Superior MHW36R, MHW36CB Installation And Operation Instructions Manual

Installation and Operation Instructions
PFS
Superior® Clean-Face Round Back Fireplace with Bi-Fold Doors and Combustion Air Kit
®
P127312-01
USC
Models
MHW36R
SAVE THIS BOOK
This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain replacement parts or accessory items when needed. Keep it with your other important papers.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
Installateur : Laissez cette notice avec l’appareil. Consommateur : Conservez cette notice pour consultation ultérieure.
This wood burning fireplace complies with UL127 CAN/ULC-S610-M87 standard as a FACTORY BUILT FIREPLACE.
This fireplace is approved for use as a wood burning fireplace or for use with a vented gas log approved to ANSI Z21.60 or Z21.84 standards or for use with a vent-free gas log heater approved to ANSI Z21.11.2 standard
An IHP hood must be installed when using a vent-free log heater (see Accessories, page 19). FOR CANADA: The authority having jurisdiction
(such as the municipal building department, fire department, etc.) should be contacted before installation to determine the need to obtain a permit.
This installation manual will enable you to obtain a safe, efficient and dependable installation of your fireplace system. Please read and understand these instructions before beginning your installation.
Do not alter or modify the fireplace or its components under any circumstances. Any modification or alteration of the fireplace system, including but not limited to the fireplace, chimney components and accessories, may void the warranty, listings and approvals of this system and could result in an unsafe and potentially dangerous installation.
IMPORTANT! TO ASSURE PROPER ALIGNMENT OF GLASS DOORS: INSTALL THIS FIREPLACE IN A SQUARE AND PLUMB CONDITION, USING SHIMS AS NECESSARY AT SIDES AND/OR BOTTOM.
Ce foyer au bois est conforme aux UL 127 CAN/ULC­S610-M87 norme comme une USINE CONSTRUITE CHEMINÉE.
.
POUR LE CANADA: L’autorité compétente (comme le service municipal du bâtiment, les pompiers, etc.) doit être contacté avant l’installation afin de déterminer la nécessité d’obtenir un permis.
TABLE OF CONTENTS
Safety ................................................................................................... 2
Fireplace Installation ............................................................................ 2
Venting Installation .............................................................................. 6
Optional Gas Line Installation ............................................................ 13
Finishing Fireplace ............................................................................. 15
Operation and Maintenance Guidelines .............................................. 15
Technical Service ...............................................................................17
Replacement Parts ............................................................................. 17
Accessories ........................................................................................ 18
Important Notices .............................................................................. 21
Warranty ............................................................................................ 23
CAUTION
Thestructural integrityof the mobilehome oor
and ceiling/roof must be maintained.
WARNING
Do not install a fireplace insert in this box unless the manufacturer's instructions with the insert specifically state this fireplace has been tested for use with the insert.
FOR YOUR SAFETY
SAFETY
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause injury, property damage or loss of life. Refer to this manual for assistance or additional information. Consult a qualified installer or local distributor.
IMPORTANT: Check HUD requirements before installing this fireplace.
These units are intended for installation in manufactured (mobile) homes. These units may also be installed in buildings of conventional construction including modular housing, providing all instructions provided herein are strictly adhered to. These fireplaces include a combustion air kit and bi-fold doors.
Before beginning the installation of the fireplace, read these instructions through completely.
• ThisIHPreplaceanditscomponentsaresafewheninstalledaccord-
ingtothisinstallationmanual.UnlessyouuseINNOVATIVEHEARTH PRODUCTS(IHP)approvedcomponents,whichhavebeendesigned
and tested for the fireplace system, you may cause a fire hazard.
• TheIHPwarrantywillbevoidedbyandIHPdisclaimsanyresponsibil­ity for the following actions. a. Modification of the fireplace, components, doors, air inlet system and
damper control.
b. UseofanycomponentpartnotmanufacturedorapprovedbyIHP
incombinationwithanIHPreplacesystem.
• Donotstoreorusegasolineoranyotherammablevapors
or liquids in the vicinity of this or any other appliance.
• Duetohightemperatures,theapplianceshouldbelocated
out of traffic and away from furniture and draperies.
• Donotplaceclothingorotherammablematerialsonor
near the appliance.
• Neverleavechildrenunattendedwhenareisburningin
the fireplace.
This fireplace is not intended to be used as a substitute for a furnace to heat an entire home. Use for supplemental heat only.
This wood burning fireplace complies with the UL 127 standard as a FACTORY BUILT FIREPLACE and is listed and tested by the PFS Corporation.
FIREPLACE INSTALLATION
SELECTING LOCATION
To determine the safest and most efficient location for the fireplace, you must take into consideration the following guidelines:
1. The location must allow for proper clearances (see Figures 2 and 3, page 4).
2. Consider a location where the heat output will not be affected by drafts, air conditioning ducts, windows or doors.
3. A location that avoids the cutting of joists or roof rafters will make installation easier.
4. An outside air kit is included with this fireplace (see Outside Air Kit on
page 6)
WARNING
Proper installation is the most important step in ensuring safe and con­tinuous operation of the fireplace. Consult the local building codes as to the particular requirements concerned with the installation of all factory built fireplaces.
SuperiorFireplaces.US.com 127312-01D2
Do not install this appliance in a bedroom.
SPECIFICATIONS
Round Top Termination
Storm Collar
Flashing
42"
1
/4"
36
J-Box Access
RH SIDE VIEW
3
7
/4"
36"
1"
41"
Gas Line Conduit Sleeve (Both Sides)
22
3
6
3"
0" To Top
1/2" Air Space
Back and Sides
0" To Bottom
1
/8"
/4"
Spacer
Firestop Thimble
221/16"
13"
Firestop
5/8"
1" Airspace
To Combustible
Materials
Combustible Wall Board
No Combustible Material On Face
Not Less Than 14" To Perpendicular Sidewall
3
9
LH SIDE VIEW
Figure 1 - Specifications
127312-01D
/8"
Rear View of Fireplace
91/2"
8" Each Side
14"
14"
SuperiorFireplaces.US.com
Hearth Extension 52" x 16"
Opening for Outside Air
3
FIREPLACE INSTALLATION
Effective Height of Termination Cap
RT-8DM
30E-8DM
40' Max.
Height
20' for
Manufactured
Home
Application
Continued
WARNING
42 1/4"
3
41
/4"
Figure 2 - Framing Dimensions
Maintain 1/2" Air Space between surface of
Maintain 1/2" Air Space
framing, insulation, and
Between Framing
drywall.
and Fireplace
13" Min.
43
22
Min.
5
/8"
10"
Do not pack required air spaces with insulation or other materials.
MINIMUM/MAXIMUM CHIMNEY HEIGHT
Minimum height of the chimney, measured from base of fireplace to flue gas outlet of termination, is 14 feet* for straight flue or a flue with one elbow set. Maximum distance between elbows is 2 feet.
Maximum height of any system is 40 feet.* This measurement includes fireplace, chimney sections and height of termination assembly at level of flue gas outlet (see Figure 5).
Effective Height of Termination Cap
5
/8"
14' Min.
Height
11' for
Manufactured
Home
Application
RT-8DM
Effective Height of Termination Cap
14' Min.
Height
11' for
Manufactured
Home
Application
RT-8DM
41 3/4" Min.
61
11/16" Min.
Figure 3 - Corner Installation
MINIMUM CLEARANCE TO COMBUSTIBLES
Back and sides of fireplace 1/2" minimum* Floor under fireplace** 0" minimum Wall to front of fireplace 36" minimum Perpendicular wall to opening 14" minimum Top spacers 0" minimum Mantel clearances see Mantels, page 15 Chimney outer pipe surfaces 1" minimum
* Not required at nailing flanges ** See step 2 of Framing, page 5
2' Max
Pipe Length
Figure 4
*For manufactured home application, minimum height is 11' for straight flue or flue with one elbow set. Maximum height of any system is 20'.
SuperiorFireplaces.US.com 127312-01D4
FIREPLACE INSTALLATION
Continued
Standard
Installation
RT-8DM
Alternate
Installation
Effective Height of Termination Cap
40' Max.
Height
20' for
Manufactured
Home
Application
FRAMING
1. Frame opening for fireplace using dimensions shown in Figures 2 and 3.
2. The fireplace may not be installed on carpeting, tile or any combustible material other than wood flooring, fireplace must be installed on a metal or wood panel extending full width and depth of fireplace. (It is acceptable to cover two outside ends or columns of top louver panel leaving four center columns open).
3. Set fireplace directly in front of this opening and slide unit back until nailing flanges touch side framing.
4. Check level of fireplace and shim with sheet metal if necessary.
5. Before securing fireplace to prepared framing, metal ember protector (provided) must be placed between hearth extension (not supplied) and under bottom front edge of fireplace to protect against glowing embers falling through. If fireplace is to be installed on a raised plat­form, a Z-type ember protector (not supplied) must be fabricated to fit your required platform height. Ember protector should extend under fireplace a minimum of 1-1/2". The ember protector should be made of metal material.
6. Using screws or nails, secure fireplace to framing through flanges located on sides of fireplace (see Figure 6).
Alternate
30E-8DM
Installation
Figure 5 - Standard and Alternate Venting Installation
Nailing Flange
Screw or Nail
Figure 6 - Nailing Flanges
127312-01D
SuperiorFireplaces.US.com
5
FIREPLACE INSTALLATION
Continued
HEARTH EXTENSION
A hearth extension projecting a minimum of 16" in front of and a minimum of 8" beyond each side of the fireplace opening is required to protect combustible floor construction in front of the fireplace. Use an equal mate­rial which meets the following specifications: a layer of noncombustible, inorganic material having a thermal conductivity of k = .84 BTU IN/FT2
HR°F(orless)at1"thick.Forexample,ifthematerialselectedhasak
factor of 0.25, such as glass fiber, the following formula would apply:
0.25 x 1.0" = 0.30" thickness required
0.84
Thermal conductivity "k" of materials can be obtained from the manufac­turer or supplier of the noncombustible material. If the hearth extension is to be covered, use noncombustible material such as tile, slate, brick, concrete, metal, glass, marble, stone, etc. Provide a means to prevent hearth extension from shifting and seal gap between fireplace frame and hearth extension with a noncombustible material (see Figure 7).
Fireplace Front
Ember Protector
Fireplace Front Elevated
Seal Gap
Seal Gap
Ember Protector
Hearth Extension
WARNING
Hearth extension is to be installed only as shown in Figure 7.
VENTING INSTALLATION
OUTSIDE AIR KIT
Installation of an outside air kit should be completed during the rough framing of fireplace due to nature of its location. The supplied flex duct measures approximately 10" compressed and up to approximately 36" extended. Outside combustion air is accessed through mobile home floor using air kit model AK6E, included with the fireplace, or a side wall using optional air kit model AK6-WE (see Accessories on page 19).
Insert Inner Tab of Inlet Tube into Slot on Outer Surround
Insulation
Figure 7 - Hearth Extension
Installer may choose either left or right side mounting to allow for proper wall/rafter clearances.
For AK6-WE Only: Construct a 4-1/2" x 4-1/2" framing or opening on exterior wall (see Figure 8, page 6).
For AK6E Only: The outside air vent is installed through a ventilated crawl space (see Figure 9, page 7).
Air Vent Location Must Allow for Bushes, Snow and Other Possible Obstructions
Left Side Mounting Shown
Secure to Collar with Metal Tape, Screws or Tie Straps
Figure 8 - Outside Air Kit AK6-WE Installation
Outside Air Vent Termination
SuperiorFireplaces.US.com 127312-01D6
VENTING INSTALLATION
Continued
1. Locate and remove air inlet cover plate on fireplace‘s outer surround. Save screws.
2. Cut out any visible insulation that may obstruct airflow.
3. Extend flex duct to attach air inlet tube.
4. Insert inner tab of inlet tube into mating slot next to opening.
5. Place outer tab of inlet tube over mating hole next to opening and secure with screws removed from cover plate in step 1.
6. Install outside air vent termination in a location that will not be obstructed by bushes, snow, etc. Locate vent near the fireplace to make flex duct installation easier.
Insert Inner Tab of Inlet Tube into Slot on Outer Surround
Left Side Mounting Shown
Insulation
CHIMNEY PIPE
WARNING
Label part number 900599-01 must be applied by the installer to all chimney pipe sections but is not required on sections that will be visible after the installation is complete. Label must wrap around the circumference of the pipe. See accessories, page 19 for Kit F2659.
The chimney system approved for this fireplace consists of 12", 18", 24", 36" and 48" snap-lock, double-wall pipe segments, planned for maximum adaptability to individual site requirements. Actual lengths gained after fitting overlaps must be taken into consideration (lineal gain) and are given in the lineal gain chart (see Figure 10). Lineal Gain is the actual measurable length of a part after two or more parts are connected.
12-3/8" Galvanized Outer Pipe
Secure to Collar with Metal Tape, Screws or Tie Straps
Flex Duct Extends Up to 36"
Figure 9 - Outside Air Kit AK6E Installation
Floor
Hemmed End 8" Stainless Inner Pipe
LINEAL GAIN
PART NO. DESCRIPTION GAIN
MHW36R Fireplace 42
12-8DM Pipe Section 10-5/8 18-8DM Pipe Section 16-5/8 24-8DM Pipe Section 23-5/8 36-8DM Pipe Section 34-5/8 48-8DM Pipe Section 46-5/8
RTL-8DM Round Termination 7-3/4
* The lineal gain for the terminations is measured to the flue gas outlet height.
Figure 10 - Lineal Gain
"
" " " " "
*
"
127312-01D
SuperiorFireplaces.US.com
7
VENTING INSTALLATION
Continued
There are three vent kits available which have been specially designed for common installations in manufactured (mobile) homes: MW8K (8'
ventkit),MW9K(9'ventkit)andMW8K-HT(8'HTventkit).Contentsof
these kits are listed under Accessories on page 20. IMPORTANT: If height of chimney assembly exceeds requirements for transportation of home, chimney installation may be completed after home is sited.
NOTE: Termination must always be installed after the home is sited.
ASSEMBLY AND INSTALLATION OF DOUBLE WALL CHIMNEY SYSTEM
Each double wall chimney section consists of a galvanized outer pipe, a stainless steel inner flue pipe and a wire spacer. Pipe sections must be as­sembled independently as chimney is installed. When connecting chimney directly to fireplace, inner flue pipe section must be installed first with lanced side up. Outer pipe section can then be installed over flue pipe section with hemmed end up. Press down on each pipe section until lances securely engage hem on fireplace starter. The wire spacer will assure proper spacing between inner and outer pipe sections.
WARNING
The opening in the collar around the chimney at the top of the fireplace must not be obstructed. Never use blown insulation to fill the chimney enclosure.
Flange End of Tube
Open End of Tube
Thimble Base
Figure 11 - Attaching Adjustable Thimble
Placement Holes
Continue to assemble chimney sections as outlined above, making sure that both inner and outer pipe sections are locked together. When install­ing double wall snap-lock chimney together, it is important to assure that the joint between chimney sections is locked. Check by pulling chimney upward after locking. Chimney will not come apart if properly locked. It is not necessary to add screws to keep chimney together (exception, see
Figure 16, page 11).
ADJUSTABLE FIRESTOP THIMBLE
This adjustable thimble adjusts to the most commonly used ceiling pitches automatically. Refer to the following procedure for installing the adjustable thimble:
The adjustable thimble may be installed around the chimney components at assembly or the chimney components may be inserted though the installed thimble.
Install the thimble from below a finished roof and ceiling assembly. Push the thimble assembly (tube section first) up into an already prepared open­ing and secure open end of the thimble base to the finished underside of the roof and ceiling assembly (Figure 11).
Note: The two screws on which the thimble base pivots may be removed and reinstalled into any of the series of placement holes provided for the adjustment of the adjustable thimble's point of rotation (Figure 11A). Adjust the pivot screens to locate the open end of the tube section as required for the roof line. Additional screws may be placed at the high and low points of the thimble base in the tabs provided.
Place the thimble base against the finished roof and ceiling assembly and secure it to the framing with screws or nails. The thimble is self-adjusting around inserted chimney components. Thimble extensions are available and may be installed into the adjustable thimble's tube section as needed to extend the thimble through the roof-line. Secure the thimble extension to the tube section with screws no more than 1/2" in length.
Pivot Screw
Figure 11A - Attaching Adjustable Thimble
Position appropriate thimble/firestop spacer combination at ceiling and nail temporarily with two (2) 8d nails or equivalent fasteners (see Figures 12A, 12B and 12C). Use one fastener on opposite sides to hold thimble/ firestop spacercombination in position. Nail permanently, using at least two (2) more fasteners, after chimney sections have been assembled through the thimble/firestop spacer combination and after any neces­sary adjustments have been made. Firestop spacer must be secured by at least four (4) fasteners when completely installed.
Note: If there is a room above ceiling level, firestop spacer must be installed on the bottom side of the ceiling. If an attic is above ceiling level, firestop thimble must be installed on the bottom side of ceiling joist (Figure 12).
Note: The installation of the thimble extension is not required in manu­factured homes having ventilated attic spaces, when the chimney height is equal to or greater than 12 feet.
Ensure the thimble penetrates the roof opening. The thimble must extend completely through the ceiling or roof cavity to the outermost plane of the roof. Note: Thimble extensions are available from your dealer for constructions in which the distance between the outside of the roof and the inside of the ceiling exceeds 13". The thimbles and their extensions provide for zero clearances to combustibles and must be used at the ceiling/roof in manufactured homes (see Figures 12B and 12C, page 9).
SuperiorFireplaces.US.com 127312-01D8
"
VENTING INSTALLATION
Continued
Room Above
WARNING
Do not allow insulating materials to be blown into the space inside the thimble and the chimney. To do so could result in a fire hazard.
Attic Above
14" Min.
Note: Trim Thimble/ Extension To Desired Length And Pitch At The Rood Line
Figure 12
Figure 12A
Thimble Extension
Pitched Roof
Firestop Spacer
Firestop Thimble
Outer Pipe Of Chimney
Thimble FM8-AT1
Pitched Roof
14" Min.
Thimble
1" Clearance Minimum
Outer Pipe Of Chimney
Outer Pipe Of
Chimney
14" Min.
Thimble Cathedral Ceiling
Figure 12C
PENETRATING ROOF
To maintain a 1" clearance to pipe on a roof with a pitch, a rectangular opening must be cut.
1. Determine center point through which pipe will penetrate the roof.
2. Determine center point of the roof. Pitch is the distance the roof drops over a given span, usually 12". A 6/12 pitch means that the roof drops 6" for each 12" measured horizontally down from roof rafters.
3. Use roof opening chart (Figure 13) to determine correct opening length and flashing required.
4. Remove shingles around opening measured. Cut out this section.
5. Add next sections of pipe until end penetrates roof line. Check to see that proper clearances are maintained. Extend chimney by adding sections of double wall pipe until pipe is minimum of 30" above highest point of roof cutout. Termination and chimney must extend a minimum of 36" above highest point where it passes through roof.
Minimum Measurements
14 3/8"
(36.5 cm)
1" (2.5 cm)
13
30"
(76.2 cm)
1"
(2.5 cm)
1" (2.5 cm)
127312-01D
14" Min.
Outer Pipe Of Chimney
Thimble
Bow Roof
Figure 12B
SuperiorFireplaces.US.com
Opening "A"
PITCH SLOPE OPENING "A" MAX FLASHING MODE NO.
Flat 15" 6F-8
0-6/12 26.6° 16-1/8" 6F-8
6/12 - 12/12 45° 20-3/8" 12F-8
Figure 13 - Determine Roof Opening
9
VENTING INSTALLATION
Continued
USING ELBOW OFFSETS (30E-8DM)
1.
To achieve desired offset, you may install combinations of 12", 18", 24", 36" and 48" length of double wall pipe (see offset chart and Figure 14).
OFFSET RISE CHIMNEY LENGTH
A B 48" 36" 24" 18" 12"
4 3/8" 16 3/8"
ELBOW SET ONLY
9" 25 3/4" 1
11 7/8" 31" 1
15" 37 3/8" 1
16 3/4" 40 1/2" 1 1
20" 47 1/8" 1 22 5/8" 52 1/8" 1 1 25 1/2" 57 7/8" 1 27 5/8" 62" 1 1 30 3/8" 67 1/4" 1 1
33" 72 5/8" 1 1 35 3/4" 78" 2 37 7/8" 82" 1 1 1 41 1/4" 88 5/8" 1 1 43 3/8" 92 3/4" 2 1
46 5/8" 99 3/8" 2 48 3/4" 103 1/2" 1 1 1 51 1/2" 108 7/8" 2 1 54 1/4" 114 1/8" 2 1
57" 119 1/2" 1 2
59" 123 5/8" 2 1 1 61 3/4" 129" 1 2 1 64 1/2" 134 3/8" 1 2 1 67 1/4" 139 5/8" 4
2. Chimney weight above offset rests on return elbow. Straps must be
securely nailed to rafters or joists (see Figure 15, details A and B).
3. Maximum length of pipe between supports (return elbow or 12S-8DM) is 6' of angle run. Maximum of two 6' angle run sections per chimney system (see Figure 14).
4. All pipe connections between offset and return must be secured with two screws on outer pipe only (see Figure 16). Do not penetrate inner stainless.
See Detail A
Straps
Straps
Detail B
Angle Firestop
Straps
Detail A
Return Elbow
Figure 15 - Ceiling Support Pipe 12S-8DM
Straps
See Detail B
OFFSET CHART (22-50 FT. SYSTEM HEIGHT)
Screws
Figure 14 - Elbow Offset
B
A
SuperiorFireplaces.US.com 127312-01D10
VENTING INSTALLATION
Continued
Return Elbow
Offset Elbow
6' Max.
Return Elbow
6' Max.
Offset Elbow
Offset Elbow
A
Offset Elbow
Return Elbow
6' Max.
Offset Elbow
6' Max.
B
Figure 16 - Typical Offset Terminations (For Systems with 2 Elbow Sets, Maximum Height is 20')
FIRESTOP SPACERS (3600FS-8DM-1)
Firestop spacers are required at each point where the chimney penetrates a floor space. Their purpose is to establish and maintain the required clearance
Storm Collar
Flashing Cone
between the chimney and the combustible materials. When the pipe passes through a framed opening into a living space above, the firestop must be placed onto the ceiling from below as shown in Figure 17.
Nail Only Outer Perimeter of Flashing
Return Elbow
Ceiling Support Pipe 12S-8DM
Return Elbow
6' Max.
6' Max.
C
Overlap Shingles Top and Sides Only
Existing Ceiling Frame
Firestop Spacer
Screws or Staples (Min. of 8)
Figure 17 - Firestop Spacer with Living Space Above Ceiling
FLASHING INSTALLATION (V6F-8DM OR V12F-8DM)
Determine the flashing to be used with the roof opening chart. Slide flashing over pipe until base is flat against roof. Replace as many shingles as needed to cover exposed area and flashing base. Secure in position by nailing through shingles (see Figure 18). DONOTNAILTHROUGH
FLASHINGCONE.
127312-01D
SuperiorFireplaces.US.com
Underlap Shingles at Bottom
Figure 18 - Flashing Installation
Installing Flashing on a Metal Roof
When installing flashing on a metal roof, it is required that putty tape be used between flashing and roof. Flashing must be secured to roof using #8 x 3/4" screws and then sealed with roof coating to prevent leakage through screw holes. A roof coating must also be applied around the perimeter of flashing to provide a proper seal.
11
VENTING INSTALLATION
Continued
RTL-8DM
Storm Collar Installation (SC1)
Place storm collar over pipe and slide down until it is snug against the open edge of flashing (see Figure 19). Use SC1 for all round terminations.
NOTE: Storm collar is required but can be installed after the home is sited.
Chimney Pipe
Storm Collar
Waterproof Caulk
Flashing
Figure 19 - Storm Collar
Terminations/Spark Arrestor
Fireplace system must be terminated with listed round top termination. In any case, refer to installation instructions supplied with termination. Terminations approved for this fireplace are RT-8DM and RTL-8DM. Figure 20 shows an RTL-8DM round top termination.
IMPORTANT: Terminations are required but can be installed once the manufactured house is sited.
CAUTION
Attach Bracket Tabs to Outer Pipe (3 Places) Secure with Screws
Overlap Shingles Top and Sides
Level of Flue Gas Outlet
Caulk
Storm Collar
Flashing
Underlap Shingles Bottom Only
Figure 20 - Termination
CHASE INSTALLATIONS
Instructions for chase installations are included with chase style termination chosen. In a multiple chase installation, be sure to provide adequate distance between terminations to prevent smoke spillage from one termination to another. We suggest that terminations be separated at least 24", center to center and stacked at a vertical height difference of 18" (see Figure 21).
Donotsealopeningsontherooftopashing.Follow
the installation instructions provided with the ter­mination being used.
Terminations with 16" slip pipe sections are available. The RTT-8DM and RTTL-8DM are approved for flashing installations. When needed, these adjustable terminations may be used in combination with the pipe assembly to achieve correct chimney height.
NOTE: In the rare instance there is a problem with side driven rain or wind, or the chimney is not drafting properly, an ADS-8DM Anti Draft Shield can be used with round terminations.
18" Min. Typ.
24" Min.
24" Min.
Figure 21 - Multiple Chase Installation
SuperiorFireplaces.US.com 127312-01D12
VENTING INSTALLATION
Continued
10 FOOT RULE
All flue gas outlet chimney terminations must extend a minimum of 3 feet in height above the highest point where it passes through the roof and must be at least 2 feet above the highest point of the roof that is within a horizontal distance of 10 feet (see Figure 22).
Self Drilling Screws
Chimney Support Bracket
18"
10'
Level of Flue Gas Outlet
10'
2' Min.
3' Min.
2' Min.
3' Min.
Figure 22 - 10 Foot Rule
CHIMNEY SUPPORT BRACKET KIT: CSK-8DM
If exposed portion of chimney is greater than five feet above roofline, support wires are recommended to keep chimney secured. Support wires must be attached to chimney support brackets. Chimney support brackets must be attached to outer pipe of chimney with self-drilling screws provided in kit (screws must not penetrate inner flue pipe). The
angle of support wires should not be more than 45°from horizontal
when fastened to roof. Place chimney support brackets approximately
18"belowreplaceterminationandspacebracketsapproximately120°
apart (see Figure 23) Follow instructions included in kit.
Support Wire
Cable Ferrule
120°
Top View of
Chimney
120°
Figure 23 - Support Wires
120°
Eye Bolt
Angle of Support Wire Should Not Be More Than 45° From Horizontal
OPTIONAL GAS LINE INSTALLATION
Permanently Located (Sited) Homes Only
Gas line hook up should be done by your supplier or a qualified service person.
NOTE: Before you proceed, make sure your gas supply is turned off.
A gas line may be installed for the purpose of installing a vented or vent free appliance available through your local distributor. Use only a 1/2" black iron pipe and appropriate fittings. When installing a gas line, a shutoff valve designed for installation outside appliance is recommended.
1. Remove knockout indentation on refractory or firebrick wall located above the refractory hearth floor. Knockout indentation must be firmly tapped with any solid object such as a 1/2" dowel until it is released. Remove fragmented portions of refractory (see Figure 24).
2. Remove gas line cover plate located on either side of fireplace and pull out insulation from gas line conduit sleeve. Save insulation for reuse. Replace screws.
127312-01D
SuperiorFireplaces.US.com
Outside of Fireplace
Gas Line Conduit
Insulation
Gas Conduit Cover
Knockout
Figure 24 - Gas Line Knockout
Side Firebrick Finished Side
1/2" Dowel
Refractory Knockout Plug
13
OPTIONAL GAS LINE INSTALLATION
Continued
NOTE: Secure incoming gas line to wood framing to provide rigidity for
threaded end.
3. Run a 1/2" black iron gas line into fireplace through rear at gas line conduit sleeve (if using a raised platform, add height). Provide sufficient gas line into fireplace chamber for fitting connection (see Figure 25, page 14).
NOTE: Secure incoming gas line to wood framing to provide rigidity for
threaded end.
4. Repack insulation around gas line and into sleeve opening. Seal any gaps between gas line and refractory knockout hole with refractory cement or commercial furnace cement, Install gas appliance or cap off gas line if desired.
CAUTION
All gas piping and connections must be tested for leaks after the installation is completed. After ensuring that the gas valve is on, apply soap and water solution to all connections and joints. Bubbles forming show a leak. Correct all leaks at once. DO NOT USE AN OPEN FLAME FOR LEAK TESTING AND DO NOT OPERATE ANY APPLIANCE IF A LEAK IS DETECTED. LEAK TESTING SHOULD BE DONE BY A QUALIFIED SERVICE PERSON.
If you wish to install an unvented (vent-free) gas log set, ONLY UNVENTED
GAS LOG SETSWHICH HAVE BEEN FOUND TO COMPLYWITH THE STANDARDFORUNVENTEDROOMHEATERS,ANSIZ21.11.2,ARETO BEINSTALLEDINTHISFIREPLACE.
A vent-free log may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where not prohibited by locator.
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer.
NOTE: A hood must be installed when using an vent-free gas log set (see Accessories, page 19).
If you install a decorative gas appliance (vented gas log), the decorative gas appliance must comply with the Standard for Decorative Gas Appliance for Installation in Solid Fuel Burning Fireplaces, ANSI Z21.60/CSA 2.26 or Z21.84 and shall also be installed in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 National Fuel Gas Codes (USA) and CAN/CGA­B149.1 National Gas And Propane Installation Code (Canada) - latest edition.
WARNING
Do not operate an unvented gas log set in this fireplace with the chimney removed.
Outside of Fireplace
Gas Line Conduit
Repack Insulation
Figure 25 - Gas Line Installation
Incoming 1/2" Black Iron Pipe
Seal Opening with Refractory Cement
Side Firebrick Finished Side
Provide Enough Threaded End for Fitting Connection
WARNING
If the fireplace has been used for wood burning, the firebox and chimney must be cleaned of soot, creosote and ashes be a qualified chimney cleaner. Creosote will ignite if heavily heated.
WARNING
When using a decorative vented gas log, the damper must be removed or permanently locked in the fully open position and the glass doors must be in the fully open position.
SuperiorFireplaces.US.com 127312-01D14
FINISHING FIREPLACE
Combustible materials, such as wallboard, gypsum board, sheet rock, dry­wall, plywood, etc. may make direct contact with sides and top around the fireplace face. It is important that combustible materials do not overlap the face itself. Brick, glass, tile or other noncombustible materials may overlap the front face provided they do not obstruct essential openings like louvered slots or any other opening. When overlapping with a noncombustible facing material, use only noncombustible mortar or adhesive.
IMPORTANT: Glass must be allowed to warm slowly and evenly. Tempered
glasswillwithstandagradualtemperatureriseto550°Fahrenheit,which
is more than a normal fire will generate.
Such materials as pitch/wax laden logs, very dry mill end lumber, and large amounts of paper or cardboard boxes can create an excessively hot fire and should not be burned in this fireplace. Always keep fire back from doors and never allow flames to contact glass.
MANTELS
A mantel may be installed if desired (see Figure 26). Woodwork such as wood trims, mantels or any other combustible material projecting from the front face must not be placed within 9" of the fireplace opening. Combustible materials above 9" and projecting more than 1-1/2" from the fireplace must not be placed less than 12" from the top opening of the fireplace (NFPA 211, Section - Clearance from Combustible Material).
NOTE: HUD requirements may supersede these minimum dimensions.
Combustible Material
Safe Zone for Projection of Combustible Materials
6"
Ref.
12" Min.
12-1/4" Ref.
33°
3" Nom.
1-1/2" Max.
WARNING
Fireplaces equipped with glass doors should be operated only with doors fully opened or fully closed.
Doors,ifleftpartlyopen,maydrawgasandame
out of the fireplace opening creating risks of both fire and smoke.
Doors Fully Closed
Fireplace Front
9" Min.
Fireplace Opening
Upper Section
of Fireplace
Figure 26 - Mantel Clearances to Combustible Material
OPERATION AND MAINTENANCE GUIDELINES
GLASS DOORS
Glass doors are standard with fireplace. When fireplace is in operation, doors must be FULLY OPENED or FULLY CLOSED position only or a fire hazard may be created (see Figure 27).
A fireplace equipped glass doors operates much differently than a fireplace with an open front. A fireplace with glass doors has a limited amount of air for combustion. Excessive heat within fireplace can result if too large a fire is built or if combustion air gate is not completely open. The following tips should be followed to assure that both fireplace and glass door retain their beauty and function properly. Both flue damper and glass doors must be fully opened before starting the fire. This will provide sufficient
combustion air and maintain safe temperatures in firebox.
Doors
Fully Opened
Fireplace Front
Figure 27 - Bi-Fold Glass Doors
127312-01D
SuperiorFireplaces.US.com
15
OPERATION AND MAINTENANCE GUIDELINES
Continued
Door Removal
1. Fold doors (fully open) and press up on upper door spring clip until top pin is free of the spring clip (see Figure 28). Tip door toward middle of fireplace opening and lift door out of the lower pivot hole.
2. Repeat step 1 for remaining door.
Fold Door and Slide Top Pins Into Track
Figure 28 - Removing / Installing Bi-Fold Doors
Installing Glass Doors
1. With bi-fold doors completely folded, insert bottom pivot pin into pivot hole located near bottom corner of front face opening and swing door to vertical position making sure top pins slide into door track. Door is installed when top door pin snaps into spring clip (see Figure 28).
2. Repeat step 1 for remaining door.
Spring Clip
Insert Pin into Spring Clip
Insert Bottom Pivot Pin into Hole
Pivot Hole
Figure 29 - Adjusting Bi-Fold Doors
CLEANING GLASS
Clean the glass with any commercial glass cleaner or soap and water. Do not use any abrasive material to clean glass. Do not clean glass with any cool water if glass is still hot from fire and smoke.
DAMPER OPERATION
The damper handle, which opens and closes damper blade, is located inside firebox at center towards back wall. Pushing handle back in keyway slot will free damper blade to automatically open. To close, reach in and push handle back into keyhole slot then pull down and forward to lock it in place (see Figure 30). Damper is not designed to be airtight. A small gap around damper blade is normal.
Damper Weight
If you find the doors do not close properly or do not appear level or straight, proceed with section on door adjustment.
Door Adjustment
Remove doors and slightly loosen lower pivot clips and upper spring clips. Replace doors and fully close them. Use 1/8" shims (any material) to level doors. Once proper setting is achieved, carefully open doors enough so that you can access spring clips with a phillips screwdriver. Tighten screws. See Figure 29.
SuperiorFireplaces.US.com 127312-01D16
Damper Handle
Closed Damper
Figure 30 - Damper Operation
Open Damper
WARNING
Risk of fire! Always replace grate with IHP part number 11116 grate only. This grate has been designed to keep the operation of your fireplace safe and efficient.
OPERATION AND MAINTENANCE GUIDELINES
Continued
LOCATING ACCESS COVER PLATE
Sheet metal cover plates located underneath front hearth refractory may have shifted or moved out of place while fireplace was in transit. These cover plates must be kept in the proper location prior to using the fireplace (See Figure 31). For further operating guidelines, instructions and warranty information, please refer to your homeowner's guide or contact your authorized dealer.
TECHNICAL SERVICE
You may have further questions about installation, operation, or troubleshooting. If so, visit SuperiorFireplaces.US.com.
Haveyourmodelandserialnumbersofyourreplaceready.
Model and serial number information are in the fireplace's rating plate located underneath the front brick liner.
YoucanalsovisitIHP'swebsiteatIHP.US.com.
REPLACEMENT PARTS
If this product is missing a part or has a broken component, please do not return it to the store. Visit IHP.US.com for more information.
NOTE: Use only original replacement parts. This will protect your warranty coverage for parts replaced under warranty.
Whencontacting IHP,please haveyour model andserial numbers of
your fireplace ready.
Access Panel
Figure 31 - Locating Access Cover Plate
Model and serial number information are in the fireplace's rating plate located on the smoke shelf on the top right side of the fireplace opening.
127312-01D
SuperiorFireplaces.US.com
17
FIREPLACE ACCESSORIES
CAT NO. MODEL DESCRIPTION
BI-FOLD GLASS DOORS
J2724 VDG36E 36" Glass Door - Brushed finish
J0468 DP36E 36" Glass Door - Platinum finish
J2709 VDBP36E 36" Glass Door - Black finish
EMBER PROTECTOR
J6906 Ember Protector
GRATE
J4515 Grate 36"
BRICK LINER
J6897 Refractory Rear
J6898 Refractory Side L/R
J6938 Refractory Bottom Rear
J6939 Refractory Bottom Front
OUTSIDE AIR KIT FOR FLOOR INSTALLATION (INCLUDED)
J7317 AK6E Outside Air Kit
INSTALLATION ACCESSORIES
DOUBLE WALL PIPE
F0895 12-8DM 12" Section Double Wall Pipe Snap Lock
F0896 18-8DM 18" Section Double Wall Pipe Snap Lock
F0897 24-8DM 24" Section Double Wall Pipe Snap Lock
F0898 36-8DM 36" Section Double Wall Pipe Snap Lock
F0899 48-8DM 48" Section Double Wall Pipe Snap Lock
CHIMNEY SUPPORT BRACKET KIT
J0380 CSK-8DM Kit Chimney Support Bracket
FIRESTOP SPACER
Support Bracket
Self Drilling Screws
Cable Ferrule
Eye Bolt Screw
Strand Wire (50 ft)
F0907 3600FS-8DM-1 1" Clearance Firestop Spacer ( 1ea.)
ROOF FLASHING
F0910 V12F-8DM Roof Flashing 6/12 to12/12 Pitch
F0909 V6F-8DM Roof Flashing 0 to 6/12 Pitch (30" Base)
SuperiorFireplaces.US.com 127312-01D18
INSTALLATION ACCESSORIES Continued
ANTI-DRAFT SHIELD
(Round Top Termination Only)
F0927 ADS-8DM Anti-Draft Shield for Round Top Only
MESH ROUND TOP TERMINATIONS
J6280 RTL-8DM Round Top Termination
SQUARE TOP TERMINATION WITH LOUVERS
F0921 ETL-8DM Square Top with Slip Section
ADJUSTABLE HOOD
Required when installing a vent-free gas log in this fireplace.
F1764 GA6050 BlackFireplaceHood
HEARTH EXTENSION
J1462 HE-36 HearthExtension-36IN
OPTIONAL OUTSIDE AIR KIT FOR SIDE WALL INSTALLATION
J0010 A-K6WE Outside Air Kit
LABEL-UL127-50PK
F2659
LABEL-UL127-
50PK
UL127 Venting Label - 50 PK
STORM COLLAR
F0946 SC2-1 Storm Collar
30° OFFSET AND RETURN
F0900 30E-8DM 30 Degree Offset and Return
ADJUSTABLE FIRESTOP THIMBLE
LB-97008A Adjustable Firestop Thimble
WARNING HOT
•Fire Risk
•Insulation and combustibles must not touch
pipe
•Consult manual for clearance requirements
•Ensure proper connection
WARNING HOT
•Fire Risk
•Insulation and combustibles must not touch
pipe
•Consult manual for clearance requirements
•Ensure proper connection
Not shown
WARNING HOT
•Fire Risk
•Insulation and combustibles must not touch
pipe
•Consult manual for clearance requirements
•Ensure proper connection
900599-01
AIR INLET HOOD
J0019 AK6-WI Termination Outside Air Vent
127312-01D
SuperiorFireplaces.US.com
19
INSTALLATION ACCESSORIES Continued
THIMBLE EXTENSIONS
99L69 8" Thimble Extension
91L46 26" Thimble Extension
FLEX DUCT (3 PACK)
J1936 MP6-75 Duct Outside Air 6" x 75'
AIR INLET HOOD (6 PACK)
MK6-WI AirInletHood
FACE EXTENSION
Front face extension would add 6” to the width and 6” to the height of the fireplace face.
J0918 FE-36R Face Extension (C36EMW-R)
VENT KIT* DESCRIPTION
36-8DM 36" Double Wall Pipe 2 2 0 24-8DM 24" Double Wall Pipe 1 0 0 18-8DM 18" Double Wall Pipe 0 2 0 LB97008A Adjustable Firestop Thimble 1 1 1 V6F-8DM Roof Flashing 1 1 1 SC1-1 Storm Collar 1 1 1 RTL-8DM Round Cap Termination 1 1 0
RLT-8HT Round Louvered Termination 0 0 1 36-8HT 36"Flue,8"HT. 0 0 2 24-8HT 24"Flue,8"HT. 0 0 1
*UseforMostCommonManufactured(Mobile)HomeInstallations
J1948
MW8K
(8' Vent Kit)
J1952
MW9K
(9' Vent Kit)
F2122
MW8K-HT
(8' HT Vent Kit)
SuperiorFireplaces.US.com 127312-01D20
IMPORTANT NOTICES
CANADA
Canadian code CAN/ULC-S610-M87 and other pertinent codes require stainless steel chimney for the installation of this fireplace. A Cold Air Climate Kit is also required in Canada and is recommended for cooler regions in the United States. Below, find a list of approved stainless steel parts.
Chimney Parts List for Canada
Catalog No.
F0881 12-8HT 12"SectionHi-TempDouble
F0882 18-8HT 18"SectionHi-TempDouble
F0883 24-8HT 24"SectionHi-TempDouble
F0884 36-8HT 36"SectionHi-TempDouble
F0885 48-8HT 48"SectionHi-TempDouble
F0886 30E-8HT 30DegreeHi-TempOffset
F0887 12S-8HT Hi-TempChimneySupport
F0888 RT-8HT Hi-TempRoundTopwith
F0889 RTT-8HT Hi-TempRoundTopwith
F0890 RLT-8HT Hi-TempRoundTopwith
F0891 RLTT-8HT Hi-TempRoundTopwith
F0892 ET-8HT Hi-TempPyramidTopwith
F0893 ETL-8HT Hi-TempLargePyramidTop
F0894 AP-8HT Hi-TempAnchorPlate/Col-
F0929 CAK-8 Cold Air Collar Kit - 8"
*When ordered alone, this part cannot ship via parcel delivery services.
Model No.
8" Hi-Temp Wood burning Chimney
Wall Pipe Snap Lock
Wall Pipe Snap Lock
Wall Pipe Snap Lock
Wall Pipe Snap Lock
Wall Pipe Snap Lock
and Return
(For Use With Chimney
HeightsInExcessof30')
Mesh Screen
Mesh Screen and Slip Sec­tion
Louvered Screen
Louvered Screen and Slip Section
Slip Section
with Slip Section (use with all 8" systems)
lar Assembly (for masonry fireplaces)
Chimney
IMPORTANT NOTICE A manufactured shroud which has been approved by a national test­ing agency for use with this fire­place may be used if installed in accordance with the instructions by its manufacturer. A locally fabricated shroud may be used with IHP Shroud Leg Spacer Kit (SLK) in accordance with instruc­tions provided with the shroud.
NOTICE: The firebox canopy (hood) must not be modified or replaced with a canopy that may be provided with the unvented decorative room heater.
CAUTION
THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR, WALL, AND CEILING/ ROOF MUST BE MAINTAINED.
WARNING
DO NOT INSTALL IN SLEEPING ROOM OF MOBILE HOMES.
WARNING
Discontinue use of the appli­ance immediately if doors are damaged and contact a qualified installer for repair. Only doors certified with the appliance shall be used.
WARNING
Do not slam or strike doors. Damage can result in a hazard­ous condition.
127312-01D
SuperiorFireplaces.US.com
21
NOTES
____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________
SuperiorFireplaces.US.com 127312-01D22
Innovative Hearth Products
®
Superior
Brand Wood-Burning Fireplace
20 Year Limited Warranty
THE WARRANTY
Innovative Hearth Products ("IHP") 20 Year Limited Warranty warrants your Superior® Brand wood burning fi replace ("Product") to be free from defects in materials and workmanship at the time of manufacture. The Product body, fi rebox and ceramic glass carry the 20 Year Limited Warranty. Ceramic glass carries the 20 Year Limited Warranty against thermal breakage only. After installation, if covered components manufactured by IHP are found to be defective in materials or workmanship during the 20 Year Limited Warranty period and while the Product remains at the site of the original installation, IHP will, at its option, repair or replace the covered components. If repair or replacement is not commercially practical, IHP will, at its option, refund the purchase price or wholesale price of the IHP product, whichever is applicable. IHP will also pay IHP prevailing labor rates, as determined in its sole discretion, incurred in repairing or replacing such components for up to fi ve years. THERE ARE EXCLUSIONS AND LIMITATIONS to this 20 Year Limited Warranty as described herein.
COVERAGE COMMENCEMENT DATE
Warranty coverage begins on the date of purchase. In the case of new home construction, warranty coverage begins on the date of fi rst occupancy of the dwelling or six months after the sale of the Product by an independent IHP dealer/distributor, whichever occurs earlier. The warranty shall commence no later than 24 months following the date of product shipment from IHP, regardless of the installation or occupancy date.
EXCLUSIONS AND LIMITATIONS
This 20 Year Limited Warranty applies only if the Product is installed in the United States or Canada and only if operated and maintained in accordance with the printed instruc­tions accompanying the Product and in compliance with all applicable installation and building codes and good trade practices.
This warranty is non-transferable and extends to the original owner only. The Product must be purchased through a listed supplier of IHP and proof of purchase must be provided. The Product body and fi rebox carry the 20 Year Limited Warranty from the date of installation. Vent components, trim components, paint and applied stains are excluded from this 20 Year Limited Warranty. The following do not carry a 20 Year Limited Warranty but are warranted as follows:
Air tubes, baffl es and brick retainers – Repair or replacement for one year from the date of installation Cast iron parts – Replacement for one year from date of installation Catalyst – Carries a separate warranty. Refer to the warranty certifi cate provided for that part Electrical components – Repair or replacement for one year from the date of installation Fireplace screens, refractory and side shields (metal or refractory) – Repair or replacement for two years from date of installation. Excludes hairline cracks. Fuel grates –These parts are considered consumable accessories and therefore are not warranted, with the exception of defects in material or workmanship which
are covered for 90 days from the date of installation Gaskets – Replacement for one year from date of installation Gold & nickel plating – Replacement for two years from date of installation. Excludes tarnishing
Optional glass doors – Repair or replacement for 90 days from the date of installation Refractory & screens – Replacement for two years from date of installation. Excludes hairline cracks Removable air tubes – Repair or replacement for seven years from date of installation. IHP prevailing labor rates for years one through fi ve. Labor coverage – Prevailing IHP labor rates apply for the warranty period of the component.
Parts not otherwise listed carry a 90 day warranty from the date of installation.
Whenever practicable, IHP will provide replacement parts, if available, for a period of 10 years from the last date of manufacture of the Product.
IHP will not be responsible for: (a) damages caused by normal wear and tear, accident, riot, fi re, fl ood or acts of God; (b) damages caused by abuse, negligence, misuse, or unauthorized alteration or repair of the Product affecting its stability or performance. (The Product must be subject to normal use with approved fuels listed in the Operation Manual provided with the product. This includes burning such fi replace fuels as wood and natural or propane gas. Fuel products with abnormal burning characteristics, including but not limited to fuel such as driftwood, coal or plywood and wood products using a binder may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly.); (c) damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product; (d) damages, repairs or ineffi ciency resulting from faulty installation or application of the Product.
Coverage of this 20 Year Limited Warranty is conditional upon use of an adequate fuel grate on factory-built fi replaces only, when applicable. IHP is not responsible for inadequate fi replace system draft caused by air conditioning and heating systems, mechanical ventilation systems, or general construction condi­tions which may generate negative air pressure in the room in which the appliance is installed. Additionally IHP assumes no responsibility for smoking conditions caused by inadequate chimney height, adjoining trees or buildings, adverse wind conditions or unusual environmental factors and conditions. Certain IHP Products are listed for use with Security Chimneys International, Ltd. or IHP chimney systems only. Use of chimney components other than that specifi ed in the Product manual will void the Product warranty.
This 20 Year Limited Warranty covers only parts and labor as provided herein. In no case shall IHP be responsible for materials, components or construction which are not manufactured or supplied by IHP or for the labor necessary to install, repair or remove such materials, components or construction. Additional utility bills incurred due to any malfunction or defect in equipment are not covered by this 20 Year Limited Warranty. All replacement or repair components will be shipped F.O.B. from the nearest stocking
IHP factory.
LIMITATION ON LIABILITY
It is expressly agreed and understood that IHP’s sole obligation and the purchaser’s exclusive remedy under this warranty, under any other warranty, expressed or implied, or in contract, tort or otherwise, shall be limited to replacement, repair, or refund, as specifi ed herein.
In no event shall IHP be liable for any incidental or consequential damages caused by defects in the Product, whether such damage occurs or is discovered before or after replacement or repair, and whether such damage is caused by IHP’s negligence. IHP has not made and does not make any representation or warranty of fi tness for a particular use or purpose, and there is no implied condition of fi tness for a particular use or purpose.
IHP makes no expressed warranties except as stated in this 20 Year Limited Warranty. The duration of any implied warranty is limited to the duration of this expressed warranty.
No one is authorized to change this 20 Year Limited Warranty or to create for IHP any other obligation or liability in connection with the Product. Some states and provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. The provisions of this 20 Year Limited Warranty are in addition to and not a modifi cation of or subtraction from any statutory warranties and other rights and remedies provided by law.
INVESTIGATION OF CLAIMS AGAINST WARRANTY
IHP reserves the right to investigate any and all claims against this 20 Year Limited Warranty and to decide, in its sole discretion, upon the method of settlement.
To receive the benefi ts and advantages described in this 20 Year Limited Warranty, the appliance must be installed and repaired by a licensed contractor approved by IHP.
Contact IHP at the address provided herein to obtain a listing of approved dealers/distributors. IHP shall in no event be responsible for any warranty work done by a contrac-
tor that is not approved without fi rst obtaining IHP's prior written consent.
HOW TO REGISTER A CLAIM AGAINST WARRANTY
In order for any claim under this warranty to be valid, you must contact the IHP dealer/distributor from which you purchased the product. If you cannot locate the dealer/ distributor, then you must notify IHP in writing. IHP must be notifi ed of the claimed defect in writing within 90 days of the date of failure. Notices should be directed to the IHP Warranty Department at 1508 Elm Hill Pike, Suite 108; Nashville, TN 37210 or visit our website at WWW.SUPERIORFIREPLACES.US.COM.
Printed in U.S.A. © 2013 Innovative Hearth Products
P/N 900224-00, Rev. A 10/2015
Innovative Hearth Products
1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210
23
WARRANTY
KEEP THIS WARRANTY
Model Number Serial Number Date Installed Dealer's Name Dealer's Phone Number
Keep receipt for warranty verification
InnovativeHearthProducts reservesthe righttomakechangesatanytime,without notice,in
design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
P127312-01
PrintedinU.S.A.©2014IHPLLC
P/N 121312-01 Rev. D 10/2015.
1508ElmHillPike,Suite108•Nashville,TN37210
Loading...