Signature Series See-Through
Power Vent DV Gas Fireplaces
P/N 506009-20 Rev. NC 12/2013
This manual is one of a set of two supporting this product.
Refer to P/N
Ce manuel est disponible en francais, simplement
en faire la demande. Numéro de la pièce 506009-21.
506010-16
for Care and Operation Instructions.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
MODELS
Intertek Report No.
100326550PRT-001
DRT63STYN
Look for the EnerGuide
Gas Fireplace Energy
Efficiency Rating in this manual.
Based on CSA P.4.1-02
INSTALLATEUR : Laissez cette notice avec l’appareil.
CONSOMMATEUR : Conservez cette notice pour
consultation ultérieure.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile
home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating
plate. This appliance is not convertible for use with other gases unless a certified kit is used.
WARNING /AVERTISSEMENT/AVISO
• HOT GLASS WILL CAUSE
BURNS.
• DO NOT TOUCH GLASS
UNTIL COOLED.
• NEVER ALLOW CHILDREN
TO TOUCH GLASS.
• UNE SURFACE VITRÉE CHAUDE
PEUT CAUSER DES BRÛLURES.
• LAISSER REFROIDIR LA SURFACE
VITRÉE AVANT D'Y TOUCHER.
• NE PERMETTEZ JAMAIS À UN ENFANT
DE TOUCHER LA SURFACE VITRÉE.
• EL VIDRIO CALIENTE
CAUSARÁ QUEMADURAS.
• USTED DEBE NUNCA
TOCAR EL VIDRIO CALIENTE.
• LOS NIÑOS DEBEN NUNCA
TOCAR EL VIDRIO.
WARNING: If the information in these instructions
is not followed exactly, a fire or explosion may
result, causing property damage, personal injury,
or death.
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a
qualified installer, service agency or the gas supplier.
AVERTISSEMENT : Assurez-vous de bien suivre les
instructions données dans cette notice pour réduire au
minimum le risque d’incindie ou d’explosion ou pour
éviter tout dommage matériel, toute blessure ou la mort.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs
ou liquides inflammables dans le voisinage de cet appareil
ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un
installateur ou un service d’entretien qualifié ou par le
fournisseur de gaz.
Page 2
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
The See-Through Power Vent is a direct-vent,
sealed combustion gas fireplace designed
for either indoor/indoor or indoor/outdoor
residential applications (including screened
porches and lanais).
NOTE: INDOOR/OUTDOOR INSTALLATIONS
REQUIRE AN OUTDOOR INSTALLATION KIT
(SOLD SEPARATELY).
These appliances are designed to operate on
natural gas. (Propane units are available as
a field conversion.) The system is switchable
between standing and intermittent pilot modes.
External electrical power is required to operate
these units.
Approved Vent Components
These fireplaces are designed, tested, and
listed for operation and installation with the
following vent components (4-1/2" inner and
7-1/2" outer) only:
• Secure Vent™ direct-vent system compo-
nents manufactured by Security Chimneys
International.
These approved vent system components are
labeled for identification. Do NOT use any other
manufacturer’s vent components with these
appliances.
GENERAL INFORMATION
WARNING
Young children should be carefully
supervised when they are in the
same room as the appliance. Toddlers, young children and others
may be susceptible to accidental
contact burns. A physical barrier
is recommended if there are at risk
individuals in the house. To restrict
access to a fireplace or stove,
install an adjustable safety gate to
keep toddlers, young children and
other at risk individuals out of the
room and away from hot surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être
surveillés étroitement lorsqu’ils
se trouvent dans la même pièce
que l’appareil. Les tout petits,
les jeunes enfants ou les adultes
peuvent subir des brûlures s’ils
viennent en contact avec la surface chaude. Il est recommandé
d’installer une barrière physique si
des personnes à risques habitent
la maison. Pour empêcher l’accès
à un foyer ou à un poêle, installez
une barrière de sécurité; cette
mesure empêchera les tout petits,
les jeunes enfants et toute autre
personne à risque d’avoir accès à
la pièce et aux surfaces chaudes.
Children and adults should be alerted to the
hazards of high surface temperature and
should stay away to avoid burns or clothing
ignition.
Les enfants et les adultes devraient être
infor-més des dangers que posent les
températures de surface élevées et se
tenir à distance afin d’éviter des brûlures
ou que leurs vêtements ne s’enflamment.
DO NOT ATTEMPT TO ALTER OR MODIFY
THE CONSTRUCTION OF THE APPLIANCE OR
ITS COMPONENTS. ANY MODIFICATION OR
ALTERATION MAY VOID THE WARRANTY,
CERTIFICATION AND LISTINGS OF THIS UNIT.
Page 3
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause injury
or property damage. Refer to
this manual. For assistance or
additional information consult
a qualified installer, service
agency or the gas supplier.
WARNING
Failure to comply with these
installation instructions will result
in an improperly installed and
operating appliance, voiding its
warranty. Any change to this appliance and/or its operating controls
is dangerous.
WARNING
Clothing or other flammable
material should not be placed
on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de
vêtements ni d’autres matières
inflammables sur l’appareil ni à
proximité.
WARNING
Any safety screen or guard
removed for servicing the appliance must be replaced prior to
operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré
pour permettre l’entretien de
l’appareil doit être remis en
place avant de mettre l’appareil
en marche.
WARNING
Improper installation or use of
this appliance can cause serious
injury or death from fire, burns,
explosion or carbon monoxide
poisoning.
Note: Installation and repair should be done
by a qualified service person. The appliance
should be inspected before use and at least
annually by a professional service person.
More frequent cleaning may be required due
to excessive lint from carpeting, bedding
material, etcetera. It is imperative that control
compartments, burners and circulating air
passageways of the appliance be kept clean.
Remarque : L’installation et la réparation devrait être confiées à un technicien
qualifié. L’appareil devrait faire l’objet
d’une inspection par un technicien professionnel avant d’être utilisé et au moins
une fois l’an par la suite. Des nettoyages
plus fréquents peuvent être nécessaires si
les tapis, la literie, et cetera produisent
une quantité importante de pous-sière.
Il est essentiel que les compartiments
abritant les commandes, les brûleurs
et les conduits de circulation d’air de
l’appareil soient tenus propres.
Do not use these appliances if any part
has been under water. Immediately call a
qualified, professional service technician to
inspect the appliance and to replace any parts
of the control system and any gas control
which have been under water.
Ne pas utiliser cet appareil s’il a été
plongé, même partiellement, dans
l’eau. Appeler un technicien qualifié pour
inspecter l’appareil et remplacer toute
partie du système de commande et toute
commande qui a été plongée dans l’eau.
Only trim kit(s) supplied by the manufacturer
shall be used in the installation of this appliance.
Seules les trousses de garniture fournies
par le fabricant doivent être utilisées pour
l’installation de cet appareil.
These appliances comply with National Safety
Standards and are tested and listed by Intertek
(Report No. 100326550PRT-001) to ANSI
Z21.88 (in Canada, CSA-2.33), and CAN/CGA-
2.17-M91 (CSA P4.1) in both USA and Canada,
as vented gas fireplace.
These appliances are listed by Intertek for
installation in bedrooms, aftermarket mobile
homes, and manufactured homes.
Misc. Codes/Standards
Installation must conform to local codes or, in
the absence of local codes, with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest
edition (in Canada, the current CAN/CSA-B149.1
installation code).
The appliance, when installed, must be electri-
cally grounded and wired in accordance with
local codes or, in the absence of local codes,
with the National Electrical Code, ANSI/NFPA
70 - latest edition, or the Canadian Electrical
Code, CSA C22.1 - latest edition.
Provide adequate clearances around air openings and adequate accessibility clearance for
service and proper operation. Never obstruct
the front or back openings of the appliance.
These appliances are designed to operate on
natural or propane gas only (if field-converted
to propane). The use of other fuels or combination of fuels will degrade the performance
of this system and may be dangerous.
The system is switchable between standing
and intermittent pilot modes. External electrical
power is required to operate these units.
These models come standard with a remotely
modulated gas valve. The included transmitter
remotely controls flame appearance and heat
output (manual gas valve adjustment is not
possible).
Inputs and Efficiencies
Appliance BTU inputs are listed in Table 1A.
Appliance efficiencies are listed in Table 1B.
INPUTS
Gas Type
Natural Gas
Liquid Propane
(field-converted to LP)
Table 1A
Inputs
40,000 to 60,000
BTU/hr
43,500 to 56,000
BTU/hr
EFFICIENCIES
Gas TypeAFUEEnerGuide
Natural Gas
Table 1B
68%62%
Gas Fireplace Energy Efciency Rating
Based on CSA P.4.1-02
Gas Supply Pressure Requirements
Inlet and manifold gas supply pressure requirements for these appliances are listed in Tables 2 and 3.
Inlet Gas Supply Pressure (all models)
Fuel #MinimumMaximum
Natural
Gas
Liquid
Propane*
Table 2
Manifold Gas Supply Pressure (all models)
Fuel #LowHigh
Natural
Gas
Liquid
Propane*
Table 3
(Continued on next page)
5.0" WC
(1.24 kPa)
11.0" WC
(2.74 kPa)
*Available as field conversion only.
(Lo) 1.6" WC
(0.4 kPa)
(Lo) 6.3" WC
(1.57 kPa)
*Available as field conversion only.
10.5" WC
(2.61 kPa)
13.0" WC
(3.23 kPa)
(Hi) 3.5" WC
(0.87 kPa)
(Hi) 10.0" WC
(2.49 kPa)
3
Page 4
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Gas Supply Pressure Requirements
(continued from previous page)
Test gauge connections are provided on the
front of the electronic gas control valve (identified IN for the inlet and OUT for the manifold
side).
The control valves have a 3/8" (10 mm) NPT
thread inlet and outlet side of the valve. Refer
to Figure 1.
Propane tanks are at pressures that will cause
damage to valve components. Verify that the
tanks have step-down regulators to reduce the
pressure to safe levels.
These appliances must not be connected to a
chimney or flue serving a separate solid fuel
burning appliance.
These appliances must be isolated from
the gas supply piping system (by closing
their individual manual shut-off valve)
during any pressure testing of the gas
supply piping system at test pressures
equal to or less than 1/2 psig (3.5 kPa).
These appliances and their individual
shut-off valves must be disconnected
from the gas supply piping system
during any pressure testing of that
system at pressures greater than 1/2
psig (3.5 kPa).
Green Wire
(From DFC Wire
Harness)
Manifold (Out)
Test Port
Line (In) Test Port
PURGE CYCLE
This is a power-vented fireplace that
requires household electrical power to
operate. When the fireplace is turned
OFF, the exhaust blower will continue
to operate for up to two minutes, to
purge exhaust gases from the venting
system. This system will not operate
during a power outage.
Orifice Sizes
Sea Level To High Altitude (All Models)
These appliances are tested and approved
for installation at elevations of 0– 4500 feet
(0– 1372 meters) above sea level using the
standard burner orifice sizes listed in Table 4).
For elevations above 4500 feet, contact your
gas supplier or qualified service technician.
Deration
At higher elevations, the amount of BTU fuel
value delivered must be reduced by either:
• using gas that has been derated by the gas
company; or
• changing the burner orice to a smaller size
as regulated by the local authorities having
jurisdiction and by the (USA) National Fuel
Gas Code NFPA 54/ANSI Z223.1 - latest
edition or, in Canada, the CAN/CSA-B149.1
codes - latest edition.
Install the appliance according to the regulations
of the local authorities having jurisdiction and,
in the USA, the National Fuel Gas Code NFPA
54 / ANSI Z223.1 - latest edition or , in Canada,
the CAN/CSA-B149.1- latest edition.
NOTE: Flame appearance will diminish
4% per 1,000 feet.
Gas Valve Diagram
The SIT Proflame valve is illustrated in Figure 1.
Connect GTMS
Wire Harness
Pressure
Regulator
Tower
Burner Orifice Sizes
(USA and Canada)
Elevation 0-4500 ft (0–1372 m)
Natural Gas
Drill size (inches)
#32 (0.116")
[Cat. No. H8002]
Standard size installed at factory.
Table 4
Standard size in LP conversion kit.
Propane
Drill size (inches)
#52 (0.0635")
[Cat. No. H8003]
Requirements for the
Commonwealth of Massachusetts
These fireplaces are approved for installation in
the US state of Massachusetts if the following
additional requirements are met:
• Install this appliance in accordance with
Massachusetts Rules and Regulations 248
C.M.R.
• Installation and repair must be done by a
plumber or gas fitter licensed in the Commonwealth of Massachusetts.
• The exible gas line connector used shall
not exceed 36 inches (92 centimeters) in
length.
• The individual manual shut-off must be a
T-handle type valve.
Massachusetts Horizontal Vent
Requirements
In the Commonwealth of Massachusetts, horizontal terminations installed less than seven
(7) feet above the finished grade must comply
with the following additional requirements:
• A hard-wired carbon monoxide detector
with an alarm and battery backup must be
installed on the floor level where the gas
fireplace is installed. The carbon monoxide
detector must comply with NFPA 720, be
ANSI/UL 2034 listed and be ISA certified.
• A metal or plastic identication plate must
be permanently mounted to the exterior of
the building at a minimum height of eight (8)
feet above grade and be directly in line with
the horizontal termination. The sign must
read, in print size no less than one-half (1/2)
inch in size, GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS.
Orange Wire
(from DFC Wire
Harness)
Inlet
3/8" NPT
Figure 1: SIT Proflame Valve
4
Outlet
3/8" NPT
Yellow Ground Wire
(From DFC Wire
Harness)
New York City, New York (MEA)
Installation of these fireplaces is approved for
installation in New York City, NY.
Page 5
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks
around the appliance with noncombustible
material and wherever cold air could enter the
room. If the floor is above ground level, it is
especially important to insulate outside chase
cavity between studs and under the floor on
which the appliance rests. Gas line holes and
other openings should be caulked or stuffed
with unfaced fiberglass insulation.
If the fireplace is being installed on a cement
slab in cold climates, a sheet of plywood or
other raised platform can be placed underneath to prevent cold transfer to the fireplace
and into the room. It also helps to sheetrock
inside surfaces and tape for maximum air
tightness and caulk firestops.
MANUFACTURED HOME
REQUIREMENTS
(Top View)
Indoors
When unit is installed with one
side flush with a wall, the wall
on other side of unit must not
extend beyond front edge of unit.
Outdoors
Drywall
Horizontal
Termination
(Outdoors)
This appliance may be installed in an aftermarket, permanently located manufactured
home and must be installed in accordance
with the manufacturer's instructions and the
Manufactured Home Construction and Safety
Standard, Title 24 CFR, Part 3280, in the
United States, or the Standard for Installation
in Mobile Homes, CAN/CSA Z240 MH Series,
in Canada.
Cet appareil peut être installé cómme
du matéri-el d'origine dans une maison
préfabriquée (É.U. seulement) ou mobile
et doit être installé selon les instructions
du fabricant et conformément à la norme
Manufactured Home Constructions and
Safety, Title 24 CFR, Part 3200 aux Unis
ou à la norme Can/CSA-Z240 Série MM,
Maisons mobiles au Canada.
This appliance is only for use with the type
of gas indicated on the rating plate. This appliance is not convertible for use with other
gases, unless a certified kit is used.
Cet appareil doit être utilisé uniquement
avec le type de gaz indiqué sur la plaque
signalétique. Cet appareil ne peut être converti à d'autres gaz, sauf si une trousse de
conversion est utilisée.
CAUTION: Ensure that the cross members
are not cut or weakened during installation.
The structural integrity of the manufactured
home floor, wall, and ceiling / roof must be
maintained.
CAUTION: This appliance must be grounded
to the chassis of the manufactured home
in accordance with local codes or in the
absence of local codes, with the National
Electrical Code ANSI / NFPA 70 - latest edition or the Canadian Electrical Code CSA
C22.1 - latest edition.
Fireplace
Figure 2: Typical Installation/Locations
LOCATION
In selecting the location, the aesthetic and
functional use of the appliance are primary
concerns; however, vent system routing to the
exterior and access to the fuel supply are also
important.
CAUTION: Due to high temperatures, the appliance should be located out of traffic and
away from furniture and draperies (Figure 2).
AVERTISSEMENT : En raison des températures élevées, l’appareil devrait
être installé dans un endroit où il y a peu
de circulation et loin du mobilier et des
tentures (Figure 2).
The location also should be free of electrical,
plumbing, or other heating/air conditioning
ducting.
These direct-vent appliances are uniquely
suited for installations requiring a utility shelf
positioned above the fireplace. Utility shelves like
these are commonly used for locating television
sets and decorative plants.
The minimum height from the base of the appliance to the underside of combustible materials
used to construct a utility shelf in this fashion
is shown in Figure 7 on Page 9.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Top of Fireplace
Opening
Be aware that this is a heat-producing appliance. Objects placed above the unit are
exposed to elevated temperatures.
Do not insulate the space between the appliance and the area above it.
The appliance should be mounted on a fully
supported base extending the full width and
depth of the unit. The appliance may be located
on or near conventional construction materials.
However, if installed on combustible materials,
(such as carpeting or vinyl tile), a metal or
wood barrier covering the entire bottom surface
must be used.
5
Page 6
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
VENT TERMINATION
CLEARANCES
These instructions should be used as a
guideline and do not supersede local codes
in any way. Install venting according to local
codes, these instructions, the current National
Fuel Gas Code (ANSI-Z223.1) in the USA or
the current standards of CAN/CSA-B149.1 in
Canada. When planning your vent run refer
to the table in Figure 22 on Page 17.
Horizontal Vent Termination Clearances
The horizontal vent termination must have
a minimum of 3" (76 mm) clearance to any
overhead combustible projection of 2-1/2" (64
mm) or less (see Figure 3). For projections
exceeding 2-1/2" (64 mm), see Figure 3. For
additional vent location restrictions refer to
Figure 4 on Page 7.
Combustible Projection
extending more than
2.5 inches
24 in (610 mm)
3 in
(76 mm)
Combustible Projection
extending up to
2.5 inches
~
Power Vent Termination
Side Elevation View
Ventilated or Unventilated Soffit
Combustible
For recess allowances of power vent termination
into exterior walls, see Figure 24 on Page 19.
Figure 3: Horizontal Power Vent Termination Clearances to Combustibles
18 in
(457 mm)
6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 7
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
C = Clearance to permanently closed window. 9 in (229 mm) recommended to prevent window
D = Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 36 in (91.4 cm)
from center line of terminal.
E = Clearance to unventilated soffit.24 in (61 cm)24 in (61 cm)
F = Clearance to outside corner.5 in (12.7 cm)5 in (12.7 cm)
G = Clearance to inside corner.24 in (61 cm)36 in (91.4 cm)
H = Clearance to each inside of center line
extended above meter/regulator assembly.
= Clearance to service regulator vent outlet. 3 ft (91.4 cm) 3 ft (91.4 cm)
I
J = Clearance to non-mechanical air supply
inlet to building or combustion air inlet to
any other appliance.
K = Clearance to mechanical air supply inlet.3 ft (91.4 cm) above, if within 10 ft (3 m) horizontally.6 ft (1.83 m)
L = Clearance above paved sidewalk or paved
driveway located on public property.
M = Clearance under veranda, porch, deck, or
balcony.
In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Codes (latest editions).
In accordance with the current CAN/CSA-B149.1 Installation Code (latest editions).
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single-family dwellings and serves both dwellings.
Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
Figure 4
18 in (46 cm) 18 in (46 cm)
6 in (15.2 cm) for appliances < 10,000 BTU/hr (3kW);
9 in (23 cm) for appliances > 10,000 BTU/hr (3kW)
and < 50,000 BTU/hr (15kW);
12 in (30 cm) for appliances > 50,000 BTU/hr (15kW).
condensation.
24 in (61 cm)24 in (61 cm)
3 ft (91.4 cm) within a height of 15 ft above the
meter/regulator assembly.
6 in (15.2 cm) for appliances < 10,000 BTU/hr (3kW);
9 in (23 cm) for appliances > 10,000 BTU/hr (3kW)
and < 50,000 BTU/hr (15kW);
12 in (30 cm) for appliances > 50,000 BTU/hr (15kW).
7 ft (2.13 m) 7 ft (2.13 m)
18 in (46.0 cm) 18 in (46.0 cm)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
6 in (15.2 cm) for appliances < 10,000 BTU/hr (3kW);
12 in (30 cm) for appliances > 10,000 BTU/hr (3kW)
and < 100,000 BTU/hr (30kW);
36 in (91.4 cm) for appliances > 100,000 BTU/hr (30kW).
12 in (305 mm) recommended to prevent window
condensation.
3 ft (91.4 cm) within a height of 15 ft above the
meter/regulator assembly.
6 in (15.2 cm) for appliances < 10,000 BTU/hr (3kW);
12 in (30 cm) for appliances > 10,000 BTU/hr (3kW)
and < 100,000 BTU/hr (30kW);
36 in (91.4 cm) for appliances > 100,000 BTU/hr (30kW).
DE
V
V
X
K
7
Page 8
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
HEARTH EXTENSIONS (OPTIONAL)
Note: Hearth extensions are not required with this appliance.
Optional Indoor Hearth Extension
Combustible indoor hearth material may only be installed at or below
the base of the fireplace (see Figures 5 and 6).
Non-combustible indoor hearth material may be installed above the base
of the fireplace and may butt against the front face of the fireplace (see
Figures 5 and 6).
Also note the following:
• Combustible material may project beyond the sides of the fireplace
opening, as long as it is within the shaded area shown in Figure 9 on Page 9.
• Vertical installation clearances to combustible mantels vary according
to the depth of the mantel (see Figure 8 on Page 9).
• Non-combustible mantels may be installed at any height above the
appliance opening.
Optional Outdoor Hearth Extension
All outdoor hearth material (combustible and non-combustible) must
be installed a minimum of 6" (152 mm) below the base of the fireplace
(see Figure 6).
Also note the following:
• For vertical installation clearances to combustible outdoor mantels and
overhangs, see Page 30 and the instructions provided in the Outdoor
Installation Kit (required for all outdoor installations; see Page 32).
• Non-combustible outdoor mantels and overhangs may be installed at
any height above the appliance opening.
Indoor
Side
Fireplace
(side view)
Outdoor
Side
Finish combustible material
must be installed at or below
base of fireplace.
Finish non-combustible material may
butt against front face of fireplace.
Figure 5: Optional Indoor Hearth Extension
8
Floor
Panel
Indoor hearth extension:
Front Face
of Fireplace
Finish combustible material must be
installed at or below base of fireplace.
Finish non-combustible material may be
installed above base of fireplace and may
butt against front face of fireplace.
Figure 6: Optional Indoor and Outdoor Hearth Extensions
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
6" (152 mm)
minimum
Outdoor hearth extension:
All finish hearth material (combustible
and non-combustible) must be at least
6" (152 mm) below base of fireplace.
Page 9
7 (178)
2
(51)
4
(102)
6
(152)
8
(203)
10
(254)
12
(305)
9 (229)
13 (330)
17 (432)
15 (381)
11 (279)
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
MINIMUM CLEARANCES TO COMBUSTIBLES
Appliance and Vent Clearances
The appliance is approved with zero clearance to combustible materials
on both sides (as detailed in Table 5), with the following exceptions:
• When the unit is installed with one side flush with a wall, the wall on the
other side of the unit must not extend beyond the front edge of the unit.
• In addition, when the unit is recessed, the side walls surrounding the
unit must not extend beyond the front edge of the unit (see Figure 2 on Page 5).
MINIMUM CLEARANCES TO COMBUSTIBLES
Back / Sides
0 in (0 mm) Spacers
Top Spacers0 in (0 mm)
Floor0 in (0 mm)
Unit Bottom to Ceiling72.0 in (1829 mm)
Vertical Vent Pipe1.0 in (25.4 mm)
Horizontal Vent PipeTop: 3.0 in (76.2 mm)
Sides: 1.0 in (25.4 mm)
Bottom: 1.0 in (25.4 mm)
SERVICE CLEARANCES
Front3 ft (0.9 m)
Table 5
3" (76 mm) above any horizontal/inclined vent component.
See Step 1 ("FRAMING") on Page 10 for clearance requirements to
the nailing flanges on each side of the unit and any adjacent screw
heads.
The appliance should be mounted on a fully supported base extending
the full width and depth of the unit. The appliance may be located on
or near conventional construction materials; however, if installed on
combustible materials, such as carpeting, vinyl tile, etc., a metal or wood
barrier covering the entire bottom surface must be used.
Do NOT insulate space between
appliance and area above it.
Combustible
Enclosure (or Shelf)
~
Min. 3"
~
(76 mm)
Min. 90"
(2287 mm)
Indoor/
Outdoor
Min. 2 ft vertical
vent section
and one 90-degree
elbow required
Min. 91.5"
(2324 mm)
Indoor/Outdoor
Top of
Fireplace
2 x 4
Figure 7: Min. Height of Combustible Enclosure
Mantel Depth
to bottom of mantel
Distance from top of appliance
Side View
Min. Height of Combustible Enclosure
To provide for the lowest possible combustible enclosure (or shelf)
surface, the venting should be routed in a way to minimize obstructions
to the space above the appliance. Do not insulate the space between the
appliance and the area above it (see Figure 7).
Wall Finishes / Surrounds / Mantels
Note: Combustible wall finish materials and/or surround materials must
not be allowed to encroach the area defined by the appliance front faces
(black sheet metal). Never allow combustible materials to be positioned
in front of or overlapping the appliance face. See Pages 29 and 30.
Non-combustible materials, such as surrounds and other appliance trim,
may be installed on the appliance front face only if they do NOT cover
any portion of the removable glass panel.
Vertical installation clearances to combustible mantels vary according
to the depth of the mantel. See Figure 8. Mantels constructed of noncombustible materials may be installed at any height above the appliance
opening.
Note: Use high-temperature paint (rated 175°F or higher) on the underside
of the mantel.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Inches
(millimeters)
Top of Appliance
Figure 8: Combustible Mantel Clearances
Minimum Distance to Unprotected Side Wall
At 14" minimum
side wall clearance,
a combustible
wall can project
to any length.
At 8-1/4" side
wall clearance,
a combustible
wall can project
12" maximum.
Gray area
is “safe
zone”
14"
(356 mm)
8.25"
(209 mm)
0.5"
(13 mm)
45°
Protected wall
shown in white
Top View of Fireplace
5 in
(127 mm)
12 in
(305 mm)
17 in
(432 mm)
Figure 9: Side Wall Clearances
Combustible materials
are allowed in gray “safe
zone” illustrated here.
Combustible walls are
shown in black.
Protected wall is shown
in white.
Combustible material
may project beyond
the side of the fireplace
opening if it is within
the gray "safe zone"
illustrated here.
9
Page 10
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
PRE-INSTALLATION STEPS
The appliance is shipped with all gas controls
and components installed and pre-wired.
1. Remove the shipping carton, exposing the
glass door on the control side.
2. Remove glass door assembly (see detailed
instructions on Page 27).
WARNING
Failure to position the parts in
accordance with these diagrams
or failure to use only parts specifically approved with this appliance
may result in property damage or
personal injury.
AVERTISSEMENT
Risque de dommages ou de
blessures si les pièces ne sont
pas installées conformément à
ces schémas et ou si des pièces
autres que celles spécifiquement
approuvées avec cet appareil sont
utilisées.
TYPICAL INSTALLATION
SEQUENCE
The typical sequence of installation is outlined
below.
Note: Each installation is unique and
may result in variations to the steps
described herein.
See the page numbers referenced in the following steps for detailed procedures.
Step 1. FRAMING (Page 10): Construct
appliance framing. Position
appliance within framing, and
secure with nailing brackets.
Step 2. ROUTE GAS LINE (Page 13):
Route gas supply line to right side
(when viewed from control side of
appliance).
Step 3.INSTALL VENT SYSTEM (Page 13):
install vent system and exterior
termination.
Step 4. FIELD WIRING (Page 20): Connect
120 Vac electrical power to the
appliance receptacle.
Step 5. REMOVE GLASS DOOR ASSEMBLY
(Page 22).
Step 6. CONNECT GAS LINE (Page 23):
Make connection to gas supply.
Step 7. INSTALL FIREBOX LINER PANELS
(Page 23).
Step 8. VERIFY APPLIANCE OPERATION
(Page 23).
Step 9. INSTALL VOLCANIC STONE,
GLOWING EMBERS, AND LOGS
(Page 24).
Step 10. INSTALL GLASS DOORS, MESH
PULL SCREENS, AND MODESTY
PANEL (Page 27).
Step 11. BURNER ADJUSTMENTS (Page
28): Adjust burner air shutter to
ensure proper flame appearance.
Frame these appliances as illustrated on Page 11.
All framing details must allow for a minimum
clearance to combustible framing members as
shown on Page 9.
If the appliance is to be elevated above floor
level, a solid continuous platform must be
constructed below the appliance.
Headers may be in direct contact with the
appliance top spacers, but must not be supported by them or notched to fit around them.
All construction above the appliance must be
self-supporting; DO NOT use the appliance for
structural support.
Secure the fireplace to the side framing members
using the unit's nailing flanges — one top and
bottom on each side of the fireplace front (see
Figure 10). Use 8d nails or their equivalent.
Securing Unit to Framing
by Nailing Flanges
Use Top Flange for
1/2” Thick Drywall
Front of Fireplace
Use Center Flange
for Flush Mount
Use Bottom Flange for
5/8” Thick Drywall
Left Side Front Corner of Fireplace Shown
(Same requirements for right side)
Note: The nailing flanges, combustible
members and screw heads in areas directly
adjacent to the nailing flanges are EXEMPT
from the 1/2-inch clearance to combustible
requirements for the firebox outer wrapper.
Combustible framing may be in direct
contact with the nailing flanges and may
be located closer than 1/2 inch from screw
heads and the firebox wrapper in areas
adjacent to the nailing flanges. Frame the
opening to the exact dimensions specified
in the framing details of the Installation
Instructions.
Figure 10
10
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 11
D
B
C
Inches
(millimeters)
A
12-1/8
(308)
5-1/8
(130)
10-1/2
(267)
C
Inches
(millimeters)
1-1/2
(38)
D
A
B
E
~
12-1/8
(308)
5-1/8
(130)
10-1/2
(267)
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
FRAMING DIMENSIONS: See-Through Power Vent
Framing should be constructions of 2x4 or larger lumber.
A
in52-1/1647-5/1699-1/226-5/166
(mm)(1322)(1202)(2527)(668)(152)
B
C
D
E
Dimension B is from fireplace base to top framing member.
Dimension C is from fireplace base to centerline of horizontal vent pipe.
Minimum vent framing: Adaptor plus 4 ft vertical vent and one 90-degree elbow.
For other venting configurations, see Step 3, INSTALL VENTING SYSTEM.
1/2-inch board for platform (shown in gray).
Dimension E is a 6-inch clearance from fireplace base to outdoor surface (e.g., deck, patio, lanai)
that is required as a moisture barrier (not a combustible clearance) on outdoor side only.
Figure 11
INDOOR SIDE*
*For indoor/outdoor installations, the control side
of the fireplace must be installed on the indoor side.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Outdoor Surface (e.g., deck, patio, lanai)
OUTDOOR SIDE*
11
Page 12
13-3/32
(333)
25-9/32
(642)
7-5/16
(186)
5-13/32
(137)
8"/11"
*
Vent/Intake
Top View
inches
(millimeters)
*Adaptor with Probe required to transition from 8"/11" fireplace vent collar to 4-1/2"/7-1/2" venting.
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Adaptor/Probe assembly (cat. no. H8313) required to
transition from fireplace vent collar to vent pipe.
34-3/4
(883)
8" Inner / 11" Outer
4-1/2” Inner / 7-1/2” Outer
5-3/32
(130)
12
46-19/32
(1184)
19-17/32
(496)
Figure 12
7 (178)
Control Switch
Wires Knock-Out
Left Side View
Gas Inlet
J-Box
29-19/32
(752)
Fireplace Dimensions
(shown with Outdoor Kit installed)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
50-1/2
(1283)
Front View (opposite valve access side)
41-1/2
(1054)
33-3/4
(857)
Page 13
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Step 2. ROUTE GAS LINE
NOTICE: For indoor/outdoor installations,
the CONTROL SIDE of the fireplace must
be installed on the INDOOR side.
Route a 1/2" (13 mm) gas line along the inside
of the right side framing as shown in Figures 13 and 14. Gas lines must be routed, constructed
and made of materials that are in strict accordance with local codes and regulations.
All appliances are factory-equipped with a
flexible gas line connector and 1/2 inch shutoff
valve (see Step 6 on Page 23).
The incoming gas line should be piped into the
valve compartment and connected in one of the
two methods as shown in Figure 35 on Page 23.
Right Side Front
Corner Of Fireplace Framing
19-1/2"
(495 mm)
7”
(178 mm)
Right Side Front Corner
(Valve Side) of Fireplace Framing
Figure 13: INDOOR / INDOOR
1-1/2”
(38 mm)
19-1/2"
7”
(178 mm)
Right Side Front Corner
(Valve Side) of Fireplace Framing
Figure 14: INDOOR / OUTDOOR
(495 mm)
Proper Sizing of Gas Line
Properly size and route the gas supply line
from the supply regulator to the area where the
appliance is to be installed per requirements
outlined in the National Fuel Gas Code, NFPA
54 - latest edition (USA) or CAN/CSA-B149.1
- latest edition (Canada).
IMPORTANT: It is critical that a licensed
installer perform this step strictly per
NFPA.
Never use galvanized or plastic pipe. Refer
to Table 6 for proper sizing of the gas supply line, if black iron pipe is being used. Gas
lines must be routed, constructed and made
of materials that are in strict accordance with
local codes and regulations. We recommend
that a qualified individual such as a plumber or
gas fitter be hired to correctly size and route
the gas supply line to the appliance. Installing
a gas supply line from the fuel supply to the
appliance involves numerous considerations of
materials, protection, sizing, locations, controls,
pressure, sediment, and more. Certainly no one
unfamiliar and unqualified should attempt sizing
or installing gas piping.
Note:
• All appliances are factory-equipped with
a flexible gas line connector and 1/2 inch
shutoff valve (see Figure 35 on Page 23).
• See Massachusetts Requirements on Page
4 for additional requirements for installations
in the state of Massachusetts in the USA.
• The gas supply line should not be connected
to the appliance until Step 6 (Page 23).
• A pipe joint compound rated for gas should be
used on the threaded joints. Ensure propane
resistant compounds are used in propane
applications. Be very careful that the pipe
compound does not get inside the pipe.
• It is recommended to install a sediment trap
in the supply line as close as possible to
the appliance (see Figure 35 on Page 23).
Appliances using Propane should have a
sediment trap at the base of the tank.
• Check with local building ofcial for local
code requirements (i.e. are below grade
penetrations of the gas line allowed?, etc).
Step 3. INSTALL VENT SYSTEM
General Information
These instructions should be used as a guideline and do not supersede local codes in any
way. Install venting according to local codes,
these instructions, the current National Fuel
Gas Code (ANSI-Z223.1) in the USA or the
current standards of CAN/CGA-B149.1 and
-B149.2 in Canada.
These fireplaces are designed, tested and
listed for operation and installation with,
and only with, Secure Vent™ (SV4.5) DirectVent System Components, manufactured by
Security Chimneys International. These approved vent system components are labeled
for identification. DO NOT use any other
manufacturer's vent components with these
appliances.
Ensure clearances are in accordance with
local installation codes and the requirements
of the gas supplier.
Dégagement conforme aux codes d’installation locaux et aux exigences du foumisseunde gaz.
Use only approved venting components. See
Approved Vent Components on Page 2.
These fireplaces must be vented directly
to the outside.
The vent system may not service multiple
appliances, and must never be connected to a
flue serving a solid fuel burning appliance. The
vent pipe is tested to be run inside an enclosed
wall (such as a chase). There is no requirement
for inspection openings in the enclosing wall at
any of the joints in the vent pipe.
Venting System
With the appliance secured in framing, determine vent routing and identify the exterior
termination location. The following sections
describe horizontal (exterior wall) vent applications. A list of approved venting components
is shown on Page 32.
Schedule 40, Black Iron Pipe
Inside Diameter (Inches)
Schedule 40 Pipe
Length (feet)
0-101/23/8
10-401/21/2
40-1001/21/2
100-1503/41/2
150-2003/41/2
Natural
Gas
Table 6
Propane
Gas
IMPORTANT NOTE REGARDING
PROPANE INSTALLATIONS
Using a propane tank smaller than
100 lbs may create pressure loss and
insufficient fuel delivery, which can
cause sooting, severe delayed ignition,
or other malfunctions (ref. NPFA 58).
Any damage as a result of insufficient
tank size or other improper installation is
NOT covered under the limited warranty.
13
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 14
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
1
1
2
3
5
4
6
7
Vent Restrictor
The adaptor/probe assembly for this appliance has a pre-installed vent restrictor with a
1-3/4" hole in the center (see Figure 15). This
pre-installed vent restrictor is not for use with
any venting configuration for this fireplace
model and must be replaced with one of the two
provided vent restrictors, as described below.
Vent Restrictor Size Guidelines
• For venting systems 30 ft in length or less,
replace the factory installed vent restrictor
with the provided vent restrictor with a 1-5/8" dia. hole.
• For venting systems greater than 30 ft in
length, replace the factory installed vent
restrictor with the provided vent restrictor
with a 2-1/4" dia. hole.
Vent Restrictor Installation Instructions
Install the appropriate vent restrictor (as
described above) into the adaptor/probe
assembly per the instructions in Figure 15.
Power Vent Components
Locate the fireplace as per the instructions in this manual. Make the following modifications to
add the components used with the Power Vent Kits. This kit can only be used in conjunction with
“Direct-Vent” series electronic fireplaces. This installation must conform with local codes or, in
the absence of local codes, with the Natural Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural
Gas and Propane Installation Code, CSA B149.1.
CAUTION: This Power Vent Kit cannot be used with Millivolt appliances. Use kit only with
the Electronically controlled fireplaces listed for its use as shown in this document.
1. Turn the adaptor/probe assembly upsidedown, as shown.
2. Remove the four screws securing the
vent restrictor in place. Lift out the vent
restrictor.
3. Install the appropriate vent restrictor,
using the four screws previously
removed. See “Vent Restrictor Size
Guidelines,” above.
9Insulated 1/4” Male Terminal4
8
9
Figure 16: Power Vent Kit Components
Figure 15: Vent Restrictor
14
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 15
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
621426384
T
OOOOO
TTTTT
AAAAA
LLLLL
QQQQQ
TTTTT
YYYYY
noitceSteN
)sehcni(htgneL
2/1-42/1-012/1-222/1-432/1-64
tneVfothgieHsnoitceStneVforebmuN
sehcnitf
5.4573.0100001
957.0200002
5.01578.0010001
5152.1110002
5.22578.1001001
5.13526.2030003
5.43578.2000101
5.73521.3111003
5.34526.3021003
5457.3002002
5.64578.3000011
1552.4100012
5.55526.4012003
7557.4001102
5.76526.5003003
9657
.5000202
5.37521.6100203
5.97526.6010203
1857.6000112
5.19526.7002013
3957.7000022
5.79521.8100023
5.301526.8000303
8019100304
71157.9105006
5.811578.9110305
6215.01001304
5.031578.01101305
53152.11006006
5.931526.11000033
5.241578.11100405
44121100034
5.451578.21110035
5.061573.31020035
5.271573.41000505
77157.41100506
6815.51000044
5.691573.61010045
70252.71000606
5.112526.71100607
5.712521.81010607
5.922521.91001607
5.23
2573.91000055
5.142521.02000707
6425.02100708
25212010708
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
621426384
T
OOOOO
TTTTT
AAAAA
LLLLL
QQQQQ
TTTTT
YYYYY
noitceSteN
)sehcni(htgneL
2/1-42/1-012/1-222/1-432/1-64
tneVfothgieHsnoitceStneVforebmuN
sehcnitf
5.4573.0100001
957.0200002
5.01578.0010001
5152.1110002
5.22578.1001001
5.13526.2030003
5.43578.2000101
5.73521.3111003
5.34526.3021003
5457.3002002
5.64578.3000011
1552.4100012
5.55526.4012003
7557.4001102
5.76526.5003003
9657
.5000202
5.37521.6100203
5.97526.6010203
1857.6000112
5.19526.7002013
3957.7000022
5.79521.8100023
5.301526.8000303
8019100304
71157.9105006
5.811578.9110305
6215.01001304
5.031578.01101305
53152.11006006
5.931526.11000033
5.241578.11100405
44121100034
5.451578.21110035
5.061573.31020035
5.271573.41000505
77157.41100506
6815.51000044
5.691573.61010045
70252.71000606
5.112526.71100607
5.712521.81010607
5.922521.91001607
5.23
2573.91000055
5.142521.02000707
6425.02100708
25212010708
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
621426384
T
O
T
A
L
Q
T
Y
noitceSteN
)sehcni(htgneL
2/1-42/1-012/1-222/1-432/1-64
tneVfothgieHsnoitceStneVforebmuN
sehcnitf
67232000808
97252.32000066
5.082573.32100809
5.982521.42010067
5.103521.52001067
5.013578.52000909
5.523521.72000077
0335.72100078
54357.8200001001
5.943521.9210001011
27313000088
5.973526.1300011011
5.814578.43000099
56457.8300000101
5.574526.9301000111
0840411000111
2941410100121
5.994526.1400010111
4052410010121
5.115526.2400001111
5.025573.3402011141
13552.4402201151
5.835578.4410021141
94557.5410211151
8555.6400002121
5.265578.6410002131
5.865573.7401002131
37557.7411002141
5.085573.8400102131
5.985521.9401220151
5.595526.9411102151
5.406573.0500003131
51652.1501003141
5.526521.2502003151
5.136526.2510103151
5.736521.3501103151
15652.4500004141
5.556526.4510004151
2766502004161
8765.6510104161
5.886573.7511104171
5.796521.8500005151
2075.8510005161
5.217573.9511005171
0270600105161
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
621426384
T
O
T
A
L
Q
T
Y
noitceSteN
)sehcni(htgneL
2/1-42/1-012/1-222/1-432/1-64
tneVfothgieHsnoitceStneVforebmuN
sehcnitf
67232000808
97252.32000066
5.082573.32100809
5.982521.42010067
5.103521.52001067
5.013578.52000909
5.523521.72000077
0335.72100078
54357.8200001001
5.943521.9210001011
27313000088
5.973526.1300011011
5.814578.43000099
56457.8300000101
5.574526.9301000111
0840411000111
2941410100121
5.994526.1400010111
4052410010121
5.115526.2400001111
5.025573.3402011141
13552.4402201151
5.835578.4410021141
94557.5410211151
8555.6400002121
5.265578.6410002131
5.865573.7401002131
37557.7411002141
5.085573.8400102131
5.985521.9401220151
5.595526.9411102151
5.406573.0500003131
51652.1501003141
5.526521.2502003151
5.136526.2510103151
5.736521.3501103151
15652.4500004141
5.556526.4510004151
2766502004161
8765.6510104161
5.886573.7511104171
5.796521.8500005151
2075.8510005161
5.217573.9511005171
0270600105161
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
VENT SECTION LENGTHS
Determine the number of straight vent sections
required. 4-1/2" (114 mm), 10-1/2" (267 mm),
22-1/2" (572 mm), 34-1/2" (876 mm) and 461/2" (1181 mm) net section lengths are available.
Refer to the Vent Section Length Chart.
Vertical (Offset) Installation
Analyze the vent routing and determine the
quantities of vent sections and number of
elbows required. Refer to Figures 21 and 22 on Page 17 showing vent run requirements to
aid in selecting the type of vertical installation
desired. Vent sections are available in net lengths
of 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2"
(572 mm), 34-1/2" (876 mm) and 46-1/2" (1181
mm). Refer to the Vent Section Length Chart
for an aid in selecting length combinations.
Elbows are available in 90° and 45° configurations. Refer to Figure 20 on Page 16 for the
SV4.5 E45 and SV4.5 E90 elbow dimensional
specifications.
Where required, a telescopic vent section (SV4.5LA) may be used to provide the installer with an option in installing in tight and
confined spaces or where the vent run made
up of fixed length pieces develops a joint in a
undesirable location, or will not build up to the
required length. The SV4.5LA Telescopic Vent
Section has an effective length of from 1-1/2"
(38 mm) to 6-3/4" (171 mm). The SV4.5LA is
fitted with a dimpled end (identical to a normal
vent section component) and a plain end with
3 pilot holes. Slip the dimpled end over the
locking channel end of a standard SV4.5 vent
component the required distance and secure
with three screws.
Maintain a minimum 1" (25 mm) clearance
to combustible materials for all vertical elements. Clearances for all horizontal elements
are 3" (76 mm) on top, 1" (25 mm) on sides
and 1" (25 mm) on the bottom.
Note: Convert inches into metric equivalent
measurement, as follows:
Millimeters (mm) = Inches x 25.4
Centimeters (cm) = Inches x 2.54
Meters (M) = Inches x .0254
15
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 16
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
7-5/8”
(194 mm)
4-13/16
(122 mm)
A.Frame ceiling opening. Use a plumb line
from the ceiling above the appliance to locate
center of the vertical run. Cut and/or frame an
opening, 10-1/2" x 10-1/2" (267 mm x 267
mm) inside dimensions, about this center mark
(Figure 17).
Min. 10-1/2"
(267 mm)
Min. 10-1/2"
(267 mm)
Plumb Bob
Ceiling
Framing
Figure 17: Ceiling Opening Framing
B. Attach adaptor (with probe) to appliance
collar. Secure Vent™ SV4.5 direct-vent sys-
tem components are unitized concentric pipe
components featuring positive twist lock connections (see Figure 18).
All of the appliances covered in this document
are fitted with collars having locking inclined
channels. The dimpled end of the adaptor fits
over the appliance collar to create the positive
twist lock connection.
Align the dimple (four places) of the
upper vent section with the opening
of the locking incline channel on
the lower vent section or appliance
collar. Twist vent component clockwise to engage and seal until arrow
Arrow
and dimple align.
Dimple
Locking Incline
Channel
The unitized design of the Secure Vent components will engage and seal both the inner
and outer pipe without the need for sealant or
screws. If desired a #6 x 1/2" screw may be
used at the joint, but it is not required as the
pipe will securely lock when twisted.
C. Attach vent components to each other. Other
vent sections may be added to the previously
installed section in accordance with the requirements shown in Figures 21 and 22 on Page 17.
To add another vent component to a length of
vent run, align the dimpled end over the inclined
channel end of the previously installed section,
adjusting the radial alignment until the four
locking dimples are aligned with the inlets of
the four incline channels of the previous section.
Push the vent component against the previous section until it fully engages, then twist
the component clockwise running the dimples
down and along the incline channels until they
seat at the end of the channels. This seating
position is indicated by the alignment of the
arrow and dimple as shown in Figure 18.
D. Install firestop/spacer at ceiling. When
using Secure Vent, use SV4.5VF firestop/spacer
at ceiling joists. If there is living space above
the ceiling level, the firestop/spacer must be
installed on the bottom side of the ceiling. If
attic space is above the ceiling, the firestop/
spacer must be installed on the top side of the
joist. Route the vent sections through the framed
opening and secure the firestop/spacer with
8d nails or other appropriate fasteners at each
corner. Remember to maintain 1" (25 mm)
clearance to combustibles, framing members,
and attic or ceiling insulation when running
vertical chimney sections. Attic insulation
shield (H3907) may be used to obtain the
required clearances indicated here. See
installation accessories on Page 32. The gap
between the vent pipe and a vertical firestop
can be sealed with non-combustible caulking.
E. Support the vertical vent run sections.
Note: Proper venting support is very important.
The weight of the vent must not be supported
by the fireplace in any degree.
Support the vertical portion of the venting
system every 8 feet (2.4 m) above the fireplace
vent outlet. One method of support is by utilizing field provided support straps (conventional
plumber's tape). Secure the plumber's tape to
the framing members with nails or screws.
Strap the tape around the vent, securing the
ends of the tape to the framing. If desired,
sheet metal screws #6 x 1/2" length may be
used to secure the support straps to the vent
pipe (see Figure 19).
F. Change vent direction to horizontal/inclined
run. At transition from or to a horizontal/inclined
run, install the SV4.5 E45 and SV4.5 E90 elbows
in the same manner as the straight vent sections. The elbows feature a twist section to
allow them to be routed about the center axis
of their initial collar section to align with the
required direction of the next vent run element.
Twist elbow sections in a clockwise direction
only so as to avoid the possibility of unlocking
any of the previously connected vent sections
(see Figures 18 and 20).
8-1/8"
(206 mm)
Swivel Joint
(360° swivel)
SV4.5E45
45° Elbow)
Swivel Joint
(360° swivel)
SV4.5E90
90° Elbow)
Figure 20
G. Continue installation of horizontal/inclined
sections. Continue with the installation of the
straight vent sections in horizontal/inclined run
as described in Step C. Install support straps
every 3' (914 mm) along horizontal/inclined
vent runs using conventional plumber’s tape
(see Page 17, Figure 21).
Connected Vent
Sections
Adaptor on Appliance Collar
or Vent Section
Figure 18
To attach a vent component to the adaptor on
appliance collar, align the dimpled end over the
adaptor collar, adjusting the radial alignment
until the four locking dimples are aligned with the
inlet of the four inclined channels on the collar
(refer to Figure 18). Push the vent component
against the collar until it fully engages, then twist
the component clockwise, running the dimples
down and along the incline channels until they
seat at the end of the channels.
16
Arrow
Blocking
Support Straps
(plumber’s tape)
Max.
8 ft (2.4 m)
Min. 0" (0 mm)
clearance
to spacers
Figure 19
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
NOTICE: It is important to install
horizontal runs on a steady, (i.e., no
“dips”), slightly positive incline of
approximately 1/4 inch rise-per-foot (20
millimeters rise-per-meter) horizontal,
in a direction away from the fireplace.
(Slightly smaller rise-per-foot run ratios
are acceptable.) Use a carpenter’s level
to measure from a constant surface, and
adjust support straps as necessary.
It is important to maintain the required clearances to combustibles: 1" (25 mm) at all sides
for all vertical runs; and 3" (76 mm) at the
top, 1" (25 mm) at sides, and 1" (25 mm) at
the bottom for all horizontal/inclined runs.
Page 17
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
VENT FIGURES
Note:
• Secure Vent™ components (rigid vent pipe and terminal) are shown in the gures.
• Two 45 degree elbows may be used in place of one 90 degree elbow.
• SV4.5VF (Secure Vent) restop/spacer must be used anytime vent pipe passes through a
combustible floor or ceiling. SV4.5HF (Secure Vent) firestop/spacer must be used anytime vent
pipe passes through a combustible wall.
Power Vent
Termination
Exterior
Wall
Horizontal / Inclined Run
SV4.5L 6 / 12 / 24 / 36 / 48
Vent Sections
Firestop / Spacer
Maximum Horizontal
Venting 110 Feet.
Up to 6 Elbows
Support
Brackets
Ceiling
Adaptor/Probe
Assembly
(required)
NOTICE: It is important to install
horizontal runs on a steady, (i.e., no
“dips”), slightly positive incline of
approximately 1/4 inch rise-per-foot (20
millimeters rise-per-meter) horizontal,
in a direction away from the fireplace.
(Slightly smaller rise-per-foot run ratios
are acceptable.) Use a carpenter’s level
to measure from a constant surface, and
adjust support straps as necessary.
Building
Support
Framing
SV4.5E90
Elbow
Vertical Rise
66 Feet Max.
4 Feet Min.
Minimum
Vent Run
Horizontal
10 Feet
Adaptor/Probe
Assembly
(required)
Power Vent
Termination
Exterior
Wall
Figure 21: Typical Power Vent Routing
POWER VENT VENTING CHART
Maximum Number Of Elbows—6
Maximum Feet Of RunA + B110 feet
Minimum Horizontal RunB10 feet
Minimum Vertical RunA
Maximum Vertical RiseA66 ft
Adaptor plus 4 ft (min.)
Vertical Vent and 90° Elbow
MINIMUM CLEARANCES TO COMBUSTIBLES
Vertical Vent Pipe1.0 in. (25.4 mm)
Horizontal Vent Pipe
Top - 3.0 in. (76.2 mm)
Sides - 1.0 in. (25.4 mm)
Bottom - 1.0 in. (25.4 mm)
Fireplace
Floor
B
A
Adaptor/Probe
Assembly
(Required)
Figure 22
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
17
Page 18
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
HORIZONTAL (OUTSIDE WALL)
TERMINATION SYSTEM
See Figures 21 and 22 on Page 17 illustrating
the various horizontal venting configurations
that are possible for use with these appliances.
The table in Figure 22 on Page 17 shows each
system’s minimum and maximum vertical and
horizontal length values that can be used to
design and install the vent components in a
variety of applications.
The horizontal vent system terminates through
an outside wall. Building Codes limit or prohibit
terminating in specific areas. Refer to Figure 3
on Page 6 for location guidelines.
Secure Vent™ SV4.5 direct-vent system com-
ponents are unitized concentric pipe components featuring positive twist lock connection,
(refer to Figure 18on Page 16). All of the
appliances covered in this document are fitted
with collars having locking inclined channels.
The dimpled end of the vent components fit
over the appliance collar to create the positive
twist lock connection.
A.Plan the vent run.
Analyze the vent routing and determine the
types and quantities of sections required
4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2"
(572 mm), 34-1/2" (876 mm) and 46-1/2"
(1181 mm) net section lengths are available.
Make allowances for elbows as indicated in
Figure 20 on Page 16.
Maintain a minimum 1" (25 mm) clearance
to combustibles on the vertical sections.
Clearances for the horizontal runs are; 3"
(76 mm) on top, 1" (25 mm) on sides, and
1" (25 mm) at the bottom.
B. Frame exterior wall opening.
Locate the center of the vent outlet on the
exterior wall according to the dimensions
shown in Figure 11 on Page 11.
Cut and/or frame an opening, 10-1/2" x 12-
1/8" (267 mm x 308 mm) inside dimensions,
with 7-1/2" above center and 5-5/8" below
center.
C.Frame ceiling opening.
If the vertical route is to penetrate a ceiling,
use plumb line to locate the center above
the appliance. Cut and/or frame an opening, 10-1/2" x 10-1/2"(267 mm x 267 mm)
inside dimensions, about this center (refer
to Figure 17 on Page 16).
18
D. Attach vent components to appliance.
To attach a vent component to the appliance
collar, align the dimpled end over the collar,
adjusting the radial alignment until the four
locking dimples are aligned with the inlets of
the four incline channels on the collar (refer to Figure 18 on Page 16).
Push the vent component against the collar
until it fully engages, then twist the component clockwise, running the dimples down
and along the incline channels until they
seat at the end of the channels. The unitized
design of the Secure Vent components will
engage and seal both the inner and outer pipe
elements with the same procedure. Sealant
and securing screws are not required.
E. Attach vent components to each other.
Other vent sections may be added to the
previously installed section in accordance
with the requirements of the vent tables.
To add another vent component to a length
of vent run, align the dimpled end of the
component over the inclined channel end of
the previously installed section, adjusting the
radial alignment until the four locking dimples
are aligned with the inlets of the four incline
channels of the previous section. Push
the vent component against the previous
section until it fully engages, then twist the
component clockwise running the dimples
down and along the incline channels until they
seat at the end of the channels. This seating
position is indicated by the alignment of
the arrow and dimple as shown in Figure 18 on Page 16.
F. Install firestop/spacer at ceiling.
When using Secure Vent, use SV4.5VF fire-
stop/spacer at ceiling joists. If there is living
space above the ceiling level, the firestop/
spacer must be installed on the bottom side
of the ceiling. If attic space is above the ceiling, the firestop/ spacer must be installed
on the top side of the joist. Route the vent
sections through the framed opening and
secure the firestop/spacer with 8d nails or
other appropriate fasteners at each corner.
Remember to maintain 1" (25 mm) clear-
ance to combustibles, framing members,
and attic or ceiling insulation when running
vertical chimney sections.
G. Support the vertical run sections.
On the vertical run, support the venting
system every 8 feet (2.4m) above the fireplace vent outlet with field provided support
straps (Plumber's tape). Attach the straps
to the vent pipe and secure to the framing
members with nails or screws. See Figure 19on Page 16.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
H. Change vent direction.
At transition from or to a horizontal/inclined
run, install the SV4.5E45 and SV4.5E90
elbows in the same manner as the straight
vent sections. The elbows feature a twist
section to allow them to be routed about the
center axis of their initial collar section to
align with the required direction of the next
vent run element. Twist elbow sections in
a clockwise direction only so as to avoid
the possibility of unlocking any of the
previously connected vent sections (see
Figures 18 and 20 on Page 16).
I. Continue installation of horizontal/inclined
sections.
Continue with the installation of the straight
vent sections in horizontal/inclined run as
described in Step E. Install support straps
every 3 feet (1914 mm) along horizontal/
inclined vent runs using conventional
plumber’s tape.
See Figure 21 on Page 17.
NOTICE: It is important to install
horizontal runs on a steady, (i.e., no
“dips”), slightly positive incline of
approximately 1/4 inch rise-per-foot (20
millimeters rise-per-meter) horizontal,
in a direction away from the fireplace.
(Slightly smaller rise-per-foot run ratios
are acceptable.) Use a carpenter’s level
to measure from a constant surface, and
adjust support straps as necessary.
Installing Power Vent Termination
J. Assemble vent run to exterior wall.
If not previously measured, locate the cen-
ter of the vent on the exterior wall. Prepare
an opening as described in this manual.
Assemble the vent system to a point where
the terminus of the last section is within 8
inches of the outside wall surface where
the power vent is to be mounted (refer to
Figure 24 on Page 19).
If the terminus of the last section is not
within this distance, use the telescopic vent section SV4.5LA, as the last vent section.
For wall thicknesses greater than that shown
in Figure 24 on Page 19, refer to Table 8 (Page 19) for the additional venting components needed (in addition to the termination
and adaptor) for a particular range of wall
thicknesses.
K.Attach termination adaptor.
Attach the adaptor (SV4.5RCH, provided
with the power vent kit) to the vent section
telescoping vent section, or elbow, as shown
in Figures 23 and 24 on Page 19 in the same
manner as any SV4.5 vent component.
Page 19
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
L.Install Firestop/Spacer at exterior wall.
Install SV4.5HF Firestop/Spacer, provided
with the power vent kit, over the opening at
the exterior side of the framing, long side
up, with the 3 inch spacer clearance at the
top as shown in Figure 23, and nail into
place.
(The Firestop/Spacer may also be installed
over the opening at the interior side of the
framing).
M.Install the Power Vent termination.
For the last step, from outside the exterior
wall, slide the collars of the termination onto
the adaptor (the outer inside the outer and
the inner outside the inner) until the termination seats against the exterior wall surface to which it will be attached. Orient the
housing of the termination with the arrow
pointed upwards. Secure the termination
to the exterior wall. The termination must
not be recessed into the exterior wall or
siding by more that the 1-1/4” (32 mm) as
shown in Figure 24.
The Power Vent termination has been
designed to perform in a wide range of
weather conditions. Our terminations meet
or exceed industry standards.
When selecting the location of your termination, do not place the termination
where water from eaves and adjoining
roof lines may create a heavy flow of
cascading water onto the terminations. If
the termination must be placed where the
possibility of cascading water exists, it is
the responsibility of the builder to direct
the water away from the termination cap
by using gutters or other means.
Take care to carefully follow the Installation Instructions for the termination,
including the use of silicone caulking
where required.
Firestop/Spacer (SV4.5HF) shown on the
exterior side of the wall. It may also be
installed on the interior side.
7"
5-1/8"
(130 mm)
(178)
12-1/8"
(308 mm)
Termination
Adaptor
SV4.5RCH
6 to 48 inch Vent Section, Telescopic vent
section, Elbow or Appliance Collar
10-1/2"
(267 mm)
NOTE: Centerline of Vent Piping is
NOT the Same as the Centerline of
the Frame Opening.
Base of Appliance
See Figure 10 on Page 10 for Minimum
Distance to Base of Appliance
Figure 23: Installing Power Vent Horizontal Termination
*Use silicone caulking to
seal the top and sides of
the termination, up to the
underlayment, stucco, or
masonry wall surface.
Siding
Caulk*
Caulk*
Stucco
Maximum Extent of Vent Run
Sections Relative to Exterior
Surface of Framing
**For thicknesses greater
than 9-1/4”, see Table 8
Interior Surface of
Finished Wall
Last Vent Section.
Use Telescopic Vent
Section (SV4.5LA),
If Necessary
Power Vent
Termination
Termination
Adaptor
SV4.5RCH
Power Vent
Termination
3"
(76 mm)
1"
(25.4 mm)
Maximum wall thickness
9-1/4 in.(235 mm)**
Exterior Surface of Siding
Exterior Surface of Framing
6 in. to 9-1/4 in.
(152 to 235 mm)**
Power Vent
Termination
1-1/4" Maximum Recess
of the Square Termination into Exterior Finishing Material
See Table 8 as an aid in venting component
selection for a particular range of exterior
wall thicknesses.
IMPORTANT: The vent termination is hot
while in operation and for a period of time
following the use of the fireplace. Young
children should be carefully supervised
when they are in the same area as a hot
termination.
Venting Connection and Exterior Wall Recessing
Figure 24
of the Power Vent Horizontal Termination
Venting Components Required for Various Exterior
Wall Thicknesses, When Using The Power Vent Termination
Termination Kit Only6 to 9-1/4 (152 to 235)
Termination Kit and 6 In. Vent Section
(SV4.5L6)
Termination Kit and 12 in. Vent Section
(SV4.5L12)
Termination Kit and Telescopic Section
(SV4.5L12)
10-3/4 to 14 (273 to 356)
16-3/4 to 20 (426 to 508)
11-3/4 to 20 (299 to 508)
Table 8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
19
Page 20
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Step 4. FIELD WIRING
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous
operation.
ATTENTION: Au moment de l'entretien des commandes,
étiquetez tous les fils avant de les débrancher. Des erreurs
de cáblage peu-vent entraîner un fonctionnement inadéquat
et dangereux.
Verify proper operation after servicing.
S'assurer que l'appareil fonctionne adé-quatement une fois
l'entretien terminé.
CAUTION: Ground supply lead must be connected to the wire
attached to the green ground screw located on the outlet box.
See Figures 32 and 33 on Page 22. Failure to do so will result
in a potential safety hazard. The appliance must be electrically
grounded in accordance with local codes or, in the absence of
local codes, the National Electrical Code, ANSI/NFPA 70-latest
edition (In Canada, the current CSA C22-1 Canadian Electrical
Code).
14 Gage
Grounded
Romex
Route Wiring
NOTE: Electrical wiring must be performed by a qualified electrician.
• Install the strain relief in the hole provided on the right side of replace
for the electrical wiring (refer to Figure 25).Standard Instruction (For use when access to the termination is
difficult because of height or other reasons).
• Locate a locally procured electrical junction box within reach of the
termination wiring pigtail (refer to Figure 28 on Page 21) and route
the pigtail to the junction box as the termination is installed.
the fireplace to the just installed junction box close to the termination. Ensure the wiring is safety plated to prevent damage by framing
nails and finish drywall screws. Route the wire into the lower control
compartment and cut to length before installing the terminals. Install
provided wiring hardware on the ends of the Romex wire.
• Refer to Figure 29 on Page 21 and install the electrical hardware on
the ends of the Romex wiring. Male terminals on the Black and White
wires, and ring terminals on the ground wire.
• Using standard electrical practices and the terminals provided, connect the three wires of the Romex cable to the termination pigtail
within the Electrical junction box. Ensure ground.
• The replace end of the Romex will be addressed in Connecting The
Power Vent To The Fireplace Control System.
Wall Switch
Harness
Figure 25
Strain
Relief
Vacuum
Hose
Snap
Bushing
Probe (1 *)
Hose Clamp (7 *)
Right Side
of Fireplace
Junction Box
Vacuum Hose
Pressure Switch
Pressure switch is located
behind the panel on the right
side of firebox
Vacuum Hose
Pressure Switch
Adaptor Assembly
*See Figure 15 on Page 13.
Figure 26: Vacuum Hose Connection To Probe
20
Vacuum Hose (2 *)
Figure 27: Vacuum Hose Connection To Pressure Switch
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 21
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Wiring: Fireplace (See Figures 32 and 33 on Page 22)
Note: These electronic appliances must be connected to the main power
supply. The gas valve is set in place and pre-wired at the factory.
1. Route a 3-wire 120Vac 60Hz 1ph power supply to the appliance junc-
tion box.
2. Remove the electrical inlet cover plate from the side of the unit by remov-
ing the plate's securing screws (see Figure 12 on Page 12).
3. Remove the cover plate's knockout and then feed the power supply wire
through the knockout opening and into the unit junction box.
4. Connect the black power supply wire to the power outlet's red pigtail lead
and the white power supply wire to the common terminal of the outlet as
shown in Figures 31 and 32.
5. Connect the ground supply wire to the pigtail lead attached to
outlet's green ground screw.
6. After the wiring is complete, replace the cover plate.
Wiring: Power Vent Termination
Alternate Instructions (For use when access to the termination is easy
and a secondary electrical junction box installation is not desired).
• Remove the junction box cover from the termination by removing the
attaching screw (refer to Figure 28).
• Loosen the strain relief on the termination shown in Figure 28. Pull
the pigtail in and shorten it to fit within the junction box cover.
fireplace to the J-Box at the termination. Ensure the wiring is safety
plated to prevent damage by framing nails and finish drywall screws.
Route the wire into the lower control compartment and cut to length
before installing the terminals. Install provided wiring hardware on the
fireplace end of the Romex wire.
• Refer to Figure 32 on Page 22 and install the electrical hardware on
the fireplace end of the Romex wiring. Male terminals (#10) on the
Black and White wires, and ring terminals (#9) on the ground wire. The
termination end of the Romex will be connected to the termination with
wire nuts (not provided).
• Refer to Figure 31 to connect the three wires of the Romex cable to
the termination. Ensure the ground ring terminal is grounded beneath
a structural screw as shown. Attach the junction box cover to the
termination with the screw previously removed.
• The replace end of the Romex will be addressed in Connecting The
Power Vent To The Fireplace Control System.
Black and White
Romex
Ground Wire
Figure 29: Romex
Strain Relief
Figure 30: Back Of Termination
Pigtail Wires Cut
Off And Shortened
7
6
Romex Wire
Ground Romex To
The Termination
Pigtail
Junction Box Cover
Figure 28: Bottom of Termination
Strain Relief Holding Romex
Figure 31: Junction Box Cover Removed
Attaching Screw
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Wire Nuts
21
Page 22
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
J-BOX/RECEPTIACLE
WIRING
120V, 60HZ, 1PH
Factory Wired
Field Wired
Junction Box
Tab Intact
Tab
Intact
n e e r G - d n u o r G
e t i h W - l a r
t
u e N
120 VAC - Black
Green
Ground
Screw
White
Green
Neutral
Side of
Receptacle
Hot
Side of
Receptacle
Black
120V AC
Junction Box
Hot
Neutral
Ground
B
W
G
Wall
Receiver
Wiring Color Code
B = Black
BL = Blue
AC/DC
Power Adaptor
BR = Brown
G = Green
Ground
B
Pressure
Switch
Cable Harness 102661-01
PU = Purple
GY = Gray
W = White
O= Orange
B
Hi-Temp Sleeve
Figure 32: Electronic Wiring Diagram
ELECTRONIC WIRING DIAGRAM FOR POWER VENT FIREPLACES
B
BR
Y
O
Exhaust
Blower
Control
Module
102663-01
R
R = Red
Y = Yellow
G
GY
NOT USED
W
Exhaust Blower
(Field Installed)
W
G
B
BR
O
Y
W
G
BL
PU
O
G
Y
Electronic Modulation
Step 5. REMOVE GLASS DOOR
ASSEMBLY (ON CONTROL SIDE)
Proflame Valve
DFC Wire Harness 102662-01
Y
G
O
W
W
G
BL
PU
THIS CONNECTOR
NOT USED ON POWER
VENT UNITS
Electronic Pilot Assembly
Igniter Rod
Hood
B
Pilot
Tube
Pilot
Ground
Wire
R
Y
Flame
Sensor
Spark Wire Cable
Pilot Sensor Cable
Proflame
DFC Board
Figure 33: Junction Box Wiring
WARNING
• Handle this glass with extreme
care! Glass is susceptible to
damage – Do not scratch or
handle roughly while reinstalling the glass door frame.
• Do not attempt to substitute the
materials used on this door,
or replace cracked or broken
glass with any materials other
than those provided by the
appliance manufacturer.
• The glass door of this appliance must only be replaced
as a complete unit as provided
by the manufacturer. Do not
attempt to replace broken,
cracked or chipped glass
separately.
If not already done, remove the glass door
assembly on the control side of the fireplace
(see Page 27).
22
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 23
Gas
Valve
3/8" NPT x
Flare Fitting
3/8" Flex Tubing
3/8" Nipple
3/8" Union
3/8" Close
Nipple
3/8" Shut-off Valve
1/2" x 3/8"
Reducer
Gas
Stub
1/2" x 3/8" Flare
Shut-off Valve
Gas Solid Line Connector
Gas Flex Line Connector
*Sediment Trap
3"
Min
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Step 6. CONNECT GAS LINE
All codes require a shut-off valve mounted in
the supply line. The orientation of the shut-off
valve should face the front. Figure 35 illustrates
two methods for connecting the gas supply.
A Sediment Trap is recommended to prevent
moisture and debris in gas line from damaging
the valve.
The flex-line method is acceptable in the U.S.A.
where local codes permit, however, Canadian
requirements vary depending on locality. Installation must be in compliance with local
codes. These appliances are equipped with a
gas flex-line for use in connecting the unit to
the gas line.
See Figure 35 for flex-line description. The flex-
line is rated for both natural and propane gas.
A manual shut off valve is also provided with
the flex-line. The gas control valve is located
on the right side of the unit.
When using solid gas line connector, access
the valve by removing the front door assembly
on the control side and the access plate (refer to Figure 34).
The electronic control valve has a 3/8" (10 mm)
NPT thread gas supply inlet.
Secure all joints tightly using appropriate
tools and sealing compounds (ensure propane
resistant compounds are used in propane applications). It is recommended to seal around
the gas line to prevent cold air leakage.
Bring the shutoff valve on the end of the flex-line
over to the hard pipe and tighten with wrenches
from above through the firebox opening.
Right Side
Modesty Panel
Access Plate
TEST ALL CONNECTIONS FOR GAS LEAKS
(FACTORY AND FIELD):
WARNING
Never use an open flame to
check for leaks.
Turn on gas supply and test for gas leaks using a gas leak test solution (also referred to
as bubble leak solution). Note: Using a soapy
water solution is an effective leak test solution
but it is not recommended, because the soap
residue that is left on the pipes/fittings can result
in corrosion over time.
A. Light the appliance (refer to the lighting
instructions label in control compartment
or in the Care and Operation Instructions
manual).
B. Brush all joints and connections with the gas
leak test solution to check for leaks. If bubbles
are formed, or gas odor is detected, turn the
receiver or remote control to the “OFF” position. Either tighten or refasten the leaking
connection, then retest as described above.
C. When the gas lines are tested and leak free
be sure to rinse off the leak testing solution.
D. Reinstall the access plate, making certain
the gasket has not been damaged.
Step 8. VERIFY APPLIANCE
OPERATION
Turn on burner; then observe the individual
tongues of flame on the burner. Make sure all
ports are open and producing flame evenly
across the burner. If any ports are blocked, or
partially blocked, clean out the ports.
With gas line installed run initial system checkout before closing up the front of the unit.
Follow the pilot lighting instructions provided.
Note: Lighting Instructions are also found on
the literature tag tied to the bracket above the
gas valve. To access the tag, reach into the
right side opening.
When first lighting the appliance, it will take
a few minutes for the line to purge itself of
air. Once purging is complete, the pilot and
burner will light and operate as indicated in
the instruction manual. Subsequent lighting
of the appliance will not require such purging.
Inspect the pilot flame (remove logs, if necessary, handling carefully).
Appliance Checkout
To light the burner, refer to the lighting instructions in the Care and Operation Instructions
manual or the lighting label located behind right
panel. Ensure the igniter lights the pilot. The
pilot flame should engulf the flame sensor as
shown in Figure 36.
Note: The gas supply line must
be installed in accordance with
building codes by a qualified
installer approved and/or
licensed as required by the
locality. In the Commonwealth
of Massachusetts, installation
must be performed by a
licensed plumber or gas fitter.
Main Gas
Shut-Off Valve
Gas Valve
Control Compartment Access
Figure 34
Figure 35: Gas Connection
Step 7. INSTALL FIREBOX LINER
PANELS
Install the ceramic or porcelain liner panels
per the instructions provided in the kit.
NOTICE: Panel liners must be
installed before operating fireplace.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
PILOT ASSEMBLY
Proper Pilot Flame Appearance
Igniter Rod
Flame
Sensor
Figure 36
Pilot Hood
Pilot
Nozzels
23
Page 24
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Step 9. INSTALL VOLCANIC STONE, GLOWING EMBERS,
AND LOGS
9-1. Remove mesh pull screens, modesty panel, and glass door as-
sembly from one side of fireplace. See Page 27.
9-2. Locate materials (log set, bag of glowing embers, and bags of
volcanic stone).
Note: LOGS ARE FRAGILE! Handle with care to prevent
breakage.
9-3. Install volcanic stone. Place some of the volcanic stone on the
firebox floor around the grate (the entire bag of volcanic stone will
NOT be used).
Note: Do NOT place volcanic stone on burner.
9-4. Prepare and install glowing embers.
Note: This appliance is provided with enough glowing
ember material for several applications. Do NOT use
the entire contents of a new bag at one time.
a) Separate some of the glowing ember material into pieces about
the size and thickness of a dime (see Figure 37). Keep the
pieces fluffed up, not matted.
IMPORTANT! Ember pieces must be
as SMALL and THIN as a dime.
b) Distribute the dime-sized pieces over the surface of the burner,
in the areas shown in Figures 38 and 39.
Note: To prevent flame impingement and soot, do not use
more ember material than necessary.
c) For best glowing effect, replace ember material annually.
Note: Use only catalog number H8312 Glowing Embers
with this fireplace.
Bag of Glowing Embers
Separate glowing ember material
into THIN, square, dime-sized pieces.
Figure 37: Preparation of Glowing Ember Material
B
A
C
Control Side
Figure 38: Placement of Glowing Ember Pieces
WARNING
• DO NOT attempt to install the logs until the appliance installation has been completed, the gas line
connected and tested for leaks, and the initial burner
operation has been checked out.
Logs get very hot and will remain hot up to one hour
•
after gas supply is turned off. Handle only when
logs are cool. Turn off all electricity to the appliance
before you installvolcanic stone, embers and logs.
The size and position of the log set was engineered
•
to give the appliance a safe, reliable and attractive
flame pattern. Any attempt to use a different log
set in the fireplace will void the warranty and will
result in incomplete combustion, sooting, and poor
flame quality.
This appliance is not designed to burn wood. Any
•
attempt to do so could cause irreparable damage to
the appliance and prove hazardous to your safety.
If logs are not installed according to the log installa-
•
tion instructions, flame impingement and improper
combustion could occur and result in soot and/or
excessive production of carbon monoxide (CO), a
colorless, odorless, toxic gas.
Place
embers
in circled
areas.
Control Side
(top view of burner shown)
• Place glowing ember material in circled areas ONLY.
• Do NOT place glowing ember material over main flame gas ports.
• To prevent flame impingement and soot, do not use more ember
material than necessary.
Figure 39: Placement of Glowing Ember Pieces
24
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 25
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
9-5. Install logs (reference Figure 40 and Table 9).
Note: Logs are FRAGILE! Handle with care to prevent breakage.
Left Rear Log
E
Left Front Log
Center Rear Log
Center Log
C
Right Rear Log
D
A
Right Front Log
F
Figure 40: Top View of Logs
LOG SET
Item*DescriptionItem*Description
ALog, CenterDLog, Top Right
BLog, Right RearELog, Top Left
CLog, Left FrontFLog, Top Front
*Item letters correspond to photos.
FIREBOX ACCESSORIES/PARTS
Cat. No.ModelDescription
H8312PGE Bag of Glowing Embers
80L42FDVS Bag of Volcanic Stone
Table 9
9-6. Place rectangular notches on underside of Center Log A (Figure
42) over Boss #1 and Boss #4 (Figure 41).
B
Pin
A
Landing
Figure 42
9-7. Place notch on underside of Right Rear Log B (Figure 43) over
Boss #2 (Figure 41).
Place opposite end of Right Rear Log B (Figure 43) on Landing for
Log B (see Figure 41).
Landing for Log D
(see Step 9-9 and Figure 45 on next page)
B
Boss #1Boss #2
Boss #3Landing for Log C
Landing for Log B
[VALVE ACCESS SIDE]
Figure 41: Burner Bosses and Landings
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 43
9-8. See Figures 41 and 44. Place notch on underside of Left Front
Log C over Boss #3.
Place opposite end of Left Front Log C on Landing for Log C (see
Figure 41).
C
Boss #4
Figure 44
25
Page 26
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
9-9. Place groove on underside of Top Right Log D over the grate as
shown in Figure 45.
The middle section of Log D will rest on the landing on Log B
(labeled as “Landing for Log D” in Figure 43).
Groove Location
D
B
Figure 45
9-10. See Figure 46. Place hole on underside of Top Left Log E over pin
on Center Log A.
9-11. See Figure 47. Place groove on underside of Top Front Log F over
the grate finger. Rest the other end of the log on the Landing on
Center Log A.
A
Landing
Groove Location
F
Figure 47
Figure 46
[DETAIL]
E
A
Pin
A
26
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 27
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
reaches EXTREMELY HIGH temperatures
and can cause severe burns if touched.
Even after the gas is turned off, fireplace
surfaces remain extremely hot.
CAUTION
RISK OF PERSONAL INJURY
OR PROPERTY DAMAGE.
• Do NOT abuse glass doors by striking or
slamming shut
• Never operate fireplace with glass door
assemblies removed.
These direct-vent appliances are designed
to operate only when both glass door
assemblies are installed. Generally, the
glass door assemblies should not be
removed, except when access to components within the firebox is required.
• Securely tighten door latch screws when
reinstalling glass door assemblies to
prevent doors from falling out.
• Handle glass door assemblies with
extreme care. Replace damaged glass
door assemblies with approved replacement assemblies only.
The door assemblies on this fireplace
contain ceramic glass. Handle with care
to prevent damage. If the door frame
or glass on either assembly becomes
damaged, replace the entire glass door
assembly with a manufacturer-approved
replacement assembly only. Do not
attempt to substitute any materials used
on door assemblies or replace cracked
or broken glass with any other materials.
Installing Glass Doors, Mesh Pull
Screens, and Modesty Panel
(see Figure 48)
Note: These instructions do NOT apply to
the Outer Glass Door provided in the Outdoor Kit (for indoor/outdoor installations).
1) Install one of the glass doors, as follows:
a) Retrieve the glass door. Visually inspect
the gasket on the back of the frame.
Gasket surface must be clean, free of
irregularities, and seated firmly.
b) Position the door in front of the firebox
opening, with the top of the door held
away from the fireplace (see Figure 48).
c) Lower the bottom of the door assembly
onto the bottom door track, engaging and
centering it in the base channel, and then
gently swing the door up.
d) Using a #3 Phillips screwdriver, fasten the
door frame to the door latches with the
two (2) latch screws. The latches should
pull forward to engage the door frame.
Note: Securely tighten latch screws when
reinstalling glass door assembly.
2) Install the modesty panel on the top flange
of the glass door, as follows:
a) Grasp the modesty panel with both hands
(with the open hem facing down).
b) Engage it with the upper lip of the glass
door frame by pushing it all the way
down. Make sure the installed modesty
panel is firmly in place.
3) Install the mesh pull screens, as follows:
a) Retrieve the rod and two mesh pull
screens. If necessary, attach screens to
rod.
b) Slowly insert the right end of the rod into
the hole in the right rod bracket.
c) Insert the left end of the rod into the slot
in the left rod bracket.
Removing Glass Doors, Mesh Pull
Screens, and Modesty Panel
(see Figure 48)
1) Remove the mesh pull screens, as follows:
a) Lift up the left end of the rod to disengage
it from the slot in the left rod bracket.
b) Slowly remove the right end of the rod
from the hole in the right rod bracket.
c) Set aside the rod and mesh pull screens
for later reinstallation.
2) Remove the modesty panel from the top
flange of the glass door by firmly pulling up
on it with both hands until it is disengaged.
3) Remove one of the glass doors, as follows:
a) See Figure 48. While holding the top of
the glass door frame in place, use a #3
Phillips screwdriver to remove the two
(2) screws securing the door frame to
the two (2) door latches.
b) Carefully tilt the top of the glass door
frame away from the unit (as shown in
Figure 48), and then lift the door assembly up and out of the lower track.
c) Carefully place the glass door assembly
on a padded surface in a safe location to
prevent damage.
Top Flange
on Glass door assembly
Figure 48
Glass Door Latch (2)
Screws
• Only doors certified with the appliance shall
be used.
• Seules des portes certifiées pour cet
appareil doivent être utilisées.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
27
Page 28
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Step 11. BURNER ADJUSTMENTS
Flame Appearance and Sooting
Proper flame appearance is a flame that is blue
at the base and becomes yellowish-orange in
the body of the flame. When the appliance is
first lit, the entire flame may be blue and will
gradually turn yellowish-orange during the first
30 minutes of operation. After 30 minutes of
operation, if the flame is blue, or if the flame is
orange with evidence of sooting (black tip), the
air shutter opening may need to be adjusted.
If the air shutter opening is closed too far,
sooting may develop. Sooting is indicated
by black puffs developing at the tips of very
long orange flames. Sooting results in black
deposits forming on the logs, appliance inside
surfaces and on exterior surfaces adjacent to
the vent termination.
Sooting is caused by incomplete combustion
in the flames and lack of combustion air entering the air shutter opening. To achieve a warm
yellowish-orange flame with an orange body
that does not soot, the shutter opening must be
adjusted between these two extremes.
Air Shutter Adjustment Guidelines
• If there is smoke or soot present, rst check
the log set positioning to ensure that the
flames are not impinging on any of the logs.
If the log set is properly positioned and a
sooting condition still exists, then the air
shutter opening should be increased.
• The more offsets in the vent system, the larger
the air shutter opening will need to be.
• An appliance operated with the air shutter
opened too far, may have flames that appear
blue and transparent. These weak, blue and
transparent flames are termed anemic.
• Propane models may exhibit ames which
candle or appear stringy. If this is present
and persists, adjust the air shutter to a more
OPEN position, then operate the appliance
for a few more minutes to ensure that the
flame normalizes and the flames do not
appear sooty.
The following chart is provided to aid you in
achieving the correct air shutter adjustment
for your installation.
Burner Air Shutter Adjustment
1. Light the appliance (follow lighting proce-
Procedure
WARNING
HOT GLASS WILL CAUSE BURNS.
DO NOT TOUCH GLASS UNTIL COOLED.
•Fireplace surfaces get EXTREMELY HOT!
•The glass on the front of the fireplace
reaches EXTREMELY HIGH temperatures
and can cause severe burns if touched.
Even after the gas is turned off, fireplace
surfaces remain extremely hot.
CAUTION
RISK OF PERSONAL INJURY
OR PROPERTY DAMAGE.
• Air shutter adjustment should only be
performed by a qualified professional
service technician.
• Soot will be produced if the air shutter
is closed too much. Any damage due
to carboning resulting from improperly
setting the air shutter is not covered
under the warranty.
Volcanic Stone
Figure 49: Burner Flame Appearance — Control Side
2. Allow the burner to operate for at least 30
3. Adjust the air shutter using the lever on
A minimum shutter setting is designed into
Note: See Figures 49 and 50 for proper burner
flame appearance.
Adjustment Lever
dure in Care and Operation Instructions or
on lighting label in control compartment).
minutes while continuously observing the
flame to ensure that the proper flame appearance has been achieved (see Figures
49 and 50).
the lower right side of the firebox on the
control side (Figure 49).
• For more OPEN air shutter,
slide lever to the RIGHT.
• For more CLOSED air shutter,
slide lever to the LEFT.
the venturi by four 1/16"-inch tabs.
• If the ame appears weak or sooty (as
described on the previous page), adjust
the air shutter until proper flame appearance is achieved.
• If ame stays lowered blue, incremen-
tally adjust the air shutter to a more
CLOSED position until proper flame
appearance is achieved.
Air Shutter
28
Air Shutter Adjustment Guidelines:
Amount of
Primary Air
If air shutter is
closed too far
If air shutter is
open too far
Flame
Color
Flame will
be orange
Flame will
be blue
Air Shutter
Adjustment
Air shutter
gap should be
increased
Air shutter
gap should be
decreased
Volcanic Stone
Figure 50: Burner Flame Appearance — Opposite Control Side
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 29
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
FINISHING REQUIREMENTS
Wall Details - INDOOR SIDE(S)
Complete the finished interior wall. To install the appliance facing flush
with the finished wall, position framework to accommodate the thickness
of the finished wall (Figure 51).
Wall Details - OUTDOOR SIDE
Complete finished exterior wall per the instructions provided in the
Outdoor Installation Kit and the instructions provided here. To install the
appliance facing flush with the finished exterior wall, position framework
to accommodate the thickness of the exterior finished wall (Figure 52).
INTERIOR WALL FINISHINGEXTERIOR WALL FINISHING
Wall Stud
Combustible
Finished Wall
Materials
Header
Combustible
materials are
allowed on face
of appliance
above this point
Min. 3 in*
(76 mm)
~
Min. 1 in*
(25 mm)
Top of
Appliance
Adaptor plus
min. 4 feet
vertical vent
and 90˚ elbow
Adaptor plus
min. 4 feet
vertical vent
and 90˚ elbow
Min. 3 in*
(76 mm)*
1"
(25.4mm)
Minimum
Top of
Appliance
Wall Stud
Combustible
Sheathing
Header
Non-combustible
sheathing required
below this point
Non-combustible
Extend housewrap
(building paper)
to this point.
*Insulation is
NOT ALLOWED in
clearance zones
around vent
components.
Keep this area free
from combustible
materials.
Figure 51
Spacers
Top of Door Frame
FIREPLACE
(side view)
Figure 52
See Page 5 for Cold Climate Insulation
and Page 9 for Clearances
Spacers
Top of Door Frame
FIREPLACE
(side view)
Note: Non-combustible
sheathing and
housewrap (building
paper) should extend
to U-channels on
sides and bottom.
*Insulation is
NOT ALLOWED in
clearance zones
around vent
components.
Keep this area free
from combustible
materials.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
29
Page 30
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Combustible Sheathing
Non-Combustible Board
A
BB
Non-Combustible Board
Combustible Sheathing
C
Non-Combustible Board
Sheathing Requirements
ABC*
12” (305mm)7” (178mm)6” (152mm)
*Dimension “C” is clearance required from fireplace base to surface
(e.g., deck, patio, lanai) as a moisture barrier (not a combustible
clearance) on outdoor side only.
Overhang
B
A
Siding
A
A
Siding
Siding
Trim
C*
Exterior Minimum Clearances
MaterialABC*
Vinyl12” (305mm)35-1/2” (902mm)6” (305mm)
Non-Vinyl7” (178mm)35-1/2” (902mm)6” (305mm)
*Dimension “C” is clearance required from fireplace base to surface
(e.g., deck, patio, lanai) as a moisture barrier (not a combustible
clearance) on outdoor side only.
Figure 53: Sheathing
Figure 54: Exterior Clearances
30
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 31
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Step 12. ATTACHING SAFETY-IN-OPERATION WARNINGS
It is the installer’s responsibility to ensure these warnings are properly affixed during installation. These warning labels are a
critical step in informing consumers of safe operation of this appliance.
ATTACHING SAFETY-IN-OPERATION
WARNINGS
It is required that the set of safety instruction labels
that have been furnished with the fireplace be affixed
to the operation and control points of the fireplace. A
safety instruction label must be affixed to the receiver
wall switch plate where the fireplace is turned on
and off (See Figure A) and on the remote control
handheld transmitter (See Figure B). To properly
complete the installation of this fireplace, locate the
multi-lingual adhesive labels provided with the Care
and Operation Instructions and proceed as follows:
1. Locate the wall receiver that controls the fireplace
(verify the switch operates the fireplace by turning it on and off). Clean the wall receiver plate
thoroughly to remove any dust and oils. Affix
the label to the surface of the plate of the wall
receiver that controls the fireplace (Figure A).
Choose the language primarily spoken in the
home. If unknown, affix the English language
label.
2. Locate the remote control transmitter and
clean it thoroughly to remove any dust and
oils. Affix the label to the surface of handheld
transmitter (Figure B). Choose the language
primarily spoken in the home. If unknown, affix
the English language label.
3. If you are unable to locate the labels, please
call Innovative Hearth Products or your nearest
Innovative Hearth Products dealer to receive additional safety instruction labels free of charge.
Cat. No. H8024 Replacement Label Kit
INNOVATIVE HEARTH PRODUCTS
Note: English is red text on clear label. French
and Spanish are white text on black label.
APPOSITION DES MISES EN GARDE RELATIVES
À LA SÉCURITÉ D’UTILISATION
Il est impératif que le jeu d’étiquettes de sécurité qui ont été
fournies avec le foyer soient collées à côté des dispositifs de
contrôle du foyer. Une étiquette de sécurité doit être collée
sur la plaque du récepteur mural contrôlant l’allumage du
foyer (voir Figure A) et sur le boîtier de la télécommande
(Figure B). Pour achever l’installation correcte de ce
foyer, procédez comme suit avec les étiquettes adhésives
en langues étrangères fournies avec les instructions
d’utilisation et d’entretien :
1. Repérez le récepteur mural qui contrôle le foyer
(vérifiez que l’interrupteur contrôle le fonction nement du foyer en le faisant basculer de Marche
à Arrêt, et vice-versa). Nettoyez soigneusement
la plaque du récepteur mural pour éliminer la poussière
et les traces de graisse ou d’huile. Collez l’étiquette sur
la surface de la plaque du récepteur mural qui contrôle
le foyer (Figure A). Choisissez la langue qui est
principalement parlée dans la résidence du propriétaire.
En cas de doute, collez l’étiquette en anglais.
2. Repérez la télécommande et nettoyez-la soigneusement pour éliminer la poussière et les traces
de graisse ou d’huile. Collez l’étiquette sur le boîtier
de la télécommande (Figure B). Choisissez la
langue qui est principalement parlée dans la
résidence du propriétaire. En cas de doute, collez
l’étiquette en anglais.
3. Si vous ne trouvez pas les étiquettes, veuillez
appeler Innovative Hearth Products ou votre distributeur Innovative Hearth Products local pour recevoir
gratuitement des étiquettes supplémentaires.
Étiquettes de remplacement, n° cat. H8024
INNOVATIVE HEARTH PRODUCTS
Remarque : Le texte anglais est rouge sur un support
transparent. Le texte français et espagnol est blanc sur un
support noir.
COLOCACIÓN DE ADVERTENCIAS DE
SEGURIDAD EN OPERACIÓN
Se requiere que el juego de etiquetas de instrucciones
de seguridad que se incluyeron con la chimenea se
coloque en los puntos de operación y control de la
misma. Se debe colocar una etiqueta de instrucciones
de seguridad en la placa del interruptor de pared
del receptor desde el cual se enciende y se apaga
la chimenea (ver la Figura A) y en el transmisor de
control remoto (ver la Figura B). Para completar
correctamente la instalación de esta chimenea,
encuentre las etiquetas adhesivas multilingües
incluidas con las instrucciones de cuidado y
operación y haga lo siguiente:
1. Identifique el receptor de pared que controla la
chimenea (verifique que el interruptor opera la
chimenea encendiéndola y apagándola). Limpie
bien la placa del receptor de pared para quitar el
polvo y aceite. Pegue la etiqueta en la superficie
de la placa del receptor de pared que controla la
chimenea (Figura A). Seleccione el idioma que
más se habla en la casa. Si no sabe cuál es, use
la etiqueta en inglés.
2. Identifique el transmisor de control remoto y
límpielo bien para quitar el polvo y aceite. Pegue
la etiqueta en la superficie del transmisor (Figura B). Seleccione el idioma que más se habla en la
casa. Si no sabe cuál es, use la etiqueta en inglés.
3. Si no puede encontrar las etiquetas, sírvase llamar
a Innovative Hearth Products o al distribuidor de
Innovative Hearth Products más cercano para
recibir etiquetas de instrucciones de seguridad
adicionales gratuitas.
Juego de etiquetas de repuesto - Nº de cat. H8024
INNOVATIVE HEARTH PRODUCTS
Nota: La etiqueta en inglés es transparente con
texto rojo. Las etiquetas en francés y español son
negras con texto blanco.
SAFETY LABEL
DIAGRAMS
DIAGRAMMES DES ÉTIQUETTES
DE SÉCURITÉ
On
Remote
Off
PRG
Figure A Figure B
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
DIAGRAMAS DE ETIQUETAS
DE SEGURIDAD
31
Page 32
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
S
e
a
l
a
n
t
INSTALLATION ACCESSORIES
Listed Secure Vent™ Components
Cat. No.Model No.Description
77L70SV4.5L6
77L71SV4.5L12
77L72SV4.5L24
77L73SV4.5L36
77L74SV4.5L48
77L75SV4.5LA
H8313—
77L76SV4.5E45
77L77SV4.5E90
H2246SV4.5HF
H2247SV4.5VF
The following flashings come packaged with a storm collar:
Through Wall
Shield Kit
(used to shield
direct-vent pipe from
blown insulation)
Listed Secure Vent™ / Secure Flex™ Components
Cat. No. Model No.Description
Attic Insulation Shield
H3907SV4.5RSA
(adjustable 12" to 22")
36" Flex Vent Kit
H7748FVK36
Note: Flex attaches to appliance collar at one end
and to rigid venting at the
other end.
10K81SFMPMill-Pac, Black, High-
Temperature Sealant
89L40SFMP-12Mill-Pac, Black, High
Temperature Sealant
(Bulk 12 pack)
91L66SF-GC4-6Gear Clamp 4.5 in.
(114 mm) for flex
(6 pieces)
91L67SF-GC7-6Gear Clamp 7.5 in.
(190.5 mm) for flex
(6 pieces)
Outdoor Kits
H7940 LSM40STODKOutdoor Kit with
Light-tint Glass
H8061 LSM40ST-ODKT Outdoor Kit with
Dark-tint Glass
32
96K93SV4.5SU
96K92SV4.5SP
Support Strap
Support Plate
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 33
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
GAS CONVERSION KITS
Gas conversion kits are available to adapt your
appliance from the use of one type of gas to
another. These kits contain all the necessary
components needed to complete the task, including labeling that must be affixed to ensure
safe operation.
Kit part numbers are listed at right.
Refer to the instructions provided with the
conversion kit when performing any gas
conversion.
Gas Conversion Kits
Kit Model No.Kit Cat. No.Description
GCK-NP-LSM40STH7951Natural Gas to Liquid Propane Conversion Kit
GCK-PN-LSM40STH7952Liquid Propane to Natural Gas Conversion Kit
Table 10
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
33
Page 34
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Innovative Hearth Products reserves the right to make changes at any time, without notice,
in design, materials, specifications, and prices, and also to discontinue colors, styles,
and products. Consult your local distributor for fireplace code information.