installing your gas logs into
a manufactured fi rebox, follow fi rebox
manufacturer’s instructions for minimum
clearances to combustible materials.
B. Clearances from the top of the fi replace
opening to the ceiling should not be less
than 42".
NOTICE: Manual control appliances may be used as a vented
product. If so, you must always
run appliance with chimney
fl ue damper open. If running
appliance with damper open,
noncombustible material above
fi replace opening is not needed.
Go to Installing Damper Clamp
Accessory for Vented Operation,
Page 12.
Noncombustible
Material Distance
(A)
1
2" or moreNoncombustible mate-
Between 8" and 12"
Less than 8"
Heat Resistant
Material
Requirements for
Safe Installation
rial OK.
Install fi replace hood ac-
cessory (GA6050 - see
Accessories, Page 41).
Noncombustible material must be extended
to at least 8". See
Between 8" and 12",
above. If you cannot
extend material, you
must operate appliance
with fl ue damper open.
(A)
Example
*
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
Minimum Noncombustible Material
Clearances
If Not Using Mantel
NOTE: If using a mantel proceed to If Using
Mantel. If not using a mantel, follow these
instructions.
You must have noncombustible material(s)
above the fi replace opening. Noncombustible
materials (such as slate, marble, tile, etc.) must
be at least 1/2" thick. With sheet metal, you
must have noncombustible material behind
it. Noncombustible material must extend at
least 8" up (for all models). If noncombustible
material is less than 12", you must install the
fi replace hood accessory (24" and 30" Models
Only). See Figure 5 for minimum clearances.
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
If Using Mantel
You must have noncombustible material(s)
above the fi replace opening. Noncombus-
tible materials (such as slate, marble, tile,
etc.) must be at least 1/2" thick. With sheet
metal, you must have noncombustible material behind it. Noncombustible material
must extend at least 8" up (for all models). If
noncombustible material is less than 12", you
must install the fi replace hood accessory (24"
and 30" Models Only). Even if noncombustible
material is more than 12", you may need the
hood accessory to defl ect heat away from
your mantel shelf. See Figure 5 and Figures
6 and 7, Page 11, for minimum clearances.
IMPORTANT: If you cannot meet these
minimum clearances, you must operate
pliance
to Installing Damper Clamp Accessory for Vented Operation, Page 12.
with chimney fl ue damper open. Go
ap-
SuperiorFireplaces.us.com
900463-01A10
INSTALLATION
Continued
MANTEL CLEARANCES
In addition to meeting noncombustible material clearances, you must also meet required
clearances between fi replace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between
mantel shelf and top of fi replace opening, a
hood is not required (see Figure 6).
Mantel Shelf
/2
"
(A)
12"
18" 20"22"24"
Distances to
Underside of
Mantel
Underside of
Mantel Shelf
All minimum
distances are
in inches
Top of Fireplace
Opening
Minimum NonCombustible
Material
10"
8"
6"
1
2
Minimum NonCombustible
Material Height
NOTICE: Surface temperatures
of adjacent walls and mantels become hot during operation. Walls
and mantels above the fi rebox
may become hot to the touch.
If installed properly, these temperatures meet the requirement
of the national product standard.
Follow all minimum clearances
shown in this manual.
NOTICE: If your installation does
not meet the minimum clearances shown, you must do one
of the following:
• operate the logs only with the
fl ue damper open
• raise the mantel to an acceptable height
• remove the mantel
Figure 6 - Minimum Mantel Clearances
Without Using Hood
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6, are not
met, you must have a hood. When using a
hood there are still certain minimum mantel
clearances required. Follow minimum clearances shown in Figure 7, when using hood.
"
8"
Min.
Mantel Shelf
12" 15" 18" 20"
Distances to
Underside of
Mantel
Underside
of Mantel
Shelf
Top of
Fireplace
Opening
Minimum
Noncombustible
Material
12"
10"
8"
6"
1
/2
2
Hood (GA6050
or GA6053)
FLOOR CLEARANCES
A. If installing appliance on the fl oor level,
you must maintain the minimum distance
of 14" to combustibles (see Figure 8).
B. If combustible materials are less than
14" to the fi replace, you must install ap-
pliance at least 5" above the top surface
of combustible fl ooring including tile and
carpet (see Figure 9).
Combustible
14"
Min.
Noncombustible Material
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Material
Hearth
Figure 7 - Minimum Mantel Clearances
When Using Hood
Minimum clearance requirements include any projections such
as shelves, window sills, mantels, etc. above the appliance.
900463-01A11
SuperiorFireplaces.us.com
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
5"
Min.
Combustible
Material
INSTALLATION
Continued
INSTALLING DAMPER CLAMP
ACCESSORY FOR VENTED
OPERATION
NOTE: When used as a vented appliance,
appliance must be installed only in a solidfuel-burning fi replace with a working fl ue and
constructed of noncombustible material.
For Massachusetts Residents Only: Installation of this gas log set as a vented appliance
in the Commonwealth of Massachusetts requires the damper be permanently removed
or welded in the fully open position.
If your appliance is a manually-controlled
model, you may use this appliance as a
vented product. There are three reasons for
operating your appliance in the vented mode.
1. The fi replace does not meet the clearance
to combustibles requirements for ventfree operation.
2. State or local codes do not permit ventfree operation.
3. You prefer vented operation.
If reasons number 1 or 2 above apply to you,
you must permanently open chimney fl ue
damper. You must install the damper clamp
accessory (to order, see Accessories, Page
41). This will ensure vented operation (see
Figure 10). The damper clamp will keep
damper open. Installation instructions are
included with clamp accessory.
See chart below for minimum permanent fl ue
opening you must provide. Attach damper
clamp so the minimum permanent fl ue open-
ing will be maintained at all times.
W ARNING: Y ou must secure
this appliance to fi replace fl oor.
If not, appliance will move when
you adjust controls. Moving appliance may cause a gas leak or
log misplacement.
WARNING: If installing in a
sunken fi replace, special care
is needed. You must raise the
fi replace fl oor to allow access
to appliance control panel. This
will ensure adequate air fl ow
and guard against sooting and
controls being damaged. Raise
fi replace fl oor with noncombus-
tible material. Make sure material
is secure.
Chimney Minimum Permanent
Height Flue Opening
6' to 15' 39 sq. inches
15' to 30' 29 sq. inches
SuperiorFireplaces.us.com
CAUTION: Do not pick up
appliance base assembly by
burners. This could damage
appliance. Only handle base
assembly by grates.
IMPORTANT: Make sure the appliance burners are level.
900463-01A12
INSTALLATION
Continued
Installation Items Needed
• hardware package (provided with appliance)
• approved fl exible gas hose and fi ttings
provided (if allowed by local codes)
• sealant (resistant to propane/LP gas, not
provided)
• electric drill with 3/16” masonry drill bit
NOTE: Install optional MRC Series receiver
and hand-held remote control kit (see Accessories, Page 41) before installing gas
log appliance. See installation instructions
included with the kit.
1. Apply pipe joint sealant lightly to male
threads of the 1/2 NPT side of gas fi tting
elbow (provided) and connect to inlet
side of gas control. Remove gas fi tting
from fl exible gas hose (provided) before
connecting to elbow (see Figure 11).
2. Position appliance base assembly in
fi replace.
3. Mark screw locations through holes in
front panel of base (see Figure 12). If
installing in a brick-bottom fi replace, mark
screw locations in mortar joint of bricks.
4. Remove appliance base from fi replace.
5. Drill holes at marked locations using 3/16"
drill bit.
6. Attach base, through holes in back side pan-
els of base, to fi replace fl oor using masonry
screws provided in hardware package (see Figure 12).
7. Connect to gas supply. See Connecting
To Gas Supply.
Flexible Gas Hose
(Provided with VGC
Series Models Only)
(Install if allowed
by local codes)
Elbow, 1/2 NPT x
3/8 Flare
Gas Control
Figure 11 - Attaching Flexible Gas Hose
to Appliance Gas Regulator
Masonry Screw
Figure 12 - Attaching Base to Fireplace
Floor
CONNECTING TO GAS SUPPLY
WARNING: This appliance
requires a 3/8" NPT (National
Pipe Thread) inlet connection to
the pressure regulator.
WARNING: A qualifi ed ser-
vice person must connect appliance to gas supply . Follow all
local codes.
CAUTION: Never connect
propane/LP appliance directly
to the propane/LP supply. This
appliance requires an external
regulator (not supplied). Install
the external regulator between
the appliance and propane/LP
supply.
WARNING: Never connect
natural gas appliance to private
(non-utility) gas wells. This
gas is commonly known as
wellhead gas.
900463-01A13
SuperiorFireplaces.us.com
INSTALLATION
Continued
Installation Items Needed
Before installing appliance, make sure you
have the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved fl exible gas line with gas connec-
tor (if allowed by local codes) (not provided)
* An equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge
connection. Purchase the optional equipment
shutoff valve from your dealer.
For propane/LP units, the installer must
supply an external regulator. The external
regulator will reduce incoming gas pressure.
You must reduce incoming gas pressure to
between 11" and 14" of water. If you do not
reduce incoming gas pressure, appliance
regulator damage could occur. Install external regulator with the vent pointing down as
shown in Figure 13. Pointing the vent down
protects it from freezing rain or sleet.
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could
result in clogged appliance valves.
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
Propane/LP
Supply Tank
External
Regulator
with Vent
Pointing
Down
Figure 13 - External Regulator With Vent
Pointing Down
CAUTION: Use only new,
black iron or steel pipe. Internally-tinned copper tubing
may be used in certain areas.
Check your local codes. Use
pipe of 1/2" diameter or greater
to allow proper gas volume to
appliance. If pipe is too small,
undue loss of volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up.
NPT tap must be upstream from appliance
(see Figure 14).
IMPORTANT: Install equipment shutoff valve
in an accessible location. The equipment
shutoff valve is for turning on or shutting off
the gas to the appliance.
Check your building codes for any special
requirements for locating equipment shutoff
valve to appliances.
Equipment Shutoff Valve
With 1/8" NPT Tap*
Approved Flexible
Gas Hose (if
allowed by local
codes)
3" Minimum
Pipe Cap Tee
Nipple Joint
Gas
Control
Figure 14 - Gas Connection (Remote-
Ready Models Only)
* Purchase the optional equipment shutoff
valve from your dealer.
** Minimum inlet pressure for purpose of input
adjustment.
Sediment Trap
PROPANE/LP
From External
Regulator
(11" W.C.**
to 14" W.C.
Pressure)
NATURAL
From Gas
Meter
(5" W.C.**
to 10.5"
W.C.
Pressure)
SuperiorFireplaces.us.com
900463-01A14