Superior Installation And Operation Instructions Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
P/N 900462-01 Rev. NC 08/2015
Installation and Operation Instructions
Superior® Unvented (Vent-Free) Gas Log Heater
Models
MNF24INE MNF24IPE MNF30INE MNF30IPE
P900462-01
PFS
Report No. 10-87
®
US
For use with log sets
LMF24GTA, LMF24GTB, LMF30GTA, LMF30GTB, LMF36GTA, and LMF36GTB
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
This appliance may be installed in an aftermarket permanently located, manufactured (mobile) home, where not
prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This
appliance is not convertible for use with other gases.
WARNING: This appliance is for installation only in a solid-fuel burning masonry or UL127 factory-built
fi replace or in a listed ventless fi rebox enclosure. It is design-certifi ed for these installations in accordance
with ANSI Z21.11.2. Exception: DO NOT install this appliance in a factory-built fi replace that includes
instructions stating it has not been tested or should not be used with unvented gas logs.
This is an unvented gas-fi red heater. It uses air (oxygen) from the room in which it is installed. Provisions
for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation
section on page 6 of this manual.
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
- Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other
appliance.
- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re department.
- Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
er installation, adjustment, alteration, service
or maintenance can cause
injury or property damage.
Refer to this manual for
correct installation and
operational procedures.
For assistance or additional information consult
a qualifi ed installer, ser-
vice agency or the gas
supplier.
WARNING: This appliance is for installation
only in a solid-fuel burning
masonry or UL127 factory-
unvented gas-fi red heat-
er. It uses air (oxygen)
from the room in which
it is installed. Provisions
for adequate combustion
and ventilation air must
be provided. Refer to Air
for Combustion and Ventilation section on page 6
of this manual.
This appliance may be in-
stalled in an aftermarket,*
permanently located,
manufactured (mobile)
home, where not prohib-
ited by local codes.
built fi replace or in a listed
ventless fi rebox enclosure.
It is design-certified for
these installations in accordance with ANSI Z21.11.2.
Exception: DO NOT install
this appliance in a factorybuilt fi replace that includes
instructions stating it has
not been tested or should
not be used with unvented
gas logs.
SuperiorFireplaces.us.com
This appliance is only for
use with the type of gas
indicated on the rating
plate. This appliance is
not convertible for use
with other gases.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
900462-01 NC2
SAFETY
Continued
WARNING: This product contains and/or generates chemicals
known to the state of California
to cause cancer or birth defects
or other reproductive harm.
IMPORT ANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate or service this fi replace.
Improper use of this fi replace
can cause serious injury or
death from burns, fi re, explo-
sion, electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning resemble the fl u,
with headaches, dizziness or nausea. If you
have these signs, the fi replace may not be
working properly. Get fresh air at once! Have
fi replace serviced. Some people are more affected by carbon monoxide than others. These
include pregnant women, people with heart
or lung disease or anemia, those under the
infl uence of alcohol and those at high altitudes.
Natural and Propane/LP
odor-making agent is added to these gases.
The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas
may be present even though no odor exists.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this fi replace.
gases are odorless. An
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not allow fans
to blow directly into the fi replace.
Avoid any drafts that alter burner
fl ame patterns. Ceiling fans can
create drafts that alter burner fl ame
patterns. Altered burner patterns
can cause sooting.
Due to high temperatures, the appliance should be located out of
traffi c and away from furniture and
draperies.
Do not place clothing or other
fl ammable material on or near the
appliance. Never place any objects
on the heater.
Heater base assembly becomes
very hot when running heater. Keep
children and adults away from hot
surface to avoid burns or clothing
ignition. Heater will remain hot for a
time after shutdown. Allow surface
to cool before touching.
Carefully supervise young children
when they are in the room with heater.
When using the hand-held remote
accessory, keep selector switch in
the OFF position to prevent children
from turning on burners with remote.
You must operate this heater with
the fi replace screen and hood in
place. Make sure fi replace screen
and hood are in place before running
heater. The fi replace screen shall
have openings for introduction of
combustion air.
WARNING: Do not use a
blower insert, heat exchanger
insert or other accessory not approved for use with this heater.
900462-01 NC3
SuperiorFireplaces.us.com
Keep the appliance area clear and
free from combustible materials,
gasoline and other fl ammable va-
pors and liquids.
SAFETY
Continued
1. This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases.
2. Do not place propane/LP supply tank(s)
inside any structure. Locate propane/LP
supply tank(s) outdoors (propane/LP units
only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas supplier’s instructions
• if you cannot reach your gas supplier,
call the fi re department
4. This heater shall not be installed in a
bedroom or bathroom.
5. Before installing in a solid fuel burning fi re-
place, the chimney fl ue and fi rebox must
be cleaned of soot, creosote, ashes and
loose paint by a qualifi ed chimney cleaner.
Creosote will ignite if highly heated. A dirty
chimney fl ue may create and distribute
soot within the house. Inspect chimney
fl ue for damage. If damaged, repair fl ue
and fi rebox before operating heater.
6. Do not burn solid-fuel in a fi replace in
which a vent-free room heater is installed.
7. If fi replace has glass doors, never operate
this heater with glass doors closed. Any
glass doors shall be fully opened when the
appliance is in operation. If you operate
heater with doors closed, heat buildup
inside fi replace will cause glass to burst.
Make sure there are no obstructions
across openings of fi replace.
8. To prevent the creation of soot, follow the
instructions in Cleaning and Maintenance,
page 29.
9. Before using furniture polish, wax, carpet
cleaner or similar products, turn heater off. If
heated, the vapors from these products may
create a white powder residue within burner
box or on adjacent walls and furniture.
10. This heater needs fresh, outside air ventilation to run properly. This heater has an
Oxygen Depletion Sensing (ODS) safety
shutoff system. The ODS shuts down the
heater if enough fresh air is not available.
See Air for Combustion and Ventilation,
page 6. If heater keeps shutting off, see
Troubleshooting, page 32.
11. Do not run heater
• where fl ammable liquids or vapors are
used or stored
• under dusty conditions
12. Do not use this heater to cook food or burn
paper or other objects.
13. Do not use heater if any part has been exposed to or under water. Immediately call
a qualifi ed service technician to inspect
the room heater and to replace any part
of the control system and any gas control
which has been under water.
14. Do not operate heater if any log is broken.
Do not operate heater if a log is chipped
(dime-sized or larger).
15. Turn heater off and let cool before servicing, installing or repairing. Only a qualifi ed
service person should install, service or
repair heater.
16. Make sure the remote is set to the OFF
position when you are away from home
for long periods of time.
17. Remote heaters must not be connected
to any external electrical source.
18. Operating heater above elevations of
4,500 feet may cause pilot outage.
19. To prevent performance problems, do
not use propane/LP fuel tank of less than
100 lb. capacity (propane/LP units only).
20. Provide adequate clearances around air
openings.
Young children should be carefully supervised when they are in the same
room as the appliance. Toddlers, young children and others may be
susceptible to accidental burns.A physical barrier is recommended if there
are at-risk individuals in the house. To restrict access to a fi replace or
stove, install an adjustable safety gate to keep toddlers, young children and
other at-risk individuals out of the room and away from hot surfaces.
SuperiorFireplaces.us.com
900462-01 NC4
Left
Side
Chassis
PRODUCT IDENTIFICATION
Glowing
Embers
Front
Figure 1 - Product Identifi cation
LOCAL CODES
Install and use heater with care. Follow all
local codes. In the absence of local codes,
use the latest edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
State of Massachusetts: The installa-
tion must be made by a licensed plumber
or gas fitter in the Commonwealth of
Massachusetts.
Sellers of unvented propane or natural
gas-fi red supplemental room heaters shall
provide to each purchaser a copy of 527
CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for
bedroom and bathroom installation in the
Commonwealth of Massachusetts.
Right
Side
UNPACKING
CAUTION: Do not remove the
data plates from the grate assembly . The data plates contain
important warranty and safety
information.
1. Remove logs and heater base assembly
from carton(s).
Note: Do not pick up heater base assem-
bly by burners. This could damage heater.
Always handle base assembly by grate.
2. Remove all protective packaging applied
to logs and heater for shipment.
3. Check heater for any shipping damage.
If the heater is damaged go to
Fireplaces.us.com or contact your dealer
for information.
Superior-
900462-01 NC5
SuperiorFireplaces.us.com
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no
outside venting. There is no heat loss out a
vent or up a chimney. Heat is generated by
both realistic fl ames and glowing coals. This
heater is designed for vent-free operation
with fl ue damper closed. It has been tested
and approved to ANSI Z21.11.2 standard for
unvented heaters.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall
not be installed in a room or space
unless the required volume of
indoor combustion air is provided
by the method described in the
National Fuel Gas Code, ANSI
Z223.1/NFP A 54, the International
Fuel Gas Code, or applicable
local codes. Read the following
instructions to insure proper fresh
air for this and other fuel-burning
appliances in your home.
Today’s homes are built more energy effi cient
than ever. New materials, increased insulation
and new construction methods help reduce
heat loss in homes. Home owners weather
strip and caulk around windows and doors to
keep the cold air out and the warm air in. During heating months, home owners want their
homes as airtight as possible.
While it is good to make your home energy
effi cient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning appliances need fresh air for proper combustion
and ventilation.
Exhaust fans, fi replaces, clothes dryers and
fuel burning appliances draw air from the house
to operate. You must provide adequate fresh
air for these appliances. This will insure proper
venting of vented fuel-burning appliances.
PROVIDING ADEQUA TE
VENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation.
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS/pilot is a required feature for vent-free
room heaters. The ODS/pilot shuts off the
heater if there is not enough fresh air.
ELECTRONIC IGNITION SYSTEM
This heater has an electronic ignitor to light
heater fuel supply.
All spaces in homes fall into one of the three
following ventilation classifi cations:
1. Unusually Tight Construction
2. Unconfi ned Space
3. Confi ned Space
The information on pages 6 through 8 will help
you classify your space and provide adequate
ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of unusually tight construction, you must provide
additional fresh air.
Unusually tight construction is defi ned as
construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6 x 10
less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window
and door frames, between sole plates
and fl oors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical and gas lines
and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh air.
See Ventilation Air From Outdoors, page 8.
If your home does not meet all of the three
criteria above, proceed to Determining Fresh-Air Flow For Heater Location, page 7.
-11
kg per pa-sec-m2) or
SuperiorFireplaces.us.com
900462-01 NC6
AIR FOR COMBUSTION AND VENTILATION
Continued
Confi ned and Unconfi ned Space
The National Fuel Gas Code, ANSI Z223.1/
NFP A 54 defi nes a confi ned space as a space
whose volume is less than 50 cubic feet per
3
1,000 Btu/hr (4.8 m
per kw) of the aggregate
input rating of all appliances installed in that
space and an unconfi ned space as a space
whose volume is not less than 50 cubic feet
3
per 1,000 Btu/hr (4.8 m
per kw) of the aggregate input rating of all appliances installed
in that space. Rooms communicating directly
with the space in which the appliances are
installed*, through openings not furnished
with doors, are considered a part of the unconfi ned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Determining if You Have a Confi ned or
Unconfi ned Space
Use this work sheet to determine if you have
a confi ned or unconfi ned space.
Space: Includes the room in which you will install
fi replace plus any adjoining rooms with doorless passageways or ventilation grills between
the rooms.
1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20
= 51,200 (maximum Btu/Hr the space can
support)
3. Add the Btu/Hr of all fuel burning appliances
in the space.
Vent-free fi replace __________ Btu/HrGas water heater* __________ Btu/Hr
Gas furnace __________ Btu/Hr
Vented gas heater __________ Btu/Hr
Gas fi replace logs __________ Btu/HrOther gas appliances* + _________ Btu/Hr
Total = _________ Btu/Hr
* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
Example:
Gas water heater __________ Btu/Hr
Vent-free fi replace + _________ Btu/Hr
Total = _________ Btu/Hr
4. Compare the maximum Btu/Hr the space
can support with the actual amount of Btu/
Hr used.
______Btu/Hr (maximum the space can
support)
______Btu/Hr (actual amount used)
Example: 51,200 Btu/Hr (maximum the
space can support)
73,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the above example is a confi ned
space because the actual Btu/Hr used is more
than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your
options are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides
an unconfi ned space, remove door to adjoin-
ing room or add ventilation grills between
rooms. See Ventilation Air From Inside Building, page 8.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 8.
C. Install a lower Btu/Hr fi replace, if lower Btu/
Hr size makes room unconfi ned.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is
an unconfi ned space. You will need no additional
fresh air ventilation.
40,000
33,000
73,000
WARNING: If the area in which
the heater may be operated does
not meet the required volume for
indoor combustion air, combustion and ventilation air shall be
provided by one of the methods
described in the National Fuel
Gas Code, ANSI Z223.1/NFPA
54, the International Fuel Gas
Code, or applicable local codes.
900462-01 NC7
SuperiorFireplaces.us.com
AIR FOR COMBUSTION AND VENTILATION
A
Continued
VENTILA TION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconfi ned space. When ventilating to an
adjoining unconfi ned space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the fl oor on the
wall connecting the two spaces (see options
1 and 2, Figure 2). You can also remove door
into adjoining room (see option 3, Figure 2).
Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and
Ventilation for required size of ventilation
grills or ducts.
12"
Ventilation
Grills Into
Adjoining
Room,
Option 1
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
12"
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two permanent openings: one within 12" of the ceiling
and one within 12" of the fl oor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings
for inlet or outlet air into attic if attic has a
thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.
Ventilated
Attic
Ventilated
Crawl Space
To Attic
To
Crawl
Space
Outlet
ir
Inlet
Air
Outlet
Air
Inlet Air
Figure 3 - Ventilation Air from Outdoors
Figure 2 - Ventilation Air from Inside Building
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your primary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
WARNING: A qualifi ed ser-
vice person must install heater .
Follow all local codes.
WARNING: Any outside air
ducts and/or ash dumps in the
fi replace shall be permanently
closed at time of appliance installation.
WARNING: Seal any fresh
air vents or ash clean-out doors
located on fl oor or wall of fi re-
place. If not, drafting may cause
pilot outage or sooting. Use a
heat-resistant sealant. Do not
seal chimney fl ue damper.
SuperiorFireplaces.us.com
900462-01 NC8
INSTALLATION
Continued
W ARNING: Before installing
CHECK GAS TYPE
Use the correct type of gas (natural or propane/
LP). If your gas supply is not the correct gas
type, do not install heater. Call dealer where
you bought heater for proper type heater.
in a solid fuel burning fi replace,
the chimney fl ue and fi rebox
must be cleaned of soot, creosote, ashes and loose paint by
a qualified chimney cleaner.
Creosote will ignite if highly
heated. A dirty chimney fl ue may
WARNING: This appliance is
equipped for either natural gas
or propane/LP gas but not both.
Gas type is indicated on the rating plate. Field conversion is not
permitted.
create and distribute soot within
the house. Inspect chimney and
fi rebox fl ue for damage. If dam-
INST ALLATION AND CLEARANCES
FOR VENT-FREE OPERATION
aged, repair fl ue and fi rebox
before operating heater.
WARNING: Maintain the
minimum clearances. If you can,
W ARNING: Never install the
heater
• in a bedroom or bathroom
• in a recreational vehicle
•
where curtains, furniture, clothing or other fl ammable objects
provide greater clearances from
fl oor, ceiling and adjoining wall.
MINIMUM FIREPLACE CLEARANCE TO
COMBUSTIBLE MATERIALS
Side Wall 16", Ceiling 42"
Floor 5", Front: 36"
are less than 36" from front, 42"
from top of heater; for side clearances see Figure 4, page 10
• in high traffi c areas
• in windy or drafty areas
CAUTION: This heater creates
warm air currents. These currents
move heat to wall surfaces next
to heater. Installing heater next
to vinyl or cloth wall coverings or
operating heater where impurities
(such as, but not limited to, tobacco smoke, aromatic candles,
cleaning fl uids, oil or kerosene
lamps, etc.) in the air exist, may
discolor walls or cause odors.
IMPORTANT: Vent-free heaters add moisture
to the air. Although this is benefi cial, installing
heater in rooms without enough ventilation
air may cause mildew to form from too much
moisture. See Air for Combustion and Ventila-tion, page 6.
900462-01 NC9
SuperiorFireplaces.us.com
LOG SIZING REQUIREMENTS
Log
Size
LMF24-
GTA/B
LMF30-
GTA/B
LMF36-
GTA/B
* Also approved for use in VEGA42 and V ALIANT42
SERIES fi replaces.
Carefully follow the instructions below. This
will ensure safe installation into a masonry,
UL127-listed manufactured fi replace or listed
vent-free fi rebox.
Minimum Clearances For Side Combustible
Material, Side Wall and Ceiling
A. Clearances from the side of the fi replace
cabinet to any combustible material and
wall should follow diagram in Figure 4,
page 10.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material
and protrudes 3
combustible material must be 4" from the
side of the fi replace cabinet (see Figure
4, page 10).
Minimum Firebox Size
Height Depth
29"15.5"32.5"22.75"
29"15.5"39"26.75"
29''20''47''33''
1
Front
Width
/2" from the wall. This
Width
Rear*
INSTALLATION
Continued
Note: When installing your gas logs into
a manufactured fi rebox, follow fi rebox
manufacturer’s instructions for minimum
clearances to combustible materials.
B. Clearances from the top of the fi replace
opening to the ceiling should not be less
than 42".
Example
*
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note: If using a mantel proceed to If Using
Mantel. If not using a mantel, follow these
instructions.
You must have noncombustible material(s)
above the fi replace opening. Noncombustible
materials (such as slate, marble, tile, etc.) must
be at least 1/2" thick. With sheet metal, you
must have noncombustible material behind
it. Noncombustible material must extend at
least 8" up (for all models). If noncombustible
material is less than 12", you must install the
fi replace hood accessory (24" and 30" Models
Only). See Figure 5 for minimum clearances.
Noncombustible
Material Distance
Requirements for
Safe Installation
(A)
1
2" or moreNoncombustible mate-
rial OK.
Between 8" and 12"
Install fi replace hood
accessory (GA6050 or
GA6053 see Accesso-ries, page 39).
Less than 8"
Noncombustible material must be extended
to at least 8". See
Between 8" and 12",
above. If you cannot
extend material, you
must operate heater
with fl ue damper open.
Heat Resistant
Material
(A)
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
If Using Mantel
You must have noncombustible material(s)
above the fi replace opening. Noncombustible
materials (such as slate, marble, tile, etc.)
must be at least 1/2" thick. With sheet metal,
you must have noncombustible material behind it. Noncombustible material must extend
at least 8" up (for all models). If noncombustible material is less than 12", you must
install the fi replace hood accessory. Even if
noncombustible material is more than 12",
you may need the hood accessory to defl ect
heat away from your mantel shelf. See Figure
5 and Figures 6 and 7, page 11, for minimum
clearances.
SuperiorFireplaces.us.com
900462-01 NC10
INSTALLATION
Continued
MANTEL CLEARANCES
In addition to meeting noncombustible material clearances, you must also meet required
clearances between fi replace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between
mantel shelf and top of fi replace opening, a
hood is not required (see Figure 6).
Mantel Shelf
/2
"
(A)
12"
18" 20"22"24"
Distances to
Underside of
Mantel
Underside of
Mantel Shelf
All minimum
distances are
in inches
Top of Fireplace
Opening
Minimum NonCombustible
Material
10"
8"
6"
1
2
Minimum NonCombustible
Material Height
NOTICE: Surface temperatures
of adjacent walls and mantels become hot during operation. Walls
and mantels above the fi rebox
may become hot to the touch.
If installed properly, these temperatures meet the requirement
of the national product standard.
Follow all minimum clearances
shown in this manual.
NOTICE: If your installation does
not meet the minimum clearances shown, you must do one
of the following:
• operate the logs only with the
fl ue damper open
• raise the mantel to an acceptable height
• remove the mantel
Figure 6 - Minimum Mantel Clearances
Without Using Hood
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6, are not
met, you must have a hood. When using a
hood there are still certain minimum mantel
clearances required. Follow minimum clearances shown in Figure 7, when using hood.
"
8"
Min.
Mantel Shelf
12" 15" 18" 20"
Distances to
Underside of
Mantel
Underside
of Mantel
Shelf
Top of
Fireplace
Opening
Minimum
Noncombustible
Material
12"
10"
8"
6"
1
/2
2
Hood (GA6050
or GA6053)
FLOOR CLEARANCES
A. If installing appliance on the fl oor level,
you must maintain the minimum distance
of 14" to combustibles (see Figure 8).
B. If combustible materials are less than
14" to the fi replace, you must install ap-
pliance at least 5" above the top surface
of combustible fl ooring including tile and
carpet (see Figure 9).
Combustible
14"
Min.
Noncombustible Material
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Material
Hearth
Figure 7 - Minimum Mantel Clearances
When Using Hood
5"
Min.
Combustible
Material
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
900462-01 NC11
SuperiorFireplaces.us.com
INSTALLATION
Continued
INSTALLING HEATER BASE
ASSEMBLY
W ARNING: Y ou must secure
this heater to fi replace fl oor. If
not, heater will move when you
adjust controls. Moving heater
may cause a gas leak.
WARNING: If installing in a
sunken fi replace, special care
is needed. You must raise the
fi replace fl oor to allow access to
heater control panel. This will insure adequate air fl ow and guard
against sooting and controls
being damaged. Raise fi replace fl oor with noncombustible material. Make sure material is secure.
3. Mark screw locations through holes in
front panel of base (see Figure 11). If
installing in a brick-bottom fi replace, mark
screw locations in mortar joint of bricks.
4. Remove heater base from fi replace.
5. Drill holes at marked locations using 3/16"
drill bit.
6. Attach base, through holes in back side panels of base, to fi replace fl oor using masonry
screws provided in hardware package (see
Figure 11).
7. Connect to gas supply. See Connecting To Gas Supply, page 13.
Heater Gas
Regulator
Flexible Gas Hose (Provided
with Models, Install if
allowed by local codes)
CAUTION: Do not pick up
heater base assembly by burners. This could damage heater.
Only handle base assembly by
grates.
IMPORTANT: Make sure the heater burners
are level.
Installation Items Needed
• hardware package (provided with heater)
• approved fl exible gas hose and fi ttings
provided (if allowed by local codes)
• sealant (resistant to propane/LP gas, not
provided)
• electric drill with 3/16” masonry drill bit
Note: Install optional MRC Series receiver
and hand-held remote control kit (see Accessories, page 39) before installing gas log
heater. See installation instructions included
with the kit.
1. Apply pipe joint sealant lightly to male
threads of the 3/8 NPT side of gas fi tting
elbow (provided) and connect to inlet
side of gas control. Remove gas fi tting
from fl exible gas hose (provided) before
connecting to elbow (see Figure 10).
2. Position heater base assembly in fi re-
place.
SuperiorFireplaces.us.com
Figure 10 - Attaching Flexible Gas Hose
to Heater Gas Regulator
Masonry Screw
Figure 11 - Attaching Base to Fireplace
Floor
900462-01 NC12
INSTALLATION
Continued
CONNECTING TO GAS SUPPLY
WARNING: This appliance
with the vent pointing down as shown in Figure
12, page 14. Pointing the vent down protects
it from freezing rain or sleet.
requires a 3/8" NPT (National
Pipe Thread) inlet connection to
the pressure regulator.
CAUTION: Use only new,
black iron or steel pipe. Internally-tinned copper tubing
WARNING: A qualifi ed service
person must connect heater to
gas supply. Follow all local codes.
may be used in certain areas.
Check your local codes. Use
pipe of 1/2" diameter or greater
to allow proper gas volume to
CAUTION: Never connect
propane/LP fi replace directly
to the propane/LP supply. This
heater requires an external regulator (not supplied). Install the
external regulator between the
heater and propane/LP supply.
WARNING: Never connect
natural gas fi replace to private
(non-utility) gas wells. This
gas is commonly known as
wellhead gas.
Installation Items Needed
Before installing heater, make sure you have
the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved fl exible gas line with gas connec-
tor (if allowed by local codes) (not provided)
* An equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge
connection. Purchase the optional equipment
shutoff valve from your dealer.
For propane/LP units, the installer must
supply an external regulator. The external
regulator will reduce incoming gas pressure.
You must reduce incoming gas pressure to
between 11" and 14" of water. If you do not reduce incoming gas pressure, heater regulator
damage could occur. Install external regulator
900462-01 NC13
SuperiorFireplaces.us.com
heater. If pipe is too small, undue
loss of volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up.
NPT tap must be upstream from heater (see
Figure 13, page 14).
IMPORTANT: Install equipment shutoff valve
in an accessible location. The equipment
shutoff valve is for turning on or shutting off
the gas to the appliance.
Check your building codes for any special
requirements for locating equipment shutoff
valve to fi replaces.
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could
result in clogged heater valves.
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
Propane/LP
Supply Tank
Figure 12 - External Regulator With Vent
Pointing Down
External
Regulator
with Vent
Pointing
Down
INSTALLATION
Continued
PROPANE/LP From
External Regulator
(11" W.C.** to 14" W.C.
Pressure)
NATURAL From Gas
Meter (5" W.C.**
to 10.5" W.C.
Pressure)
3" Minimum
Tee Cap Pipe
Joint Nipple
Sediment Trap
Figure 13 - Gas Connection
* Purchase the optional equipment shutoff
valve from your dealer.
**Minimum inlet pressure for purpose of input
adjustment.
We recommend that you install a sediment
trap in supply line as shown in Figure 13.
Locate sediment trap where it is within reach
for cleaning. Install in piping system between
fuel supply and heater. Locate sediment trap
where trapped matter is not likely to freeze.
A sediment trap traps moisture and contaminants. This keeps them from going into heater
controls. If sediment trap is not installed or is
installed wrong, heater may not run properly.
CAUTION: A void damage to
gas control. Hold gas control
with wrench when connecting
it to gas piping and/or fi ttings.
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
Equipment Shutoff
Valve With 1/8"
NPT Tap*
Approved
Flexible Gas
Hose (if allowed
by local codes)
Gas
Regulator
WARNING: Never use an open
fl ame to check for a leak. Apply a
noncorrosive leak detection fl uid
to all joints. Bubbles forming show
a leak. Correct all leaks at once.
CAUTION: Make sure external regulator has been installed
between propane/LP supply and
heater. See guidelines under Con-necting to Gas Supply, page 13.
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance
main gas valve (control valve) and equipment shutoff valve from gas supply piping
system. Pressures in excess of 1/2 psig
(3.5 kPa) will damage heater regulator.
2. Cap off open end of gas pipe where equipment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
4. Check all joints of gas supply piping system.
Apply noncorrosive leak detection fl uid to
all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff
valve to gas supply. Check reconnected
fi ttings for leaks.
Test Pressures Equal To or Less Than 1/2
PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 15).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
3. Check all joints from gas meter to equipment shutoff valve for natural gas or propane/LP supply to equipment shutoff valve
for propane/LP (see Figure 15 or Figure
16). Apply noncorrosive leak detection fl uid
to all joints. Bubbles forming show a leak.
4. Correct all leaks at once.
SuperiorFireplaces.us.com
900462-01 NC14
INSTALLATION
Continued
PRESSURE TESTING HEATER GAS
CONNECTIONS
Open equipment shutoff valve (see Figure 14).
1.
2. Open main gas valve located on or near
gas meter for natural gas or open propane/LP supply tank valve.
3. Make sure control knob of heater is in the
OFF position.
4. Check all joints from gas meter to equipment shutoff valve for natural gas or propane/LP supply to equipment shutoff valve
for propane/LP (see Figure 15, or Figure
16). Apply noncorrosive leak detection fl uid
to all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light heater (see Operation, page 22).
Check all other internal joints for leaks.
Turn off heater (see To Turn Off Gas to
7.
Appliance, page 22 for Remote models.
Equipment
Shutoff
Valve
Open
Closed
Propane/LP
Supply Tank
Figure 15 - Checking Gas Joints
(Propane/LP Only)
Equipment
Shutoff Valve
Gas Meter
Figure 16 - Checking Gas Joints (Natural
Equipment Shutoff Valve
Control Valve
Location
Control Valve
Location
Gas Only)
Figure 14 - Equipment Shutoff Valve
900462-01 NC15
SuperiorFireplaces.us.com
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.