Superior DRC3035DEN, DRT3045 series, DRT3035 series, DRT3040 series, DRC3040DEN, DRT3033 series Installation And Operation Instructions Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
Installation and Operation Instructions
PFS
USC
P900285-00
SuperiorTM DRT3000 and DRC3000 Series Direct-Vent Gas
Fireplaces
P/N 900285-00 Rev. E 05/2015
Ce manuel est disponible en francais, simplement
en faire la demande. Numéro de la pièce 900285-02.
Report No. F13-094
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
A barrier designed to reduce the risk of burns
from the hot viewing glass is provided with
this appliance and shall be installed for
the protection of children and other at-risk
Models
DRT3033xxx*DRT3035xxx*
®
DRC3035DEN
DRT3040xxx*
DRC3040DEN
DRT3045xxx*
* “xxx” indicates unique model identifiers.
This manual covers all SuperiorTM DRT3000 and DRC3000 models.
Installateur : Laissez cette notice avec l’appareil.
Consommateur : Conservez cette notice pour consultation ultérieure.
L’écran pare-étincelles fourni avec ce foyer réduit le
risque de brûlure en cas de contact accidentel avec la
vitre chaude et doit être installé pour la protection Des
enfants et Des personnes à risques.
individuals.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile
home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the
rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
Cet appareil peut installé dans une maison préfabriquée (mobile) déjà installée à demeure, si les réglements
locaux le permettent. Ce appareil doit être utilisé uniquement avec le type de gaz indiqué sure la plaque
signalétique. Cet appareil ne peut être converti à d’autres gaz, sauf si une trousse de conversion est utilsée.
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result
in serious injury, death, or property damage.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
— Installation and service must be performed by a
qualified installer, service agency or the gas supplier.
AVERTISSEMENT:
RISQUED’INDENDIE OU D’EXPLOSION
Le non-respect Des avertissements de sécurité
pourrait d’entraîner des blessures graves, la mort
ou des dommages matériels.
— Ne pas entreposer ni utilizer d’essence ni d’autres
vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
— QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous
servir des téléphones se trouvant dans le bâtiment où vous trouvez.
• Sortez immédiatement de bâtiment.
• Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions du
fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de
gaz, appelez le service des incindies.
— L’installation et l’entretien doivent être assurés par
un installateur ou un service d’entretien qualifié
ou par le fournisseur de gaz.
Innovative Hearth Products
TM
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
General Information
900285-00 05/2015
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the hot viewing glass
is provided with this appliance and shall be installed for the protection of
children and other at-risk individuals.
See attached color flyer for proper color representation
DANGER
VITRE CHAUDE
RISQUE DE BRÛLURES.
NE TOUCHEZ PAS UNE VITRE
NON REFROIDIE.
NE LAISSEZ JAMAIS UN ENFANT
DE TOUCHER LA VITRE.
L’écran pare-étincelles fourni avec ce foyer réduit le risque de brûlure en
cas de contact accidentel avec la vitre chaude et doit être installé pour la
protection Des enfants et Des personnes à risques.
Voir ci-joint tract pour une bonne représentation de la couleur
PELIGRO
EL VIDRIO CALIENTE
CAUSARÁ QUEMADURAS.
USTED DEBE NUNCA
TOCAR EL VIDRIO CALIENTE.
LOS NIÑOS DEBEN NUNCA
TOCAR EL VIDRIO.
Una barrera diseñada para reducir el riesgo de quemaduras desde la
mirilla (vidrio) caliente es proveida con este aparato y deberá instalarse
para la protección de los niños y otros individuos en riesgo.
2
Vea el volante adjunto para la representación de color adecuado
Innovative Hearth Products
TM
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
General Information
900285-00 05/2015
Safety and Your
Fireplace
All parts of your
IHP fireplace get
EXTREMELY HOT!
To prevent severe
burns and injuries,
install a screen or
physical barrier to
prevent direct contact
with the glass.
Follow the safety instructions
below and be sure everyone in
your household understands this
burn hazard:
• The surfaces on your fireplace get
EXTREMELY HOT!
• The glass on the front of the
fireplace reaches EXTREMELY
HIGH temperatures and can cause
severe burns if touched.
• Keep children away from an
operating fireplace. Closely
supervise children in any room
where a fireplace is operating to
prevent contact with glass.
• Keep clothing, furniture,
gasoline, and other flammable
liquids away from the fireplace.
• Even after the gas is turned
off, fireplace surfaces remain
extremely hot.
Be sure to attach the enclosed
Safety-in-Operation Warnings where
you turn on your fireplace, to help
remind everyone of the dangers
associated with high temperatures
(Page 47).
Read Important Safety Information
(Page 5)
3
EXTRÊMEMENT CHAUDES !
La sécurité et
votre foyer
Toutes les parties de votre
foyer IHP deviennent
Afin d'éviter de vous
brûler gravement ou de
vous blesser, installez
une grille ou une barrière
physique pour empêcher
tout contact direct avec la vitre.
Suivez les instructions de sécurité
ci-dessous et veillez à ce que tous les
membres de votre famille soient conscients
du danger de brûlure encouru :
• Les surfaces de votre foyer deviennent
EXTRÊMEMENT CHAUDES !
• La vitre située à l'avant du
foyer atteint des températures
EXTRÊMEMENT ÉLEVÉES et peut
causer de graves blessures en
cas de contact.
• Tenez les enfants à l'écart
du foyer lorsqu'il fonctionne.
Surveillez attentivement les
enfants dans les pièces où un
foyer est utilisé afin d'éviter qu'ils
ne soient en contact avec la vitre.
• Tenez tous les vêtements, les
meubles, l'essence et tout autre liquide
inflammable à l'écart du foyer.
• Même après fermeture du gaz,
les surfaces du foyer restent
extrêmement chaudes.
Veillez à coller les Étiquettes de mise
en garde relatives à la sécurité
d'utilisation à l'endroit où vous
utilisez le foyer, pour rappeler à tous
les utilisateurs les dangers liés aux
températures élevées (Page 47).
Lisez L’information de sûreté
importante (Page 5).
[FRENCH][ENGLISH]
Seguridad y su
chimenea
¡Todas las partes de la
chimenea IHP se ponen
MUY CALIENTES!
Instale una malla o barrera física para evitar
el contacto directo con el vidrio y prevenir
las quemaduras y lesiones graves.
Siga las instrucciones de seguridad
a continuación y asegúrese de que
todos en su hogar sepan acerca de
este peligro de quemadura:
• ¡Las superficies de la chimenea
se ponen MUY CALIENTES!
• El vidrio delante de la
chimenea alcanza temperaturas
EXTREMADAMENTE ALTAS
y puede causar quemaduras
graves si se toca.
• Mantenga a los niños alejados de
la chimenea en funcionamiento.
Supervise en forma cercana a los
niños en cualquier cuarto donde haya
una chimenea funcionando para
impedir el contacto con el vidrio.
• Mantenga la ropa, mobiliario,
gasolina y otros líquidos
inflamables alejados de la
chimenea.
• Aún después de haber apagado
el gas, las superficies de
la chimenea permanecen
extremadamente calientes.
Asegúrese de colocar las Etiquetas
de advertencia de seguridad
de operación en el lugar donde
enciende la chimenea, para que todos
recuerden los peligros asociados con
las altas temperaturas (Página 47).
Lea Información importante de
seguridad (Página 5).
[SPANISH]
Innovative Hearth Products
TM
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
THANK YOU FOR YOUR PURCHASE. WE APPRECIATE YOUR BUSINESS!
Please carefully read and follow all instructions in this manual. Pay special attention to all warnings and safety
information. Following these safety, care, and operation instructions will help ensure many years of dependable and
enjoyable service from your fireplace.
General Information
900285-00 05/2015
Space Reserved
for
Contemporary Image
Please read and understand these instructions before installing,
operating, or servicing this product.
General Information
Important Safety Information ............................................................5
Fireplace Installation, Operation, and Maintenance Notices ............... 6
Construct the Fireplace Framing ...................................................... 16
Route the Gas Supply Line to the Fireplace .....................................18
Install the Vent System ....................................................................25
Complete the Field Wiring ................................................................37
Install the [Optional] Blower Kit after Installation in the Framing ..... 39
We recommend that our
gas hearth products be
installed and serviced by
professionals who are
certied in the U.S. by the
National Fireplace Institute®
(NFI) as NFI Gas Specialists.
Connect the Gas Line ....................................................................... 40
IMPORTANT SAFETY INFORMATIONL’information de sûreté importanteInformación importante de seguridad
WARNING AVERTISSEMENT ADVERTENCIA
Do not operate appliance with the
glass front removed, cracked or
broken.
Do not use this fireplace if any part has
been under water. Immediately call a
qualified service technician to inspect the
fireplace and to replace any part of the
control system and any gas control which
has been under water.
Due to high temperatures, the fireplace
should be located out of traffic and away
from furniture and draperies.
Children and adults should be alerted to
the hazards of high surface temperature
and should stay away to avoid burns or
clothing ignition.
Clothing or other flammable material
should not be placed on or near the
fireplace.
Young children should be carefully
supervised when they are in the same
room as the fireplace. Toddlers, young
children, and others may be susceptible
to accidental contact burns. A physical
barrier is recommended if there are
at-risk individuals in the house. To
restrict access to a fireplace or stove,
install an adjustable safety gate to keep
toddlers, young children, and other atrisk individuals out of the room and away
from hot surfaces.
Any safety screen or guard removed for
servicing a fireplace must be replaced
prior to operating the fireplace.
Installation and repair should be done
by a qualified service person. The
fireplace should be inspected before use
and at least annually by a professional
service person. More frequent cleaning
may be required due to excessive lint
from carpeting, bedding material, et
cetera. It is imperative that control
compartments, burners, and circulating
air passageways of the fireplace be kept
clean (Maintenance on Page 63).
[English][French][Spanish]
Ne pas utiliser l’appareil si le
panneau frontal en verre n’est pas
en place, est craqué ou brisé.
Ne pas utiliser cet appareil s’il a été
plongé, même partiellement, dans l’eau.
Appeler un technicien qualifié pour
inspecter l’appareil et remplacer toute
partie du système de commande et toute
commande qui a été plongée dans l’eau.
En raison des températures élevées,
l’appareil devrait être installé dans un
endroit où il y a peu de circulation et loin
du mobilier et des tentures.
Les enfants et les adultes devraient être
informés des dangers que posent les
températures de surface élevées et se
tenir à distance afin d’éviter des brûlures
ou que leurs vêtements ne s’enflamment.
On ne devrait pas placer de vêtements
ni d’autres matières inflammables sur
l’appareil ni à proximité.
Les jeunes enfants devraient être
surveillés étroitement lorsqu’ils se
trouvent dans la même pièce que
l’appareil. Les tout petits, les jeunes
enfants ou les adultes peuvent subir des
brûlures s’ils viennent en contact avec
la surface chaude. Il est recommandé
d’installer une barrière physique si des
personnes à risques habitent la maison.
Pour empêcher l’accès à un foyer ou à un
poêle, installez une barrière de sécurité
; cette mesure empêchera les tout petits,
les jeunes enfants et toute autre personne
à risque d’avoir accès à la pièce et aux
surfaces chaudes.
Tout écran ou protecteur retiré pour
permettre l’entretien de l’appareil doit
être remis en place avant de mettre
l’appareil en marche.
L’installation et la réparation devrait
être confiées à un technicien qualifié.
L’appareil devrait faire l’objet
d’une inspection par un technicien
professionnel avant d’être utilisé et au
moins une fois l’an par la suite. Des
nettoyages plus fréquents peuvent être
nécessaires si les tapis, la literie, et
cetera produisent une quantité importante
de poussière. Il est essentiel que les
compartiments abritant les commandes,
les brûleurs et les conduits de circulation
d’air de l’appareil soient tenus propres
(Page 63).
No opere el artefacto con el frente
de vidrio quitado, agrietado o roto.
No use este artefacto si alguna de sus
partes ha estado bajo agua. Llame
de inmediato a un técnico de servicio
calificado para que inspeccione el
artefacto y reemplace cualquier parte del
sistema de control y cualquier control de
gas que haya estado bajo agua.
Debido a las altas temperaturas, el
artefacto debe situarse fuera de las
áreas de tráfico y lejos del mobiliario y
cortinas.
Se debe alertar a los niños y adultos
sobre los peligros de las altas
temperaturas en la superficie y que
se mantengan alejados para evitar
quemaduras o ignición de la ropa.
No debe colocarse ropa u otros
materiales inflamables sobre y cerca del
artefacto.
Se debe supervisar de cerca a los niños
cuando estén en el mismo cuarto que
el artefacto. Los niños pequeños, los
jóvenes y otras personas pueden ser
susceptibles a quemaduras por contacto
accidental. Se recomienda instalar
una barrera física si hay personas en
riesgo en la casa. Para restringir el
acceso a una chimenea o estufa, instale
una puerta de seguridad ajustable
para mantener a los niños pequeños,
jóvenes y otras personas en riesgo fuera
del cuarto y lejos de las superficies
calientes.
Cualquier malla o resguardo de seguridad
quitado para dar servicio a un artefacto,
debe reinstalarse antes de operar
el artefacto.
Una persona de servicio competente
debe realizar la instalación y reparación.
Una persona de servicio profesional
debe inspeccionar el artefacto antes
de usar al menos una vez por año. Se
puede requerir limpieza más frecuente
debido a la pelusa excesiva del
alfombrado, del material de cobijas,
etc. Es imprescindible mantener limpios
los compartimientos de control, los
quemadores y los pasajes de circulación
del aire del artefacto (Página 63).
5
Innovative Hearth Products
TM
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
FIREPLACE INSTALLATION, OPERATION, AND MAINTENANCE NOTICES
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY
MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION, AND LISTINGS OF THIS UNIT.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause injury or
property damage. Refer to this manual. For assistance or additional information consult a
qualified installer, service agency or the gas supplier.
AVERTISSEMENT
Une installation, un réglage,une modification, une réparation ou un entretien mal effectué
peut causer des dommages matériels ou des blessures. Voir la notice de l’utilisateur qui
accompagne l’appareil. Pour de l’aide ou des renseignements supplémentaires, consultez
un installateur, un technicien agréé ou le fournisseur de gaz.
WARNING
General Information
900285-00 05/2015
Failure to comply with these installation instructions will result in an improperly installed
and operating appliance, voiding its warranty. Any change to this appliance and/or its
operating controls is dangerous.
6
Innovative Hearth Products
TM
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
General Information
900285-00 05/2015
WARNING
Clothing or other flammable material should not be placed on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de vêtements ni d’autres matières inflammables sur l’appareil ni à proximité.
WARNING
Improper installation or use of this appliance can cause serious injury or death from fire, burns,
explosion or carbon monoxide poisoning.
CAUTION
Hot while in operation. Do not touch. Severe Burns may result. Keep children, clothing
furniture, gasoline and other liquids having flammable vapors away.
ATTENTION
L’appareil est chaud lorsqu’il fonctionne. Ne pas toucher l’appareil. Risque de brûlures
graves. Surveiller les enfants. Garder les vêtements, les meubles, l’essence ou autres
liquides produisant des vapeur inflammables loin de l’appareil.
NOTE:
• If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this
appliance.
• For use with barrier(s) Part No(s). F1902 (33” Models), F1839 (35” Models), F1840 (40” Models), and
F1903 (45” Models). Follow installation instructions.
• These fireplaces are designed as supplemental heaters, and are not to be used as the primary heat source
when installed.
• Provide adequate clearances around air openings and adequate accessibility clearance for service and proper
operation. Never obstruct the front or back openings of the fireplace.
• These fireplaces are designed to operate on natural or propane gas only. The use of other fuels or combination of
fuels will degrade the performance of this system and may be dangerous.
• These fireplaces must not be connected to a chimney or flue serving a separate solid fuel burning fireplace.
• Only trim kit(s) supplied by the manufacturer shall be used in the installation of this fireplace.
Remarqué :
• Seules les trousses de garniture fournies par le fabricant doivent être utilisées pour l’installation de cet appareil.
7
Innovative Hearth Products
TM
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
INSTALLATION
PACKAGING
All models include
INTRODUCTION
General Information
900285-00 05/2015
The assembled vented gas fireplace heater is packaged with:
• Literature Kit (envelope in bottom compartment containing Installation and Operation Instructions (this manual),
and Safety-In-Operation Warning Labels)
• U-Shaped Vent Restrictor (attached to Literature Kit envelope)
• Hood (Inside firebox, Traditional Models)
• Log Set (Traditional Fireplaces, in firebox) or Glass Media (Contemporary Fireplaces)
• Volcanic Stone—1 bag (in bottom compartment, Traditional Models)
• Glowing Embers—1 bag (in bottom compartment, Traditional Models)
These vented gas fireplace heaters are sealed combustion, air-circulating gas fireplaces designed for residential and
commercial applications.
Millivolt fireplaces have a millivolt gas control valve with piezo ignition system. If a blower will be installed, electrical
power must be provided at the time of fireplace installation.
Electronic fireplaces are designed with an electronic intermittent pilot ignition system. External electrical power is
required to operate these units. In the event of a power outage, four (4) AA batteries (in battery holder) provide
backup power for fireplace operation. Battery backup will not operate optional/standard blower. Traditional units
require an additional four (4) AA batteries to provide power to the split-flow system.
NOTE: Installation and repair should be done by a qualified service person. The fireplace should be inspected before
use and at least annually by a professional service person. More frequent cleaning may be required due to excessive
lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air
passageways of the fireplace be kept clean.
Remarqué : L’installation et la réparation devrait être confiées à un technicien qualifié. L’appareil devrait faire
l’objet d’une inspection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite.
Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité
importante de pous-sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les
conduits de circulation d’air de l’appareil soient tenus propres.
NOTE: Diagrams and illustrations are not necessarily shown to scale.
Approved Vent Components
These fireplaces are designed, tested and listed for operation and installation with the following vent
components only:
• Secure Vent® Direct-Vent System Components,
• Secure Flex® Flexible Vent Components, and
• Z-FLEX® Model GA Venting Systems listed to UL1777 and ULCS635 manufactured by Flexmaster
Canada Limited.
Use only the correct size venting (4 1/2” inner and 7 1/2” outer).
These approved vent system components are labeled for identification. DO NOT use any other manufacturer’s vent
components with these fireplaces.
Codes and Standards
These fireplaces comply with National Safety Standards and are tested and listed by PFS Corporation
(Report No. F13-094) to ANSI Z21.88 (in Canada, CSA-2.33), and CAN/CGA-2.17-M91 in both USA and Canada, as
vented gas fireplace heaters.
These fireplaces are listed for installation in bedrooms and manufactured homes.
The installation must conform to local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54—latest edition (In Canada, the current CAN/CGA-B149.1 installation code).
The fireplace, when installed, must be electrically grounded and wired in accordance with local codes or, in the
absence of local codes, with the National Electrical Code, ANSI/NFPA 70—latest edition, or the Canadian Electrical
Code, CSA C22.1—latest edition.
* AFUE is a measurement of the US Department of Energy, ** P4 (EnerGuide) is a measurement of the Canadian Office of Energy Efficiency.
Efficiencies are based on Normal input operation.
Test gauge connections are provided on the front of the millivolt and electronic gas control valve (identified IN for the
inlet and OUT for the manifold side). The control valves have a 3/8” (10 mm) NPT thread inlet and outlet side of the
valve (Figure 1 and Figure 2).
Figure 1: Millivolt Gas ValveFigure 2: Electronic Gas Valves
ContemporaryTraditional
Propane tanks are at pressures that will cause damage to valve components. Verify that the tanks have step down
regulators to reduce the pressure to safe levels.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during
any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
9
Innovative Hearth Products
TM
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
Orifice Sizes—Sea Level to High Altitude
These fireplaces are tested and approved for installation at elevations of 0–4500 ft (0–1372 m) above sea level
using the standard burner orifice sizes (Table 5). For elevations above 4500 ft, contact your gas supplier or qualified
service technician.
Table 5: Burner Orifice Sizes, Elevation 0–4500 ft ( 0–1372 m)
At elevations above 4500 ft, the amount of BTU fuel value delivered must be reduced by either:
• Using gas that has been derated by the gas company.
• Changing the burner orifice to a smaller size as regulated by the local authorities having jurisdiction and by the
(USA) National Fuel Gas Code NFPA 54/ANSI Z223.1—latest edition or, in Canada, the CAN/CGA-B149.1 codes—
latest edition.
NOTE: Flame breadth, height and width will diminish 4% for every 1,000 ft of altitude.
IN CANADA—CAN/CGA-2.17-M91 (HIGH ALTITUDE):
THE CONVERSION SHALL BE CARRIED OUT BY A MANUFACTURER’S AUTHORIZED REPRESENTATIVE,
IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER, PROVINCIAL OR TERRITORIAL
AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/
CGA-B149.1 OR CAN/CGA-B149.2 INSTALLATION CODES.
Natural Gas
drill size
Installation
900285-00 05/2015
Propane
drill size
COMMONWEALTH OF MASSACHUSETTS REQUIREMENTS
These appliances are approved for installation in the US state of Massachusetts if the following additional
requirements are met:
• Install this appliance in accordance with Massachusetts Rules and Regulations 248 C.M.R. Sections 4.00
through 8.00.
• Installation and repair must be done by a plumber or gas fitter licensed in the Commonwealth of Massachusetts.
• The flexible gas line connector used shall not exceed 36 inches (92 centimeters) in length.
• The individual manual shut-off must be a T-handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, horizontal terminations installed less than seven (7) feet above the finished
grade must comply with the following additional requirements:
• A hard wired carbon monoxide detector with an alarm and battery back-up must be installed on the floor level
where the gas fireplace is installed. The carbon monoxide detector must comply with NFPA 720, be ANSI/UL
2034 listed and be ISA certified.
• A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minimum height
of eight (8) feet above grade and be directly in line with the horizontal termination. The sign must read, in print size no
less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks around your fireplace with noncombustible material and wherever cold
air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on
which fireplace rests, if floor is above ground level. Gas line holes and other openings should be caulked or stuffed
with unfaced fiberglass insulation.
10
NOTE: Do not use loose, or blown-in insulation in the cavity surrounding the fireplace.
If the fireplace is being installed on a cement slab in cold climates, a sheet of plywood or other raised platform can
be placed underneath to prevent conduction of cold transferring to the fireplace and into the room. It also helps to
seal inside surfaces and tape for maximum air tightness and caulk firestops.
Innovative Hearth Products
(Rear Vent Application)
VERTICAL VENT
(Rear Vent Application without a chase)
HORIZONTAL VENT
TM
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
MANUFACTURED HOME REQUIREMENTS
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile
home, where not prohibited by local codes.
Cet appareil peut être installé dans une maison préfabriquée (mobile) déjà installée à demeure si les règlements
locaux le permettent.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for
use with other gases, unless a certified kit is used.
Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil ne
peut être converti à d’autres gaz, sauf si une trousse de conversion est utilisée.
Ensure that the cross members are not cut or weakened during installation. The structural
integrity of the manufactured home floor, wall, and ceiling / roof must be maintained.
This appliance must be grounded to the chassis of the manufactured home in accordance
with local codes or in the absence of local codes, with the National Electrical Code ANSI /
NFPA 70—latest edition or the Canadian Electrical Code CSA C22.1—latest edition.
Installation
900285-00 05/2015
CAUTION
CAUTION
LOCATION
In selecting the location, the aesthetic and functional use of the fireplace are primary concerns. However, vent
system routing to the exterior and access to the fuel supply are also important.
Due to high temperatures, the fireplace should be located out of traffic and away from furniture and draperies.
En raison des températures élevées, l’appareil devrait être installé dans un endroit où il y a peu de
circulation et loin du mobilier et des tentures.
The location should also be free of electrical, plumbing or other heating/air conditioning ducting.
These direct-vent fireplaces are uniquely suited for installations requiring a utility shelf positioned directly above the
fireplace. Utility shelves like these are commonly used for locating television sets and decorative plants.
Be aware that this is a heat producing fireplace. Objects placed above the unit are exposed to elevated temperatures.
Do not insulate the space between the fireplace and the area above it.
The minimum height from the base of the fireplace to the underside of combustible materials used to construct a
utility shelf in this fashion is shown in Table 9 and Table 10.
Figure 3: Typical Locations and Venting
Top Vent
Top Vent
Rear Vent
Top Vent
Rear Vent
Horizontal Vent
(Rear Vent with chase)
Horizontal Vent
(Rear Vent without chase)
Recessed
Installation
Top Vent
Top VentTop Vent
Vertical Vent
(Rear Vent)
Horizontal Vent
(Top Vent)
Vertical Vent
(Top Vent)
11
Innovative Hearth Products
12
X
Roof pitch is X/12
2 ft
minimum
2 ft minimum
Lowest
discharge
opening
H*
*H = minimum height from roof to
lowest discharge opening of vent
Horizontal overhang
Vertical
wall
Vent
termination
Storm collar
Concentric
vent pipe
Flashing
1” (25.4 mm) minimum
clearance to combustibles
TM
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
VENT TERMINATION CLEARANCES
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting
according to local codes, these instructions, the current National Fuel Gas Code (ANSI Z223.1/NFPA 54) in the USA or
the current standards of CAN/CGA-B149.1 in Canada.
Vertical Vent Termination Clearances
Terminate multiple vent terminations according to the installation codes listed above and Figure 4.
Figure 4: Multiple Terminations
Terminate single vent caps relative to building components according to Table 6 and Figure 4.
Table 6: Termination Heights for Vents above Flat or Sloped Roofs (NFPA 54 / ANSI Z223.1)—Gas Vent Rule
12”
(305 mm)
minimum
Installation
900285-00 05/2015
6”
(153 mm)
Roof PitchTermination Height *
Flat to 6/121.0 ft (0.3 m)
6/12 to 7/121.25 ft (0.38 m)
7/12 to 8/121.5 ft (0.46 m)
8/12 to 9/122.0 ft (0.61 m)
9/12 to 10/122.5 ft (0.76 m)
10/12 to 11/123.25 ft (0.99 m)
11/12 to 12/124.0 ft (1.22 m)
12/12 to 14/125.0 ft (1.52 m)
14/12 to 16/126.0 ft (1.83 m)
16/12 to 18/127.0 ft (2.13 m)
18/12 to 20/127.5 ft (2.29 m)
20/12 to 21/128.0 ft (2.44 m)
Horizontal Vent Termination Clearances
12
The horizontal vent termination must have a minimum of 6” (152 mm) clearance to any overhead combustible
projection of 2 1/2” (64 mm) or less (Figure 5). For projections exceeding 2 1/2” (64 mm) (Figure 5). For additional
vent location restrictions refer to Table 7.
All horizontal terminations may be located as close as 6” (152mm) to any (non-combustible and combustible)
exterior sidewall. This distance may be decreased to 2” (51mm) for noncombustible exterior sidewalls with all
approved terminations (Table 21).
Figure 5: Horizontal Vent Termination Clearances
*10” to center of termination for H1968
Combustible projection
2 1/2” or less in length
Combustible projection
greater than 2 1/2” in length
Ventilated
soffit - 18”
(457 mm)
Unventilated
soffit - 12”
(305 mm)
*
Termination kit
6
(152)
6”
Termination kit**
**Use 6.5”
from center of
termination for
all horzontal
terminations
applicable
Innovative Hearth Products
(TERMINATION PROHIBITED)
Inside Corner
Balcony with No Side
TM
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
Table 7: Horizontal vent termination clearances for buildings with combustible and noncumbustible exteriors
Outside CornerRecessed Location
D
E
V
B
L
C
F
V
B
TERMINATION CAP
V
Fixed
Closed
Openable
V
Openable
V
B
A
AIR SUPPLY INLET
X
Fixed
Closed
J
B
V
B
X
G
GAS METERRESTRICTED AREA
A Clearance above grade, veranda, porch, desk, or balcony12” (300 mm) **12” (300 mm) *
B Clearance to window or door that may be opened6” (150 mm)
C Clearance to permanently closed window9” (229 mm)
D Vertical clearance to ventilated soffit located above the
termination within a horizontal distance of 18” (458 mm)
E Clearance to unventilated soffit12” (305 mm) 12” (305 mm)
See Table 6
H
G
V
V
F
I
G
G
M
V
K
V
G
V
X
A
WallVBalcony with Perpendicular Side Wall
M
M
V
U.S. Installation **Canadian Installation *
6” (150 mm)
for fireplaces < 10,000 Btu/h (3 kW),
9” (230 mm)
for fireplaces > 10,000 Btu/h (3 kW), and < 50,000 Btu/h
for fireplaces < 10,000 Btu/h (3 kW),
12” (300 mm)
for fireplaces > 10,000 Btu/h (3 kW)
(15 kW),
12” (300 mm)
for fireplaces > 50,000 Btu/h (15 kW) **
12” (305 mm)
recommended to prevent window condensation
recommended to prevent
window condensation
18” (458 mm)18” (458 mm)
Installation
900285-00 05/2015
P
N
Q
O
V
F Clearance to outside corner5” (127 mm)
minimum
5” (127 mm)
minimum
G Clearance to inside corner6” (152 mm) minimum6” (152 mm) minimum
H Clearance to each inside of center line extended above
meter / regulator assembly
36” (910 mm)
within a height of 15 ft above the meter / regulator assembly **
36” (910 mm)
within a height of 15 ft above the meter /
regulator assembly *
I Clearance to service regulator vent outlet36” (910 mm)**36” (910 mm)*
J Clearance to nonmechanical air supply inlet to building or
the combustion air inlet to any other fireplace
6” (150 mm)
for fireplaces < 10,000 Btu/h (3 kW),
9” (230 mm)
for fireplaces > 10,000 Btu/h (3 kW) and < 50,000 Btu/h (15 kW),
6” (150 mm)
for fireplaces < 10,000 Btu/h (3 kW),
12” (300 mm)
for fireplaces > 10,000 Btu/h (3 kW)
12” (300 mm)
for fireplaces > 50,000 Btu/h (15 kW)**
K Clearance to a mechanical air supply inlet36” (910 mm) above if within 10 ft (3 m) horizontally **72” (1830 mm) *
L Clearance above paved sidewalk or paved diveway located
84” (2130 mm) ‡84” (2130 mm) ‡
on public property
M Clearance under veranda, porch, deck or balcony12” (300 mm) *‡12” (300 mm) *‡
N Depth of alcove (maximum)72” (1830 mm) **72” (1830 mm) *
O Clearance to termination (alcove)6” (15.2 mm) **6” (15.2 mm)*
P Width of alcove (minimum)36” (910 mm) **36” (910 mm) *
Q Clearance to combustible above (alcove)18” (457 mm) **18” (457 mm) *
*
In accordance with the current CSA-B149.1 National Gas And Propane Installation Code
**
In accordance with the curent ANSI Z223.1/NFPA 54 National Fuel Gas Codes
‡
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
*‡
Only permitted if veranda, porch, deck, or balcony is fully-open on a minimum two sides beneath the floor
13
Innovative Hearth Products
TM
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
MINIMUM CLEARANCES TO COMBUSTIBLES
Fireplace And Vent Clearances
The fireplace is approved with zero clearance to combustible materials on all sides (Table 8), with the following
exception: The unit may not be recessed (allowance made for mantel legs / side trim in (Figure 6). When the unit is
installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge
of the unit (Figure 6).
Table 8: Minimum Clearances *
From Bottom of Unit to Ceiling64” (1626 mm)
clearance immediately in front of viewing area(s)
* 3” (76 mm) above any horizontal/inclined vent component.
** See Page 21 for clearance requirements to the nailing flange located at each side of the unit and any screw heads adjacent to it.
Front Service Clearance—
Back
Sides
Top Standoffs0” (0 mm) to top standoffs
Floor0” (0 mm)
Vent
1” (26mm) to wrapper
0” (0 mm) to Spacers
1/2” (13 mm) to wrapper
0” (0 mm) to Spacers **
3” (76 mm)—Top *
1” (25.4 mm)—Sides and Bottom
36” (914 mm)
Installation
900285-00 05/2015
The fireplace must be mounted on a fully supported base extending the full width and depth of the unit. The fireplace
may be located on or near conventional construction materials. However, if installed on combustible materials, such
as carpeting, vinyl tile or other combustible material other than wood flooring, the appliance shall be installed on a
metal or wood panel extending the full width and depth of the appliance.
Hearth Extension
A hearth extension is not required with this fireplace. If a hearth extension is used, do not block the lower control
compartment door. Any hearth extension used is for appearance only and does not have to conform to standard
hearth extension installation requirements.
Shelf Height
To provide for the lowest possible shelf surface, use the rear vent model. For top vent models, the venting attached
to the top vent should be routed in a way to minimize obstructions to the space above the fireplace. Do not insulate
the space between the fireplace and the area above it (Table 9 and Table 10). The minimum height from the base
of the fireplace to the underside of combustible materials used to construct a utility shelf in this fashion is shown in
No combustibles or
insulation
in the
shaded area
between the
appliance
and the
shelf
above it.
14
Innovative Hearth Products
(152 mm)
mantel legs may
At 6 in. minimuside wall clearance,a combustible walcan project to anlength
TM
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
Figure 6: Combustible Side ClearancesFigure 7: Mantel Height
At 6” minimum
side wall
clearance, a
combustible
wall can project
to any length.
.
6 in.
6”
45
45
m
l
y
o
o
3 1/2”
3 1/2 in.
(89 mm)*
(89 mm)
Top View of
Top View of
Fireplace
Fireplace
Combustible materials
Combustible Materials
Allowed In Shaded Area
allowed in shaded area
“Safe Zone”
“Safe Zone”.
Combustible Walls
Combustible walls
shown in dark gray
shown in dark gray
Combustible
Combustible mantel
project beyond either side
legs may project
of the fireplace opening
beyond either side of
as long as they are keptwithin the shaded area
the fireplace opening
illustrated here.
as long as they are kept
within the shaded area
illustrated here.
20 (508)
18 (457)
16 (406)
14 (356)
12 (305)
10 (254)
in. (mm)
12
(305)
Mantel depth
(203)
10
(254)
8
(152)
(152 mm)
* 6” (152 mm) in 35” and 40” Contemporary units
TraditionalContemporary
Wall Finishes / Surrounds / Mantels
Installation
900285-00 05/2015
Mantel depth
25 (635)
23 (584)
21 (533)
19 (483)
17 (432)
15 (381)
4
(102)
6
Hood
2
(51)
Fireplace
12
(305)
10
(254)
8
(203)
6
(152)
4
(102)
(51)
2
Fireplace
Opening
Fireplace
NOTE: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined
by the fireplace front face (black sheet metal). Never allow combustible materials to be positioned in front of or
overlapping the fireplace face (Figure 40).
Non-combustible materials, such as surrounds and other fireplace trim, may be installed on the fireplace face, but they
must not cover any portion of the removable glass panel or control compartment.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel (Figure 7). Mantels
constructed of non-combustible materials may be installed at any height above the fireplace opening. However, do
not allow anything to hang below the fireplace hood.
Minimum clearance requirements include any projections such as shelves, window sills, mantels, etc. above
the fireplace.
NOTE: To avoid heat-related finish damage, use finish materials rated 175 °F, or higher, on the underside of the mantel.
INSTALLATION PREPARATION
The fireplace is shipped with all gas controls and components installed and pre-wired. Before installing the fireplace,
follow these steps:
1. Remove the shipping carton, and retain the front of the carton (used to protect the fireplace during construction).
2. Remove the shipping pad, exposing the front glass door.
3. Remove the glass door (Page 61).
NOTE: Place the glass door on the shipping carton to protect its surface.
15
Innovative Hearth Products
TM
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
INSTALLATION SEQUENCE
The typical sequence of installation is outlined below; however, each installation is unique and may result in
variations to the steps described.
See the pages referenced in the following steps for detailed instructions.
Framing
1. Construct the Fireplace Framing (Page 16).
2. Prepare the Fireplace Top Spacers (Page 18).
3. Route the Gas Supply Line to the Fireplace (Page 18).
4. Determining Vent Setup in the Combination Venting Unit (Page 19)
5. Installing Metal, Non-Combustible Front Standoff (Page 19)
6. Rough in the Electrical Supply, if Needed (Page 20).
7. Install the [Optional] Blower Kit before Installation in the Framing (Page 20).
Venting
8. Place the Fireplace in the Framing and Secure (Page 21).
9. Select a Horizontal or Vertical Vent System (Page 21).
10. Install the Vent Restrictor (if necessary) (Page 22).
11. Install the Vent System (Page 25).
Electrical Connection
12. Complete the Field Wiring (Page 37).
13. Install the [Optional] Blower Kit after Installation in the Framing (Page 39).
Gas Connection
14. Connect the Gas Line (Page 40).
15. Verify Proper Fireplace Operation (Page 41).
Finishing
16. Optional: Install the Firebox Liners (Page 58).
17. Install the Logs, Volcanic Stone, and Glowing Embers or Glass Media (Page 58).
18. Install the Glass Door (Page 62).
19. Adjust the Air Shutter to Ensure Proper Flame Appearance (Page 42).
20. Install the Hood in Traditional Fireplaces (Page 43).
21. Reinstall the Included Barrier (Page 44).
22. Install the Finishing Materials and Facade in Contemporary Fireplaces (Page 44).
23. Attach the Safety-in-Operation Warning Labels (Page 47).
24. Installing Batteries for Backup and Wall Switch (Page 44).
Installation
900285-00 05/2015
1. Construct the Fireplace Framing
1. Frame the fireplace as illustrated in Table 10. For corner framing installations, use Table 11. All framing details
must allow for a minimum clearance to combustible framing members as shown in Table 8.
2. If the fireplace is to be elevated above floor level, a solid continuous platform must be constructed below the fireplace.
NOTE: Headers may be in direct contact with the fireplace top standoff spacers when they are bent up vertically,
maintaining the 4” clearance to the fireplace top, but must not be supported by them or notched to fit around them.
All construction above the fireplace must be self-supporting. DO NOT use the fireplace for structural support.
NOTE: For contemporary models, leave a minimum of 6” clearance to any side wall for proper facade installation and
fit.
16
Innovative Hearth Products
TM
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
Table 10: Fireplace Framing Specifications
ModelA *BCDE
33” Models
35” Models
40” Models
45” Models
33 3/4
(857)
35 3/8
(899)
40 3/8
(1026)
45 3/8
(1153)
34 1/4
(845)
36 1/4
(895)
41 1/4
(1048)
41 1/4
(1048)
36 7/8
(930)
38 3/4
(984)
43 3/4
(1111)
43 3/4
(1111)
14 1/2
(368)
18
(447)
18
(447)
18
(447 )
C = Minimum height of top vent installations
E = Minimum height of rear vent installations
* Minimum opening size; additional 1/8” per side is recommended.
NOTE: Framing specifications do NOT apply for flexible venting.
When using flexible venting, refer to the kit requirements for
framing specifications.
19 5/8
(499)
23 3/8
(594)
28 1/4
(717)
28 1/4
(717)
NOTE: Dimension “D” is the
required framing depth when
the finish material (drywall)
thickness is 1/2” (13mm).
Vent Framing—Top Vent
with One 90° Elbow
B
C
1/2 A
A
Inches (millimeters)
Installation
900285-00 05/2015
Framing
construction to be
10 1/2
2 x 4, or larger.
(267)
7 (178)
5 1/8
(130)
12 1/8
(308)
E
D
Table 11: Fireplace Framing Specifications—Corner Installation with Horizontal Termination
ModelABCDEF
33”
35”
40”
45”
33 3/4
(857)
35 3/8
(899)
40 3/8
(1025)
45 3/8
(1153)
51 1/4
(1302)
59 1/2
(1511)
63 13/16
(1621)
70 3/8
(1788)
36 1/4
(921)
42 1/16
(1068)
45 11/32
(1152)
49 3/4
(1264)
25 5/8
(651)
30 1/4
(768)
33 3/16
(818)
35 1/4
(895)
12 1/8
(308)
14 1/4
(362)
15 7/8
(403)
17 1/2
(445)
5 1/2
(140)
6 5/8
(168)
8 1/2
(216)
10 1/4
(260)
C
Back wall of chase/enclosure (including finishing materials)
Table 12: Fireplace Specifications
NOTE: When finishing the area around the hood, 5/8” clearance above hood is required for hood installation.
1. Route a 1/2” (13 mm) gas line to the left side of the fireplace (Figure 10).
NOTE: Gas lines must be routed, assembled, and made of materials that are in strict accordance with local codes
and regulations. All fireplaces are factory-equipped with a flexible gas line connector and a 1/2” shutoff valve
(Page 40).
Figure 10: Routing the gas line - 35”, 40”,
45” Models
Left side front corner of
fireplace framing
Pipe coupling
(recommended)
7 5/8”
(195 mm)
3”
(76 mm)
Proper Sizing of Gas Line
Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed
per requirements outlined in the National Fuel Gas Code, NFPA 54—latest edition (USA) or CAN/CGA-B149.1—
latest edition (Canada).
The gas supply line should not be connected to the appliance until step 14. Connect the Gas Line (Page 40).
Fireplace
Front
Figure10a: Routing the Gas Line - 33” Model
Figure 60: Routing the gas line
Left side front corner of
fireplace framing
Pipe coupling
(recommended)
5 1/4”
(140 mm)
3”
(76 mm)
Fireplace
Front
18
NOTE:
• All fireplaces are factory-equipped with a flexible gas line connector and 1/2” shutoff valve (Figure 35).
• See Massachusetts Horizontal Vent Requirements for additional requirements for installations in the state of
Massachusetts in the USA.
• A pipe joint compound rated for gas should be used on the threaded joints. Ensure propane-resistant
compounds are used in propane applications. Be very careful that the pipe compound does not get inside
the pipe.
• A sediment trap in the supply line as close as possible to the fireplace is recommended.
• Check with the local building official for local code requirements (e.g., Are below grade penetrations of the gas
line allowed?, etc).
CAUTION
If propane is used, be aware that with a tank that is too small (i.e., under 100 lbs, if this
is the only gas appliance in the dwelling—see NPFA 58), there may be a loss of pressure.
This can result in insufficient fuel delivery that can cause sooting, delayed ignition, or other
malfunctions. Any damage resulting from an improper installation is not covered by the
limited warranty.
Innovative Hearth Products
TM
Superior
4.
DRT/C3000 Series Direct-Vent Gas Fireplaces
Determining Vent Setup in the Combination Venting Unit
900285-00 05/2015
Combination venting units are shipped with rear venting setup nearly ready for install. If this is the type of vent you require, remove
all insulation packing and flue plug block off from rear venting and proceed with fireplace installation. If you require a top-vented
unit, use the following steps to convert the fireplace before use.
Outside preparation of the fireplace for top-vent conversion
Installation
Step 1: Remove the eight (8) screws holding the top vent cover
Step 2: Remove the round flue cover from the top venting outlet.
plate and gasket. Discard cover plate and reinstall screws.
Step 3: Remove insulation from inside flue pipe.Step 4: Make sure insulation disc is still in the round cover. Re-
move the flue plug from the top flue.
Installing Metal, Non-Combustible Front Standoff
5.
A non-combustible metal standoff is provided with the fireplace to prevent overlap of drywall or other material of portions of the
fireplace that may be prone to the buildup of heat. Standoff arrives on the lower front of the unit. A field-supplied, noncombustible board may be substituted for the metal standoff.
Use raised locating dimples
to position front standoff.
Step 1: Carefully bend up the two (2) tabs on the heat shield at a 90° angle from each opposite
joint and then the foot of the Standoff at approximately a 45° angle.
Step 2: Secure all three of the screws to the up-right positioned heat shield - one (1) at both ends and one (1) in the
center.
Step 3: Top of front standoff
should be flush with top
standoffs.
Step 4: Standoff should be
flush with front of unit.
19
Innovative Hearth Products
TM
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
Installation
900285-00 05/2015
Installing Non-Combustible Fireboard Standoff in 35” and 40” Contemporary Fireplaces
A non-combustible standoff board is provided for 35” and 40” Contemporary fireplaces to prevent overlap of drywall or other material
of portions of the fireplace that may be prone to the buildup of heat. It is supported by a middle bracket and two side brackets.
Separate and note metal side
(2) and center (1) brackets.
Step 2: Remove the three screws that align with the clearance
screwholes from the top of the unit. Secure the center bracket to
the top center of the fireplace
Rough in the Electrical Supply, if Needed
6.
Step 1: Remove two screws from the top and side of the unit. Bend the side bracket securing tab
over the edge of the unit and secure. Secure bracket to the top through the clearance screwhole.
Step 3: Top of front fireboard
standoff should be flush with
top standoffs (not shown).
As necessary, rough in the fireplace electrical supply per NEC and local codes.
7. Install the [Optional] Blower Kit before Installation in the Framing
1. Remove the left side blower cover panel screw, and blower cover panel in Table 12. Retain the panel and screw
for later reinstallation.
2. Slide the blower through the opening and position it with the bracket oriented to the front of the firebox and
the blower discharge to the rear of the firebox. Bend the two tabs in the firebox floor to secure the blower to
the floor.
3. Reinstall the blower cover panel and secure with the removed screw.
4. Access the blower supply wiring through the front of the fireplace and plug it into the junction box in the right,
rear of the fireplace (Figure 32).
5. Install the blower control switch according to its included instructions.
Step 4: Fireboard standoff
can be secured to the capture
screwholes.
20
Innovative Hearth Products
TM
Superior
8.
DRT/C3000 Series Direct-Vent Gas Fireplaces
Place the Fireplace in the Framing and Secure
NOTE: Nailing flanges, combustible members, and screw heads in areas directly adjacent to the nailing flanges are
EXEMPT from the 1/2” clearance to combustible requirements for the firebox outer wrapper.
NOTE: Combustible framing may be in direct contact with the nailing flanges and may be located within 1/2” of screw
heads and the firebox wrapper in areas adjacent to the nailing flanges.
Frame the opening to the exact dimensions specified in the framing details in this manual.
1. Bend out the appropriate nailing flanges for the drywall / finish material to be used (Figure 11). Nailing flanges
are provided for:
• flush framing,
• 1/2”, and
• 5/8” framing depths.
2. Secure the fireplace to the side framing members using the unit’s nailing flanges —one top and bottom on each
side of the fireplace front (Figure 11). Use 8d nails or the equivalent.
Figure 11: Nailing Flanges
Unit nailing flange
Side
framing
(no clearance to combustible
framing is required)
Installation
900285-00 05/2015
VENT SYSTEM PREPARATION
9. Select a Horizontal or Vertical Vent System
1. With the fireplace secured in the framing, determine the vent route and identify the exterior termination location.
The following sections describe vertical (roof) and horizontal (exterior wall) vent applications. Use only approved
vent components (Page 19 and Page 48).
NOTE: This fireplace must be vented directly to the outside.
The vent system may not service multiple appliances, and must never be connected to a
flue serving a separate solid fuel burning appliance.
NOTE: The vent pipe is tested to be run inside an enclosed wall (such as a chase). There is no requirement for
inspection openings in the enclosing wall at any of the joints in the vent pipe.
WARNING
21
Innovative Hearth Products
2 1/2”
Break-Away
1
3
20
40
6
10
40
25 ft Maximum
horizontal run (flat to near level)
60 ft Maximum vertical run
60
1.9
25
Horizontal Distance (ft)
Vertical Height (ft) from top of unit
Vertical Height (ft)
2
5
Elbow**
510
15
3” Base + wing3” Base
6 ft Minimum
vertical run
6 ft Minimum vertical run
None
Appliance Top Vent Outlet
U-Shaped Vent
Restrictor
Inner
Fireplace
Collar
Appliance Top Vent Outlet
U-SHAPED VENT
Appliance Rear
ent
U-Shaped Vent
Restrictor
Inner
Fireplace
Collar
Appliance Top Vent Outlet
U-SHAPED VENTRESTRICTOR
APPLIANCE REAR
VENT OUTLET
INNER FIREPLACE
COLLAR
Inner Fireplace CollarAppliance Rear
Vent Outlet
U-Shaped Vent Restrictor
Intake Air Baffle
With break-away raised***
U-Shaped Vent
Restrictor
Inner
Fireplace
Collar
Appliance Top Vent Outlet
U-SHAPED VENTRESTRICTOR
APPLIANCE REAR
VENT OUTLET
INNER FIREPLACE
COLLAR
Inner Fireplace CollarAppliance Rear
Vent Outlet
U-Shaped Vent Restrictor
Intake Air Baffle
Base Vent Restrictor
With break-away raised***
TM
Superior
10.
DRT/C3000 Series Direct-Vent Gas Fireplaces
Install the Vent Restrictor (if necessary)
Installation
900285-00 05/2015
1. Use the vent run descriptions in Figure 12 to determine if a vent restrictor is necessary.
2. If necessary, assemble the vent restrictor and wing as detailed in Figure 12 and Figure 15.
3. If necessary, install the appropriate vent restrictor (Figure 13 and Figure 14).
NOTE: If installing the vent restrictor in a rear vent application, ensure the factory-installed intake air baffle is in place (Figure 14).
NOTE: The vent restrictor is shipped in the firebox.
Figure 12: When to use a vent restrictorFigure 13: Vent restrictor installation, Top vent
U-Shaped Vent
*
Restrictor
Inner
Fireplace
Collar
* For straight runs or runs with elbows as illustrated in Vertical Vent Figures/Tables starting on
Page 28
** No rise required.
*** On 33” Models, use the 3” base restrictor. Do not raise the break-away tab.
NOTE: When venting Rear Horizontal with slip collar and termination only, install base vent
When horizontally terminating a vent system with a vertical vent run up to 4 ft through an exterior wall, no vent
restrictor is required.
If installing more than 4 ft of vertical venting, install the restrictor (Figure 14), from inside or outside the unit, in the
inner fireplace collar. The vent restrictor is held in place by friction.
Secure Vent® SV4.5 direct-vent system components are unitized concentric pipe components featuring positive twist
lock connections (Figure 16 and Figure 17). All of the fireplaces covered in this document are fitted with collars
having locking inclined channels. The dimpled end of the vent components fit over the fireplace/vent collar to create
the positive twist lock connection.
1. Align the dimpled end over the collar, adjusting the radial alignment until the four (4) locking dimples are aligned
with the inlet of the four (4) inclined channels on the collar (Figure 16).
2. Push the vent component against the collar until it fully engages, then twist the component clockwise, running
the dimples down and along the incline channels until they seat at the end of the channels.
Installation
900285-00 05/2015
Vent elbows
NOTE: The unitized design of the Secure Vent® components will engage and seal both the inner and outer vent pipe.
3. If desired, a #6 x 1/2” screw can be used at the joint, but is not required as the pipe will securely lock
when twisted (Figure 17).
Where required, a telescopic vent section (SV4.5LA) may be used to provide the installer with an option to install
in tight and confined spaces, or where the vent run made up of fixed length pieces develops a joint in a undesirable
location, or will not build up to the required length. The SV4.5LA Telescopic Vent Section has an effective length of
from 1 1/2–7” (38–191 mm). The SV4.5LA is fitted with a locking inclined channel end (identical to a normal vent
section component) and a plain end with three (3) pilot holes. Slip the plain end over the locking channel end of a
standard SV4.5 vent component the required distance and secure with three (3) screws.
Figure 16: Connecting vent
components
Arrow
Dimple
Locking
Incline
Channel
Appliance Collar or
Vent Section
Figure 17: Connected vent
components
Dimple
Locking
Incline
Channel
Arrow
Figure 18: Elbow Dimensions
4 13/16”
(122 mm)
Swivel Joint
(360°)
SV4.5E45
(45° elbow)
Swivel Joint
(360°)
SV4.5E90
(90° elbow)
8 1/8”
(206 mm)
Vent elbows are available in 90° and 45° configurations. Refer to Figure 18 for the SV4.5E45 and SV4.5E90
elbow dimensions. The elbows feature a twist section to allow them to be routed about the center axis of their initial
collar section to align with the required direction of the next vent run element.
1. Rotate the elbow in a clockwise direction (to avoid the possiblity of unlocking any of the previously connected
vent sections) for proper alignment (Figure 18). See Connecting the vent pipe for more information.
23
Innovative Hearth Products
TM
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
Vent section length table
Table 14: Vent Section Length
Nominal Section
Length (in.)
Net Section Length
(in.)
Height of Vent
in.ftin.ft
4.50.37510000125221010708
90.7520000227623000808
10.50.87501000127923.25000066
151.25110002280.523.375100809
22.51.875001001289.524.125010067
31.52.625030003301.525.125001067
34.5 2.875000101310.525.875000909
37.53.125111003325.527.125000077
43.53.62502100333027.5100078
453.7500200234528.7500010010
46.53.875000011349.529.12510010011
514.2510001237231000088
55.54.625012003379.531.62500011011
574.75001102418.534.875000099
67.55.62500300346538.7500001010
695.75000202475.539.62501001011
73.56.1251002034804011001012
79.56.6250102034924110101012
816.75000112499.541.62500011011
91.57.6250020135044210011012
937.75000022511.542.62500001111
97.58.125100023520.543.37502011114
103.58.625000303531
1089100304538.544.87510021114
1179.7510500654945.7510211115
118.59.87511030555846.500001212
12610.5001304562.546.87510001213
130.510.875101305568.547.37501001213
13511.2500600657347.7511001214
139.511.625000033580.548.37500101213
142.511.875100405589.549.12501221015
14412100034595.549.62511101215
154.512.875110035604.550.37500001313
160.513.37502003561551.2501001314
172.514.375000505625.552.12502001315
17714.75100506631.552.62510101315
18615.5000044637.553.12501101315
196.516.37501004565154.2500001414
20717.25000606655.554.62510001415
211.517.6251006076725602001416
217.518.12501060767856.510101416
229.519.125001607688.557.37511101417
232.519.375000055697.558.12500001515
241.520.12500070770258.510001516
24620.5100708712.559.37511001517
24
Installation
900285-00 05/2015
Table 15 will assist calculating how many vent sections are needed for the planned vent configuration. When a vent
section is engaged with another section, its effective length will be 1 1/2” shorter.
Maintain the minimum clearance to combustibles (e.g., framing, attic, ceiling insulation, etc.).
For all vertical runs:
• 1” (25 mm) from all sides
NOTE: Attic insulation shield (H3907, see Page 45) must be installed when blown or loose-fill insulation is used,
and is required for all attic installations.
For all horizontal/inclined runs:
• 3” (76 mm) from the top
• 1” (25 mm) from the sides
• 1” (25 mm) from the bottom
11. Install the Vent System
Install the Vertical Termination Vent System
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting
according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the
current standards of CAN/CGA-B149.1 in Canada.
Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier.
Dégagement conforme aux codes d’installa tion locaux et aux exigences du foumisseunde gaz.
Vertical vent systems terminate through the roof. The minimum vent height above the roof and/or adjacent walls
is specified in ANSI Z223.1 (In Canada, the current CAN/CGA-B149.1 installation code) by major building codes.
Always consult your local codes for specific requirements. A general guide to follow is the gas vent rule (Table 6).
The following figures and their associated vertical vent tables illustrate the various configurations that are possible
for use with these fireplaces. Secure Vent® pipe is shown in these figures; Secure Flex® pipe may also be used.
A table summarizes each configuration’s minimum and maximum vertical and horizontal length parameters for a
variety of applications.
1. Refer to Figure 25 and Table 17–Table 20 on Page 28–29 to select the type of vertical installation desired.
Elbows are available in 90° and 45° configurations. Refer to Figure 18 on Page 23 for the SV4.5E45 and
SV4.5E90 elbow dimensional specifications.
Installation
900285-00 05/2015
Vertical (Straight) Installation
1. Determine the number of straight vent sections required—See Effective Vent Length on Page 23 for more
information. Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists.
Figure 19: Vertical (Straight) Installation
Termination
Max. 60 ft
(18.3 m)
SV4.5FA or
SV4.5FB Flashing
AND SV4.5SC
Storm Collar
1” (25.4 mm)
Minimum
Clearance to
Combustibles
SV4.5VF
Firestop/Spacer*
*When using Secure Flex,
use Firestop/Spacer
SF4.5VF.
SV4.5L6/12/24/36/48
Vent Sections
25
Loading...
+ 57 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.