S9361A CONTROL SUPPLEMENT MANUAL
MG & SG SERIES BOILERS
FOR MODELS MG-50-E TO MG-150-E AND
SG-135-E TO SG-270-E
This supplement manual must be used in conjunction with the
Installation and Service Manual provided with your boiler. It
provides important instructions relevant to controller
programming, operation, troubleshooting, and wiring.
WARNING
PN9362763
Improper installation, adjustment, alteration, service or maintenance can cause propert
damage, injury, or loss of life. Please carefully read this manual along with the
Installation and Service Manual. For assistance or additional information, consult a
qualified installer, service agency or the gas supplier.
Manufacturers of Gas and Electric Boilers, Stainless Steel Tanks, Heat Exchangers and Electric Boosters.
94 Riverside Drive, North Vancouver, B.C. V7H 2M6 • Telephone (604) 929-1214 • www.alliedboilers.com
NEW CONTROLLER
Allied Engineering Company
Division of E-Z-Rect Manufacturing Ltd.
Branches: Calgary • Edmonton • Toronto • Denver
![](/html/04/04ac/04ac26faa8765620423d0c1488b8121bd5d2a6a8ae2c7c037eb7069f16dbfb3a/bg2.png)
CONTROLLER PROGRAMMING AND SERVICE CODES Section 1
1.1 CONTROLLER PROGRAMMING AND SERVICE CODES
2012 NRCan and DOE Compliance and Operation
Operation of this control may delay the burner operation while the residual heat is circulated
out of the boiler.
The integrated boiler control module provides ignition
sequence, flame monitoring and safety shutoff for
intermittent pilot spark ignition. It also provides limit rated
water temperature control for with two separate sensors in
one casing (3-wire).
The control is located on the front panel inside the boiler.
The control display, along with Up ▲, Down ▼, and “I” keys
may be used to view boiler operating status and program
parameters (Figure 1).
1.1.1 RUN MODE
In the RUN mode, status items and parameters are viewable.
Figure 1 Control Displa
To read settings, press and release the “I” key to find the parameter of interest. Each setting will
alternately flash between the relevant display code listed in the Table 1 and its corresponding value. For
example, press and release “I” key until “HL_” setpoint is displayed, it will then flash a three-digit number,
i.e., 220, followed by ˚F (or ˚C). This indicates that the boiler water temperature of 220 ˚F is set. Other
operating parameters display the settings in a similar fashion.
Table 1 Run Mode Parameters
Text Description
STA
BT
SP
HL
HDF
FLA
RUN
CYC
ERR
Status (see status numbers)
Boiler temperature
Operating setpoint
High limit setpoint
Differential set-point
Flame current
Run time hours
Boiler cycles
Error (see error numbers)
Display
StA
bt
SP
HL
HdF
FLA
run
CYC
Err
2
![](/html/04/04ac/04ac26faa8765620423d0c1488b8121bd5d2a6a8ae2c7c037eb7069f16dbfb3a/bg3.png)
1.1.2 INSTALLER MODE
To enter the adjustment mode:
1. Press with Up ▲, Down ▼, and “I” keys (see Figure 1) simultaneously for three seconds.
2. Press and release the “I” key until the parameter (listed in the Table 2) requiring adjustment is
displayed.
3. Press with Up ▲ or Down ▼ key until the parameter has reached the desired value.
4. After 60 seconds without any key inputs, the control will automatically return to the RUN Mode.
Table 2 Installer Mode O
3-Digit 7-Segment Display
1st Screen 2nd Screen (setting value) 3rd Screen
HL_
HdF
Or_
otH
otL
btL
tPL
tPt
rSt
F-C
<high limit> ˚F or ˚C 180 ˚F 130 to 220 ˚F Adjust high limit setting
<high limit differential> ˚F or ˚C 15 ˚F 10 to 30 ˚F
<pump overrun time> Sec 60 sec
<ODR maximal temp.> ˚F or ˚C 55 ˚F 40 to 70 ˚F
<ODR minimal temp.> ˚F or ˚C 0 ˚F -40 to 40 ˚F
<minimal water temp.> ˚F or ˚ C 140 ˚F 130 to 150 ˚F
<minimal boiler temp.> ˚F or ˚C 140 ˚F
<maximal delay> Min 2 1 to 10 minutes
On or OFF N/A N/A Reset lockout
˚F or ˚C
tions
Default Range
0 to 120
seconds
OFF,
120 to 160 ˚F
˚F ˚F or ˚C
Description
Adjust high limit
differential
Pump post-purge time
Maximal outdoor
temperature
Minimal outdoor
temperature
Minimal boiler
temperature
Thermal purging
minimal temperature
(parameter is available
only if outdoor
temperature is invalid)
Maximal thermal purge
time (parameter is
available only if outdoor
temperature is invalid)
Select degrees ˚F or ˚C
mode
3