Superior DRT63STYN Installation Instructions Manual

Page 1
INSTALLATION INSTRUCTIONS
Signature Series See-Through Power Vent DV Gas Fireplaces
P/N 506009-20 Rev. NC 12/2013
This manual is one of a set of two supporting this product. Refer to P/N
Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 506009-21.
for Care and Operation Instructions.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
MODELS
Intertek Report No. 100326550PRT-001
DRT63STYN
Look for the EnerGuide
Gas Fireplace Energy
Efficiency Rating in this manual.
Based on CSA P.4.1-02
INSTALLATEUR : Laissez cette notice avec l’appareil. CONSOMMATEUR : Conservez cette notice pour consultation ultérieure.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used.
WARNING /AVERTISSEMENT/AVISO
• HOT GLASS WILL CAUSE BURNS.
• DO NOT TOUCH GLASS UNTIL COOLED.
• NEVER ALLOW CHILDREN TO TOUCH GLASS.
• UNE SURFACE VITRÉE CHAUDE PEUT CAUSER DES BRÛLURES.
• LAISSER REFROIDIR LA SURFACE VITRÉE AVANT D'Y TOUCHER.
• NE PERMETTEZ JAMAIS À UN ENFANT DE TOUCHER LA SURFACE VITRÉE.
• EL VIDRIO CALIENTE CAUSARÁ QUEMADURAS.
• USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE.
• LOS NIÑOS DEBEN NUNCA TOCAR EL VIDRIO.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury, or death.
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
AVERTISSEMENT : Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incindie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
Page 2
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
TABLE OF CONTENTS
Packaging ................................................... 2
Introduction ................................................ 2
Approved Vent Components .................... 2
General Information .................................... 2
Misc. Codes/Standards ........................... 3
Inputs and Efficiencies ............................ 3
Gas Supply Pressure Requirements ........ 3
Orifice Sizes ............................................ 4
Gas Valve Diagram ................................. 4
Massachusetts / NYC Requirements ....... 4
Cold Climate Insulation ............................... 5
Manufactured Home Requirements ............ 5
Location ...................................................... 5
Vent Termination Clearances ...................... 6
Hearth Extensions (Optional) ...................... 8
Minimum Clearances to Combustibles ........ 9
Pre-Installation Steps .................................. 10
Typical Installation Sequence ..................... 10
Detailed Installation Steps:
Step 1. Framing .......................................... 10
Framing Dimensions ................................ 11
Fireplace Specifications ............................ 12
Step 2. Route Gas Line .............................. 13
Step 3. Install Vent System ........................ 13
General Information ................................. 13
Vent Restrictor ......................................... 14
Power Vent Components.......................... 14
Vent Section Lengths ............................... 15
Vertical (Offset) Installation...................... 15
Vent Figures ............................................. 17
Horizontal (Outside Wall) Termination
System ................................................. 18
Step 4. Field Wiring .................................... 20
Step 5. Remove Glass Door Assembly ....... 22
Step 6. Connect Gas Line ........................... 23
Step 7. Install Firebox Liner Panels ............ 23
Step 8. Verify Appliance Operation ............. 23
Step 9. Install Volcanic Stone, Glowing
Embers, and Logs .................................... 24
Step 10. Install Glass Doors, Mesh Pull
Screens, and Modesty Panel ................... 27
Step 11. Burner Adjustments ..................... 28
Finishing Requirements .............................. 29
Step 12. Attaching Safety-in-Operation
Warnings ..................................... 31
Installation Accessories .............................. 32
Gas Conversion Kits .......................... 33
2
PACKAGING
The assembled vented gas fireplace is pack­aged with the following items:
Fireplace Components:
(1) Literature Kit (in envelope in firebox;
contains Care and Operation Instruc- tions, Installation Instructions, safety­in-operation warning labels, warranty)
(1) Remote Control Kit (in plastic bag in fire-
box; contains remote control, receiver) (1) Log Set (1) Vent Restrictor Assembly (1) bag Glowing Embers (4) bags Volcanic Stone (1) ea. Door Modesty Shield (1) Firebox liner panels (1) Andirons
Power Vent Components:
(1) ea.
Power Vent Termination
(1) ea. Termination Adaptor (1) ea. Horizontal Firestop Assembly (1) ea. Vacuum Hose (1) ea. 11/32" Hose Clamp (1) ea. Strain Relief (1) ea. Bushing (4) ea. 1/4" Insulated Male Terminals (2) ea. #10 Ring Terminals
Outdoor Kit (sold separately; REQUIRED for
indoor/outdoor installations)
INTRODUCTION
The See-Through Power Vent is a direct-vent, sealed combustion gas fireplace designed for either indoor/indoor or indoor/outdoor residential applications (including screened porches and lanais).
NOTE: INDOOR/OUTDOOR INSTALLATIONS REQUIRE AN OUTDOOR INSTALLATION KIT (SOLD SEPARATELY).
These appliances are designed to operate on natural gas. (Propane units are available as a field conversion.) The system is switchable between standing and intermittent pilot modes.
External electrical power is required to operate these units.
Approved Vent Components
These fireplaces are designed, tested, and listed for operation and installation with the following vent components (4-1/2" inner and 7-1/2" outer) only:
• Secure Vent™ direct-vent system compo-
nents manufactured by Security Chimneys International.
These approved vent system components are labeled for identification. Do NOT use any other manufacturer’s vent components with these appliances.
GENERAL INFORMATION
WARNING
Young children should be carefully supervised when they are in the same room as the appliance. Tod­dlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être surveillés étroitement lorsqu’ils se trouvent dans la même pièce que l’appareil. Les tout petits, les jeunes enfants ou les adultes peuvent subir des brûlures s’ils viennent en contact avec la sur­face chaude. Il est recommandé d’installer une barrière physique si des personnes à risques habitent la maison. Pour empêcher l’accès à un foyer ou à un poêle, installez une barrière de sécurité; cette mesure empêchera les tout petits, les jeunes enfants et toute autre personne à risque d’avoir accès à la pièce et aux surfaces chaudes.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Les enfants et les adultes devraient être infor-més des dangers que posent les températures de surface élevées et se tenir à distance afin d’éviter des brûlures ou que leurs vêtements ne s’enflamment.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
Page 3
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
WARNING
Improper installation, adjust­ment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
WARNING
Failure to comply with these installation instructions will result in an improperly installed and operating appliance, voiding its warranty. Any change to this appli­ance and/or its operating controls is dangerous.
WARNING
Clothing or other flammable material should not be placed on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de vêtements ni d’autres matières inflammables sur l’appareil ni à proximité.
WARNING
Any safety screen or guard removed for servicing the appli­ance must be replaced prior to operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré pour permettre l’entretien de l’appareil doit être remis en place avant de mettre l’appareil en marche.
WARNING
Improper installation or use of this appliance can cause serious injury or death from fire, burns, explosion or carbon monoxide poisoning.
Note: Installation and repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
Remarque : L’installation et la répara­tion devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une inspection par un technicien profes­sionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de pous-sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les conduits de circulation d’air de l’appareil soient tenus propres.
Do not use these appliances if any part has been under water. Immediately call a qualified, professional service technician to inspect the appliance and to replace any parts of the control system and any gas control which have been under water.
Ne pas utiliser cet appareil s’il a été plongé, même partiellement, dans l’eau. Appeler un technicien qualifié pour inspecter l’appareil et remplacer toute partie du système de commande et toute commande qui a été plongée dans l’eau.
Only trim kit(s) supplied by the manufacturer shall be used in the installation of this ap­pliance.
Seules les trousses de garniture fournies par le fabricant doivent être utilisées pour l’installation de cet appareil.
These appliances comply with National Safety Standards and are tested and listed by Intertek (Report No. 100326550PRT-001) to ANSI Z21.88 (in Canada, CSA-2.33), and CAN/CGA-
2.17-M91 (CSA P4.1) in both USA and Canada, as vented gas fireplace.
These appliances are listed by Intertek for installation in bedrooms, aftermarket mobile homes, and manufactured homes.
Misc. Codes/Standards
Installation must conform to local codes or, in the absence of local codes, with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest edition (in Canada, the current CAN/CSA-B149.1
installation code). The appliance, when installed, must be electri-
cally grounded and wired in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA
70 - latest edition, or the Canadian Electrical Code, CSA C22.1 - latest edition.
Provide adequate clearances around air open­ings and adequate accessibility clearance for service and proper operation. Never obstruct the front or back openings of the appliance.
These appliances are designed to operate on natural or propane gas only (if field-converted to propane). The use of other fuels or combi­nation of fuels will degrade the performance of this system and may be dangerous.
The system is switchable between standing and intermittent pilot modes. External electrical power is required to operate these units.
These models come standard with a remotely modulated gas valve. The included transmitter remotely controls flame appearance and heat output (manual gas valve adjustment is not possible).
Inputs and Efficiencies
Appliance BTU inputs are listed in Table 1A. Appliance efficiencies are listed in Table 1B.
INPUTS
Gas Type
Natural Gas
Liquid Propane
(field-converted to LP)
Table 1A
Inputs
40,000 to 60,000
BTU/hr
43,500 to 56,000
BTU/hr
EFFICIENCIES
Gas Type AFUE EnerGuide
Natural Gas
Table 1B
68% 62%
Gas Fireplace Energy Efciency Rating
Based on CSA P.4.1-02
Gas Supply Pressure Requirements
Inlet and manifold gas supply pressure require­ments for these appliances are listed in Tables 2 and 3.
Inlet Gas Supply Pressure (all models)
Fuel # Minimum Maximum
Natural
Gas
Liquid
Propane*
Table 2
Manifold Gas Supply Pressure (all models)
Fuel # Low High
Natural
Gas
Liquid
Propane*
Table 3
(Continued on next page)
5.0" WC
(1.24 kPa)
11.0" WC
(2.74 kPa)
*Available as field conversion only.
(Lo) 1.6" WC
(0.4 kPa)
(Lo) 6.3" WC
(1.57 kPa)
*Available as field conversion only.
10.5" WC
(2.61 kPa)
13.0" WC
(3.23 kPa)
(Hi) 3.5" WC
(0.87 kPa)
(Hi) 10.0" WC
(2.49 kPa)
3
Page 4
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Gas Supply Pressure Requirements
(continued from previous page)
Test gauge connections are provided on the front of the electronic gas control valve (identi­fied IN for the inlet and OUT for the manifold side).
The control valves have a 3/8" (10 mm) NPT thread inlet and outlet side of the valve. Refer to Figure 1.
Propane tanks are at pressures that will cause damage to valve components. Verify that the tanks have step-down regulators to reduce the pressure to safe levels.
These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance.
These appliances must be isolated from the gas supply piping system (by closing their individual manual shut-off valve) during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
These appliances and their individual shut-off valves must be disconnected from the gas supply piping system during any pressure testing of that system at pressures greater than 1/2 psig (3.5 kPa).
Green Wire
(From DFC Wire
Harness)
Manifold (Out)
Test Port
Line (In) Test Port
PURGE CYCLE
This is a power-vented fireplace that requires household electrical power to operate. When the fireplace is turned OFF, the exhaust blower will continue to operate for up to two minutes, to purge exhaust gases from the venting system. This system will not operate during a power outage.
Orifice Sizes
Sea Level To High Altitude (All Models)
These appliances are tested and approved for installation at elevations of 0– 4500 feet (0– 1372 meters) above sea level using the standard burner orifice sizes listed in Table 4). For elevations above 4500 feet, contact your gas supplier or qualified service technician.
Deration
At higher elevations, the amount of BTU fuel value delivered must be reduced by either:
• using gas that has been derated by the gas
company; or
• changing the burner orice to a smaller size
as regulated by the local authorities having jurisdiction and by the (USA) National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition or, in Canada, the CAN/CSA-B149.1 codes - latest edition.
Install the appliance according to the regulations of the local authorities having jurisdiction and, in the USA, the National Fuel Gas Code NFPA 54 / ANSI Z223.1 - latest edition or , in Canada, the CAN/CSA-B149.1- latest edition.
NOTE: Flame appearance will diminish 4% per 1,000 feet.
Gas Valve Diagram
The SIT Proflame valve is illustrated in Figure 1.
Connect GTMS Wire Harness
Pressure Regulator Tower
Burner Orifice Sizes
(USA and Canada)
Elevation 0-4500 ft (0–1372 m)
Natural Gas
Drill size (inches)
#32 (0.116") 
[Cat. No. H8002]
Standard size installed at factory.
Table 4
Standard size in LP conversion kit.
Propane
Drill size (inches)
#52 (0.0635")
[Cat. No. H8003]
Requirements for the Commonwealth of Massachusetts
These fireplaces are approved for installation in the US state of Massachusetts if the following additional requirements are met:
• Install this appliance in accordance with
Massachusetts Rules and Regulations 248 C.M.R.
• Installation and repair must be done by a
plumber or gas fitter licensed in the Com­monwealth of Massachusetts.
• The exible gas line connector used shall
not exceed 36 inches (92 centimeters) in length.
• The individual manual shut-off must be a
T-handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, hori­zontal terminations installed less than seven (7) feet above the finished grade must comply with the following additional requirements:
• A hard-wired carbon monoxide detector
with an alarm and battery backup must be installed on the floor level where the gas fireplace is installed. The carbon monoxide detector must comply with NFPA 720, be ANSI/UL 2034 listed and be ISA certified.
• A metal or plastic identication plate must
be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade and be directly in line with the horizontal termination. The sign must read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
Orange Wire
(from DFC Wire
Harness)
Inlet 3/8" NPT
Figure 1: SIT Proflame Valve
4
Outlet 3/8" NPT
Yellow Ground Wire (From DFC Wire Harness)
New York City, New York (MEA)
Installation of these fireplaces is approved for installation in New York City, NY.
Page 5
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks around the appliance with noncombustible material and wherever cold air could enter the room. If the floor is above ground level, it is especially important to insulate outside chase cavity between studs and under the floor on which the appliance rests. Gas line holes and other openings should be caulked or stuffed with unfaced fiberglass insulation.
If the fireplace is being installed on a cement slab in cold climates, a sheet of plywood or other raised platform can be placed under­neath to prevent cold transfer to the fireplace and into the room. It also helps to sheetrock inside surfaces and tape for maximum air tightness and caulk firestops.
MANUFACTURED HOME REQUIREMENTS
(Top View)
Indoors
When unit is installed with one side flush with a wall, the wall on other side of unit must not extend beyond front edge of unit.
Outdoors
Drywall
Horizontal Termination (Outdoors)
This appliance may be installed in an after­market, permanently located manufactured home and must be installed in accordance with the manufacturer's instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States, or the Standard for Installation in Mobile Homes, CAN/CSA Z240 MH Series, in Canada.
Cet appareil peut être installé cómme du matéri-el d'origine dans une maison préfabriquée (É.U. seulement) ou mobile et doit être installé selon les instructions du fabricant et conformément à la norme Manufactured Home Constructions and Safety, Title 24 CFR, Part 3200 aux Unis ou à la norme Can/CSA-Z240 Série MM, Maisons mobiles au Canada.
This appliance is only for use with the type of gas indicated on the rating plate. This ap­pliance is not convertible for use with other gases, unless a certified kit is used.
Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil ne peut être con­verti à d'autres gaz, sauf si une trousse de conversion est utilisée.
CAUTION: Ensure that the cross members are not cut or weakened during installation. The structural integrity of the manufactured home floor, wall, and ceiling / roof must be maintained.
CAUTION: This appliance must be grounded to the chassis of the manufactured home in accordance with local codes or in the absence of local codes, with the National Electrical Code ANSI / NFPA 70 - latest edi­tion or the Canadian Electrical Code CSA C22.1 - latest edition.
Fireplace
Figure 2: Typical Installation/Locations
LOCATION
In selecting the location, the aesthetic and functional use of the appliance are primary concerns; however, vent system routing to the exterior and access to the fuel supply are also important.
CAUTION: Due to high temperatures, the ap­pliance should be located out of traffic and away from furniture and draperies (Figure 2).
AVERTISSEMENT : En raison des tem­pératures élevées, l’appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures (Figure 2).
The location also should be free of electrical, plumbing, or other heating/air conditioning ducting.
These direct-vent appliances are uniquely suited for installations requiring a utility shelf positioned above the fireplace. Utility shelves like these are commonly used for locating television sets and decorative plants.
The minimum height from the base of the appli­ance to the underside of combustible materials used to construct a utility shelf in this fashion is shown in Figure 7 on Page 9.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Top of Fireplace
Opening
Be aware that this is a heat-producing ap­pliance. Objects placed above the unit are exposed to elevated temperatures.
Do not insulate the space between the appli­ance and the area above it.
The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materials. However, if installed on combustible materials, (such as carpeting or vinyl tile), a metal or wood barrier covering the entire bottom surface must be used.
5
Page 6
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
VENT TERMINATION CLEARANCES
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CSA-B149.1 in Canada. When planning your vent run refer to the table in Figure 22 on Page 17.
Horizontal Vent Termination Clearances
The horizontal vent termination must have a minimum of 3" (76 mm) clearance to any overhead combustible projection of 2-1/2" (64 mm) or less (see Figure 3). For projections exceeding 2-1/2" (64 mm), see Figure 3. For additional vent location restrictions refer to Figure 4 on Page 7.
Combustible Projection
extending more than
2.5 inches
24 in (610 mm)
3 in
(76 mm)
Combustible Projection extending up to
2.5 inches
~
Power Vent Termination
Side Elevation View
Ventilated or Unventilated Soffit
Combustible
For recess allowances of power vent termination into exterior walls, see Figure 24 on Page 19.
Figure 3: Horizontal Power Vent Termination Clearances to Combustibles
18 in
(457 mm)
6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 7
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
V
X
V
= Vent terminal
= Air supply inlet
= Area terminal NOT permitted
= 9" U.S. (12" Canada)
A
G
X
V
= Vent terminal
= Air supply inlet
= Area terminal NOT permitted
EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS
NOTE:
•Local codes or regulations may require
different clearances.
•Location of vent termination must NOT
interfere with access to electrical service.
= Vent terminal
V
= Area terminal NOT permitted
= Air supply inlet
X
= 9" U.S. (12" Canada)
Center Line of
D
Horizontal
Termination
36"
(91.4 cm)
Exterior Wall
D
36"
(91.4 cm)
Inside Corner
[DETAIL]
See Item “D” in table below.
Ventilated
Soffit
V
A
G
V
G
A
[DETAIL]
Inside Corner
H
B
V
F
L
V
Fixed Closed
Window
C
Operable
Window
B
X
V V
V
A
C
C
C
B B
B
J
M
I
MINIMUM CLEARANCES
Clearance Description US Installation Canadian Installation
A = Clearance above grade, veranda, porch,
deck, or balcony.
B = Clearance to window or door that may be
opened.
C = Clearance to permanently closed window. 9 in (229 mm) recommended to prevent window
D = Vertical clearance to ventilated soffit
located above the terminal within a horizontal distance of 36 in (91.4 cm)
from center line of terminal. E = Clearance to unventilated soffit. 24 in (61 cm) 24 in (61 cm) F = Clearance to outside corner. 5 in (12.7 cm) 5 in (12.7 cm) G = Clearance to inside corner. 24 in (61 cm) 36 in (91.4 cm) H = Clearance to each inside of center line
extended above meter/regulator assembly.
= Clearance to service regulator vent outlet. 3 ft (91.4 cm) 3 ft (91.4 cm)
I
J = Clearance to non-mechanical air supply
inlet to building or combustion air inlet to
any other appliance.
K = Clearance to mechanical air supply inlet. 3 ft (91.4 cm) above, if within 10 ft (3 m) horizontally. 6 ft (1.83 m) L = Clearance above paved sidewalk or paved
driveway located on public property. M = Clearance under veranda, porch, deck, or
balcony.
In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Codes (latest editions). In accordance with the current CAN/CSA-B149.1 Installation Code (latest editions). A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single-family dwellings and serves both dwellings. Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
Figure 4
18 in (46 cm) 18 in (46 cm)
6 in (15.2 cm) for appliances < 10,000 BTU/hr (3kW); 9 in (23 cm) for appliances > 10,000 BTU/hr (3kW)
and < 50,000 BTU/hr (15kW);
12 in (30 cm) for appliances > 50,000 BTU/hr (15kW).
condensation.
24 in (61 cm) 24 in (61 cm)
3 ft (91.4 cm) within a height of 15 ft above the
meter/regulator assembly.
6 in (15.2 cm) for appliances < 10,000 BTU/hr (3kW); 9 in (23 cm) for appliances > 10,000 BTU/hr (3kW)
and < 50,000 BTU/hr (15kW);
12 in (30 cm) for appliances > 50,000 BTU/hr (15kW).
7 ft (2.13 m) 7 ft (2.13 m)
18 in (46.0 cm)   18 in (46.0 cm)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
6 in (15.2 cm) for appliances < 10,000 BTU/hr (3kW); 12 in (30 cm) for appliances > 10,000 BTU/hr (3kW)
and < 100,000 BTU/hr (30kW);
36 in (91.4 cm) for appliances > 100,000 BTU/hr (30kW). 12 in (305 mm) recommended to prevent window
condensation.
3 ft (91.4 cm) within a height of 15 ft above the
meter/regulator assembly.
6 in (15.2 cm) for appliances < 10,000 BTU/hr (3kW); 12 in (30 cm) for appliances > 10,000 BTU/hr (3kW)
and < 100,000 BTU/hr (30kW);
36 in (91.4 cm) for appliances > 100,000 BTU/hr (30kW).
D E
V
V
X
K
7
Page 8
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
HEARTH EXTENSIONS (OPTIONAL)
Note: Hearth extensions are not required with this appliance.
Optional Indoor Hearth Extension
Combustible indoor hearth material may only be installed at or below the base of the fireplace (see Figures 5 and 6).
Non-combustible indoor hearth material may be installed above the base of the fireplace and may butt against the front face of the fireplace (see
Figures 5 and 6).
Also note the following:
Combustible material may project beyond the sides of the fireplace opening, as long as it is within the shaded area shown in Figure 9 on Page 9.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel (see Figure 8 on Page 9).
Non-combustible mantels may be installed at any height above the appliance opening.
Optional Outdoor Hearth Extension
All outdoor hearth material (combustible and non-combustible) must be installed a minimum of 6" (152 mm) below the base of the fireplace (see Figure 6).
Also note the following:
For vertical installation clearances to combustible outdoor mantels and overhangs, see Page 30 and the instructions provided in the Outdoor
Installation Kit (required for all outdoor installations; see Page 32).
Non-combustible outdoor mantels and overhangs may be installed at any height above the appliance opening.
Indoor
Side
Fireplace
(side view)
Outdoor
Side
Finish combustible material must be installed at or below base of fireplace.
Finish non-combustible material may butt against front face of fireplace.
Figure 5: Optional Indoor Hearth Extension
8
Floor Panel
Indoor hearth extension:
Front Face of Fireplace
Finish combustible material must be installed at or below base of fireplace.
Finish non-combustible material may be installed above base of fireplace and may butt against front face of fireplace.
Figure 6: Optional Indoor and Outdoor Hearth Extensions
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
6" (152 mm)
minimum
Outdoor hearth extension:
All finish hearth material (combustible and non-combustible) must be at least 6" (152 mm) below base of fireplace.
Page 9
7 (178)
2
(51)
4
(102)
6
(152)
8
(203)
10
(254)
12
(305)
9 (229)
13 (330)
17 (432)
15 (381)
11 (279)
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
MINIMUM CLEARANCES TO COMBUSTIBLES
Appliance and Vent Clearances
The appliance is approved with zero clearance to combustible materials on both sides (as detailed in Table 5), with the following exceptions:
When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit.
In addition, when the unit is recessed, the side walls surrounding the unit must not extend beyond the front edge of the unit (see Figure 2 on Page 5).
MINIMUM CLEARANCES TO COMBUSTIBLES
Back / Sides
0 in (0 mm) Spacers Top Spacers 0 in (0 mm) Floor 0 in (0 mm) Unit Bottom to Ceiling 72.0 in (1829 mm) Vertical Vent Pipe 1.0 in (25.4 mm) Horizontal Vent Pipe Top: 3.0 in (76.2 mm)
Sides: 1.0 in (25.4 mm)
Bottom: 1.0 in (25.4 mm)
SERVICE CLEARANCES
Front 3 ft (0.9 m)
Table 5
3" (76 mm) above any horizontal/inclined vent component.See Step 1 ("FRAMING") on Page 10 for clearance requirements to
the nailing flanges on each side of the unit and any adjacent screw heads.
The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materials; however, if installed on combustible materials, such as carpeting, vinyl tile, etc., a metal or wood barrier covering the entire bottom surface must be used.
Do NOT insulate space between appliance and area above it.
Combustible
Enclosure (or Shelf)
~
Min. 3"
~
(76 mm)
Min. 90" (2287 mm) Indoor/ Outdoor
Min. 2 ft vertical vent section and one 90-degree elbow required
Min. 91.5" (2324 mm) Indoor/Outdoor
Top of Fireplace
2 x 4
Figure 7: Min. Height of Combustible Enclosure
Mantel Depth
to bottom of mantel
Distance from top of appliance
Side View
Min. Height of Combustible Enclosure
To provide for the lowest possible combustible enclosure (or shelf) surface, the venting should be routed in a way to minimize obstructions to the space above the appliance. Do not insulate the space between the appliance and the area above it (see Figure 7).
Wall Finishes / Surrounds / Mantels
Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front faces (black sheet metal). Never allow combustible materials to be positioned in front of or overlapping the appliance face. See Pages 29 and 30.
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance front face only if they do NOT cover any portion of the removable glass panel.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel. See Figure 8. Mantels constructed of non­combustible materials may be installed at any height above the appliance opening.
Note: Use high-temperature paint (rated 175°F or higher) on the underside of the mantel.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Inches
(millimeters)
Top of Appliance
Figure 8: Combustible Mantel Clearances
Minimum Distance to Unprotected Side Wall
At 14" minimum side wall clearance, a combustible wall can project to any length.
At 8-1/4" side wall clearance, a combustible wall can project 12" maximum.
Gray area is “safe zone”
14" (356 mm)
8.25" (209 mm)
0.5"
(13 mm)
45°
Protected wall shown in white
Top View of Fireplace
5 in (127 mm)
12 in (305 mm)
17 in (432 mm)
Figure 9: Side Wall Clearances
Combustible materials are allowed in gray “safe zone” illustrated here.
Combustible walls are shown in black.
Protected wall is shown in white.
Combustible material may project beyond the side of the fireplace opening if it is within the gray "safe zone" illustrated here.
9
Page 10
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
PRE-INSTALLATION STEPS
The appliance is shipped with all gas controls and components installed and pre-wired.
1. Remove the shipping carton, exposing the glass door on the control side.
2. Remove glass door assembly (see detailed instructions on Page 27).
WARNING
Failure to position the parts in accordance with these diagrams or failure to use only parts specifi­cally approved with this appliance may result in property damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées.
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation is outlined below.
Note: Each installation is unique and may result in variations to the steps described herein.
See the page numbers referenced in the fol­lowing steps for detailed procedures.
Step 1. FRAMING (Page 10): Construct
appliance framing. Position appliance within framing, and secure with nailing brackets.
Step 2. ROUTE GAS LINE (Page 13):
Route gas supply line to right side (when viewed from control side of appliance).
Step 3. INSTALL VENT SYSTEM (Page 13):
install vent system and exterior termination.
Step 4. FIELD WIRING (Page 20): Connect
120 Vac electrical power to the appliance receptacle.
Step 5. REMOVE GLASS DOOR ASSEMBLY
(Page 22).
Step 6. CONNECT GAS LINE (Page 23):
Make connection to gas supply.
Step 7. INSTALL FIREBOX LINER PANELS
(Page 23).
Step 8. VERIFY APPLIANCE OPERATION
(Page 23).
Step 9. INSTALL VOLCANIC STONE,
GLOWING EMBERS, AND LOGS
(Page 24).
Step 10. INSTALL GLASS DOORS, MESH
PULL SCREENS, AND MODESTY PANEL (Page 27).
Step 11. BURNER ADJUSTMENTS (Page
28): Adjust burner air shutter to ensure proper flame appearance.
FINISHING REQUIREMENTS (Page 29). Step 12. ATTACH SAFETY-IN-OPERATION
WARNINGS (Page 31).
DETAILED INSTALLATION STEPS
Step 1. FRAMING
Frame these appliances as illustrated on Page 11. All framing details must allow for a minimum clearance to combustible framing members as shown on Page 9.
If the appliance is to be elevated above floor level, a solid continuous platform must be constructed below the appliance.
Headers may be in direct contact with the appliance top spacers, but must not be sup­ported by them or notched to fit around them. All construction above the appliance must be self-supporting; DO NOT use the appliance for structural support.
Secure the fireplace to the side framing members using the unit's nailing flanges — one top and bottom on each side of the fireplace front (see Figure 10). Use 8d nails or their equivalent.
Securing Unit to Framing by Nailing Flanges
Use Top Flange for 1/2” Thick Drywall
Front of Fireplace Use Center Flange
for Flush Mount
Use Bottom Flange for 5/8” Thick Drywall
Left Side Front Corner of Fireplace Shown
(Same requirements for right side)
Note: The nailing flanges, combustible
members and screw heads in areas directly adjacent to the nailing flanges are EXEMPT from the 1/2-inch clearance to combustible requirements for the firebox outer wrapper. Combustible framing may be in direct contact with the nailing flanges and may be located closer than 1/2 inch from screw heads and the firebox wrapper in areas adjacent to the nailing flanges. Frame the opening to the exact dimensions specified in the framing details of the Installation
Instructions.
Figure 10
10
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 11
D
B
C
Inches
(millimeters)
A
12-1/8
(308)
5-1/8 (130)
10-1/2
(267)
C
Inches
(millimeters)
1-1/2
(38)
D
A
B
E
~
12-1/8
(308)
5-1/8 (130)
10-1/2
(267)
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
FRAMING DIMENSIONS: See-Through Power Vent
Framing should be constructions of 2x4 or larger lumber.
A
in 52-1/16 47-5/16 99-1/2 26-5/16 6
(mm) (1322) (1202) (2527) (668) (152)
B
C
D
E
Dimension B is from fireplace base to top framing member. Dimension C is from fireplace base to centerline of horizontal vent pipe.
Minimum vent framing: Adaptor plus 4 ft vertical vent and one 90-degree elbow. For other venting configurations, see Step 3, INSTALL VENTING SYSTEM.
1/2-inch board for platform (shown in gray). Dimension E is a 6-inch clearance from fireplace base to outdoor surface (e.g., deck, patio, lanai)
that is required as a moisture barrier (not a combustible clearance) on outdoor side only.
Figure 11
INDOOR SIDE*
*For indoor/outdoor installations, the control side
of the fireplace must be installed on the indoor side.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Outdoor Surface (e.g., deck, patio, lanai)
OUTDOOR SIDE*
11
Page 12
13-3/32
(333)
25-9/32
(642)
7-5/16
(186)
5-13/32
(137)
8"/ 11"
*
Vent/Intake
Top View
inches
(millimeters)
*Adaptor with Probe required to transition from 8"/11" fireplace vent collar to 4-1/2"/7-1/2" venting.
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
8"/ 11"
*
13-3/32
(333)
25-9/32
(642)
7-5/16
(186)
5-13/32
(137)
8"/ 11"
*
Vent/Intake
Top View
inches
(millimeters)
FIREPLACE SPECIFICATIONS: See-Through Power Vent
inches
(millimeters)
13-3/32
(333)
inches
(millimeters)
25-9/32
27-7/16
(697)
3-15/32
(88)
(642)
5-13/32
(137)
26-3/16
(665)
Fireplace Vent Collar
Vent/Intake
8" Inner / 11" Outer
7-5/16
(186)
Top View
inches
(millimeters)
12-5/16
(313)
FIREPLACE COLLAR AND VENT SIZES
Fireplace Vent Collar (Coaxial DV) Vent Pipe (Coaxial DV)
Adaptor/Probe assembly (cat. no. H8313) required to
transition from fireplace vent collar to vent pipe.
34-3/4
(883)
8" Inner / 11" Outer 4-1/2” Inner / 7-1/2” Outer
5-3/32
(130)
12
46-19/32
(1184)
19-17/32
(496)
Figure 12
7 (178)
Control Switch Wires Knock-Out
Left Side View
Gas Inlet
J-Box
29-19/32
(752)
Fireplace Dimensions
(shown with Outdoor Kit installed)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
50-1/2
(1283)
Front View (opposite valve access side)
41-1/2
(1054)
33-3/4
(857)
Page 13
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Step 2. ROUTE GAS LINE
NOTICE: For indoor/outdoor installations,
the CONTROL SIDE of the fireplace must be installed on the INDOOR side.
Route a 1/2" (13 mm) gas line along the inside of the right side framing as shown in Figures 13 and 14. Gas lines must be routed, constructed and made of materials that are in strict accor­dance with local codes and regulations.
All appliances are factory-equipped with a flexible gas line connector and 1/2 inch shutoff valve (see Step 6 on Page 23).
The incoming gas line should be piped into the valve compartment and connected in one of the two methods as shown in Figure 35 on Page 23.
Right Side Front Corner Of Fire­place Framing
19-1/2"
(495 mm)
7”
(178 mm)
Right Side Front Corner
(Valve Side) of Fireplace Framing
Figure 13: INDOOR / INDOOR
1-1/2”
(38 mm)
19-1/2"
7”
(178 mm)
Right Side Front Corner
(Valve Side) of Fireplace Framing
Figure 14: INDOOR / OUTDOOR
(495 mm)
Proper Sizing of Gas Line
Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code, NFPA 54 - latest edition (USA) or CAN/CSA-B149.1
- latest edition (Canada).
IMPORTANT: It is critical that a licensed installer perform this step strictly per NFPA.
Never use galvanized or plastic pipe. Refer to Table 6 for proper sizing of the gas sup­ply line, if black iron pipe is being used. Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations. We recommend that a qualified individual such as a plumber or gas fitter be hired to correctly size and route the gas supply line to the appliance. Installing a gas supply line from the fuel supply to the appliance involves numerous considerations of materials, protection, sizing, locations, controls, pressure, sediment, and more. Certainly no one unfamiliar and unqualified should attempt sizing or installing gas piping.
Note:
• All appliances are factory-equipped with
a flexible gas line connector and 1/2 inch shutoff valve (see Figure 35 on Page 23).
• See Massachusetts Requirements on Page 4 for additional requirements for installations
in the state of Massachusetts in the USA.
• The gas supply line should not be connected
to the appliance until Step 6 (Page 23).
• A pipe joint compound rated for gas should be
used on the threaded joints. Ensure propane resistant compounds are used in propane applications. Be very careful that the pipe
compound does not get inside the pipe.
• It is recommended to install a sediment trap
in the supply line as close as possible to the appliance (see Figure 35 on Page 23). Appliances using Propane should have a sediment trap at the base of the tank.
• Check with local building ofcial for local
code requirements (i.e. are below grade penetrations of the gas line allowed?, etc).
Step 3. INSTALL VENT SYSTEM
General Information
These instructions should be used as a guide­line and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 and
-B149.2 in Canada. These fireplaces are designed, tested and
listed for operation and installation with, and only with, Secure Vent™ (SV4.5) Direct­Vent System Components, manufactured by Security Chimneys International. These ap­proved vent system components are labeled for identification. DO NOT use any other manufacturer's vent components with these appliances.
Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier.
Dégagement conforme aux codes d’installa­tion locaux et aux exigences du foumis­seunde gaz.
Use only approved venting components. See Approved Vent Components on Page 2.
These fireplaces must be vented directly to the outside.
The vent system may not service multiple appliances, and must never be connected to a flue serving a solid fuel burning appliance. The vent pipe is tested to be run inside an enclosed wall (such as a chase). There is no requirement for inspection openings in the enclosing wall at any of the joints in the vent pipe.
Venting System
With the appliance secured in framing, de­termine vent routing and identify the exterior termination location. The following sections describe horizontal (exterior wall) vent applica­tions. A list of approved venting components
is shown on Page 32.
Schedule 40, Black Iron Pipe
Inside Diameter (Inches)
Schedule 40 Pipe
Length (feet)
0-10 1/2 3/8
10-40 1/2 1/2
40-100 1/2 1/2 100-150 3/4 1/2 150-200 3/4 1/2
Natural
Gas
Table 6
Propane
Gas
IMPORTANT NOTE REGARDING
PROPANE INSTALLATIONS
Using a propane tank smaller than 100 lbs may create pressure loss and insufficient fuel delivery, which can cause sooting, severe delayed ignition, or other malfunctions (ref. NPFA 58).
Any damage as a result of insufficient tank size or other improper installation is NOT covered under the limited warranty.
13
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 14
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
1
1
2
3
5
4
6
7
Vent Restrictor
The adaptor/probe assembly for this appli­ance has a pre-installed vent restrictor with a 1-3/4" hole in the center (see Figure 15). This pre-installed vent restrictor is not for use with any venting configuration for this fireplace model and must be replaced with one of the two provided vent restrictors, as described below.
Vent Restrictor Size Guidelines
For venting systems 30 ft in length or less,
replace the factory installed vent restrictor with the provided vent restrictor with a 1-5/8" dia. hole.
For venting systems greater than 30 ft in length, replace the factory installed vent
restrictor with the provided vent restrictor with a 2-1/4" dia. hole.
Vent Restrictor Installation Instructions
Install the appropriate vent restrictor (as described above) into the adaptor/probe assembly per the instructions in Figure 15.
Power Vent Components
Locate the fireplace as per the instructions in this manual. Make the following modifications to add the components used with the Power Vent Kits. This kit can only be used in conjunction with “Direct-Vent” series electronic fireplaces. This installation must conform with local codes or, in the absence of local codes, with the Natural Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CSA B149.1.
CAUTION: This Power Vent Kit cannot be used with Millivolt appliances. Use kit only with the Electronically controlled fireplaces listed for its use as shown in this document.
POWER VENT COMPONENTS
Item No.
1 Vacuum Hose 1 2 Termination Assembly 1 3 SV Termination Adaptor (SV4.5RCH) 1 4 Strain Relief - 3/8” 2 5 Firestop Assembly (Horizontal) 1 6
Hose Clamp - 11/32” 2 7 Snap Bushing 1 8 Ring Terminal - #10 2
Description Qty.
< 30 ft. 1-5/8" Dia. > 30 ft. 2-1/4" Dia.
Vent Restrictor
Adaptor/Probe Assembly (shown upside-down)
Vent Restrictor Installation Instructions
1. Turn the adaptor/probe assembly upside­down, as shown.
2. Remove the four screws securing the vent restrictor in place. Lift out the vent restrictor.
3. Install the appropriate vent restrictor, using the four screws previously removed. See “Vent Restrictor Size
Guidelines,” above.
9 Insulated 1/4” Male Terminal 4
8
9
Figure 16: Power Vent Kit Components
Figure 15: Vent Restrictor
14
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 15
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
6 21 42 63 84
T OOOOO TTTTT AAAAA LLLLL
QQQQQ TTTTT YYYYY
noitceSteN
)sehcni(htgneL
2/1-4 2/1-01 2/1-22 2/1-43 2/1-64
tneVfothgieH snoitceStneVforebmuN
sehcni tf
5.4 573.0 1 0 0 0 0 1
9 57.0 2 0 0 0 0 2
5.01 578.0 0 1 0 0 0 1
51 52.1 1 1 0 0 0 2
5.22 578.1 0 0 1 0 0 1
5.13 526.2 0 3 0 0 0 3
5.43 578.2 0 0 0 1 0 1
5.73 521.3 1 1 1 0 0 3
5.34 526.3 0 2 1 0 0 3
54 57.3 0 0 2 0 0 2
5.64 578.3 0 0 0 0 1 1
15 52.4 1 0 0 0 1 2
5.55 526.4 0 1 2 0 0 3
75 57.4 0 0 1 1 0 2
5.76 526.5 0 0 3 0 0 3
96 57
.5 0 0 0 2 0 2
5.37 521.6 1 0 0 2 0 3
5.97 526.6 0 1 0 2 0 3
18 57.6 0 0 0 1 1 2
5.19 526.7 0 0 2 0 1 3
39 57.7 0 0 0 0 2 2
5.79 521.8 1 0 0 0 2 3
5.301 526.8 0 0 0 3 0 3 801 9 1 0 0 3 0 4
711 57.9 1 0 5 0 0 6
5.811 578.9 1 1 0 3 0 5
621 5.01 0 0 1 3 0 4
5.031 578.01 1 0 1 3 0 5
531 52.11 0 0 6 0 0 6
5.931 526.11 0 0 0 0 3 3
5.241 578.11 1 0 0 4 0 5
441 21 1 0 0 0 3 4
5.451 578.21 1 1 0 0 3 5
5.061 573.31 0 2 0 0 3 5
5.271 573.41 0 0 0 5 0 5
771 57.41 1 0 0 5 0 6
681 5.51 0 0 0 0 4 4
5.691 573.61 0 1 0 0 4 5
702 52.71 0 0 0 6 0 6
5.112 526.71 1 0 0 6 0 7
5.712 521.81 0 1 0 6 0 7
5.922 521.91 0 0 1 6 0 7
5.23
2 573.91 0 0 0 0 5 5
5.142 521.02 0 0 0 7 0 7
642 5.02 1 0 0 7 0 8
252 12 0 1 0 7 0 8
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
6 21 42 63 84
T OOOOO TTTTT AAAAA LLLLL
QQQQQ TTTTT YYYYY
noitceSteN
)sehcni(htgneL
2/1-4 2/1-01 2/1-22 2/1-43 2/1-64
tneVfothgieH snoitceStneVforebmuN
sehcni tf
5.4 573.0 1 0 0 0 0 1
9 57.0 2 0 0 0 0 2
5.01 578.0 0 1 0 0 0 1
51 52.1 1 1 0 0 0 2
5.22 578.1 0 0 1 0 0 1
5.13 526.2 0 3 0 0 0 3
5.43 578.2 0 0 0 1 0 1
5.73 521.3 1 1 1 0 0 3
5.34 526.3 0 2 1 0 0 3
54 57.3 0 0 2 0 0 2
5.64 578.3 0 0 0 0 1 1
15 52.4 1 0 0 0 1 2
5.55 526.4 0 1 2 0 0 3
75 57.4 0 0 1 1 0 2
5.76 526.5 0 0 3 0 0 3
96 57
.5 0 0 0 2 0 2
5.37 521.6 1 0 0 2 0 3
5.97 526.6 0 1 0 2 0 3
18 57.6 0 0 0 1 1 2
5.19 526.7 0 0 2 0 1 3
39 57.7 0 0 0 0 2 2
5.79 521.8 1 0 0 0 2 3
5.301 526.8 0 0 0 3 0 3 801 9 1 0 0 3 0 4
711 57.9 1 0 5 0 0 6
5.811 578.9 1 1 0 3 0 5
621 5.01 0 0 1 3 0 4
5.031 578.01 1 0 1 3 0 5
531 52.11 0 0 6 0 0 6
5.931 526.11 0 0 0 0 3 3
5.241 578.11 1 0 0 4 0 5
441 21 1 0 0 0 3 4
5.451 578.21 1 1 0 0 3 5
5.061 573.31 0 2 0 0 3 5
5.271 573.41 0 0 0 5 0 5
771 57.41 1 0 0 5 0 6
681 5.51 0 0 0 0 4 4
5.691 573.61 0 1 0 0 4 5
702 52.71 0 0 0 6 0 6
5.112 526.71 1 0 0 6 0 7
5.712 521.81 0 1 0 6 0 7
5.922 521.91 0 0 1 6 0 7
5.23
2 573.91 0 0 0 0 5 5
5.142 521.02 0 0 0 7 0 7
642 5.02 1 0 0 7 0 8
252 12 0 1 0 7 0 8
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
6 21 42 63 84
T O T A L
Q T Y
noitceSteN
)sehcni(htgneL
2/1-4 2/1-01 2/1-22 2/1-43 2/1-64
tneVfothgieH snoitceStneVforebmuN
sehcni tf
672 32 0 0 0 8 0 8
972 52.32 0 0 0 0 6 6
5.082 573.32 1 0 0 8 0 9
5.982 521.42 0 1 0 0 6 7
5.103 521.52 0 0 1 0 6 7
5.013 578.52 0 0 0 9 0 9
5.523 521.72 0 0 0 0 7 7
033 5.72 1 0 0 0 7 8
543 57.82 0 0 0 01 0 01
5.943 521.92 1 0 0 01 0 11
273 13 0 0 0 0 8 8
5.973 526.13 0 0 0 11 0 11
5.814 578.43 0 0 0 0 9 9
564 57.83 0 0 0 0 01 01
5.574 526.93 0 1 0 0 01 11
084 04 1 1 0 0 01 11
294 14 1 0 1 0 01 21
5.994 526.14 0 0 0 1 01 11
405 24 1 0 0 1 01 21
5.115 526.24 0 0 0 0 11 11
5.025 573.34 0 2 0 1 11 41
135 52.44 0 2 2 0 11 51
5.835 578.44 1 0 0 2 11 41
945 57.54 1 0 2 1 11 51
855 5.64 0 0 0 0 21 21
5.265 578.64 1 0 0 0 21 31
5.865 573.74 0 1 0 0 21 31
375 57.74 1 1 0 0 21 41
5.085 573.84 0 0 1 0 21 31
5.985 521.94 0 1 2 2 01 51
5.595 526.94 1 1 1 0 21 51
5.406 573.05 0 0 0 0 31 31
516 52.15 0 1 0 0 31 41
5.526 521.25 0 2 0 0 31 51
5.136 526.25 1 0 1 0 31 51
5.736 521.35 0 1 1 0 31 51
156 52.45 0 0 0 0 41 41
5.556 526.45 1 0 0 0 41 51
276 65 0 2 0 0 41 61
876 5.65 1 0 1 0 41 61
5.886 573.75 1 1 1 0 41 71
5.796 521.85 0 0 0 0 51 51
207 5.85 1 0 0 0 51 61
5.217 573.95 1 1 0 0 51 71
027 06 0 0 1 0 51 61
TRAHCHTGNELNOITCESTNEV
lanimoN
htgneLnoitceS
)sehcni(
6 21 42 63 84
T O T A L
Q T Y
noitceSteN
)sehcni(htgneL
2/1-4 2/1-01 2/1-22 2/1-43 2/1-64
tneVfothgieH snoitceStneVforebmuN
sehcni tf
672 32 0 0 0 8 0 8
972 52.32 0 0 0 0 6 6
5.082 573.32 1 0 0 8 0 9
5.982 521.42 0 1 0 0 6 7
5.103 521.52 0 0 1 0 6 7
5.013 578.52 0 0 0 9 0 9
5.523 521.72 0 0 0 0 7 7
033 5.72 1 0 0 0 7 8
543 57.82 0 0 0 01 0 01
5.943 521.92 1 0 0 01 0 11
273 13 0 0 0 0 8 8
5.973 526.13 0 0 0 11 0 11
5.814 578.43 0 0 0 0 9 9
564 57.83 0 0 0 0 01 01
5.574 526.93 0 1 0 0 01 11
084 04 1 1 0 0 01 11
294 14 1 0 1 0 01 21
5.994 526.14 0 0 0 1 01 11
405 24 1 0 0 1 01 21
5.115 526.24 0 0 0 0 11 11
5.025 573.34 0 2 0 1 11 41
135 52.44 0 2 2 0 11 51
5.835 578.44 1 0 0 2 11 41
945 57.54 1 0 2 1 11 51
855 5.64 0 0 0 0 21 21
5.265 578.64 1 0 0 0 21 31
5.865 573.74 0 1 0 0 21 31
375 57.74 1 1 0 0 21 41
5.085 573.84 0 0 1 0 21 31
5.985 521.94 0 1 2 2 01 51
5.595 526.94 1 1 1 0 21 51
5.406 573.05 0 0 0 0 31 31
516 52.15 0 1 0 0 31 41
5.526 521.25 0 2 0 0 31 51
5.136 526.25 1 0 1 0 31 51
5.736 521.35 0 1 1 0 31 51
156 52.45 0 0 0 0 41 41
5.556 526.45 1 0 0 0 41 51
276 65 0 2 0 0 41 61
876 5.65 1 0 1 0 41 61
5.886 573.75 1 1 1 0 41 71
5.796 521.85 0 0 0 0 51 51
207 5.85 1 0 0 0 51 61
5.217 573.95 1 1 0 0 51 71
027 06 0 0 1 0 51 61
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
VENT SECTION LENGTHS
Determine the number of straight vent sections required. 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46­1/2" (1181 mm) net section lengths are available. Refer to the Vent Section Length Chart.
Vertical (Offset) Installation
Analyze the vent routing and determine the quantities of vent sections and number of elbows required. Refer to Figures 21 and 22 on Page 17 showing vent run requirements to aid in selecting the type of vertical installation desired. Vent sections are available in net lengths of 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm). Refer to the Vent Section Length Chart for an aid in selecting length combinations. Elbows are available in 90° and 45° configura­tions. Refer to Figure 20 on Page 16 for the SV4.5 E45 and SV4.5 E90 elbow dimensional specifications.
Where required, a telescopic vent section (SV4.5LA) may be used to provide the in­staller with an option in installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location, or will not build up to the required length. The SV4.5LA Telescopic Vent Section has an effective length of from 1-1/2" (38 mm) to 6-3/4" (171 mm). The SV4.5LA is fitted with a dimpled end (identical to a normal vent section component) and a plain end with 3 pilot holes. Slip the dimpled end over the locking channel end of a standard SV4.5 vent component the required distance and secure with three screws.
Maintain a minimum 1" (25 mm) clearance to combustible materials for all vertical ele­ments. Clearances for all horizontal elements are 3" (76 mm) on top, 1" (25 mm) on sides and 1" (25 mm) on the bottom.
Table 7
Effective Vent Length
Model Effective Length
SV4.5L6 4-1/2" SV4.5L12 10-1/2" SV4.5L24 22-1/2" SV4.5L36 34-1/2" SV4.5L48 46-1/2"
Note: Convert inches into metric equivalent measurement, as follows:
Millimeters (mm) = Inches x 25.4 Centimeters (cm) = Inches x 2.54 Meters (M) = Inches x .0254
15
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 16
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
7-5/8
(194 mm)
4-13/16
(122 mm)
A. Frame ceiling opening. Use a plumb line from the ceiling above the appliance to locate center of the vertical run. Cut and/or frame an opening, 10-1/2" x 10-1/2" (267 mm x 267 mm) inside dimensions, about this center mark (Figure 17).
Min. 10-1/2" (267 mm)
Min. 10-1/2" (267 mm)
Plumb Bob
Ceiling Framing
Figure 17: Ceiling Opening Framing
B. Attach adaptor (with probe) to appliance collar. Secure Vent™ SV4.5 direct-vent sys-
tem components are unitized concentric pipe components featuring positive twist lock con­nections (see Figure 18).
All of the appliances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the adaptor fits over the appliance collar to create the positive twist lock connection.
Align the dimple (four places) of the upper vent section with the opening of the locking incline channel on the lower vent section or appliance collar. Twist vent component clock­wise to engage and seal until arrow
Arrow
and dimple align.
Dimple
Locking Incline Channel
The unitized design of the Secure Vent com­ponents will engage and seal both the inner and outer pipe without the need for sealant or screws. If desired a #6 x 1/2" screw may be used at the joint, but it is not required as the pipe will securely lock when twisted.
C. Attach vent components to each other. Other vent sections may be added to the previously installed section in accordance with the require­ments shown in Figures 21 and 22 on Page 17.
To add another vent component to a length of vent run, align the dimpled end over the inclined channel end of the previously installed section, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section.
Push the vent component against the previ­ous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels. This seating
position is indicated by the alignment of the arrow and dimple as shown in Figure 18.
D. Install firestop/spacer at ceiling. When
using Secure Vent, use SV4.5VF firestop/spacer at ceiling joists. If there is living space above the ceiling level, the firestop/spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/ spacer must be installed on the top side of the joist. Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner. Remember to maintain 1" (25 mm)
clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections. Attic insulation shield (H3907) may be used to obtain the required clearances indicated here. See installation accessories on Page 32. The gap between the vent pipe and a vertical firestop can be sealed with non-combustible caulking.
E. Support the vertical vent run sections.
Note: Proper venting support is very important. The weight of the vent must not be supported by the fireplace in any degree.
Support the vertical portion of the venting system every 8 feet (2.4 m) above the fireplace vent outlet. One method of support is by utiliz­ing field provided support straps (conventional plumber's tape). Secure the plumber's tape to the framing members with nails or screws. Strap the tape around the vent, securing the ends of the tape to the framing. If desired, sheet metal screws #6 x 1/2" length may be used to secure the support straps to the vent pipe (see Figure 19).
F. Change vent direction to horizontal/inclined run. At transition from or to a horizontal/inclined
run, install the SV4.5 E45 and SV4.5 E90 elbows in the same manner as the straight vent sec­tions. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element.
Twist elbow sections in a clockwise direction only so as to avoid the possibility of unlocking any of the previously connected vent sections
(see Figures 18 and 20).
8-1/8"
(206 mm)
Swivel Joint
(360° swivel)
SV4.5E45
45° Elbow)
Swivel Joint
(360° swivel)
SV4.5E90
90° Elbow)
Figure 20
G. Continue installation of horizontal/inclined sections. Continue with the installation of the
straight vent sections in horizontal/inclined run as described in Step C. Install support straps every 3' (914 mm) along horizontal/inclined vent runs using conventional plumber’s tape (see Page 17, Figure 21).
Connected Vent Sections
Adaptor on Appliance Collar or Vent Section
Figure 18
To attach a vent component to the adaptor on appliance collar, align the dimpled end over the adaptor collar, adjusting the radial alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar (refer to Figure 18). Push the vent component against the collar until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the end of the channels.
16
Arrow
Blocking
Support Straps
(plumber’s tape)
Max.
8 ft (2.4 m)
Min. 0" (0 mm) clearance to spacers
Figure 19
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
NOTICE: It is important to install
horizontal runs on a steady, (i.e., no “dips”), slightly positive incline of approximately 1/4 inch rise-per-foot (20 millimeters rise-per-meter) horizontal, in a direction away from the fireplace.
(Slightly smaller rise-per-foot run ratios are acceptable.) Use a carpenter’s level to measure from a constant surface, and adjust support straps as necessary.
It is important to maintain the required clear­ances to combustibles: 1" (25 mm) at all sides for all vertical runs; and 3" (76 mm) at the top, 1" (25 mm) at sides, and 1" (25 mm) at the bottom for all horizontal/inclined runs.
Page 17
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
VENT FIGURES
Note:
• Secure Vent™ components (rigid vent pipe and terminal) are shown in the gures.
• Two 45 degree elbows may be used in place of one 90 degree elbow.
• SV4.5VF (Secure Vent) restop/spacer must be used anytime vent pipe passes through a
combustible floor or ceiling. SV4.5HF (Secure Vent) firestop/spacer must be used anytime vent pipe passes through a combustible wall.
Power Vent Termination
Exterior Wall
Horizontal / Inclined Run
SV4.5L 6 / 12 / 24 / 36 / 48
Vent Sections
Firestop / Spacer
Maximum Horizontal
Venting 110 Feet.
Up to 6 Elbows
Support Brackets
Ceiling
Adaptor/Probe Assembly (required)
NOTICE: It is important to install
horizontal runs on a steady, (i.e., no “dips”), slightly positive incline of approximately 1/4 inch rise-per-foot (20 millimeters rise-per-meter) horizontal, in a direction away from the fireplace.
(Slightly smaller rise-per-foot run ratios are acceptable.) Use a carpenter’s level to measure from a constant surface, and adjust support straps as necessary.
Building Support Framing
SV4.5E90 Elbow
Vertical Rise
66 Feet Max.
4 Feet Min.
Minimum
Vent Run
Horizontal
10 Feet
Adaptor/Probe
Assembly
(required)
Power Vent Termination
Exterior Wall
Figure 21: Typical Power Vent Routing
POWER VENT VENTING CHART
Maximum Number Of Elbows 6 Maximum Feet Of Run A + B 110 feet Minimum Horizontal Run B 10 feet
Minimum Vertical Run A
Maximum Vertical Rise A 66 ft
Adaptor plus 4 ft (min.)
Vertical Vent and 90° Elbow
MINIMUM CLEARANCES TO COMBUSTIBLES
Vertical Vent Pipe 1.0 in. (25.4 mm)
Horizontal Vent Pipe
Top - 3.0 in. (76.2 mm)
Sides - 1.0 in. (25.4 mm)
Bottom - 1.0 in. (25.4 mm)
Fireplace
Floor
B
A
Adaptor/Probe Assembly (Required)
Figure 22
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
17
Page 18
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
HORIZONTAL (OUTSIDE WALL) TERMINATION SYSTEM
See Figures 21 and 22 on Page 17 illustrating the various horizontal venting configurations that are possible for use with these appliances. The table in Figure 22 on Page 17 shows each system’s minimum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications.
The horizontal vent system terminates through an outside wall. Building Codes limit or prohibit terminating in specific areas. Refer to Figure 3
on Page 6 for location guidelines. Secure Vent™ SV4.5 direct-vent system com-
ponents are unitized concentric pipe compo­nents featuring positive twist lock connection, (refer to Figure 18 on Page 16). All of the appliances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent components fit over the appliance collar to create the positive twist lock connection.
A. Plan the vent run. Analyze the vent routing and determine the
types and quantities of sections required 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm) net section lengths are available. Make allowances for elbows as indicated in Figure 20 on Page 16.
Maintain a minimum 1" (25 mm) clearance
to combustibles on the vertical sections. Clearances for the horizontal runs are; 3" (76 mm) on top, 1" (25 mm) on sides, and 1" (25 mm) at the bottom.
B. Frame exterior wall opening.
Locate the center of the vent outlet on the
exterior wall according to the dimensions shown in Figure 11 on Page 11.
Cut and/or frame an opening, 10-1/2" x 12-
1/8" (267 mm x 308 mm) inside dimensions, with 7-1/2" above center and 5-5/8" below
center.
C. Frame ceiling opening. If the vertical route is to penetrate a ceiling,
use plumb line to locate the center above the appliance. Cut and/or frame an open­ing, 10-1/2" x 10-1/2"(267 mm x 267 mm) inside dimensions, about this center (refer to Figure 17 on Page 16).
18
D. Attach vent components to appliance. To attach a vent component to the appliance
collar, align the dimpled end over the collar, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels on the collar (refer to Figure 18 on Page 16).
Push the vent component against the collar
until it fully engages, then twist the compo­nent clockwise, running the dimples down and along the incline channels until they seat at the end of the channels. The unitized design of the Secure Vent components will engage and seal both the inner and outer pipe elements with the same procedure. Sealant and securing screws are not required.
E. Attach vent components to each other. Other vent sections may be added to the
previously installed section in accordance with the requirements of the vent tables. To add another vent component to a length of vent run, align the dimpled end of the component over the inclined channel end of the previously installed section, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section. Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels. This seating
position is indicated by the alignment of the arrow and dimple as shown in Figure 18 on Page 16.
F. Install firestop/spacer at ceiling.
When using Secure Vent, use SV4.5VF fire-
stop/spacer at ceiling joists. If there is living space above the ceiling level, the firestop/ spacer must be installed on the bottom side of the ceiling. If attic space is above the ceil­ing, the firestop/ spacer must be installed on the top side of the joist. Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Remember to maintain 1" (25 mm) clear-
ance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections.
G. Support the vertical run sections.
On the vertical run, support the venting
system every 8 feet (2.4m) above the fire­place vent outlet with field provided support straps (Plumber's tape). Attach the straps to the vent pipe and secure to the framing members with nails or screws. See Figure 19 on Page 16.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
H. Change vent direction.
At transition from or to a horizontal/inclined
run, install the SV4.5E45 and SV4.5E90 elbows in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element. Twist elbow sections in
a clockwise direction only so as to avoid the possibility of unlocking any of the previously connected vent sections (see Figures 18 and 20 on Page 16).
I. Continue installation of horizontal/inclined
sections.
Continue with the installation of the straight
vent sections in horizontal/inclined run as described in Step E. Install support straps every 3 feet (1914 mm) along horizontal/ inclined vent runs using conventional plumber’s tape.
See Figure 21 on Page 17.
NOTICE: It is important to install
horizontal runs on a steady, (i.e., no “dips”), slightly positive incline of approximately 1/4 inch rise-per-foot (20 millimeters rise-per-meter) horizontal, in a direction away from the fireplace.
(Slightly smaller rise-per-foot run ratios are acceptable.) Use a carpenter’s level to measure from a constant surface, and adjust support straps as necessary.
Installing Power Vent Termination
J. Assemble vent run to exterior wall.
If not previously measured, locate the cen-
ter of the vent on the exterior wall. Prepare an opening as described in this manual. Assemble the vent system to a point where the terminus of the last section is within 8 inches of the outside wall surface where the power vent is to be mounted (refer to Figure 24 on Page 19).
If the terminus of the last section is not
within this distance, use the telescopic vent section SV4.5LA, as the last vent section. For wall thicknesses greater than that shown in Figure 24 on Page 19, refer to Table 8 (Page 19) for the additional venting compo­nents needed (in addition to the termination and adaptor) for a particular range of wall thicknesses.
K. Attach termination adaptor. Attach the adaptor (SV4.5RCH, provided
with the power vent kit) to the vent section telescoping vent section, or elbow, as shown in Figures 23 and 24 on Page 19 in the same manner as any SV4.5 vent component.
Page 19
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
L. Install Firestop/Spacer at exterior wall. Install SV4.5HF Firestop/Spacer, provided
with the power vent kit, over the opening at the exterior side of the framing, long side up, with the 3 inch spacer clearance at the top as shown in Figure 23, and nail into place.
(The Firestop/Spacer may also be installed
over the opening at the interior side of the framing).
M. Install the Power Vent termination. For the last step, from outside the exterior
wall, slide the collars of the termination onto the adaptor (the outer inside the outer and the inner outside the inner) until the termi­nation seats against the exterior wall sur­face to which it will be attached. Orient the housing of the termination with the arrow pointed upwards. Secure the termination to the exterior wall. The termination must
not be recessed into the exterior wall or siding by more that the 1-1/4” (32 mm) as
shown in Figure 24.
The Power Vent termination has been designed to perform in a wide range of weather conditions. Our terminations meet or exceed industry standards.
When selecting the location of your ter­mination, do not place the termination where water from eaves and adjoining roof lines may create a heavy flow of cascading water onto the terminations. If the termination must be placed where the possibility of cascading water exists, it is the responsibility of the builder to direct the water away from the termination cap by using gutters or other means.
Take care to carefully follow the Instal­lation Instructions for the termination, including the use of silicone caulking where required.
Firestop/Spacer (SV4.5HF) shown on the exterior side of the wall. It may also be installed on the interior side.
7"
5-1/8"
(130 mm)
(178)
12-1/8"
(308 mm)
Termination Adaptor SV4.5RCH
6 to 48 inch Vent Section, Telescopic vent section, Elbow or Appliance Collar
10-1/2"
(267 mm)
NOTE: Centerline of Vent Piping is NOT the Same as the Centerline of the Frame Opening.
Base of Appliance
See Figure 10 on Page 10 for Minimum Distance to Base of Appliance
Figure 23: Installing Power Vent Horizontal Termination
*Use silicone caulking to seal the top and sides of the termination, up to the underlayment, stucco, or masonry wall surface.
Siding
Caulk*
Caulk*
Stucco
Maximum Extent of Vent Run Sections Relative to Exterior Surface of Framing
**For thicknesses greater than 9-1/4”, see Table 8
Interior Surface of Finished Wall
Last Vent Section. Use Telescopic Vent Section (SV4.5LA), If Necessary
Power Vent Termination
Termination
Adaptor
SV4.5RCH
Power Vent Termination
3"
(76 mm)
1"
(25.4 mm)
Maximum wall thickness 9-1/4 in.(235 mm)**
Exterior Surface of Siding
Exterior Surface of Framing
6 in. to 9-1/4 in. (152 to 235 mm)**
Power Vent Termination
1-1/4" Maximum Recess of the Square Termina­tion into Exterior Finish­ing Material
See Table 8 as an aid in venting component selection for a particular range of exterior wall thicknesses.
IMPORTANT: The vent termination is hot while in operation and for a period of time following the use of the fireplace. Young children should be carefully supervised when they are in the same area as a hot termination.
Venting Connection and Exterior Wall Recessing
Figure 24
of the Power Vent Horizontal Termination
Venting Components Required for Various Exterior
Wall Thicknesses, When Using The Power Vent Termination
Vent Components Required Exterior Wall Thickness - inches (mm)
Termination Kit Only 6 to 9-1/4 (152 to 235) Termination Kit and 6 In. Vent Section
(SV4.5L6) Termination Kit and 12 in. Vent Section
(SV4.5L12) Termination Kit and Telescopic Section
(SV4.5L12)
10-3/4 to 14 (273 to 356)
16-3/4 to 20 (426 to 508)
11-3/4 to 20 (299 to 508)
Table 8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
19
Page 20
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Step 4. FIELD WIRING
CAUTION: Label all wires prior to disconnection when servic­ing controls. Wiring errors can cause improper and dangerous operation.
ATTENTION: Au moment de l'entretien des commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de cáblage peu-vent entraîner un fonctionnement inadéquat et dangereux.
Verify proper operation after servicing.
S'assurer que l'appareil fonctionne adé-quatement une fois l'entretien terminé.
CAUTION: Ground supply lead must be connected to the wire attached to the green ground screw located on the outlet box. See Figures 32 and 33 on Page 22. Failure to do so will result in a potential safety hazard. The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70-latest edition (In Canada, the current CSA C22-1 Canadian Electrical Code).
14 Gage Grounded Romex
Route Wiring
NOTE: Electrical wiring must be performed by a qualified electrician.
• Install the strain relief in the hole provided on the right side of replace
for the electrical wiring (refer to Figure 25). Standard Instruction (For use when access to the termination is
difficult because of height or other reasons).
• Locate a locally procured electrical junction box within reach of the
termination wiring pigtail (refer to Figure 28 on Page 21) and route the pigtail to the junction box as the termination is installed.
• Route 14 gauge AWG grounded Romex wiring (not provided) from
the fireplace to the just installed junction box close to the termina­tion. Ensure the wiring is safety plated to prevent damage by framing nails and finish drywall screws. Route the wire into the lower control compartment and cut to length before installing the terminals. Install provided wiring hardware on the ends of the Romex wire.
• Refer to Figure 29 on Page 21 and install the electrical hardware on the ends of the Romex wiring. Male terminals on the Black and White wires, and ring terminals on the ground wire.
• Using standard electrical practices and the terminals provided, con­nect the three wires of the Romex cable to the termination pigtail within the Electrical junction box. Ensure ground.
• The replace end of the Romex will be addressed in Connecting The Power Vent To The Fireplace Control System.
Wall Switch Harness
Figure 25
Strain Relief
Vacuum Hose
Snap Bushing
Probe (1 *)
Hose Clamp (7 *)
Right Side
of Fireplace
Junction Box
Vacuum Hose
Pressure Switch
Pressure switch is located behind the panel on the right side of firebox
Vacuum Hose
Pressure Switch
Adaptor Assembly
*See Figure 15 on Page 13.
Figure 26: Vacuum Hose Connection To Probe
20
Vacuum Hose (2 *)
Figure 27: Vacuum Hose Connection To Pressure Switch
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 21
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Wiring: Fireplace (See Figures 32 and 33 on Page 22)
Note: These electronic appliances must be connected to the main power
supply. The gas valve is set in place and pre-wired at the factory.
1. Route a 3-wire 120Vac 60Hz 1ph power supply to the appliance junc-
tion box.
2. Remove the electrical inlet cover plate from the side of the unit by remov-
ing the plate's securing screws (see Figure 12 on Page 12).
3. Remove the cover plate's knockout and then feed the power supply wire
through the knockout opening and into the unit junction box.
4. Connect the black power supply wire to the power outlet's red pigtail lead and the white power supply wire to the common terminal of the outlet as shown in Figures 31 and 32.
5. Connect the ground supply wire to the pigtail lead attached to outlet's green ground screw.
6. After the wiring is complete, replace the cover plate.
Wiring: Power Vent Termination
Alternate Instructions (For use when access to the termination is easy
and a secondary electrical junction box installation is not desired).
• Remove the junction box cover from the termination by removing the
attaching screw (refer to Figure 28).
• Loosen the strain relief on the termination shown in Figure 28. Pull
the pigtail in and shorten it to fit within the junction box cover.
• Route 14 gauge AWG grounded Romex wiring (not provided) from
fireplace to the J-Box at the termination. Ensure the wiring is safety plated to prevent damage by framing nails and finish drywall screws. Route the wire into the lower control compartment and cut to length before installing the terminals. Install provided wiring hardware on the fireplace end of the Romex wire.
• Refer to Figure 32 on Page 22 and install the electrical hardware on
the fireplace end of the Romex wiring. Male terminals (#10) on the Black and White wires, and ring terminals (#9) on the ground wire. The termination end of the Romex will be connected to the termination with wire nuts (not provided).
• Refer to Figure 31 to connect the three wires of the Romex cable to
the termination. Ensure the ground ring terminal is grounded beneath a structural screw as shown. Attach the junction box cover to the termination with the screw previously removed.
• The replace end of the Romex will be addressed in Connecting The
Power Vent To The Fireplace Control System.
Black and White
Romex
Ground Wire
Figure 29: Romex
Strain Relief
Figure 30: Back Of Termination
Pigtail Wires Cut
Off And Shortened
7
6
Romex Wire
Ground Romex To The Termination
Pigtail
Junction Box Cover
Figure 28: Bottom of Termination
Strain Relief Holding Romex
Figure 31: Junction Box Cover Removed
Attaching Screw
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Wire Nuts
21
Page 22
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
J-BOX/RECEPTIACLE
WIRING
120V, 60HZ, 1PH
Factory Wired
Field Wired
Junction Box
Tab Intact
Tab Intact
n e e r G - d n u o r G
e t i h W - l a r
t u e N
120 VAC - Black
Green Ground Screw
White
Green
Neutral Side of Receptacle
Hot Side of Receptacle
Black
120V AC
Junction Box
Hot
Neutral
Ground
B
W
G
Wall Receiver
Wiring Color Code
B = Black BL = Blue
AC/DC
Power Adaptor
BR = Brown G = Green
Ground
B
Pressure
Switch
Cable Harness 102661-01
PU = Purple
GY = Gray
W = White
O= Orange
B
Hi-Temp Sleeve
Figure 32: Electronic Wiring Diagram
ELECTRONIC WIRING DIAGRAM FOR POWER VENT FIREPLACES
B
BR
Y
O
Exhaust Blower Control Module
102663-01
R
R = Red Y = Yellow
G
GY
NOT USED
W
Exhaust Blower
(Field Installed)
W
G
B
BR
O
Y
W
G
BL
PU
O
G
Y
Electronic Modulation
Step 5. REMOVE GLASS DOOR ASSEMBLY (ON CONTROL SIDE)
Proflame Valve
DFC Wire Harness 102662-01
Y
G
O
W
W
G
BL
PU
THIS CONNECTOR NOT USED ON POWER VENT UNITS
Electronic Pilot Assembly
Igniter Rod
Hood
B
Pilot Tube
Pilot Ground Wire
R
Y
Flame Sensor
Spark Wire Cable
Pilot Sensor Cable
Proflame DFC Board
Figure 33: Junction Box Wiring
WARNING
Handle this glass with extreme care! Glass is susceptible to damage – Do not scratch or handle roughly while reinstall­ing the glass door frame.
Do not attempt to substitute the materials used on this door, or replace cracked or broken glass with any materials other than those provided by the appliance manufacturer.
The glass door of this appli­ance must only be replaced as a complete unit as provided by the manufacturer. Do not attempt to replace broken, cracked or chipped glass separately.
If not already done, remove the glass door assembly on the control side of the fireplace (see Page 27).
22
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 23
Gas Valve
3/8" NPT x
Flare Fitting
3/8" Flex Tubing
3/8" Nipple
3/8" Union
3/8" Close Nipple
3/8" Shut-off Valve
1/2" x 3/8"
Reducer
Gas
Stub
1/2" x 3/8" Flare
Shut-off Valve
Gas Solid Line Connector
Gas Flex Line Connector
*Sediment Trap
3"
Min
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Step 6. CONNECT GAS LINE
All codes require a shut-off valve mounted in the supply line. The orientation of the shut-off valve should face the front. Figure 35 illustrates two methods for connecting the gas supply. A Sediment Trap is recommended to prevent moisture and debris in gas line from damaging the valve.
The flex-line method is acceptable in the U.S.A. where local codes permit, however, Canadian requirements vary depending on locality. In­stallation must be in compliance with local codes. These appliances are equipped with a gas flex-line for use in connecting the unit to the gas line.
See Figure 35 for flex-line description. The flex- line is rated for both natural and propane gas.
A manual shut off valve is also provided with the flex-line. The gas control valve is located on the right side of the unit.
When using solid gas line connector, access the valve by removing the front door assembly on the control side and the access plate (refer to Figure 34).
The electronic control valve has a 3/8" (10 mm) NPT thread gas supply inlet.
Secure all joints tightly using appropriate tools and sealing compounds (ensure propane resistant compounds are used in propane ap­plications). It is recommended to seal around the gas line to prevent cold air leakage.
Bring the shutoff valve on the end of the flex-line over to the hard pipe and tighten with wrenches from above through the firebox opening.
Right Side
Modesty Panel
Access Plate
TEST ALL CONNECTIONS FOR GAS LEAKS (FACTORY AND FIELD):
WARNING
Never use an open flame to check for leaks.
Turn on gas supply and test for gas leaks us­ing a gas leak test solution (also referred to as bubble leak solution). Note: Using a soapy
water solution is an effective leak test solution but it is not recommended, because the soap residue that is left on the pipes/fittings can result in corrosion over time.
A. Light the appliance (refer to the lighting
instructions label in control compartment or in the Care and Operation Instructions manual).
B. Brush all joints and connections with the gas
leak test solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the receiver or remote control to the “OFF” posi­tion. Either tighten or refasten the leaking connection, then retest as described above.
C. When the gas lines are tested and leak free
be sure to rinse off the leak testing solution.
D. Reinstall the access plate, making certain
the gasket has not been damaged.
Step 8. VERIFY APPLIANCE OPERATION
Turn on burner; then observe the individual tongues of flame on the burner. Make sure all ports are open and producing flame evenly across the burner. If any ports are blocked, or partially blocked, clean out the ports.
With gas line installed run initial system check­out before closing up the front of the unit. Follow the pilot lighting instructions provided.
Note: Lighting Instructions are also found on the literature tag tied to the bracket above the gas valve. To access the tag, reach into the right side opening.
When first lighting the appliance, it will take a few minutes for the line to purge itself of air. Once purging is complete, the pilot and burner will light and operate as indicated in the instruction manual. Subsequent lighting of the appliance will not require such purging. Inspect the pilot flame (remove logs, if neces­sary, handling carefully).
Appliance Checkout
To light the burner, refer to the lighting instruc­tions in the Care and Operation Instructions manual or the lighting label located behind right panel. Ensure the igniter lights the pilot. The pilot flame should engulf the flame sensor as shown in Figure 36.
Note: The gas supply line must be installed in accordance with building codes by a qualified installer approved and/or licensed as required by the locality. In the Commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter.
Main Gas
Shut-Off Valve
Gas Valve
Control Compartment Access
Figure 34
Figure 35: Gas Connection
Step 7. INSTALL FIREBOX LINER PANELS
Install the ceramic or porcelain liner panels per the instructions provided in the kit.
NOTICE: Panel liners must be
installed before operating fireplace.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
PILOT ASSEMBLY
Proper Pilot Flame Appearance
Igniter Rod
Flame Sensor
Figure 36
Pilot Hood
Pilot Nozzels
23
Page 24
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Step 9. INSTALL VOLCANIC STONE, GLOWING EMBERS, AND LOGS
9-1. Remove mesh pull screens, modesty panel, and glass door as-
sembly from one side of fireplace. See Page 27.
9-2. Locate materials (log set, bag of glowing embers, and bags of
volcanic stone).
Note: LOGS ARE FRAGILE! Handle with care to prevent breakage.
9-3. Install volcanic stone. Place some of the volcanic stone on the
firebox floor around the grate (the entire bag of volcanic stone will NOT be used).
Note: Do NOT place volcanic stone on burner.
9-4. Prepare and install glowing embers.
Note: This appliance is provided with enough glowing ember material for several applications. Do NOT use the entire contents of a new bag at one time.
a) Separate some of the glowing ember material into pieces about
the size and thickness of a dime (see Figure 37). Keep the
pieces fluffed up, not matted.
IMPORTANT! Ember pieces must be
as SMALL and THIN as a dime.
b) Distribute the dime-sized pieces over the surface of the burner,
in the areas shown in Figures 38 and 39.
Note: To prevent flame impingement and soot, do not use more ember material than necessary.
c) For best glowing effect, replace ember material annually.
Note: Use only catalog number H8312 Glowing Embers with this fireplace.
Bag of Glowing Embers
Separate glowing ember material into THIN, square, dime-sized pieces.
Figure 37: Preparation of Glowing Ember Material
B
A
C
Control Side
Figure 38: Placement of Glowing Ember Pieces
WARNING
DO NOT attempt to install the logs until the appli­ance installation has been completed, the gas line connected and tested for leaks, and the initial burner operation has been checked out.
Logs get very hot and will remain hot up to one hour
after gas supply is turned off. Handle only when logs are cool. Turn off all electricity to the appliance before you install volcanic stone, embers and logs.
The size and position of the log set was engineered
to give the appliance a safe, reliable and attractive flame pattern. Any attempt to use a different log set in the fireplace will void the warranty and will result in incomplete combustion, sooting, and poor flame quality.
This appliance is not designed to burn wood. Any
attempt to do so could cause irreparable damage to the appliance and prove hazardous to your safety.
If logs are not installed according to the log installa-
tion instructions, flame impingement and improper combustion could occur and result in soot and/or excessive production of carbon monoxide (CO), a colorless, odorless, toxic gas.
Place embers in circled areas.
Control Side
(top view of burner shown)
Place glowing ember material in circled areas ONLY.
Do NOT place glowing ember material over main flame gas ports.
To prevent flame impingement and soot, do not use more ember
material than necessary.
Figure 39: Placement of Glowing Ember Pieces
24
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 25
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
9-5. Install logs (reference Figure 40 and Table 9).
Note: Logs are FRAGILE! Handle with care to prevent breakage.
Left Rear Log
E
Left Front Log
Center Rear Log
Center Log
C
Right Rear Log
D
A
Right Front Log
F
Figure 40: Top View of Logs
LOG SET
Item* Description Item* Description
A Log, Center D Log, Top Right B Log, Right Rear E Log, Top Left C Log, Left Front F Log, Top Front
*Item letters correspond to photos.
FIREBOX ACCESSORIES/PARTS
Cat. No. Model Description
H8312 PGE Bag of Glowing Embers 80L42 FDVS Bag of Volcanic Stone
Table 9
9-6. Place rectangular notches on underside of Center Log A (Figure
42) over Boss #1 and Boss #4 (Figure 41).
B
Pin
A
Landing
Figure 42
9-7. Place notch on underside of Right Rear Log B (Figure 43) over
Boss #2 (Figure 41).
Place opposite end of Right Rear Log B (Figure 43) on Landing for
Log B (see Figure 41).
Landing for Log D
(see Step 9-9 and Figure 45 on next page)
B
Boss #1 Boss #2
Boss #3 Landing for Log C
Landing for Log B
[VALVE ACCESS SIDE]
Figure 41: Burner Bosses and Landings
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 43
9-8. See Figures 41 and 44. Place notch on underside of Left Front
Log C over Boss #3.
Place opposite end of Left Front Log C on Landing for Log C (see
Figure 41).
C
Boss #4
Figure 44
25
Page 26
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
9-9. Place groove on underside of Top Right Log D over the grate as
shown in Figure 45.
The middle section of Log D will rest on the landing on Log B
(labeled as “Landing for Log D” in Figure 43).
Groove Location
D
B
Figure 45
9-10. See Figure 46. Place hole on underside of Top Left Log E over pin
on Center Log A.
9-11. See Figure 47. Place groove on underside of Top Front Log F over
the grate finger. Rest the other end of the log on the Landing on Center Log A.
A
Landing
Groove Location
F
Figure 47
Figure 46
[DETAIL]
E
A
Pin
A
26
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 27
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Step 10. INSTALL GLASS DOORS, MESH PULL SCREENS, AND MODESTY PANEL
WARNING
HOT GLASS WILL CAUSE BURNS.
DO NOT TOUCH GLASS UNTIL COOLED.
Install only when fireplace is OFF and
COLD
.
•Fireplace surfaces get EXTREMELY HOT!
•The glass on the front of the fireplace
reaches EXTREMELY HIGH temperatures and can cause severe burns if touched. Even after the gas is turned off, fireplace surfaces remain extremely hot.
CAUTION
RISK OF PERSONAL INJURY
OR PROPERTY DAMAGE.
Do NOT abuse glass doors by striking or
slamming shut
Never operate fireplace with glass door
assemblies removed.
These direct-vent appliances are designed to operate only when both glass door assemblies are installed. Generally, the glass door assemblies should not be removed, except when access to compo­nents within the firebox is required.
Securely tighten door latch screws when
reinstalling glass door assemblies to prevent doors from falling out.
Handle glass door assemblies with
extreme care. Replace damaged glass door assemblies with approved replace­ment assemblies only.
The door assemblies on this fireplace contain ceramic glass. Handle with care to prevent damage. If the door frame or glass on either assembly becomes damaged, replace the entire glass door assembly with a manufacturer-approved replacement assembly only. Do not attempt to substitute any materials used on door assemblies or replace cracked or broken glass with any other materials.
Installing Glass Doors, Mesh Pull Screens, and Modesty Panel
(see Figure 48)
Note: These instructions do NOT apply to the Outer Glass Door provided in the Out­door Kit (for indoor/outdoor installations).
1) Install one of the glass doors, as follows: a) Retrieve the glass door. Visually inspect
the gasket on the back of the frame. Gasket surface must be clean, free of irregularities, and seated firmly.
b) Position the door in front of the firebox
opening, with the top of the door held away from the fireplace (see Figure 48).
c) Lower the bottom of the door assembly
onto the bottom door track, engaging and centering it in the base channel, and then gently swing the door up.
d) Using a #3 Phillips screwdriver, fasten the
door frame to the door latches with the two (2) latch screws. The latches should pull forward to engage the door frame.
Note: Securely tighten latch screws when
reinstalling glass door assembly.
2) Install the modesty panel on the top flange
of the glass door, as follows:
a) Grasp the modesty panel with both hands
(with the open hem facing down).
b) Engage it with the upper lip of the glass
door frame by pushing it all the way down. Make sure the installed modesty panel is firmly in place.
3) Install the mesh pull screens, as follows: a) Retrieve the rod and two mesh pull
screens. If necessary, attach screens to rod.
b) Slowly insert the right end of the rod into
the hole in the right rod bracket.
c) Insert the left end of the rod into the slot
in the left rod bracket.
Removing Glass Doors, Mesh Pull Screens, and Modesty Panel
(see Figure 48)
1) Remove the mesh pull screens, as follows: a) Lift up the left end of the rod to disengage
it from the slot in the left rod bracket.
b) Slowly remove the right end of the rod
from the hole in the right rod bracket.
c) Set aside the rod and mesh pull screens
for later reinstallation.
2) Remove the modesty panel from the top
flange of the glass door by firmly pulling up on it with both hands until it is disengaged.
3) Remove one of the glass doors, as follows: a) See Figure 48. While holding the top of
the glass door frame in place, use a #3 Phillips screwdriver to remove the two (2) screws securing the door frame to the two (2) door latches.
b) Carefully tilt the top of the glass door
frame away from the unit (as shown in Figure 48), and then lift the door as­sembly up and out of the lower track.
c) Carefully place the glass door assembly
on a padded surface in a safe location to prevent damage.
Top Flange on Glass door assembly
Figure 48
Glass Door Latch (2)
Screws
Only doors certified with the appliance shall be used.
Seules des portes certifiées pour cet appareil doivent être utilisées.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
27
Page 28
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Step 11. BURNER ADJUSTMENTS
Flame Appearance and Sooting
Proper flame appearance is a flame that is blue at the base and becomes yellowish-orange in the body of the flame. When the appliance is first lit, the entire flame may be blue and will gradually turn yellowish-orange during the first 30 minutes of operation. After 30 minutes of operation, if the flame is blue, or if the flame is orange with evidence of sooting (black tip), the air shutter opening may need to be adjusted.
If the air shutter opening is closed too far, sooting may develop. Sooting is indicated by black puffs developing at the tips of very long orange flames. Sooting results in black deposits forming on the logs, appliance inside surfaces and on exterior surfaces adjacent to the vent termination.
Sooting is caused by incomplete combustion in the flames and lack of combustion air enter­ing the air shutter opening. To achieve a warm yellowish-orange flame with an orange body that does not soot, the shutter opening must be adjusted between these two extremes.
Air Shutter Adjustment Guidelines
• If there is smoke or soot present, rst check
the log set positioning to ensure that the flames are not impinging on any of the logs. If the log set is properly positioned and a sooting condition still exists, then the air shutter opening should be increased.
• The more offsets in the vent system, the larger
the air shutter opening will need to be.
• An appliance operated with the air shutter
opened too far, may have flames that appear blue and transparent. These weak, blue and transparent flames are termed anemic.
• Propane models may exhibit ames which
candle or appear stringy. If this is present and persists, adjust the air shutter to a more OPEN position, then operate the appliance for a few more minutes to ensure that the flame normalizes and the flames do not appear sooty.
The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation.
Burner Air Shutter Adjustment
1. Light the appliance (follow lighting proce-
Procedure
WARNING
HOT GLASS WILL CAUSE BURNS.
DO NOT TOUCH GLASS UNTIL COOLED.
•Fireplace surfaces get EXTREMELY HOT!
•The glass on the front of the fireplace
reaches EXTREMELY HIGH temperatures and can cause severe burns if touched. Even after the gas is turned off, fireplace surfaces remain extremely hot.
CAUTION
RISK OF PERSONAL INJURY
OR PROPERTY DAMAGE.
Air shutter adjustment should only be performed by a qualified professional service technician.
Soot will be produced if the air shutter is closed too much. Any damage due to carboning resulting from improperly setting the air shutter is not covered under the warranty.
Volcanic Stone
Figure 49: Burner Flame Appearance — Control Side
2. Allow the burner to operate for at least 30
3. Adjust the air shutter using the lever on
A minimum shutter setting is designed into
Note: See Figures 49 and 50 for proper burner flame appearance.
Adjustment Lever
dure in Care and Operation Instructions or on lighting label in control compartment).
minutes while continuously observing the flame to ensure that the proper flame ap­pearance has been achieved (see Figures
49 and 50).
the lower right side of the firebox on the control side (Figure 49).
For more OPEN air shutter, slide lever to the RIGHT.
For more CLOSED air shutter, slide lever to the LEFT.
the venturi by four 1/16"-inch tabs.
• If the ame appears weak or sooty (as
described on the previous page), adjust the air shutter until proper flame appear­ance is achieved.
• If ame stays lowered blue, incremen-
tally adjust the air shutter to a more
CLOSED position until proper flame appearance is achieved.
Air Shutter
28
Air Shutter Adjustment Guidelines:
Amount of
Primary Air
If air shutter is closed too far
If air shutter is open too far
Flame
Color
Flame will be orange
Flame will be blue
Air Shutter
Adjustment
Air shutter gap should be increased
Air shutter gap should be decreased
Volcanic Stone
Figure 50: Burner Flame Appearance — Opposite Control Side
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 29
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
FINISHING REQUIREMENTS
Wall Details - INDOOR SIDE(S)
Complete the finished interior wall. To install the appliance facing flush with the finished wall, position framework to accommodate the thickness of the finished wall (Figure 51).
Wall Details - OUTDOOR SIDE
Complete finished exterior wall per the instructions provided in the Outdoor Installation Kit and the instructions provided here. To install the appliance facing flush with the finished exterior wall, position framework to accommodate the thickness of the exterior finished wall (Figure 52).
INTERIOR WALL FINISHING EXTERIOR WALL FINISHING
Wall Stud
Combustible
Finished Wall
Materials
Header
Combustible
materials are
allowed on face
of appliance
above this point
Min. 3 in*
(76 mm)
~
Min. 1 in*
(25 mm)
Top of Appliance
Adaptor plus min. 4 feet vertical vent and 90˚ elbow
Adaptor plus
min. 4 feet
vertical vent
and 90˚ elbow
Min. 3 in*
(76 mm)*
1"
(25.4mm)
Minimum
Top of
Appliance
Wall Stud
Combustible Sheathing
Header
Non-combustible sheathing required below this point
Non-combustible
Extend housewrap (building paper) to this point.
*Insulation is
NOT ALLOWED in clearance zones around vent components. Keep this area free from combustible materials.
Figure 51
Spacers
Top of Door Frame
FIREPLACE (side view)
Figure 52
See Page 5 for Cold Climate Insulation
and Page 9 for Clearances
Spacers
Top of Door Frame
FIREPLACE (side view)
Note: Non-combustible sheathing and housewrap (building paper) should extend to U-channels on sides and bottom.
*Insulation is NOT ALLOWED in clearance zones around vent components. Keep this area free from combustible materials.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
29
Page 30
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Combustible Sheathing
Non-Combustible Board
A
B B
Non-Combustible Board
Combustible Sheathing
C
Non-Combustible Board
Sheathing Requirements
A B C*
12” (305mm) 7” (178mm) 6” (152mm)
*Dimension “C” is clearance required from fireplace base to surface (e.g., deck, patio, lanai) as a moisture barrier (not a combustible clearance) on outdoor side only.
Overhang
B
A
Siding
A
A
Siding
Siding
Trim
C*
Exterior Minimum Clearances
Material A B C*
Vinyl 12” (305mm) 35-1/2” (902mm) 6” (305mm)
Non-Vinyl 7” (178mm) 35-1/2” (902mm) 6” (305mm)
*Dimension “C” is clearance required from fireplace base to surface (e.g., deck, patio, lanai) as a moisture barrier (not a combustible clearance) on outdoor side only.
Figure 53: Sheathing
Figure 54: Exterior Clearances
30
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 31
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Step 12. ATTACHING SAFETY-IN-OPERATION WARNINGS It is the installer’s responsibility to ensure these warnings are properly affixed during installation. These warning labels are a
critical step in informing consumers of safe operation of this appliance.
ATTACHING SAFETY-IN-OPERATION WARNINGS
It is required that the set of safety instruction labels that have been furnished with the fireplace be affixed to the operation and control points of the fireplace. A safety instruction label must be affixed to the receiver wall switch plate where the fireplace is turned on and off (See Figure A) and on the remote control handheld transmitter (See Figure B). To properly complete the installation of this fireplace, locate the multi-lingual adhesive labels provided with the Care and Operation Instructions and proceed as follows:
1. Locate the wall receiver that controls the fireplace (verify the switch operates the fireplace by turn­ing it on and off). Clean the wall receiver plate thoroughly to remove any dust and oils. Affix the label to the surface of the plate of the wall receiver that controls the fireplace (Figure A). Choose the language primarily spoken in the home. If unknown, affix the English language label.
2. Locate the remote control transmitter and clean it thoroughly to remove any dust and oils. Affix the label to the surface of handheld transmitter (Figure B). Choose the language primarily spoken in the home. If unknown, affix the English language label.
3. If you are unable to locate the labels, please call Innovative Hearth Products or your nearest Innovative Hearth Products dealer to receive ad­ditional safety instruction labels free of charge.
Cat. No. H8024 Replacement Label Kit
INNOVATIVE HEARTH PRODUCTS
Note: English is red text on clear label. French and Spanish are white text on black label.
APPOSITION DES MISES EN GARDE RELATIVES À LA SÉCURITÉ D’UTILISATION
Il est impératif que le jeu d’étiquettes de sécurité qui ont été fournies avec le foyer soient collées à côté des dispositifs de contrôle du foyer. Une étiquette de sécurité doit être collée sur la plaque du récepteur mural contrôlant l’allumage du foyer (voir Figure A) et sur le boîtier de la télécommande (Figure B). Pour achever l’installation correcte de ce foyer, procédez comme suit avec les étiquettes adhésives en langues étrangères fournies avec les instructions d’utilisation et d’entretien :
1. Repérez le récepteur mural qui contrôle le foyer (vérifiez que l’interrupteur contrôle le fonction ­nement du foyer en le faisant basculer de Marche à Arrêt, et vice-versa). Nettoyez soigneusement la plaque du récepteur mural pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur la surface de la plaque du récepteur mural qui contrôle le foyer (Figure A). Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
2. Repérez la télécommande et nettoyez-la soigneuse­ment pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur le boîtier de la télécommande (Figure B). Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
3. Si vous ne trouvez pas les étiquettes, veuillez appeler Innovative Hearth Products ou votre distribu­teur Innovative Hearth Products local pour recevoir gratuitement des étiquettes supplémentaires.
Étiquettes de remplacement, n° cat. H8024
INNOVATIVE HEARTH PRODUCTS
Remarque : Le texte anglais est rouge sur un support transparent. Le texte français et espagnol est blanc sur un support noir.
COLOCACIÓN DE ADVERTENCIAS DE SEGURIDAD EN OPERACIÓN
Se requiere que el juego de etiquetas de instrucciones de seguridad que se incluyeron con la chimenea se coloque en los puntos de operación y control de la misma. Se debe colocar una etiqueta de instrucciones de seguridad en la placa del interruptor de pared del receptor desde el cual se enciende y se apaga la chimenea (ver la Figura A) y en el transmisor de control remoto (ver la Figura B). Para completar correctamente la instalación de esta chimenea, encuentre las etiquetas adhesivas multilingües incluidas con las instrucciones de cuidado y operación y haga lo siguiente:
1. Identifique el receptor de pared que controla la chimenea (verifique que el interruptor opera la chimenea encendiéndola y apagándola). Limpie bien la placa del receptor de pared para quitar el polvo y aceite. Pegue la etiqueta en la superficie de la placa del receptor de pared que controla la chimenea (Figura A). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
2. Identifique el transmisor de control remoto y límpielo bien para quitar el polvo y aceite. Pegue la etiqueta en la superficie del transmisor (Figura B). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
3. Si no puede encontrar las etiquetas, sírvase llamar a Innovative Hearth Products o al distribuidor de Innovative Hearth Products más cercano para recibir etiquetas de instrucciones de seguridad adicionales gratuitas.
Juego de etiquetas de repuesto - Nº de cat. H8024
INNOVATIVE HEARTH PRODUCTS
Nota: La etiqueta en inglés es transparente con texto rojo. Las etiquetas en francés y español son negras con texto blanco.
SAFETY LABEL
DIAGRAMS
DIAGRAMMES DES ÉTIQUETTES
DE SÉCURITÉ
On
Remote
Off
PRG
Figure A Figure B
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
DIAGRAMAS DE ETIQUETAS
DE SEGURIDAD
31
Page 32
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
S
e
a
l
a
n t
INSTALLATION ACCESSORIES
Listed Secure Vent™ Components
Cat. No. Model No. Description
77L70 SV4.5L6
77L71 SV4.5L12
77L72 SV4.5L24
77L73 SV4.5L36
77L74 SV4.5L48
77L75 SV4.5LA
H8313
77L76 SV4.5E45
77L77 SV4.5E90
H2246 SV4.5HF
H2247 SV4.5VF
The following flashings come packaged with a storm collar:
H5816
SV4.5-TWSK
750,247M
Vent Section, 6 inch (152mm)
Vent Section, 12 inch (305mm)
Vent Section, 24 inch (610mm)
Vent Section, 36 inch (914mm)
48 inch (1219mm) Vent Section
Telescopic Section
Adaptor/Probe Assembly
45 Degree Elbow
90 Degree Elbow
Firestop/Spacer, Horizontal (3-1-1 spacing) 10 pack
Firestop/Spacer, Vertical (1-1-1 spacing) 10 pack
Through Wall Shield Kit (used to shield direct-vent pipe from blown insulation)
Listed Secure Vent™ / Secure Flex™ Components
Cat. No. Model No. Description
Attic Insulation Shield
H3907 SV4.5RSA
(adjustable 12" to 22")
36" Flex Vent Kit
H7748 FVK36
Note: Flex attaches to ap­pliance collar at one end and to rigid venting at the other end.
10K81 SFMP Mill-Pac, Black, High-
Temperature Sealant
89L40 SFMP-12 Mill-Pac, Black, High
Temperature Sealant (Bulk 12 pack)
91L66 SF-GC4-6 Gear Clamp 4.5 in.
(114 mm) for flex (6 pieces)
91L67 SF-GC7-6 Gear Clamp 7.5 in.
(190.5 mm) for flex (6 pieces)
Outdoor Kits
H7940 LSM40STODK Outdoor Kit with
Light-tint Glass
H8061 LSM40ST-ODKT Outdoor Kit with
Dark-tint Glass
32
96K93 SV4.5SU
96K92 SV4.5SP
Support Strap
Support Plate
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 33
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
GAS CONVERSION KITS
Gas conversion kits are available to adapt your appliance from the use of one type of gas to another. These kits contain all the necessary components needed to complete the task, in­cluding labeling that must be affixed to ensure safe operation.
Kit part numbers are listed at right. Refer to the instructions provided with the
conversion kit when performing any gas conversion.
Gas Conversion Kits
Kit Model No. Kit Cat. No. Description
GCK-NP-LSM40ST H7951 Natural Gas to Liquid Propane Conversion Kit GCK-PN-LSM40ST H7952 Liquid Propane to Natural Gas Conversion Kit
Table 10
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
33
Page 34
INNOVATIVE HEARTH PRODUCTS • SEE-THROUGH POWER VENT DV GAS FIREPLACES (DRT63STYN) • INSTALLATION INSTRUCTIONS
Innovative Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, and prices, and also to discontinue colors, styles, and products. Consult your local distributor for fireplace code information.
Printed in U.S.A. © 2013 Innovative Hearth Products
P/N 506009-20 Rev. NC 12/2013
1508ElmHillPike,Suite108•Nashville,TN37210
Loading...