Super Hot 304B, 306B, 305B, 312B, 309B Installation And Sevice Manual

...
RISK OF ELECTRIC SHOCK - This unit may be connected to more than
PHONE :
INSTALLATION AND SERVICE MANUAL
SPACESAVER ELECTRIC BOOSTER
HOT WATER HEATERS
4 kW to 54 kW, 208 Vac to 600 Vac, Single or Three Phase
180ºF instantaneous hot water for commercial dishwashers
Suitable for installation with all “name-brand” dishwashers
WARNING
one electrical circuit. Turn off all electrical supply circuits before servicing.
Failure to follow the information in this manual exactly may result in property damage, personal injury or loss of life. Read all instructions provided in this manual and all other information supplied with the booster before installing. This manual must be used by a qualified heating installer or service technician only.
IMPORTANT
The booster heater must be installed in accordance with all applicable
national, provincial/state, and local codes, laws, regulations, and ordinances.
Carefully read this manual. This manual must be left with the owner and
should be located adjacent to the booster for reference.
Ensure booster heater is full of water before turning on electricity.
Elements will burn out immediately without water in the booster heater.
Booster heater voltage must be correct for voltage available. Check
nameplate on the booster heater for full information.
Overcurrent protection between the power supply and the booster heater
must be provided in accordance with the national and/or local codes.
Always ensure power switch is turned off before servicing. Under no circumstances should any electrical wiring or internal controls be
touched, except by a qualified electrician or any heating system be adjusted, except by a qualified service technician.
SAVE THESE INSTRUCTIONS.
DATE OF INSTALLATION :
INSTALLED BY :
Manufactured by
Manufacturers of Gas and Electric Boilers, Heat Exchangers, Electric Boosters, Indirect Tanks
94 Riverside Drive, North Vancouver, B.C. V7H 2M6  Telephone 604-929-1214 www.alliedboilers.com
PN6510930
Allied Engineering Company
Division of E-Z-Rect Manufacturing Ltd.
Branches: Calgary Edmonton Toronto Denver
Electric Booster– Installation, Operating and Maintenance Instructions
Dimensions, Piping Diagram and Specifications Section 1
1.1 DIMENSIONS AND PIPING DIAGRAM
Figure 1 – Dimensions and Piping Diagram
1.2 TECHNICAL SPECIFICATIONS
Maximum Operating Pressure 130 p.s.i. Maximum Operating Water Temperature 210ºF Water Capacity in booster – 4-18kW 4.27 US Gallons Water Capacity in booster – 24-54kW 5.80 US Gallons Inlet and Outlet Pipe Size 3/4” NPT
2
Electric Booster– Installation, Operating and Maintenance Instructions
TABLE 1. Super Hot Electric Booster Heater Specifications (Flange Type Elements)
BOOSTER MODEL NUMBERS, kW RATINGS AND MAX. AMPERAGE DRAW
Model
Number
304B 4 13,649 4.27 41 19.2 16.7 -- -- -- -- 60 LBS
305B 5 17.062 4.27 52 24.0 20.8 -- -- -- -- 60 LBS 306B 6 20,474 4.27 62 28.8 25.0 16.6 14.4 7.2 5.8 60 LBS
309B 9 30,711 4.27 93 43.3 37.5 25.0 21.6 10.8 8.7 60 LBS 312B 12 40,948 4.27 124 57.7 50.0 33.3 28.8 14.4 11.5 65 LBS
315B 15 51,185 4.27 156 72.1 62.5 318B 18 61,422 4.27 187 86.5 75.0 54.6* 47.3* 23.7* 18.9* 70 LBS
424B 24 81,895 5.80 249 115 100 66.5 57.7 28.8 23.1 70 LBS 430B 30 102,369 5.80 311 144 125 83.2 72.1 36.0 28.8 75 LBS
436B 36 122,843 5.80 373 173 150 100 86.5 43.3 34.6 75 LBS 545B 45 153,554 5.80 467 216 188 125 108 54.1 43.3 90 LBS
554B 54 184,264 5.80 560 260 225 150 130 64.9 51.9 90 LBS
SPECIFY MODEL NUMBER, VOLTAGE AND EITHER 1 OR 3 PHASE WHEN ORDERING
kW Btu/Hr
Tank
Capacity
U.S. Gal
U.S. Gal./Hr
40ºF Rise
Single Phase Three Phase
208 240 208 240 480 600
* Delta connection (unbalanced load): Leg with highest value of line current is indicated.
Maximum Amperage Draw
46.4* 40.2* 20.1* 16.1*
Approx.
Shipping
Weight
65 LBS
1.3 WATER TEMPERATURE RECOVERY
Booster Heater water recovery formulas:
G.P.H. (U.S.) =
415 x kW
L.P.H. =
Temp. Rise (ºF) Temp. Rise (ºC)
TABLE 2. Water Temperature Recovery in GPH (LPH)
Model kW 30ºF (17ºC) 40ºF (22ºC) 50ºF (28ºC) 60ºF (33ºC) 70ºF (39ºC) 80ºF (44ºC) 90ºF (50ºC)
304B 4 55 (208) 41 (155) 33 (125) 28 (106) 24 (91) 21 (79) 18 (68)
305B 5 69 (261) 52 (197) 41 (155) 34 (129) 29 (110) 26 (98) 23 (87)
306B 6 83 (314) 62 (235) 50 (189) 41 (155) 35 (132) 31 (117) 27 (102)
309B 9 124 (469) 93 (352) 75 (284) 62 (235) 53 (200) 47 (178) 41 (155)
312B 12 166 (628) 124 (469) 100 (379) 83 (314) 71 (269) 62 (235) 55 (208)
315B 15 208 (787) 156 (590) 125 (473) 104 (394) 89 (337) 78 (295) 69 (261)
318B 18 249 (942) 187 (708) 149 (564) 125 (473) 107 (405) 93 (352) 83 (314)
424B 24 332 (1256) 249 (942) 199 (753) 166 (628) 142 (537) 125 (473) 111 (420)
430B 30 415 (1571) 311 (1177) 249 (942) 207 (783) 178 (673) 156 (590) 138 (522)
436B 36 498 (1885) 373 (1412) 299 (1132) 249 (942) 213 (806) 187 (708) 166 (628)
545B 45 622 (2354) 467 (1767) 373 (1412) 311 (1177) 267 (1010) 233 (882) 207 (783)
554B 54 747 (2827) 560 (2120) 448 (1695) 373 (1412) 320 (1211) 280 (1060) 249 (942)
874 x kW
3
Electric Booster– Installation, Operating and Maintenance Instructions
Installation Instructions Section 2
2.1 RECEIVING
INSPECT SHIPMENT FOR POSSIBLE DAMAGE. All goods are carefully manufactured, inspected,
checked and packed by experienced workers. The manufacturer's responsibility ceases upon delivery of goods to the carrier in good condition. Any claims for damage and/or shortage in shipment or non-delivery must be filed immediately against the carrier by the consignee.
Use care when receiving and unpacking the tank. Dropping the booster heater may cause damage and prevent safe and proper operation.
2.2 INTRODUCTION
Super Hot Electric Boosters are designed to produce 180ºF rinse water for commercial dishwashers to use in cleaning and sanitizing dishware. The high efficiency and powerful rinse output of the booster heater should result in significant savings on detergent and rinse additives. Compared with other methods of sanitizing, the Super Hot Electric Booster is the economical choice and provides exceptional quality and reliability.
2.3 INSTALLATION CODES AND REQUIREMENTS
All applicable national, provincial/state, and local codes, laws, regulations, and ordinances must be followed. They expand on and take precedence over any recommendations in this booklet. Authorities having jurisdiction shall be consulted before installations are made.
If an external electrical source is utilized, the booster heater, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70 (current edition) and/or the Canadian Electrical Code, CSA C22.1 Part 1 (current edition).
If there is any conflict in the above requirements, the more stringent requirement applies.
The installation and service must also conform to the additional requirements in this manual. If there is any conflict with a requirement in this manual and a code requirement, the code requirement must be followed.
4