Sunx FX-301, FX-301P-HS, FX-305, FX-301P, FX-305P Operation Manual

1. Functional Description
1-1. Functional Description ..........................P.1
1-2. Setting Procedure.................................P.1
2. Diagram of Functions and Settings
2-1. Diagram of Functions and Settings......P.2
3. Others 3-1.
.....P.3
3-2. Factory Settings ...................................P.4
3-3. Error Display Indicator Readings .........P.4
3-4.
Introducing FX-301(P) Updated Version Unit
..P.5
4. Settings for NAVI Mode
4-1. NAVI Mode Functions and Settings .....P.6
4-2. Teaching Mode
[when using FX-301(P)(-HS) or FX-305(P) normal mode]
P.10
4-3. Teaching Mode
[when using FX-305(P) window comparator mode]
P.13
4-4. Threshold Value Fine Adjustment Mode
[when using FX-301(P)(-HS) or FX-305(P) normal mode]
P.19
4-5. Threshold Value Fine Adjustment Mode
[when using FX-305(P) window comparator mode]
P.20
4-6. Output Operation Setting Mode .........P.22
4-7. Timer Operation Setting Mode...........P.23
5. PRO1 Mode 5-1.
PRO1 Mode Functions and Settings
.....P.24
5-2. Response Time Change Function......P.27
5-3.
Timer Setting Function [FX-301(P)(-HS)]
....
P.28
5-4. Timer Setting Function [FX-305(P)]....P.29
5-5. Hysteresis Function ............................P.31
5-6. Stability Function................................P.32
5-7. Shift Function .....................................P.33
5-8.
Light Emitting Amount Selection Function
..P.34
6. PRO2 Mode 6-1.
PRO2 Mode Functions and Settings....
P.35
6-2. Digital Display Setting Function .........P.37
6-3. Digital Display Inversion Function......P.38
6-4. ECO Mode Setting Function ..............P.39
7. PRO3 Mode 7-1.
PRO3 Mode Functions and Settings...
P.40
7-2. Data Bank Load Setting Function......P.41
7-3. Data Bank Save Setting Function......P.42
8. PRO4 Mode 8-1.
PRO4 Mode Functions and Settings...
P.43
8-2. Setting Contents Copy Function ........P.44
8-3.
Remote Data Bank Load Setting Function ..
P.45 8-4.
Remote Data Bank Save Setting Function..
P.46 8-5.
Selection for Communication Change to Permit / Not to Permit
..
P.47
8-6. Backup Setting Function....................P.48
9. PRO5 Mode 9-1.
PRO5 Mode Functions and Settings .....
P.49
9-2. Code Setting Function........................P.51
9-3. Adjust Lock Function..........................P.52
9-4. Setting Reset Function.......................P.53
9-5.
Interference Prevention Switching Function [FX-305(P) only]
....P.54
10.PRO6 Mode [FX-305(P) only] 10-1.
PRO6 Mode Functions and Settings....
P.55
10-2. Output 1 Sensing Mode Settings.....P.56
10-3. Output 2 Sensing Mode Settings.....P.58
11.Others
11-1. Key Lock Functions..........................P.59
11-2.
Threshold Value Confirmation Function
..P.59
PRO Mode Operation Guide
FX-301(P)(-HS)/305(P)
DIGITAL FIBER SENSOR
For t
he operation method of FX-301B/G/H, refer to ‘Digital fiber sensor FX-301/302/303 series
PRO mode operation guide’ on the SUNX home page.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Functional Description
1-1. Functional Description
1-2. Setting Procedure
1
1 Operation indicator (Orange) FX-301(P)(-HS) : Lights up when output is ON.
Output 1 operation indicator (Orange)…
FX-305(P) : Lights up when output 1 is ON.
2 Stability indicator (Green)
Output 2 operation indicator (Orange)
3 MODE indicator RUN (Green) :
TEACH (Yellow) :
ADJ (Yellow) :
L/D (Yellow) : TIMER (Yellow) :
PRO (Yellow) :
4 Jog switch Turning this switch in the or direction, allows different items to be viewed for
selection and pressing the switch then confirms the selected setting.
5 MODE key
This key is used to select operating modes and to cancel settings during the configuration process.
The [MODE key] and [Jog switch] are utilized to configure various settings.
Cancel: If the [MODE key] is pressed, the unit will return to the previous settings status, immediately before the
[Jog switch] was pressed (the selected setting has been confirmed).
Selection and confirmation of settings are performed according to the order of the numbers, as shown on the amplifier: 1, 2 and 3.
Press the [MODE key] (mode selection / cancellation)
1
Turn the [Jog switch] in the or direction (chooses setting for selection)
2
Press the [Jog switch] (confirms the selected setting)
3
1FX-301(P)(-HS): Operation indicator (Orange)
FX-305(P): Output 1 operation indicator (Orange)
2FX-301(P)(-HS): Stability indicator (Green)
FX-305(P): Output 2 operation indicator (Orange)
3MODE indicator
4Jog switch
5MODE key
, and are in the correct order for selecting settings.
Lights up during normal sensing operation. When this indicator lights up, the threshold value can be set by utilizing either 2-level teaching’, ‘limit teaching or full-auto teaching’. When the FX-305(P) is in window comparator mode, the ‘threshold value can be set by either 1-level teaching, 2-level teachingor 3-level teaching whenever this indicator lights up. When this indicator lights up, fine adjustment of the threshold value can be performed. When this indicator lights up, the output operation can be set. When this indicator lights up, timer operation can be set. (Timer period can be set in PRO1 mode.) When this indicator lights up, further advanced functions, such as the copying and memory functions, can be set.
FX-301(P)(-HS) :
Lights up when the incident light intensity is great enough for stable operation.
FX-305(P) : Lights up when output 2 is ON.
1
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Diagram of Functions and Settings
2-1. Diagram of Functions and Settings
2
The amplifier features and settings are generally classified into two main modes; the NAVI mode for items and settings that are frequently reconfigured, and the PRO mode that contains more detailed settings.
Allows fine adjustment of the threshold value. (Refer to p.19~)
Adjust
ADJ
The threshold value can be set by utilizing either 2-level teaching, limit teaching or full-auto teaching. (Refer to p.10~)
This indicates normal sensing operation.
Run
RUN
NAVI mode
PRO mode
Sets output operation either Light­ON, or Dark-ON. (Refer to p.22)
L-ON / D-ON
L/D
Configures operation of the timer. (Refer to p.23)
Timer
TIMER
Switches among response times. (Refer to p.27)
Response Time Change
Configures timer operation. (Refer to p.28~)
Timer Setting
Sets hysteresis level. (Refer to p.31)
Hysteresis
Teaching
TEACH
PRO1
PRO2
PRO3
PRO4
PRO5
Shifts the threshold value by a certain percentage increment in limit teaching. (Refer to p.33)
Shift
Permits selection of stability indicator response levels for changes in the range for lighting up. (Refer to p.32) [FX-301(P)(-HS) only]
Stability
Changes the light emitting a­mount selection setting. (Refer to p.34)
Light Emitting Amount Selection
Allows selection of different content to be indicated in the digital display. (Refer to p.37)
Digital Display Setting
Sets the viewing orientation of the digital display. (Refer to p.38)
Digital Display Inversion
Sets the digital display to turn ON / OFF. (Refer to p.39)
ECO Mode
Loads configuration setting from the data bank. (Refer to p.41)
Data Bank Load
Saves configuration setting into the data bank. (Refer to p.42)
Data Bank Save
Using optical communications, configuration settings from the main unit are copied to connected sub units all at once. (Refer to p.44)
Copy
Using optical communication, configuration settings can be loaded from respective data banks all at once. (Refer to p.45)
Remote Data Bank Load
Using optical communication, current configu­ration settings can be saved into respective data banks all at once. (Refer to p.46)
Remote Data Bank Save
Allows basic configuration information to be set in a single step, by inputting a 4-digit code. (Refer t o p .5 1 )
Code
Allows fine adjustment of the ‘threshold value to be directly performed during RUN mode. (Refer to p.52)
Adjust Lock
All settings, except for data bank information, revert to factory settings. (Refer to p.53)
Reset
Switches the number of units for which interference prevention switching is enabled. * FX-305(P) only. (Refer to p.54)
Interference Prevention Switching
P.24~
P.35~
P.40~
P.43~
P.49~
When using optical communication for carrying out copy / load / save operations all at once, this function allows optical communication to pass through the unit. (Refer to p.47)
Communication Change To Permit / Not to Permit
Allows not to save the threshold value, by teaching via external input in EEPROM. (Refer to p.48)
* The FX-301(P)-HS is not
equipped with a PRO4 setting function.
Backup
The items that can be set are different for output 1 and output 2.
P.55~
Output 1
Output 2
Sets a threshold value for ON / OFF operation. (Refer to p.56)
Normal Mode
Judges if set two threshold values are within the required range or not. This can be selected in 1-level / 2-level / 3-level teaching. (Refer to p.56)
Window Comparator Mode
Sensing mode that cancels out slight changes in light intensity so that only sudden increases in incident light intensity are sensed. (Refer to p.56)
Rising Differential Mode
PRO6
Trailing Differential Mode
Sensing mode that cancels out slight changes in light intensity so that only sudden decreases in incident light intensity are sensed. (Refer to p.56)
Error Output
Output when overcurrent occurs or when a communication error occurs from connected incompletely. (Refer to p.58)
Alarm Output
Be used as alarm output when the threshold value for output 2 is linked to output 1 and the light amount drops. (Refer to p.58)
Available only in FX-305(P)
*
When the FX-305(P) is in window comparator mode, the threshold value can be set by either 1-level teaching, 2-level teaching or 3-level teaching.
Allows various detailed settings to be configured, such as optical communications, save / load and other settings.
Pro
PRO
2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Others
3-1. Precautions When Selecting Settings
3
Press the MODE key once.
Example: When operating in PRO mode.
Press the Jog switch.
To cancel
Canceling operations
1Select PRO mode.
To cancel any operation, press the [MODE key]. If the [MODE key] is pressed once, the unit will return to
the previous settings status immediately before the [Jog switch] was pressed.
When changing the status of any setting, ensure that the selected setting is subsequently confirmed.
If confirmation is not performed, the new setting will not take effect.
Confirming settings
Example: When setting response time change.
(In case of FX-301)
S-D ( reduced intensity )
STD (standard)
H-SP (ultra high-speed)
FAST (high-speed)
LONG (long-range)
Press the Jog switch.
Press the Jog switch.
The digital display will quickly blink 3 times to confirm the setting.
2If the [Jog switch] is pressed, the current mode will be displayed.
* The factory setting is STD (standard).
4If the [Jog switch] is pressed, the digital display will quickly blink 3 times, confirming the setting.
Setting protection
1Select response time change.
2If the [Jog switch] is pressed once, the unit will enter
the response time change state.
3If the [Jog switch ] is turned, the digital display
will blink. Select the desired mode.
3To cancel the response time change operation,
press the [MODE key] once.
4The display will return to the previous [PRO1 mode]
selection screen.
You can use the key lock function to protect settings. (Refer to p.59.) Key lock function This function can be used to prevent the operator from accidentally changing the sensor settings.
Turn the Jog switch to select the desired mode.
3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
3-2. Factory Settings
Factory settings for the FX-301(P)(-HS)/305(P) are indicated below: If the unit is reset using the 9-4 Setting Reset Function from PRO5 Mode on p.53, the resulting settings will be those indicated below:
Output 1:
,
Output 2:
Model No.
Item
Response time
Timer period
Hysteresis
Stability
Shift amount during limit teaching
Light emitting amount selection function
Display
Display turning
ECO mode
Selection for transmission change to permit / not to permit
Backup
Code
Adjust lock Interference prev ention s witching function [FX-305(P) only] Sensing mode [FX-305(P) only] (Note)
Settings
Standard (standard)
10 ms H-02 (standard) S-02 (standard)
15 %
Level 4 (MAX)
Incident light intensity display
OFF OFF OFF
ON
0004
ON
Settings
40
L-ON
Without timer
Digital display
FX-301(P)FX-301(P)-HS
Digital displaySettings
80
L-ON
Without timer
Digital display
Digital display
FX-301(P)
Error description
FX-305(P)
Measures
Turn off the power, then check the load.
Confirm that all amplifiers are properly connected to each other.
The load has short-circuited and excess current is flowing. : Output 1, : Output 2
FX-301(P)FX-301(P)-HS
FX-305(P)
FX-305(P)
Settings
Standard F (standard 2)
10 ms
H-02 (standard)
15 %
Level 4 (MAX)
Incident light intensity display
OFF OFF OFF
ON
J004
ON
IP-1
Normal mode
Settings
Output 1: 80, Output 2: 120
L-ON
Without timer
Digital display
Settings
H-SP (ultra high-speed)
10 ms
H-02 (standard)
S-02
(standard) 15 %
Level 2
Incident light intensity display
OFF OFF
ON
004
ON
Digital display
NAVI mode
PRO mode
3-3. Error Display Indicator Readings
In case of errors, attempt the following measures:
Note: In window comparator mode, the factory settings for teaching method is 2-level teaching’.
Model No.
Item
Threshold value
Light-receiving operation
Timer operation
Communication error has occurred at time of connection.
In case of using functions of PRO4 mode
()
(ON when light is received) (ON when light is received)(ON when light is received)
4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
3-4. Introducing FX-301(P) Updated Version Unit
Upgraded functions
Changes in appearance
Updated version units of the FX-301(P) (red LED type) have been manufactured since June 2004. There are some differences in the functions and communication method between these units and previous version units.
Before change After change
Top view
Side view
Name
plate Display Uses special parts
*
NAVI is printed on the both sides
* NAVI’ is printed only on a side
Top view
Side view
Change in shape of jog switch
Added to name plate
Checking minor changes between previous and new models can be done by checking whether the printing is on both sides or only one side.
An ultra high-speed mode (H-SP) has been added to the existing 4 response time modes [high-speed (FAST), reduced intensity (S-D), standard (STD) and long range (LONG)]. This is changed using ’ in .
1. Response times added
Before change After change
4 steps
150 !s (FAST) 250 !s (S-D) 250 !s (STD) 2 ms (LONG)
5 steps
150 !s (FAST)
65 ¨s (added)(H-SP)
250 !s (S-D) 250 !s (STD) 2 ms (LONG)
2. Extension of timer period
The setting range for the timer period was previously 500 ms, but this has been extended to a new range of 9999 ms.
3. Light emitting amount selection function
The light emitting amount can be changed to one of 4 levels (5 levels when emission halt is included). However, the number of levels that can be set will vary depending on the response time settings. For further details, refer to p.34.
4. Backup, copy lock and key lock functions added
Backup Copy lock Key lock
: This selects whether or not threshold values set by
teaching are written to (stored in) an EEPROM.
: This selects whether copy function and data bank
function communication are possible or not.
: This disables input using switches to prevent
accidental changing of settings.
Digital display only
Previous version unit: Sensitivity surplus is indicated by the number
of blinks of the stability indicator.
After change
Changes in operation
1. Timer selection method
Previous version unit:
Timer type was changed using PRO1 mode. The ‘TIMER’ setting in NAVI mode could onlybe turned on or off.
After change : The type of timer can be changed using the
TIMER function in NAVI mode.
Display changes
1. Checking blinking of sensitivity margin
The stable margin display method after teaching has been changed.
2. Initial direct code value changed
The factory default settings for the direct codes have been changed.
2. Checking threshold value in RUN mode
After change: The threshold values can be checked by turning the jog switch.
Previous version unit 0000
m The default setting for the timer period is 10 ms, and the direct code for
10 ms is 4, so this has been changed.
After change 0004
Internal circuit changes
1. Addition of an APC circuit
A four-chemical emitting element which provides stable sensing over long periods has been added, as well as an APC (Auto Power Control) circuit that improves stability during short periods.
1 Program the sensor to indicate PRO4.
2 Press the jog switch and the MODE key
simultaneously.
3
When stop pressing the jog switch and the MODE key, the spec. is set and PRO4 is indicated.
The optical communications spec. of the group B
The optical communications spec. of the group A
Stop optical communications
When the units of the group A and the group B are connected in cascade as Figure B shown above, optical communications cannot be done. When the optical communications function is used, connect them as Figure A shown above. If the units cannot be placed as Figure A, the following measure 1 or 2 should be taken.
Affix the communication window seal of the accessory amplifier protection seal (FX-MB1) to the communication window of the amplifier.
If the measure 1 described above cannot be taken, change the optical communications spec. of the group B units.
1
2
Cautions on sensor connection in cascade
When the units in the group A and the group B shown in the table below are connected in cascade, connect them in cascade as Figure A shown below.
<Figure A><Figure B>
Optical communications are possible
Optical communications are impossible
Group A
Group B
Group A
Group B
Group A
Group B
FX-301(P): Updated version unit, FX-305(P),
FX-301(P)-C1
FX-301(P): Previous
version unit,
FX-301G(P) / B(P) / H(P), FX-302(P), FX-303(P), LS-400 series (Note 1)
How to change the optical communications spec. of Group B units
Follow the procedure given below to change the optical communications spec. of the group B units. Be sure to set the optical communications spec. to ‘3 (the optical communications spec. of the group A)’ or 0 (stop of the optical communications).
Notes:1)
When LS-400 series is connected with the digital fiber amplifier in cascade, be sure to locate LS-400 series at the left-most position (when viewed from the connector side).
Every time the jog switch and the MODE key are pressed simul­taneously, the indicated No. will change from 5n0n0n3n5’ in turn.
Notes: 2)
When the optical communications spec. is set to ‘3 (the optical communications spec. of the group A), be sure to mount the units close together. Furthermore, take care of the following.
The optical communications function may not be usable due to the environment. etc. Do not carry out the collective channel load or save.
Notes: 3)
<Procedure to change>
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Settings for NAVI Mode
4-1. NAVI Mode Functions and Settings
4
In [NAVI mode], frequently changed settings can be easily configured. Settings for four functions can be configured.
RUN :
Normal Sensing Operation
TEACH : Teaching Mode
This indicates normal sensing operation. Incident light intensity is displayed in real time. The factory setting is that the threshold value cannot be changed directly. When the Adjust Lock Function in PRO5 Mode is disabled, manual fine adjustment of the threshold value can be performed during normal sensing operation. The threshold value can be confirmed by turning the jog switch (Refer to p.59). In addition, key lock function can also be set (Refer to p.59).
This mode sets the threshold value by utilizing teaching.
When using FX-301(P)(-HS) or FX-305(P) normal mode
The threshold value can be set with any of the 3 teaching methods, 2-level teaching, limit teaching and full-auto teaching.
2-level teaching is a method of setting the threshold value by teaching the amplifier unit two different status conditions - sensing object present and sensing object absent. The threshold value is usually set using this method.
Sensing operation * Sensing operation when threshold value
can be fine adjusted
Refer to the section entitled 9-3. Adjust Lock
Function from PRO5 Mode on p.52.
Refer to p.10 ~ for setting procedure
P.10
2-level Teaching
Thru-beam type Reflective type
Sensing object present Sensing object absent Sensing object present Sensing object absent
Teaches only the status condition in which no sensing object is within sensing range (status in which incident light intensity is stable). This method is used to set a threshold value for conducting sensing in the presence of a background, or when extremely small objects are to be detected.
P.11
Limit Teaching
P.12
Full-auto Teaching
This method is used to set the threshold value while the sensing objects are still moving on the production line, without stopping the production line.
Thru-beam type
Thru-beam type
Reflective type
Reflective type
Background
Minute object
6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
TEACH : Teaching Mode
Refer to p.13 ~ for setting procedure
P.13~
1-level Teaching
When using FX-305(P) window comparator mode The threshold value can be set with any of the 3 teaching methods, 1-level teaching, 2-level teaching and 3-level teaching. By setting two threshold values, both ON and OFF can occur between the two threshold value levels.
This sets the shift value to any desired value, and sets the threshold values (1_SL, 2_SL) by means of 1-level teaching.
P.15~
2-level Teaching
This carries out 2-level teaching (P-1, P-2) and sets the threshold values (1_SL, 2_SL).
ON
0
P.17~
3-level Teaching
This carries out 3-level teaching (P-1, P-2, P-3) and sets the threshold value (1_SL) between A and B and the threshold value (2_SL) between B and C as shown in the diagram below. After teaching, P-1, P-2 and P-3 are automatically assigned in ascending order to A, B, and C.
Hysteresis
Output (L-ON)
4,000 / 9,999
Incident light intensity
ON
1_SL 2_SL
OFF
Time
Shift value
Shift value
ON
1_SL
2_SL
P-1
0
P-1
2_SL1_SL
Output
(L-ON)
Shift value
OFF
Incident light
intensity
4,000 / 9,999
Output (L-ON)
OFF ON OFF
Time
ON
P-1
1_SL
P-2
2_SL
0
OFF
Incident light
intensity
4,000 / 9,999
Output (L-ON)
Output
(L-ON)
P-1
1_SL
OFF ON OFF
P-2
2_SL
* In this figure, the incident
light intensity of P-1 is less than that of P-2.
Time
ON
A
1_SL
2_SL
B
C
0
OFF
Incident light
intensity
4,000 / 9,999
Output (L-ON)
Output
(L-ON)
P-1
1_SL
OFF ON OFF
P-2
2_SL
P-3
When using FX-305(P) differential mode Sensing of only sudden changes in incident light intensity is carried out, so that this is ideal for sensing edges of object such as glass. Set to full-auto teaching’ if teaching is to be carried out. (Refer to p.12 for details.) Furthermore, if the response time has been set in STDF, LONG or U-LG mode, mount to make the threshold values to more than the following values.
STDF mode : 40 digits LONG mode: 60 digits U-LG mode : 100 digits
7
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
ADJ : Threshold Value Fine Adjustment Mode
This mode allows fine adjustment of the threshold value setting. When the incident light intensity display has been selected, the threshold value can be adjusted in increments as low as a one digit. When the percentage display has been selected, the threshold value can be adjusted in increments of one digit (varies depending on the threshold value). However, when FX-305(P) is in window comparator mode, the percentage display function cannot be utilized. * The factory setting is; FX-301(P): 40, FX-301(P)-HS: 80,
FX-305(P) output 1: 80, FX-305(P) output 2: 120.
Refer to p.19~ for setting procedure
0
Threshold value
Threshold
value 1
Threshold
value 2
Incident light intensity
Output operation
L-ON
D-ON
Output operation
L-ON
D-ON
* The factory setting is L-ON (Light-ON).
0
L/D: Output Operation Setting Mode
Refer to p.22 for setting procedure
When using FX-301(P)(-HS) or FX-305(P) normal mode
When using FX-305(P) window comparator mode
When set to ‘L-ON’, the output will be ON if the incident light intensity becomes greater than the threshold value. When set to ‘D-ON’, the output will be ON if the incident light intensity becomes less than the threshold value.
When set to ‘L-ON’, if the incident light intensity is between the two ‘threshold value levels, the output will be ON. If the incident light intensity is outside of the two threshold value levels, the output will be OFF. When set to ‘D-ON’, if the incident light intensity is between the two ‘threshold value levels, the output will be OFF. If the incident light intensity is outside of the two threshold value levels, the output will be ON.
This mode allows the selection of output operation from either L-ON (Light-ON), or D-ON (Dark-ON).
When using rising differential mode
Output operation
L-ON
Time
ON
Output operation
L-ON
D-ON
ON
TT
OFF
When using trailing differential mode
Time
ON
OFF
OFF
ON
OFF
TT
Incident
light
intensity
Incident
light
intensity
* The output time ‘T’ can be set by changing
the timer period in timer setting mode (initial value: 10 ms).
* The output time ‘T’ can be set by changing
the timer period in timer setting mode (initial value: 10 ms).
For L-ON, output is ON for a constant period of time when the incident light intensity is rising. For D-ON, output is OFF for a constant period of time when the incident light intensity is rising.
For L-ON, output is ON for a constant period of time when the incident light intensity is trailing. For D-ON, output is OFF for a constant period of time when the incident light intensity trailing.
Incident light intensity
0 4,000 / 9,999
ONOFF
OFFON
ONOFF OFF
OFFON ON
0 4,000 / 9,999
TT
D-ON
TT
8
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
PRO mode allows the configuration and usage of the following timer operations: OFF-delay / ON-delay / ONE SHOT. Timer period can be selected from 0.5 ms to 9,999 ms. Please refer to the section entitled 5-3. Timer Setting Function [FX-301(P)(-HS)] from PRO1 Mode on p.28.
PRO mode allows the configuration and usage of the following
timer
operations: OFF-delay / ON-delay / ONE SHOT / ON-delay OFF-delay /
ON­delay ONE SHOT. Timer period can be selected from 0.5 ms to 9
,999 ms.
Please refer to the section entitled 5-4. Timer Setting Function [FX-305(P)] from PRO1 Mode on p.29.
TIMER : Timer Operation Setting Mode
Refer to p.23 for setting procedure
FX-305(P)
This mode sets the timer operation and set the type of timer. For FX-301(P)(-HS) the setting can be selected from Without timer / OFF-delay / ON-delay / ONE SHOT timer, and the FX-305(P) includes these and also ON-delay OFF-delay / ON-delay ONE SHOT timers.
FX-301(P)(-HS)
9
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
10
4-2. Teaching Mode [when using FX-301(P)(-HS) or FX-305(P) normal mode]
The threshold value can be set by utilizing three kinds of teaching, whichever 2-level teaching, limit teaching or full-auto teaching’. * The factory setting is this mode for FX-305(P). (Refer to p.55)
2-level teaching is a method of setting the threshold value by teaching the amplifier two different status conditions - sensing object present and sensing object absent. The threshold value is usually set using this method.
2-level Teaching
1 Press the [MODE key] once to select TEACH mode.
3 Press the [Jog switch] when in the status condition of -
sensing object is present.
2 FX-305(P): Turn the [Jog switch] to select the desired
output for setting.
5 Press the [Jog switch] when in the status condition of -
sensing object is absent.
8 The threshold value setting will be displayed.
9 The incident light intensity will again be displayed, indicating
that configuration is now complete. FX-305(P): The output that has been set will be displayed.
0 Press the [MODE key] 5 times or keep it pressed for 2 sec.
or more, the amplifier will return to RUN mode (normal sensing operation).
4The digital display will blink and indicate the incident light
intensity reading, then the MODE indicator / TEACH (yellow) will blink. This indicates that the second point item is now ready for input.
6
The digital display will again blink and indicate the incident light intensity reading
and the threshold value will be set to a value midway between the incident light intensities when the sensing object is present and when it is absent. The blinking MODE indicator / TEACH will stop blinking and continuously light up. *
Fine adjustment of the threshold value can be performed in the 4-4.
Threshold Value Fine Adjustment Mode [when using FX-301(P)(-HS) or FX-305(P) normal mode] described on p.19.
()
7 The sensing stability status will be displayed.
When stable sensing can be performed nThe digital display will blink the word .
When stable sensing cannot be performed nThe digital display will blink the word .
Place a fiber within sensing range.
Turn the Jog switch to select the desired output for setting.
Press the MODE key once.
Press the Jog switch.
Press the Jog switch.
Press the Jog switch.
Status condition - sensing object is present
Status condition - sensing object is absent
Stable sensing
Output 1 Output 2
In case of FX-301(P)(-HS)
In case of FX-305(P)
Thru-beam type Reflective type
Thru-beam type Reflective type
Difference between incident light intensities is not great enough.
Press the MODE key 5 times or keep it pressed for 2 . or more .
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Teaches only the status condition in which no sensing object is within sensing range (status in which incident light intensity is stable). This method is used to set a threshold value for conducting sensing in the presence of a background, or when extremely small objects are to be detected.
Limit Teaching
1 Press the [MODE key] once to select TEACH mode.
3 Press the [Jog switch] when in the status condition of -
sensing object is absent.
2 FX-305(P): Turn the [Jog switch] to select the desired
output for setting.
5 Turn the [Jog switch] in the or direction.
When using thru-beam fiber
When using reflective fiber
6 The sensing stability status will be displayed.
When stable sensing can be performed
nThe digital display will blink the word .
When stable sensing cannot be performed
nThe digital display will blink the word .
7 The threshold value setting will be displayed.
If the switch is turned toward the direction, the digital display will scroll
from the left to the right (twice) and the threshold value will be shifted down by approximately 15 %, to a value lower than the incident light intensity reading.
If the switch is turned toward the direction, the digital display will scroll from the right to the left (twice) and the threshold value will be shifted up by approximately 15 %, to a value higher than the incident light intensity reading.
*
The initial factory-set value of the shift amount is approximately 15 %. The shift amount can be changed by utilizing the 5-7. Shift Function from PRO1 Mode’, described on p.33. (The percentage adjustment is variable from 0 % to 80 %, in increments of 5 %.)
4The digital display will blink and indicate the incident light
intensity reading, then the MODE indicator / TEACH (yellow) will blink.
Press the MODE key once.
Status condition - sensing object is absent
Press the MODE key 5 times or keep it pressed for 2 sec. or more.
Turn the Jog switch in the or direction.
The digital display will scroll (twice).
Press the Jog switch.
Stable sensing
Turn the Jog switch to select the desired output for setting.
Press the Jog switch.
Output 1 Output 2
Place a fiber within sensing range.
Minute object
In case of FX-301(P)(-HS)
In case of FX-305(P)
Background
Thru-beam type Reflective type
Stable sensing cannot be performed.
9Press the [MODE key] 5 times or keep it pressed for 2 sec.
or more, the amplifier will return to RUN mode (normal sensing operation).
8The incident light intensity will again be displayed, indicating
that configuration is now complete. FX-305(P): The output that has been set will be displayed.
11
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
12
Stable sensing
Difference between incident light intensities is not great enough.
Full-auto teaching is used to set the threshould value while the sensing objects are still moving on the production line, without stopping the production line. * When the FX-305(P) is in differential sensing mode, set the threshold value by full-auto teaching.
(Refer to p.55)
Full-Auto Teaching
1 Press the [MODE key] once to select TEACH mode.
7The threshold value setting will be displayed.
5The threshold value is set to a value midway between the
incident light intensities in the object present and object absent conditions.
9Press the [MODE key] 5 times or keep it pressed for 2 sec.
or more, the amplifier will return to RUN mode (normal sensing operation).
8The incident light intensity will again be displayed, indicating
that configuration is now complete.
4 is displayed on the display.
Release the jog switch when the object has passed. * The incident light intensity is read when is displayed.
3In the status condition keep the [Jog switch] pressed for
0.5 sec. or more, when the object is moving on the production line.
2 FX-305(P): Turn the [Jog switch] to select the desired
output for setting.
6 The sensing stability status will be displayed.
When stable sensing can be performed nThe digital display will blink the word .
When stable sensing cannot be performed nThe digital display will blink the word .
Place a fiber within sensing range.
Status condition-moving the production line.
Press the MODE key once.
Keep the Jog switch pressed.
Press the MODE key 5 times or keep it pressed for 2 sec. or more .
Turn the Jog switch to select the desired output for setting.
Press the Jog switch.
Output 1 Output 2
In case of FX-301(P)(-HS)
In case of FX-305(P)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
This is the method of setting the threshold values (1_SL, 2_SL) by one level (P-1) teaching. The shift value can be set as desired.
*
The shift value units can be selected from two units: ‘digit’ or ‘%.
*
The shift value of the factory setting is set to ‘100 of ‘digit’ units. To set the shift value, refer to the section entitled 10-2. Output 1 Sensing Mode Settings’ from PRO6 Mode’ on p.56.
1Press the [MODE key] once to select TEACH mode.
2Press the [Jog switch] to select output 1.
4-3. Teaching Mode [when using FX-305(P) window comparator mode]
1-level Teaching
The threshold value can be set using 1-level teaching, 2-level teaching or 3-level teaching. When FX-305(P) is in window comparator mode, teaching is performed using the teaching methods described in the section entitled 10-2. Output 1 Sensing Mode Settings’ from PRO6 Mode on p.56. To change the teaching method, follow the procedures also described under the same heading. * Window comparator mode can be set for output 1 only.
* The factory setting is 1-level teaching ( ).
3The current teaching method will be displayed for 0.5 sec.,
and then the unit will enter the P-1 setting state.
1Press the [MODE key] 5 times to select PRO mode.
2Turn the [Jog switch] 6 times towards the
’ direction to
select PRO mode.
3Turn the [Jog switch] to select ‘output 1, and then press the
[Jog switch] to confirm the setting.
4Turn the [Jog switch] to select ‘window comparator mode,
and then press the [Jog switch] to confirm the setting.
5Turn the [Jog switch] to select ‘1-level teaching, and then
press the [Jog switch] to confirm the setting.
4If the [Jog switch] is pressed while in the status condition
when a sensing object is present that can be used as a baseline, then the display will blink and indicate the incident light intensity reading.
Time
Shift value
Shift value
1_SL
2_SL
P-1
0
Incident light
intensity
9,999
Output (L-ON)
P-1
2_SL1_SL
Output
(L-ON)
Shift value
OFF ON OFF
ON OFF
For further details, refer to 10-2. Output 1 Sensing Mode Settings’ on p.56.
The status condition when a sensing object is present that can be used as a baseline.
Setting in PRO6 mode beforehand
Setting in NAVI mode
Incident light intensity of P-1.
Press the Jog switch.
Press the Jog switch.
Turn the Jog switch 6 times toward the direction.
Turn the Jog switch to select output 1.
Press the MODE key once.
Press the MODE key 3 times or keep it pressed for 2 sec. or more .
Output 1
Press the MODE key 5 times.
Turn the Jog switch to select window comparator mode.
Turn the Jog switch to select 1-level teaching.
To be continued on the next page
13
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
14
Press the MODE key 5 times or keep it pressed for 2 sec. or more.
9Press the [MODE key] 5 times or keep it pressed for 2 sec.
or more, the amplifier will return to RUN mode (normal sensing operation).
6The setting for lower limit value 1_SL will be displayed.
7The setting for upper limit value 2_SL will be displayed.
5The display will indicate whether the upper and lower
threshold value limits have been correctly set or not.
If is blinkingthe upper and lower limits have been set correctly.
If is blinkingthe upper and lower limits have not been set correctly.
* The factory setting for shift value is 100.
To set the shift value, refer to the section entitled 10-2. Output 1 Sensing Mode Settings from PRO6 Mode on p.56.
8The output 1 will again be displayed, indicating that
configuration is now complete.
Lower limit value 1_SL
Upper limit value 2_SL
Upper and lower limits have not been correctly set.
Stable sensing
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
The status condition when a sensing object is present that can be used as a baseline for the lower limit.
2-level Teaching
This is a method of setting the thresh­old values (1_SL, 2_SL) by two levels (P-1, P-2) teaching. Select 2-level teaching ( ) in PRO6 mode beforehand.
1Press the [MODE key] once to select TEACH mode.
2Press the [Jog switch] to select output 1.
3The current teaching method will be displayed, and then the
unit will enter the P-1 setting state.
4If the [Jog switch] is pressed while in the status condition
when a sensing object is present that can be used as a baseline for the lower limit, then the display will blink and indicate the incident light intensity reading.
When using thru-beam type fiber
Press the [Jog switch] for the sensing object that has the greatest amount of interrupted light.
When using reflective type fiber
Press the [Jog switch] for the sensing object with the lowest incident light intensity.
Note) Even if procedures 4 and 6 are reversed, teaching for a
sensing object with low incident light intensity will automatically cause the setting of lower limit value 1_SL.
Time
ON
P-1
1_SL
P-2
2_SL
0
OFF
Incident light intensity
9,999
Output (L-ON)
P-1
1_SL
OFF ON OFF
P-2
2_SL
Output
(L-ON)
Turn the Jog switch 6 times toward the direction.
Turn the Jog switch to select output 1.
Press the MODE key 3 times or keep it pressed for 2 sec. or more .
Press the MODE key 5 times.
Turn the Jog switch to select window comparator mode.
Turn the Jog switch to select 2-level teaching.
1Press the [MODE key] 5 times to select PRO mode.
2Turn the [Jog switch] 6 times towards the direction to
select PRO mode.
3Turn the [Jog switch] to select ‘output 1, and then press
the [Jog switch] to confirm the setting.
4Turn the [Jog switch] to select ‘window comparator mode,
and then press the [Jog switch] to confirm the setting.
5Turn the [Jog switch] to select ‘2-level teaching, and then
press the [Jog switch] to confirm the setting.
For further details, refer to 10-2. Output 1 Sensing Mode Settings’ on p.56.
Setting in PRO6 mode beforehand
Setting in NAVI mode
Press the MODE key once.
Incident light intensity of P-1.
Press the Jog switch.
Press the Jog switch.
Output 1
To be continued on the next page
15
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
16
The status condition when a sensing object is present that can be used as a baseline for the upper limit.
Upper and lower limits have not been correctly set.
8The setting for lower limit value 1_SL will be displayed.
9The setting for upper limit value 2_SL will be displayed.
0The output 1 will again be displayed, indicating that
configuration is now complete.
APress the [MODE key] 5 times or keep it pressed for 2 sec.
or more, the amplifier will return to RUN mode (normal sensing operation).
Press the MODE key 5 times or keep it pressed for 2 sec. or more.
6If the [Jog switch] is pressed while in the status condition
when a sensing object is present that can be used as a baseline for the upper limit, then the display will blink and indicate the incident light intensity.
When utilizing thru-beam type fiber
Press the [Jog switch] for the sensing object that has the least amount of interrupted light.
When utilizing reflective type fiber
Press the [Jog switch] for the sensing object with the greatest incident light intensity .
5The unit will enter the P-2 setting state and TEACH (yellow)
will blink on the MODE display.
7The display will indicate whether the upper and lower limits
have been correctly set or not.
If is blinking the upper and lower limits have
been set correctly.
If is blinking the upper and lower limits have not
been set correctly.
Incident light intensity of P-2.
Lower limit value 1_SL
Upper limit value 2_SL
Press the Jog switch.
Stable sensing
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
3-level Teaching
This is a method of setting the threshold range by three levels (P-1, P-2, P-3) teaching and set the threshold values at the middle of ‘A’ and ‘B’ (1_SL) and ‘B and C (2_SL). After teaching, P-1, P-2 and P-3 are automatically assigned in ascending order to ‘A’, ‘B’, and ‘C’. Select 3-level teaching ( ) in PRO6 mode beforehand.
The status condition when sensing object A’ is present that has the lowest incident light intensity.
1Press the [MODE key] once to select TEACH mode.
2Press the [Jog switch] to select output 1.
3The current teaching method will be displayed, and then the
unit will enter the P-1 setting state.
4If the [Jog switch] is pressed while in the status condition
when sensing object A is present that has the lowest incident light intensity, then the display will blink and indicate the incident light intensity reading. And then the unit will enter the P-2 setting state and TEACH (yellow) will blink on the MODE display.
Note) P-1, P-2 and P-3 are set in that order even if
procedures 4, 5 and 6 are changed around.
Output
(L-ON)
Time
ON
A
1_SL
2_SL
B
C
0
OFF
Incident light
intensity 9,999
Output (L-ON)
P-1
1_SL
OFF ON OFF
P-2
2_SL
P-3
AB C
For further details, refer to 10-2. Output 1 Sensing Mode Settings’ on p.56.
Setting in PRO6 mode beforehand
Turn the Jog switch 6 times toward the direction.
Turn the Jog switch to select output 1.
Press the MODE key 3 times or keep it pressed for 2 sec. or more .
Press the MODE key 5 times.
Turn the Jog switch to select window comparator mode.
Turn the Jog switch to select 3-level teaching.
1Press the [MODE key] 5 times to select PRO mode.
2Turn the [Jog switch] 6 times towards the
’ direction to
select PRO mode.
3Turn the [Jog switch] to select ‘output 1, and then press
the [Jog switch] to confirm the setting.
4Turn the [Jog switch] to select ‘window comparator mode,
and then press the [Jog switch] to confirm the setting.
5Turn the [Jog switch] to select ‘3-level teaching, and then
press the [Jog switch] to confirm the setting.
Setting in NAVI mode
Press the MODE key once.
Incident light intensity of P-1.
Press the Jog switch.
Press the Jog switch.
Output 1
To be continued on the next page
17
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com