Sunways NT 6000, NT 5000, NT 4000, NT 2600 User Manual

Page 1
200
User Manual for Sunways Solar Inverters NT 6000, NT 5000, NT 4000 and NT 2600
New Version
850 V
Page 2
User Manual for Sunways Solar Inverters NT 6000, NT 5000, NT 4000 and NT 2600
Page 3
EN
List of Contents
1.0 General information
1.1 Safety information
1.2 Sunways Solar Inverters NT 6000, NT 5000, NT 4000 and NT 2600
2.0 Information on installation
2.1 Safety information
2.2 Basic configuration
2.3 Installation
93 94
95
96
97 98
100
101
102 103
105 106 107
89
General safety information Opening the unit
Scope of supply Inspecting the delivery Integration into the PV system Design of the PV generator Standard components of a PV system Protection concept
Electrical safety Mechanical safety Information on cleaning
Fixed voltage setting Country selection
Requirements on the place of installation Electrical connection and cable entry Grid connection
Page 4
2.4 Commissioning
3.0 Information on operation
3.1 Monitoring and diagnosis
3.2 Sunways NT Monitor software
3.3 Fault indications
3.4 Fault diagnosis
109 111 112 114 116
118 120
125 126
127 128 129 134 136 137
139
143
90
PV generator connection Important Information Communication connections Connection of the alarm relay Connecting the sensors
Switching the solar inverter on and off Configurations
Display Data memory
General information Initialising the remote modem Connection and circuitry options Configuring the interface cables Data acquisition Operation
Fault indications
Fault display, causes and remedies
Page 5
EN
3.5 Warranty terms and conditions
4.0 Appendix
4.1 Subject and abbreviation index
4.2 Function and information index
150
153
155 158
160 164 166 170
91
Warranty terms and conditions
Designation and description
Functional principle and explanations Block diagram of the Solar Inverter in the PV system Technical data Tyco Solarlok connectors Conformity and safety declarations General exclusion of liability Rights Registered trademarks
Page 6
1.0 General information
92
Page 7
EN
!
93
1.1 Safety information
The User Manual contains safety hints. These are identified by a triangle with an exclamation mark.
General safety information
All safety hints contained in this section and throughout the User Manual must be complied with at all times to guarantee the user's safety. The described product must not be operated if any mechanical or electrical components are defective.
Before commissioning the system, we strongly advise you to carefully read and heed the instructions! Non-compliance can have serious consequences, for exam­ple damage to the unit or other property or physical injuries with possible loss of life.
The solar inverter must be installed by a trained, qualified electrician. The electrici­an must be approved by the competent electricity board (EB). The relevant tasks to be carried out are identified by an addi­tional adjacent symbol in the respective chapter headings.
Page 8
!
94
Opening the unit
Before opening the cabinet, the unit must always be disconnected from the grid and from the PV generator. The unit continues to conduct a hazardous voltage internally and at the connection sockets for ca. five minutes after disconnec­ting from the PV generator. The energy storage capacitors are only fully discharged after this period. After disconnecting the unit from the grid and from the PV generator, you must wait at least five minutes before opening the unit.
Page 9
EN
1.2 Sunways Solar Inverters NT 6000,
NT 5000, NT 4000 and NT 2600
Scope of supply
· Sunways Solar Inverter in the NT series
· Installation frame
· Manual, setup, warranty card, CD-Rom
with software
· 2 pairs of Tyco Solarlok connectors
95
Inspecting the delivery
The condition of our products is checked prior to delivery. Although our products are carefully packed in recyclable packing, transportation damages can still occur. These are generally the transport compa­ny's responsibility.
Please inspect the delivered solar inverter thoroughly!
If you discover any damage to the packing or the solar inverter, please inform the transport company immediately. Your specialist dealer will be glad to assist you if required. Any damages must always be reported to the transport company in wri­ting seven days after receipt of the goods at the latest.
Page 10
96
Integration of the solar inverter into the PV system
Design of the PV generator
The technical data of the selected PV generator must be within the specification of the solar inverter (see Technical Data). Incorrect dimensioning can cause losses in yield and destruction of the unit. The Sunways NT Sundim design program for the PV generator may be helpful. Sunways NT Sundim is available on the enclosed CD or from our website, www.sunways.de.
Please take account of the following points before planning your system:
· Pay attention to the skyward alignment of the modules. You will obtain maxi­mum yield in Central Europe with a module inclination of 30° to the hori­zontal and a direct southerly alignment of the generator field.
· The output of the cells decreases as the module temperature increases. Install your PV generator with adequate rear ventilation.
· Check your PV generator for soiling ca. every three years. This occurs particularly at the lower edge of the modules and forms a film, which even heavy rain can­not wash away. Decreases in yield can be prevented by cleaning with a wet cloth or a brush.
· Avoid shading of individual modules or solar cells in your system. This can result in heavy losses in yield.
Page 11
Standard components of a PV system
Depending on the recommendations of your electrician, your PV system will consist of the following components:
PC
(3)
INVERTER
PV
PV
(1)
(2)
(4)
GRID
PV generator switch: Designed as DC load break cut-out to cut off the PV generator from the solar inverter. Dimensioning: min. 900 V, ≥ 16 A
Grid connection: 3-phase (Feed-in: 1-phase; grid monitoring: 3-phase)
Standard components of the PV system
97
(1) PV generator switch (2) Irradiation sensor with
integrated temperature
sensor (3) Mains fuse (4) Energy meter
Page 12
Protection concept
The following parameters are monitored continuously and in parallel by the micro­controller and displayed on the screen:
· DC overvoltage (Fault 3)
· Frequency error (Fault 4)
· Overheating (Fault 5)
· Grid undervoltage, 1-phase (Fault 6)
· Grid overvoltage, 1-phase (Fault 7)
· Grid undervoltage, 3-phase (Fault 8)
· AFI error (Fault 9)
· Insulation error (Fault 10)
· DC feed (Fault 11)
· Isolated operation (Fault 12)
· Grid overvoltage, 3-phase (Fault 13)
· Surge error (Fault 14)
· Grid voltage 10-minute average value > 10 % U
NOM
(Fault 15)
98
In the event of a fault, the conversion is blocked immediately and the grid relay is isolated. An alarm relay with floating output is activated (not for Fault 6). In addition, the following protective devices are provided on both grid and PV generator side:
· Grid-side varistors Protect the power semiconductors from high-energy, time-limited voltage spikes on the grid and provide for a reduction of energy in the throttle in the event of grid disconnection.
· Generator-side varistors Thermally monitored varistors provide protection against atmospheric overvol­tages (e.g. due to remote strikes during storms).
Page 13
200
2.0 Information on installation
99
Page 14
2.1 Safety information
!
100
Electrical safety
Before opening the cabinet, the solar inverter must be disconnected from the grid and from the PV generator.
The solar inverter conducts a hazardous voltage internally and at the connectors of the PV generator for approx. five minutes after isolation from the PV generator and the grid. The energy storage capacitors are only fully discharged after this period.
After disconnecting the solar inverter from the grid and PV generator, you must wait at least five minutes before opening the solar inverter.
Mechanical safety
During installation, make sure that the cables or connection lines fitted to the solar inverter are securely laid and that suitable mechanical cable supports (cable ducts etc.) are used.
Page 15
EN
!
101
Information on cleaning
Before cleaning, disconnect the system from the power grid by opening the grid breaker (main fuse) and open the DC switch on the PV generator, in order to exclude the danger of electric shocks.
Use a soft, dry cloth to clean the system. Never use corrosive, solvent-containing or abrasive cleaners or polishes.
Page 16
2.2 Basic configuration
Fixed voltage setting
Your Sunways solar inverter has a precise MPP control. The control operates in fixed voltage mode beneath a feed-in capacity of 200 watts. This prevents unnecessary MPP search behaviour. In order to minimi­se the adaptive losses in fixed voltage mode, the solar inverter has the facility to set the fixed voltage level. The optimal fixed voltage level is dependent on your PV generator model.
The fixed voltage can be set with the S100 slide switch on the control board. At the factory, the switch is set on the right in status «410 V». In order to set a fixed vol­tage of 530 V, slide the switch to the left into the «530 V» position.
Fixed voltage level depending on no­load voltage
410 V 530 V
No-load voltage PV generator at 25°C
≤ 630 V > 630 V
Switch position «410 V»
Switch position «530 V»
(Fig.) Sliding switch to set the fixed voltage level
102
Page 17
EN
Country selection
Please note that a different device confi­guration is required to operate Sunways Solar Inverters in different countries. You can make the relevant setting with DIP switch S300 beneath the display panel.
Country
Germany
Spain
modification
· Disconnect interval after power failure 3 minutes
· 1-phase grid monitoring
switch position
(Fig.) DIP switch S300 for country selection
103
Page 18
2.3 Installation
The solar inverter must be installed by a trained, qualified electrician. A special tool is necessary for installation. Please read this chapter very carefully.
➟
150 mm
Cool air
Warm air
300 mm
300 mm
150 mm
➟
➟
➟
(Fig.) Minimum distances that must be kept clear around the solar inverter
104
Page 19
EN
105
If installing the solar inverter in a switch box, ensure adequate heat dissipation.
The ambient temperature must not fall below or exceed –25°C or +40°C.
The solar inverter should not be exposed to direct solar irradiation, so as to protect it from unnecessary external heating.
· Protection from damp and foreign bodies
The IP54 high protection class permits instal­lation both inside and in roofed outdoor areas, but the solar inverter must not be exposed to direct rain.
Make sure that the solar inverter cannot be exposed to foreign bodies (deposits of dust and dirt). In order to avoid losses in yield, the unit should be regularly freed from dust deposits.
Requirements on the place of installation
· Mechanical bearing capacity
During installation please bear in mind that the solar inverter weighs 26 kg. The installation base must be firm and capable of continuously bearing the weight.
· Thermal interaction
The installation base must consist of flame-retardant material (e.g. no wood or plastic in the base; concrete and brickwork are suitable), as the heat sink emits tempe­ratures up to max. 85°C.
A minimum distance of 300 mm must be maintained above and below the cabinet, and 150 mm on right and left from other units, cabinets, ceilings, cable ducts etc..
The solar inverter must be installed verti­cally, so as not to hinder adequate free convection.
Several solar inverters must not be instal­led on top of each other, so as to prevent reciprocal heating.
Page 20
Electrical connection and cable entry
For installation, please observe the instructions in the «Setup» leaflet!
!
If the solar inverter is fixed to the installa­tion frame, the electrical connection can be led through. The unit may only be ope­ned by a qualified electrician. The cabinet cover must first be released and removed.
The SUB-D connector for the RS 232 con­nection is located on the bottom, as well as inlets for cables:
DC– DC– DC+ DC+
AC wiring loom L1, N, L2, L3, PE
(Fig.) Inlets on the unit underside
Alarm relay
Irradiation sensor with integrated temperature sensor cable
RS 232
RS 485
106
Page 21
EN
Grid connection
The grid connection of the solar inverter must have 5 wires (L1, N, L2, L3, PE). Cable cross-sections of 5 x 4 mm
2
are recommen-
ded.
The solar inverter is connected to the sup­ply grid via the circuit board terminals insi­de the unit.
!
We recommend a 3 x 25 A safety cutout for devices NT 6000, NT 5000 and NT 4000 and a 3 x 16 A safety cutout for device NT 2600 as grid protection element in the grid feed-in direction. No consumption units must be connected to the feed line from the solar inverter to the automatic cut-out. The solar inverter only feeds in via terminal L1. Please always observe the connection configuration. Incorrect confi­guration can result in destruction of the unit.
L1 N L2 L3 PE
L1 N L2 L3 PE L1 N L2 L3 PE
L1 L2 L3 N PE
Three-phase grid connection distributed over three units
107
Page 22
If several solar inverters are operated in parallel, the feed-in phase L1 of the unit must be evenly distributed over grid pha­ses L1, L2 and L3 (see Fig. page 107).
You must use adequately dimensioned cable cross-sections in order to avoid a considerable increase in the grid impe­dance between the domestic distribution and the solar inverter. The terminal range of the AC terminals is 0.5 to 6 mm2 for rigid cables and 0.5 to 10 mm2 for flexible cables. With a high grid impedance, i.e. with a long line or too small a cross­section, the voltage increases at the grid terminal during feed-in.
If the terminal voltage exceeds the per­missible value, the solar inverter is dis­con-nected from the grid. In the case of poorly designed electric grids and high PV output, this can also result in repeated switching off and on of individual solar inverters.
Carefully perform the following steps:
· Check that there is no voltage before introducing the supply main into the unit.
· Lead the 5-core AC cable (outer dia­meter 9 – 17 mm) through the M32 threaded cable gland.
· Connect cables L1, N, L2, L3 and PE to the relevant circuit board terminal with the help of a slot-head screwdriver
(Fig.) Circuit board terminal for fixing the grid cable
· Tighten the M32 screw connection, so that the cable cannot exert any mechani­cal force on the circuit board terminal.
108
Page 23
EN
PV generator connection
!
· Preparation
Execute the DC cabling according to your electrician's system dimensioning. Check each PV string for correct functioning by performing a no-load voltage current and short-circuit current measurement.
Check the rating plate on the solar inver­ter to ensure that the inverter is appro­ved for the maximum PV generator vol­tage.
To achieve the necessary protection against hazardous contact voltage during the installation of PV systems, the positi­ve and negative conductors must be kept separate from the ground potential (PE).
Contactable, conductive parts of the PV generator (e.g. metal frame, supporting structure etc.) must be earthed (connec­ted to PE).
Check that the generator is free from ground faults.
Make the electrical connection to the solar inverter.
109
Page 24
· Connection
The PV generator is connected via the externally accessible, shock-proof Tyco Solarlok connectors, which are enclosed with the delivery. The Tyco Solarlok con­nectors are designed for a cable cross­section of 4 mm
2
and must be crimped (see chapter 4.2 «Tyco Solarlok connec­tion»).
Connect the two right DC female connec­tors with «+», the two left DC female connectors with «–» of the PV generator. Always ensure the correct polarity!
(Fig.) PV generator connection via Tyco Solarlok connector
110
Page 25
EN
!
111
Important information
· The direct PV generator voltage is availa­ble internally after connecting the PV generator to the solar inverter via the DC connectors and switching on the PV generator switch!
· Please note that the input capacitors are still charged even after switching off the PV generator switch or removing the PV generator plug connection!
· After disconnecting the AC and DC side, the solar inverter still conducts voltage for up to ca. five minutes!
· Therefore, wait for at least five minutes until the internal voltage has dissipated. Then you can work on the terminals! Note chapter 2.1 «Safety information»!
· The DC voltage can be up to 850 V. The unit may only be opened by a qualified electrician!
· Always disconnect the PV generator side first by opening the PV generator switch, and then the grid connection by isolating the relevant mains fuse!
· If you do not have a PV generator switch in your PV system, you must disconnect the grid connection first of all by isola­ting the relevant mains fuse. However, an error will be entered in the error memory of the solar inverter!
· Disconnection of the PV generator by removing the Tyco Solarlok DC con­nectors must never be performed under load. In the event of non-compliance, the connectors could be damaged by a strong electric arc. In this case, the rele vant connectors must be replaced!
Page 26
!
(Fig.) SUB-D connector for RS 232 connec­tion
Attention: RS 485+ and RS 485- are dupli­cated. This means that the cable entry and exit are additionally clamped.
(Fig.) Connection block for RS 485
112
Communication connections
Via the communication connections (inter­faces), operating data can be retrieved from the data memory with an external computer and specific operating settings made. Several communication interfaces are available: RS 232 and RS 485.
The standard communication interface is the RS 232 interface, which is installed in all current PCs and notebooks. This inter­face allows you to establish contact with your PC immediately, using a connecting cable. The use of more than one solar inverter or cable lengths of more than 25 m requires the use of the RS 485 interface.
The RS 232 interface is connected directly to the outside of the housing via a SUB-D connector. The RS 485 interface is connec­ted via the circuit board terminals and the corresponding M12 threaded cable glands in the housing.
Page 27
EN
· Connection RS 485
Remove the cover of the solar inverter before connecting an interface cable. Note chapter 2.1 «Safety information»!
The necessary cable terminal block (X400) with the RS 485+, RS 485+, RS 485- and RS 485- connections is located in the lower section of the board (see fig. page 112). Note the following terminal configura­tion:
RS 485: RS 485+, RS 485+, RS 485-, RS 485-
Use a small screwdriver. Press the orange terminal. The terminal will open.
Insert the cable stripped to a minimum of 11 mm into the respective terminal hole.
Release the screwdriver. The cable is fixed in the connection.
Once again, check that the cable connec­tion is firmly located.
Seal the unrequired cable glands by pla­cing a spare piece of cable in the gland hole and tightening with the screw clamp.
Please note chapter 3.2 «Sunways NT Monitor software».
· RS 232 connection
The RS 232 interface is externally accessible via the SUB-D connector.
Please note chapter 3.2 «Sunways NT Monitor software».
113
Page 28
Connection of the alarm relay
Sunways Solar Inverters are equipped as standard with an alarm relay with floating output. The relay is designed as a make contact and is activated in the case of all faults reported by the unit (not for Fault 6). This guarantees quick and reliable indi­cation of possible faults in the PV system. In the case of PV systems with several solar inverters,the individual relays can
!
be parallel-connected and connected via a joint signal light.
· Connection
Remove the housing of the solar inverter before connecting the status signal relay. Note chapter 2.1 «Safety information»!
The necessary terminal block with the con­nections «S-» and «S+» is located on the board at the bottom right (X402). Note the following terminal configuration:
L1 N
Parallel connection of the alarm relays of several solar inverters
INVERTER
(1)
SIGNAL LIGHT
INVERTER
(n)
INVERTER
(2)
S– S– S+ S+
Terminal configuration for the alarm relay
Page 29
(Fig.) Connection of the alarm relay
Important information: The alarm relay is designed for 230 V / 2 A. Higher outputs / voltages can result in destruction of the relay. The connected signal input must have separate fuse protection!
Using a small screwdriver, press the orange terminal. The terminal will open. Insert the minimum 11 mm stripped cable into the respective terminal hole. Loosen the screw­driver. The cable is fixed in the connection. Once again, check that the cable connec­tion is firmly located.
EN
The terminals are designed for a cable cross-section of 0.2 mm
2
to 1.5 mm2. Please also take account of the power consumption of the connected signal input when dimensioning the cross-sec­tion!
!
115
Page 30
!
116
Connecting the sensors
· Optional irradiation sensor
The optional addition of an irradiation sensor (type Si-01TC-T from Ing.-Büro Mencke & Tegtmeyer ) with integrated PT-100 temperature sensor for tempera­ture measurement enables recording of the irradiation data and the correspon­ding module temperature in the cycle of the internal data memory.
This additional measuring unit helps with analysis of the system. On the basis of the values, possible errors in the PV generator, such as e.g. shading or failure of solar cells, can be detected.
For demonstration purposes, the irradia­tion sensor and the corresponding data can be used to show how a PV system functions. In conjunction with the Sunways NT Monitor visualisation soft­ware, the stored data can be displayed.
Before you connect an irradiation sensor, you must remove the cover of the solar inverter. Please note that the inputs and outputs are not short-circuit resistant. Note chapter 2.1 «Safety information»!
The optional irradiation sensor with tem­perature probe is connected to cable terminal block X401 in the lower section of the board.
(Fig.) Connection block for the irradiation sensor
Page 31
EN
117
Configuration of the cable terminal block:
Temperature sensor measuring signal: Temp Solar radiation measuring signal: Solar Positive supply, 5V: V+ Supply, GND: V –
Using a small screwdriver, press the orange terminal. The terminal will open.
Insert the cable stripped to a minimum of 11 mm into the respective terminal hole.
Loosen the screwdriver. The cable is fixed in the connection.
Once again, check that the cable connec­tion is firmly located.
Page 32
118
2.4 Commissioning
Connect the solar inverter internally via the ground cable (yellow-green) to the cabinet cover. See also Setup, step 7.
Put the cabinet cover on.
Screw it down tightly with the four screws on the front.
Do not place any objects (e.g. this manu­al) on the cabinet of the solarinverter. Free ventilation behind the solar inverter must be able to take place unimpeded.
If the unit is mounted outdoors, please ensure proper sealing of the threaded cable glands and precise positioning of the housing cover as well as the protecti­ve cover of the SUB-D connector, if this connection is not configured.
Switching the solar inverter on and off
· Switching on
When the solar inverter is mechanically installed and connected to the electrical cables, the unit can be commissioned as follows:
Switch the grid connection on through the external safety cutouts.
Switch the PV generator voltage on by closing the PV generator switch. The solar inverter will start up with adequate PV power. If the PV input voltage is high enough, the solar inverter will begin ope­ration and feed the solar energy into the electrical grid. You can see the operation on the display. The current feed-in power is shown here.
The solar inverter is supplied by the grid. With adequate PV output, the solar inver­ter switches on automatically. Appropriate switch-on and switch-off thresholds are fixed for this purpose.
Page 33
EN
!
119
· Switching off
Disconnect the PV generator side first by opening the PV generator switch, and then the grid connection by isolating the relevant mains fuse.
If your PV system does not have a PV generator switch, you must disconnect the grid connection first of all by isolating the relevant mains fuse. When you do this, an error will be entered in the error memory of the solar inverter.
If the solar inverter is to be completely disconnected (e.g. removal) from the PV system, reconfigured or extended, the cabinet cover must be removed. Note chapter 2.1 «Safety information»!
Open the main switch for the PV DC voltage and the mains fuse as described above. After a waiting period of at least five minutes, the solar inverter will be voltage-free.
Disconnection of the PV generator by removing the Tyco Solarlok connectors must never be performed under load. In the event of non-compliance, the con­nectors could be damaged by a strong electric arc. In this case, the relevant con­nectors must be replaced!
Remove the cabinet cover.
Check that the grid connection terminals are voltage-free.
Page 34
!
120
However, language setting, LCD contrast and total energy offset (only to be used
in the event of replacement) must be configured directly on the unit. If you wish to configure the solar inverter without an external laptop or PC, or to change the language setting, please follow the instructions below:
Direct configuration of the solar inverter occurs in operation!
Please note that the unit is under DC voltage for configurations via the keys. Danger to life!
Please observe all essential regulations for «Working under voltage»!
Configurations
The solar inverter is basically configured with the Sunways NT Monitor program, using a laptop or PC (see enclosed CD).
Please read the chapter 3.1 «System Monitoring and Diagnosis» and 3.2 «Sunways NT Monitor».
Page 35
EN
AD
(Fig.) The setting keys are located beneath the display
B
C
121
This is the only exception for which work may be performed on the open unit under voltage!
Remove the cabinet cover to carry out the configuration.
The following settings can be performed using the illustrated keys:
· Address of the solar inverter: address «1» is stored in the memory at the factory. In the case of several solar inver­ters, consecutive numbering must be set. For three solar inverters e.g. the addres­ses «1», «2» and «3».
· Date
· Time
· Language (German, English, French, Spanish, Italian)
Page 36
SOLAR INVERTER
ADRESS
PERFORMANCE
AND
OPERATING DATA
DATE TIME
HOURS
A
B
MINUTES
A
B
SECONDS
A
B
SAVE
ADRESS
1 ... 99
A
B
DAY
A
B
MONTH
A
B
YEAR
A
B
D
START
Structure and menu levels for configuration
▲
Use insulating material to press the keys (e.g. a plastic rod). Avoid direct contact with the printed circuit board, so that the electronics cannot be damaged by electro­static charging. Starting from the current
display on the screen, you can reach the next menu level with the D-key. The illu­strated structure facilitates settings on the menu levels. Then save your settings by pressing the C-key.
D D D D D D
C
C
C C
C
C
C
C
A/B A/B A/B
122
Page 37
LANGUAGE
SOFTWARE
VERSION
ENGLISH/GERMAN/
ITALIAN/FRENCH/
SPANISH
A
B
LCD CONTRAST
CONTRAST
A
B
TOTAL POWER
OFFSET
kWh
A
B
INCREMENT
(100 OR 1)
D D D D D D
C
A/B A/B A/B
123
Page 38
3.0 Information on operation
124
Page 39
3.1 Monitoring and diagnosis
Display
The dot matrix LCD display is integrated into the cabinet of the solar inverter so that it is easily visible. The display consists of 16 characters and 2 lines. The top line 1 shows the current feed-in power of the solar inverter. The bottom line 2 outputs operating data. The data can be displayed in the German, English, French, Spanish or Italian language.
* if the optional irradiation sensor with integrated temperature sensor is connec­ted
EN
Line 1 Current fed-in power Power kW
Line 2 AC voltage U-AC V
DC voltage U-DC V Daily yield W-DAY Wh Total yield W-TOT kWh Irradiation * SOLAR W/m
2
PV generator temperature * TEMP-PAN °C Time TIME
125
Page 40
126
Data memory
Your solar inverter is equipped with an internal data memory as standard. This data memory provides you with a detailed view of the mode of functioning and the relevant values of your solar power supply at all times. You can access these data with the help of the NT Monitor software described below. The following measured values can be determined:
· DC voltage
· AC voltage and AC current (power calcu­lation)
· Irradiation and module temperature (if a sensor is connected)
· Time and date
The following values are accumulated, stored and continuously overwritten:
· 15 minute values for AC current, DC and AC voltages, irradiation and temperature
· 500 times storage of 15-minute average values in the recirculating storage; stora­ge depth: ten days on average, then overwriting of values
· Storage of accumulated daily work in Wh and of 40 daily values in the recircu­lating storage and successive overwriting of values
· Storage of accumulated monthly work in kWh and of 13 monthly values in the recirculating storage, then overwriting of values
· Storage of faults with max. ten values, then successive overwriting of values
Please note that all displayed data are displayed with a nominal measuring accu­racy of maximum 5 per cent. The energy counter of your EVU should be used as absolute reference for the fed-in energy.
Page 41
EN
127
3.2 Sunways NT Monitor software
General information
The Sunways NT Monitor visualisation soft­ware was developed for PV system monito­ring and configuration of the solar inverter using PC. It is contained on the enclosed CD and can also be downloaded free of charge on the Internet from www.sunways.de. System prerequisites are:
· Intel Pentium from 100 MHz or higher
· Microsoft Windows 95/98/2000/NT
· At least 6 MB free hard disk storage space
· At least 16 MB main memory
· VGA monitor with at least 800 x 600 (120 dpi) resolution
All measured values can be transferred to a PC and visualised with the Sunways NT Monitor software. Online, fault, minute, daily and monthly values are available.
For connecting to your PC, Sunways solar inverters in the NT series are equipped with the RS 232 and RS 485 interfaces as stan­dard. In the case of larger distances bet­ween PV system and PC, the data can also
be transferred via a modem. We recom­mend using two external analogue modems made by ACER. If other modems are used, the functional reliability cannot always be guaranteed.
The modem (remote modem) installed in the solar inverter must be initialised prior to installation with the help of the Sunways NT Monitor software. Note the "Help" function in the program in this regard.
The second modem (local modem) is connected to the RS 232 interface of your PC. This modem must not be initialised.
Different interface cables are required, depending on the type of connection. These are included in the accessories.
Up to 99 solar inverters can be monitored and read out by means of a connection via the RS 485 interface.
If the data are read out via the RS 485 interface and converted to RS 232 with an interface converter, we recommend the converter type «I-7520 Converter»
Page 42
128
from ICP-Deutschland, (available from your specialist dealer), which will guarantee reliable data transfer.
The addresses of the solar inverter must be input with the Sunways NT Monitor software. Alternatively, see chapter 2.4 «Commissioning, configurations».
Initialising the remote modem
If a remote modem is installed in the solar inverter, it must be initialised using a PC and the Sunways NT Monitor software.
· Connect the powered remote modem to the PC via the COM port. Use the inter­face cable provided with the modem for this purpose. Start the Sunways NT Monitor and set «Acer Modem» under the «Settings/Remote Modem» menu.
· Click «Perform initialisation» and wait until the scroll bar has come to an end. The modem can now be switched off and connected to the solar inverter via the RS 232 interface.
· Attention! Do not initialise the local modem which is intended for use on the PC!
· The remote modem is now initialised so that it automatically accepts a connec­tion after two rings and connects at 9600 Baud.
Page 43
(1) Individual PV system with maximum distance of 25 m between solar inverter an PC
Connection to the PC via RS 232
An individual solar inverter can be connected directly to the PC via the external RS 232 interface on the bottom of the device.
Jumper JP400: open
Connection and circuitry options
(1) An individual solar inverter can be read out using this connection, unless the distance from the PC exceeds a distance of 25 m. For this purpose, cable type 1 is connected with the solar inverter via the SUB-D connector and connected to a PC. Jumper JP400 must be in open position.
PC
INVERTER
(1)
PV
RS 232
SUB-D connector
129
Page 44
(2) Individual PV system with modem for remote inquiry
Connection to modem via RS 232
When connecting an individual solar inverter, the remote modem is connected directly to an external interface converter (IC) RS 232 at the bottom of the solar inverter.
Jumper JP400: open
(2) For installation of the remote inquiry of an individual solar inverter, the RS 232 signal can be conducted directly from the solar inverter to the remote modem via the SUB-D connector. Cable type 2 is used for this purpose. A cable length of 25 m should not be exceeded for the RS 232 connection between solar inverter and modem. Jumper JP400 must be in open position.
INVERTER
(1)
PV
PC
MODEM
MODEM
RS 232
RS 232
SUB-D connector
130
Page 45
(3) PV system for 2 to 99 solar inverters with interface converter (IC) RS 485 / RS 232
Connection to PC via RS 485 / RS 232
In order to connect several solar inverters to a PC, the RS 485 signal is looped through from inverter to inverter, until it is led into the inter­face converter. From here, the RS 232 signal is conducted to the PC. Jumper JP400 is connected to the solar inverter that is furthest away from the interface converter. It must be open for all other solar inverters.
Stripped length: 11 mm Jumper JP400: see above
(3) Up to 99 solar inverters can be connec­ted together and read out using this con­nection. In this case, there is a maximum cable length of 500 m between
the interface converter and the furthest solar inverter. The individual solar inverters are connected together via the RS 485 interface.
PC
SSW
INVERTER
(2 bis 99)
INVERTER
(1)
PV
PV
RS 232
RS 485
RS 485+
RS 485+
RS 485–
RS 485–
RS 485+
RS 485+
RS 485–
RS 485–
131
Page 46
PC
SSW
INVERTER
(2 bis 99)
INVERTER
(1)
PV
PV
MODEM
MODEM
RS 232
RS 232
RS 485
(4) PV system for 2 to 99 solar inverters with interface converter (IC) and modem for remote inquiry
132
The signal is looped through all units. Two «RS 485+» terminals and two «RS 485-» terminals are located on each terminal block. This means that the signal can be led into the solar inverter at one terminal and out of the solar inverter at the other termi­nal. The RS 485 signal is led out of the last solar inverter in the series into the interface converter using the following configuration: «RS 485+» to «DATA+» and «RS 485-» to «DATA-».
The interface converter generates an RS 232 signal. It is connected to the PC with the standard modem cable type D. Jumper JP400 must be closed at the solar inverter that is furthest away from the interface converter. For all other solar inverters it must be open. An address must be alloca­ted, to enable identification of the indivi­dual solar inverters. Note chapter 2.4 «Commissioning, configurations».
Page 47
Connection to modem via RS 485 / RS 232
In order to connect several solar inverters to the remote monitoring, the interface converter is connected directly to a modem via RS 232. Jumper JP400 is connected to the solar inverter that is furthest away from the interface conver­ter. It must be open for all other solar inverters.
Stripped length: 11 mm Jumper JP400: see above
(4) If several solar inverters are to be con­nected to the remote inquiry, then the individual inverters are connected together by means of the RS 485 signal, as when reading out several units locally. This signal is converted by the interface converter into the RS 232 signal, from where it is led to the modem using cable type 3. Jumper JP400 must be closed at the solar inverter that is furthest away from the interface converter. For all other solar inverters it must be open. An address must be alloca­ted, to enable identification of the indivi­dual solar inverters. Note chapter 2.4 «Commissioning, configurations».
RS 485+
RS 485+
RS 485–
RS 485–
RS 485+
RS 485+
RS 485–
RS 485–
133
Page 48
Configuring the interface cables
Cable type 1
Female connector to PC, 9-pole
1 2 3 4 5
6 7 8 9
5 4 3 2 1
9 8 7 6
Cable type 2 (Provided in the scope of supply of the «Acer» modem)
Connector to modem, 9-pole
1 2 3 4 5
6 7 8 9
5 4 3 2 1
9 8 7 6
9-pole female connector to solar inverter
9-pole female connector to solar inverter
134
Page 49
Jumper JP400 in the Sunways Solar Inverter
Please check the correct position of jum­per JP400, depending on your selected communication circuit. This jumper is located above the RS 485 communication connection in the lower section of the board.
1 2 3 4 5
6 7 8 9
Cable type 3
Connector to modem, 9-pole
Connector to interface con­verter
5 4 3 2 1
9 8 7 6
(Fig.) Position of jumper JP400
135
Page 50
136
Data acquisition
· Online values
DC voltage (U_DC), AC voltage (U_AC), AC current (I_AC), date, time, AC power, module temperature, module irradiation, «fed-in today», «fed-in since commissio­ning», error.
· 15 minute values
DC voltage (U_DC), AC voltage (U_AC), AC current (I_AC), date, time, temperature, irradiation, «fed-in in 15 minutes», accumu­lated daily total of all 15 minute average values.
Representation as graphic or print; Option of saving as bitmap; Fade-in of graphics possible. Individual solar inverters can be called up with the scroll menu.
· Daily values
Date and daily energy in the solar inverter.
Representation as graphic or print; Option of saving as bitmap; Zoom-in of graphics possible. Individual solar inverters can be called up with the scroll menu.
· Monthly values
Date in the solar inverter, fed-in since commissioning and monthly energy.
Representation as graphic or print; Option of saving as bitmap; Zoom-in of graphics possible. Individual solar inverters can be called up with the scroll menu.
· Fault data
Date, time and type of fault (for the last ten faults)
· Calendar
Date and time in the solar inverter
· Modem
Selection of the modem type and input of the address signal
If required, detailed information on Sunways NT Monitor can be found under the «Help» menu item in the program software.
Page 51
EN
137
Operation
After installing the Sunways NT Monitor software on your PC, you can start the program. The word «Sunways» will now appear on your screen.
On the menu bar at the top, you will see the four menu areas «Program», «Data», «Settings» and «Help».
· Setting menu
To configure your solar inverter, open the «Settings» menu by clicking on it with the mouse, and click on the «Inverter» key. Enter the address number that you have defined for your solar inverter next to «Inverter». For example, the number «1» for one solar inverter. In the case of several units, select «all».
Then enter the desired date and time. The settings are transferred to the solar inver­ter by clicking on the «Make change» key.
If you are using several solar inverters and wish to make a change to the numbering, you can enter the old number of the
solar inverter in the top section of the right window half and the new number beneath it. The numbering is changed by clicking on the «Make change» key.
Exit the window with the «Close» key.
You can set the interface configuration with your PC by clicking on the «Connec­tion» key.
By clicking on the «Remote modem» key, you can configure an optional modem (e. g. if you wish to retrieve data by remote inquiry).
· Data menu
In the «Data» menu, you can call up the current accumulated performance and energy of the solar inverter by clicking on the «Online» key.
You can display the data measured at 15 minute intervals by clicking on the «Minute values» key. The data and values are graphically visualised by clicking on the «Graphic representation» key.
Page 52
You can call up «Daily values» and «Monthly values» in the same way, by clicking on the respective keys.
Exit the window with the «Close» key. You will return to the «Settings» menu.
· Help menu
You will find further helpful information on operating the Sunways NT Monitor software in the "Help" menu.
138
Page 53
3.3 Fault indications
Your solar inverter operates fully automati­cally and maintenance-free. However, should malfunctions occur due to external or internal causes, these will be indicated in the first line of the display. The available measured values will be provided in the second line.
Fault 3
· DC overvoltage
A maximum no-load voltage of 750 V is permitted for the PV generator. All com­ponents of the DC input are adequately dimensioned with a safety factor. If the threshold is exceeded, the solar inverter stops the feed-in and a «DC overvoltage error» is displayed.
Fault 4
· Frequency error
The solar inverter constantly monitors the grid frequency. If this is outside the range permitted by DIN V VDE V 0126-1-1, the solar inverter will stop the feed and «Fault 4» will be indicated.
EN
Fault 5
· Overheating
Your solar inverter is designed for an ambient temperature of up to +40°C. When the maximum upper temperature threshold is reached, the feed-in is stop­ped. When the heat sink temperature has decreased, the solar inverter starts up again automatically.
Fault 6
· Grid undervoltage, 1-phase
Your solar inverter constantly monitors the voltage level of the feed-in phase. If the level falls below the minimum permissible limit value, the solar inverter stops the feed and only restarts when the voltage value rises above the minimum permissible limit value. If the voltage at L1 falls below 160 V, the solar inverter can no longer be supplied.
139
Page 54
system and the solar inverter has subse­quently disconnected from the grid. The AFI residual current (insulation error, ground fault) is displayed if a residual current has occurred in the PV system and the solar inverter has subsequently disconnected from the grid. Ground faults are monitored on both the AC and DC side (universal cur­rent-sensitive FI). If this error message is displayed, the entire PV system must be checked for insulation errors. The mode of functioning complies with DIN V VDE V 0126-1-1.
Fault 10
· Insulation error
Before every activation, your solar inverter checks the PV system for possible ground faults or insulation errors. If such an error is detected, no feed occurs. The mode of func­tioning complies with DIN V VDE V 0126-1-1.
Fault 11
· DC feed
Your solar inverter constantly monitors the quality of the fed-in current. The solar inverter stops the feed as soon as an
Fault 7
· Grid overvoltage, 1-phase
Your solar inverter constantly monitors the voltage level of the feed-in phase. If the level exceeds the maximum permissible limit value, the solar inverter stops the feed and only restarts it when the voltage value falls below the maximum permissible limit value.
Fault 8
· Grid undervoltage, 3-phase
Your solar inverter is equipped with intrin­sically safe 3-phase grid monitoring accor­ding to DIN V VDE V 0126-1-1. The voltage level of phases L2 and L3 is constantly monitored. If the level falls below the minimum permissible limit value, the solar inverter stops the feed and only restarts it when the voltage value rises above the minimum permissible limit value.
Fault 9
· AFI residual current
The «AFI error current» fault occurs when an error current has occurred in the PV
140
Page 55
increased DC component is detected in the fed-in current. The solar inverter only attempts to feed again after a reset (the next day).
Fault 12
· Isolated operation
Your solar inverter is equipped with high quality redundant grid monitoring according to DIN V VDE V 0126-1-1 and constantly monitors the grid. If one of the monitored phases drops out, or if the phase position between the individual conductors changes, the solar inverter stops the feed and only restarts when the error has been eliminated.
Fault 13
· Grid overvoltage, 3-phase
Your solar inverter is equipped with intrin­sically safe 3-phase grid monitoring accor­ding to DIN V VDE V 0126-1-1. The voltage level of phases L2 and L3 is constantly monitored. If the level exceeds the maxi­mum permissible limit value, the solar inverter stops the feed and only restarts it when the voltage value falls below the maximum permissible limit value.
Fault 14
· Surge error
Your solar inverter constantly monitors the quality of the AC grid. In the event of high voltage peaks in the grid, the solar inver­ter stops the feed and attempts to restart.
Fault 15
· Grid overvoltage > 10 %
If the voltage of the fed-in phase excee­ded 253 V for a period of ten minutes, the solar inverter stops the feed and attempts to switch on again when the grid voltage is in the permitted range. The mode of functioning complies with DIN V VDE V 0126-1-1.
Fault 16
· Control error
Your solar inverter is equipped with a self-monitored microcontroller. If an error occurs in the control cycle, the solar inver­ter stops the feed and only switches on again when the error is eliminated.
141
EN
Page 56
Two LEDs, D302 and D304, are located on the control board in the solar inverter. These describe the current status of the solar inverter:
LED green LED red
LED green LED red
LED green LED red
illuminated off
flashing flashing
off illuminated
Solar inverter operating in normal mode
Solar inverter has detected an error
internal error in the control
(Fig.) LED for functional check
142
Page 57
200
3.4 Fault diagnosis
Fault display
Fault 3 DC overvoltage
Fault 4 Frequency error
Fault 5 Overheating
Causes
The maximum DC voltage has been exceeded.
Too many modules are connected in series.
The grid frequency is out­side the permissible range.
The maximum permissible ambient temperature of 40°C has been exceeded.
The necessary air circulation was not taken into account during installation.
Objects have been stored on the heat sink, impeding free convection.
Remedies
Check the dimensioning of your PV generator.
Reduce the number of modules and re-commission the system.
Ask your electricity board about grid stability and design.
The installation location is not suitable. Please find another installation location.
Clean the solar inverter if dirt is impe­ding the cooling unit.
Remove the objects.
143
Page 58
Fault display
Fault 6 Grid under­voltage, 1-phase
Fault 7 Grid overvoltage, 1-phase
Causes
The grid voltage of the fed­in phase is too low.
The grid voltage of the fed­in phase is too high.
Remedies
The solar inverter monitors the limits of the minimum and maximum permissible 3-phase grid voltage. If the values fall below these limits (U
min
= 184 V), the solar inverter switches off and only restarts automatically when the voltage value has returned within the limits. The fault cut-out can be triggered even
if the values only exceed or fall below
the limits very briefly.
Ask your electricity board about grid stability and design.
Check the format of your grid connection (energy counter) and the grid feed-in point to your electricity board.
The solar inverter monitors the limits of the minimum and maximum permissible 3-phase grid voltage. If the values exceed below these limits (U
max
= 264 V), the solar inverter switches off and only restarts automatically when the voltage value has returned within the limits. The fault cut-out can be triggered even if the values only exceed or fall below
144
Page 59
Fault display
Fault 8 Grid under voltage, 3-phase
Causes
The cable cross-section in the AC feed line to the solar inverter is too small.
Your solar system feeds into a spur line, which is inade­quately dimensioned.
The grid voltage is too low.
Remedies
the limits very briefly.
Ask your electricity board about grid stability and design.
Check the format of your grid connection (energy counter) and the grid feed-in point to your electricity board.
The solar inverter monitors the limits of the minimum and maximum permissible 3-phase grid voltage. If the values fall below these limits (U
min
= 184 V), the solar inverter switches off and only restarts automatically when the voltage value has returned within the limits. The fault cut-out can be triggered even if the values only exceed or fall below the limits very briefly.
Ask your electricity board about grid stability and design.
145
Page 60
Fault display
Fault 9 AFI residual cur­rent
Fault 10 Insulation error
Fault 11 DC feed
Fault 12 Isolated opera­tion
Causes
The AFI error is displayed if a residual current has occur­red in the PV system and the solar inverter has subse­quently disconnected from the grid.
The solar inverter has de­tected an insulation error in the PV system during startup.
The solar inverter has detected a DC component > 1 A in the grid current.
Dropout of monitored phase L2 or L3.
Phase difference between individual grid conductors outside the permitted limit values.
Remedies
Check the format of your grid connection (energy counter) and the grid feed-in point to your electricity board.
Check your PV system for possible insulation errors.
Restart the solar inverter. If the error still occurs, please contact the technical hotline. You will find the telephone number on the back of the manual.
Check phases L2 and L3.
Ask your electricity board about grid
stability and design.
146
Page 61
Fault display
Fault 13 Grid overvoltage, 3-phase
Fault 14 Surge error
Fault 15 Grid overvoltage > 10 %
Causes
The grid voltage is too high.
The solar inverter has de­tected a high voltage peak in fed-in phases.
The grid voltage of the fed­in phase is too high.
Remedies
The solar inverter monitors the limits of the minimum and maximum permissible 3-phase grid voltage. If the values exceed below these limits (U
max
= 264 V), the solar inverter switches off and only restarts automatically when the voltage value has returned within the limits. The fault cut-out can be triggered even if the values only exceed or fall below the limits very briefly.
Ask your electricity board about grid stability and design.
The solar inverter starts automatically after fault elimination. If the error occurs more frequently, please contact your energy supply company.
The solar inverter monitors the limits of the minimum and maximum permissible grid voltage.If the limit is exceeded by 10 % (U
max
= 253 V), the solar inverter disconnects from the grid after 10 minu­tes (in accordance with DIN V VDE V 0126-1-1).
147
Page 62
Fault display
Fault 16 Control error
Causes
The cable cross-section in the AC feed line to the solar inverter is too small.
Your PV system feeds into a stub line which is too weakly dimensioned.
The intrinsic monitoring of the solar inverter has detected an error in the control.
Remedies
Ask your electricity board about grid stability and design.
Check the format of your grid connection (energy counter) and the grid feed-in point to your electricity board.
Please contact the technical hotline. You will find the telephone number on the back of the manual.
148
Page 63
Fault display
Incorrect time, date are stored in Sunways NT Monitor with incorrect time data
No data displayed, suffi­cient irradiation
Causes
The battery is empty.
The display contrast is poor on account of high tempe­rature.
The display board is not receiving any voltage supply.
The PV generator is (partially) covered with snow.
Remedies
Have the battery (button cell) replaced by an expert. The battery is located on the LCD display board.
This can occur with high ambient tempe­ratures. The display will operate normally again when the temperature decreases. The current feed is not affected by this.
Check that the flat cable between display and control board is firmly located. To do this, switch off the solar inverter and isolate on the DC and AC sides.
Clear the snow from the PV generator or wait until the snow has thawed.
149
Page 64
150
3.5 Warranty terms and conditions
· Warranty period
The warranty period is five years from purchase of the solar inverter by the end user. Please complete the enclosed war­ranty card and return it to Sunways AG. Please keep the original invoice with the date of purchase in a safe place. This will be required as proof, in addition to the warranty card, in the event of a claim.
· Conditions
During the warranty period, the solar inverter will be repaired free of labour and material costs in Constance. Instal­lation costs are borne by the customer, unless agreed otherwise. The completed warranty card must be sent to Sunways AG, Constance within seven days of purchase.
Please notify us of any warranty claims by telephone stating your name, address, telephone and serial number, and your email address if applicable. You will find the telephone number on the back of the manual.
Sunways AG must be allowed the necessary time to eliminate the defect. Sunways AG will endeavour to eliminate the defect within 14 days of receipt of the unit. If this is not possible, the customer will be infor­med of the reason and the time when the defect will be eliminated will be specified.
Please preserve the original packing, even after expiry of the warranty period. Carriers may only accept solar inverters in transport-safe original packing. Therefore, please inform us before collection if you have lost the original packing. We will gladly provide you with new packing for a charge.
Page 65
EN
151
· Exclusion of liability
Warranty claims and liability are excluded for direct or indirect damages due to:
· Interventions, modifications or attempted repairs
· Inadequate ventilation
· Force majeure (e.g. lightning strike, water damage, vandalism, fire, overvoltage, thunderstorms etc.)
· Inappropriate transport
· Non-observance of pertinent regulations or incorrect installation or commissioning
· Leakage of overvoltages from the varis­tors on the DC side on the PV generator
More extensive or other claims for direct or indirect damages, particularly claims for damages, including those arising from positive contract violation, are excluded, unless legally prescribed.
Page 66
4.0 Appendix
152
Page 67
4.1 Subject and abbreviation index
EN
153
Designation
AC
AFI, RCD
DC
EMC
EB
I
NDC
IP
kW
LCD
MPP
Description
Alternating Current: grid current
Operator protection in the event of residual currents AFI: Universal Sensitive Residual Current RCD: Residual Current Device
Direct Current PV generator side of the solar inverter
Electromagnetic Compatibility
Electricity Board
Current used to operate the solar inverter
Identification of class of protection against external environ-mental influences (penetration of water and mechanical foreign bodies)
Kilowatt
Liquid Crystal Display
Maximum Power Point
Page 68
154
Designation
Grid impedance
P
NDCPNAC
PT
PV
PV generator switch
U
NDC
Description
AC resistance of grid, impedance
DC and AC rated power: Power which the inverters can permanently consume (DC) or emit (AC).
Temperature sensor
Photovoltaic
DC load break switch to cut off the PV generator from the solar inverter
Voltage: specifies the normal operating voltage at which the solar inverter is operated
Page 69
EN
155
4.2 Function and information index
Functional principle and explanations
The electrical energy of the PV generator is buffered by a capacitive storage, from where it is fed into the public grid via a solar inverter synchronised with the grid, with an ideal phase angle of [cos phi = 1].
A sinusoidal current with a very low harmo­nic distortion is injected into the public grid by the current injection inductor. This improves the grid quality.
Thanks to the HERIC
®
technology (patent applied for) in the self-commutated Sunways Solar Inverter, the hysteresis losses in the current injection inductors that occur in conventional solar inverters and the switching losses in the semiconductors are considerably reduced. Consequently, Sunways Solar Inverters achieve a peak efficiency during conversion. The concept of the Sunways Solar Inverter is completed by a rapid MPP control, which maintains the MPP point with a very high adaptation efficiency.
· DC and AC filters
The DC and AC filters are specially designed EMC filters, which are integrated as direct components on the board. They guarantee compliance with the EMC limit values on the AC side and on the PV generator side. High-frequency emissions are avoided by the filters on the PV generator side.
· Differential measurement
The generator current and the voltage are recorded via a current transformer and a differential measurement. The values are important input values for the regulation and setting of the correct working point.
· Solar inverter with HERIC
®
technology
The heart of the solar inverter with the power semiconductors serves for conver­sion of the current from direct into alternating current. Peak efficiencies are achieved, thanks to the HERIC
®
techno­logy. The switching frequency (PWM) is 16 kHz.
Page 70
156
· Sensor interface
An irradiation sensor with integrated temperature sensor can be optionally con­nected to the relevant interface. This allows first time users to quickly grasp the mode of functioning of their PV system, and facilitates monitoring of the PV system for professionals.
· AFI universal sensitive residual current device
The universal (DC and AC) sensitive residu­al current device (AFI) monitors the solar system for residual currents. To do this, it disconnects the solar inverter from the grid by means of a relay as soon as a resi­dual current occurs on the PV generator side or on the AC side in the solar inverter. After cutoff by the relay and as soon as the residual current has stopped, the AFI automatically attempts to reconnect the solar inverter to the grid. The AFI of the Sunways solar inverter complies with standard DIN V VDE V 0126-1-1.
In addition, the AFI of Solar Inverters NT 6000, NT 5000, NT 4000 and NT 2600 has an absolutely time-independent
· Grid protection
The grid protection is a powerful relay which ensures reliable grid disconnection in the case of error and for night switch­off. This relay fulfils the requirement for trouble-free grid disconnection.
· Microcontroller
As well as system management, the efficient microcontroller undertakes additional tasks, such as saving data and communication.
· LCD display
Important information for the operator about the system operation and status is displayed on an LCD display of 2 x 16 characters.
· RS 485 and RS 232 interfaces
The two RS 485 and RS 232 interfaces installed as standard serve for communi­cation with the solar inverter and the PV system. The system can be visualised via the Sunways NT Monitor software.
Page 71
EN
157
effective value cutoff threshold. The solar inverter is switched off and isolated from the grid in the case of an error current of ≥ 300 mA.
· MPP control
The solar inverter has a rapid MPP control, which maintains the MPP point with a very high adaptation efficiency. If surplus power is provided by the PV generator, the solar inverter limits this by shifting the working point of the characteristic curve of the PV generator, so as not to exceed the maxi­mum permissible AC feed-in power in accordance with VDEW.
Page 72
DC FILTER
CAPACITIVE STORAGE
Block diagram of the solar inverter in the PV system
HERIC
®
=
≈
DIFFERER. MEASUREMENT
R
T
IRRADIATION SENSOR AND
TEMPERATURE SENSOR
(OPT.)
RS 232 RS 485
MICRO-
CONTROLLER
CONTROL DATAPRO
TEMP CONTROLLER
I
DC
U
DC
RADIATION AND TEMPERATURE
DATA
PV GENERATOR
158
Page 73
CURRENT IMPRESSION
INDUCTOR
AC FILTER GRID PROTECTION
RESIDUAL CURRENT
AFI
DIFFERER. MEASUREMENT
LCD-DISPLAY
(2 LINES)
KEYBOARD
AND
CESSING
AFI
U
AC
I
AC
GRID
L1, N, L2,L3,
PE
159
Page 74
Technical data
Solar Inverter NT 2600
Recommended solar generator power
Rated input power Stand-by consumption Night-time consumption AC energy generated from Nominal voltage U
MPP
voltage range Open-circuit voltage Switch-on voltage Switch-off voltage Maximum current Nominal current Number of inputs
Maximum efficiency European efficiency (weighted) HERIC
®
topology
Rated continuous output power Pn Maximum power Pp Nominal frequency Grid voltage Nominal current Maximum current Distortion factor at Pn Reactive power factor (cos phi) Output current
Model
1500 to 2750 W
2300 W 9 W < 0,15 W 15 W 400 V 350 ≤ U
MPP
≤ 750 V 850 V 410 V 340 V 7 A 5,75 A 2 (with adapter: 4)
97 per cent 96,5 per cent yes
2200 W 2200 W 50 Hz 230 V 9,6 A 9,6 A < 3 per cent ~1 sinusoidal
DC
AC
160
Page 75
Solar Inverter NT 4000 Solar Inverter NT 6000
2000 to 4125 W
3400 W 9 W < 0,15 W 15 W 400 V 350 ≤ U
MPP
≤ 750 V 850 V 410 V 340 V 10 A 8,5 A 2 (with adapter: 4)
97 per cent 96,4 per cent yes
3300 W 3300 W 50 Hz 230 V 14,3 A 14,3 A < 3 per cent ~1 sinusoidal
4000 to 6250 W
5200 W 9 W < 0,15 W 15 W 400 V 350 ≤ U
MPP
≤ 750 V 850 V 410 V 340 V 18 A 13 A 2 (with adapter: 4)
97 per cent 96,3 per cent yes
4600 W 5000 W 50 Hz 230 V 20 A 21,7 A < 3 per cent ~1 sinusoidal
Solar Inverter NT 5000
3000 to 4800 W
4300 W 9 W < 0,15 W 15 W 400 V 350 ≤ U
MPP
≤ 750 V 850 V 410 V 340 V 13 A 10,8 A 2 (with adapter: 4)
97 per cent 96,4 per cent yes
4000 W 4200 W 50 Hz 230 V 17,4 A 18,3 A < 3 per cent ~1 sinusoidal
161
Page 76
Grid voltage monitoring Earth fault protection Isolation, Frequency and DC-Current Monitoring Output characteristic Grid connection fuse layout Required number of grid connection phases Number of feed-in phases (230 V single-phase)
Data interfaces
Sensor interfaces Display
System of protection against envir. influences Relative air humidity, max. Cooling Ambient temperature (Celsius) Dimensions (height x width x depth) Weight Noise development Standard warranty period (option)
threephase RCD (universally sensitive) integrated current source 16 A 3 1
external RS 232, RS 485, status signal relay irradiation, temperature LCD, 2 x 16 characters
IP 54 95 per cent free convection
-25°C to 40°C 515 x 300 x 190 mm 26 kg silent (< 35 dB (A)) 5 years (10 years)
162
Page 77
threephase RCD (universally sensitive) integrated current source 25 A 3 1
external RS 232, RS 485, status signal relay irradiation, temperature LCD, 2 x 16 characters
IP 54 95 per cent free convection
-25°C to 40°C 515 x 300 x 190 mm 26 kg silent (< 35 dB (A)) 5 years (10 years)
threephase RCD (universally sensitive) integrated current source 25 A 3 1
external RS 232, RS 485, status signal relay irradiation, temperature LCD, 2 x 16 characters
IP 54 95 per cent free convection
-25°C to 40°C 515 x 300 x 190 mm 26 kg silent (< 35 dB (A)) 5 years (10 years)
threephase RCD (universally sensitive) integrated current source 25 A 3 1
external RS 232, RS 485, status signal relay irradiation, temperature LCD, 2 x 16 characters
IP 54 95 per cent free convection
-25°C to 40°C 515 x 300 x 190 mm 26 kg silent (< 35 dB (A)) 5 years (10 years)
163
Page 78
Tyco Solarlok connector
The Tyco Solarlok connectors are only approved for connection to permanently laid cables!
They must not be disconnected under load!
The circuit must be interrupted at a sui­table point! The cables must be provided with a suitable adhesive label close to the Tyco Solarlok connector!
The Tyco Solarlok connectors must always be disconnected from other vol­tage sources on all sides during assem­bly, in order to protect against electric shock.
!
(Fig.) Manual crimping tool for assembly of Tyco Solarlok connectors
(Fig.) Tyco Solarlok connectors
164
Page 79
Any type of soiling (dust, humidity etc.) will negatively affect the operation of the system over the desired period of use. This applies particularly for the usability of the seals and crimping of the contacts. The utmost care must therefore be taken to work cleanly during installation.
Different circular contacts are used for dif­ferent conductor cross-sections for the Tyco Solarlok connectors. The correct tool insert must be used, depending on this cross-sec­tion. The enclosed Tyco Solarlok connectors are equipped with circular contacts for a cable cross-section of 4 mm. The enclosed seals have internal dimensions of 6 (for cables of 5.3 to 6.2 mm sheath diameter) and 8 mm (for cables of 7.2 to 8.0 mm she­ath diameter). The seal must be matched to the sheath diameter of the cables used.
EN
The following sequence must be observed for assembly of Tyco Solarlok connectors:
1. Strip the voltage-free cable by 8 mm.
2. Crimp on the circular contact.
3. Push the cable gland, clamping piece and seal onto the cable.
4. Engage the contact in the connector housing.
5. Screw on the clamping nut.
6. Tightening torque of the threaded cable gland is 1.5 Nm.
165
Page 80
166
Declaration of Conformity as per EG Low Voltage Guidelines 73/23/EWG, attachment III B
We herewith declare that the following product including the required accessories has been manufactured according to the EG guidelines 73/23/EWG and 93/68/EWG:
Product Manufacture
Type From date of manufacture Applied standards
Standard Title
Edition
Solar Inverter Sunways AG, Photovoltaic Technology Macairestr. 3-5, D - 78467 Konstanz Sunways NT 6000, NT 5000, NT 4000, NT 2600 2005-05-02 EN 50178 Electronic equipment for use in power instal­lations 1998
Explanation This product is a component intended for further assembly. Due to the features resulting therefrom, the product cannot initially meet requirements made of finished products, machines or plants. It must thus be used for mounting / assembly only. An evaluation of electrical and mechanical safety and of environmental conditions (e.g. extrinsic objects and / or humidity) must be performed after mounting / assembly in the finished plant. The EMC characteristics of this product can change in a mounted / assembled state. An EMC check must thus be made for the PV-System by the manufacturer of the PV-System.
City, Date Roland Burkhardt,CEO
Konstanz, 2005-03-05
Page 81
EN
167
Declaration of Conformity as defined by the EMC guideline 89/336/EWG with revisions 91/263/EWG and 93/68/EWG.
We herewith declare that the following product has been manufactured according to the requirements outlined in the EG requirements on 89/336/EWG (EMC guideline with revisions 91/263/EWG)
Product Manufacturer
Type from date of manufacture applied standards
Standard
Solar Inverter Sunways AG, Photovoltaic Technology Macairestr. 3-5, D - 78467 Konstanz Sunways NT 6000, NT 5000, NT 4000, NT 2600 2005-05-02 EN 50082-2 (EN 61000-4-2, -4-3, -4-4, -4-6, -4-8) EN 55014-1; EN 55011; EN 61000-3-2; EN 61000-3-3; E DIN VDE 0126-1-1
Explanation Maintaining the EMC guideline assumes an EMC adapted installation of the component within the plant or the machine. Please pay attention to the installation notes of the technical specifications. Tests were carried out using a typical construction in a test assembly that conforms with the stands. The legal requirements with regard to resistance to interference and to emission of interference, limit values and standards are outlined in the above mentioned documentation. These Sunways products are intended for installation into a PV-System. The test results are not applicable to every installed state in every PV-System. This declaration therefore does not guarantee the EMC characteristics of the end product.
City, Date Roland Burkhardt,CEO
Konstanz, 2005-03-05
Page 82
168
Declaration of Conformity of nominal power and maximum output power of solar inverters.
Product Manufacturer
Type Sunways Nominal power S
N
Maximum output power S
max10Min
S
max10Min/SN
Solar Inverter Sunways AG, Photovoltaic Technology Macairestr. 3-5, D - 78467 Konstanz
Explanation The maximum output power of the solar inverter has to be declarated as a max. 10 minute average.
City, Date Roland Burkhardt,CEO
Konstanz, 2005-22-03
NT 4000 3,3 kVA 3,3 kVA 1
NT 2600 2,2 kVA 2,2 kVA 1
NT 6000 4,6 kVA 5 kVA 1,08
NT 5000 4,0 kVA 4,2 kVA 1,05
Page 83
EN
169
Declaration of Conformity as defined by the guidelines for connection and grid feeding in parallel of in-plant generation on low-voltage-guidelines (VDEW 4. Edition 2001).
We herewith declare that the following product has been manufactured according to the requirements outlined in the guidelines for connection and grid feeding in parallel of in-plant generation on low-voltage-guidelines:
Product Manufacturer
Type From date of manufacture Applied standard
Standard Title
Edition
Solar Inverter Sunways AG, Photovoltaic Technology Macairestr. 3-5, D - 78467 Konstanz Sunways NT 6000, NT 5000, NT 4000, NT 2600 2005-05-02
In-plant generation on low-voltage­guidelines
4. Edition 2001
Explanation The NT series of solar inverters from Sunways are monophase inverters that are not capable of isolated operation. They are equipped with a voltage monitor and three phase monitoring of the line voltage for undervoltage in accordance with section
2.4.2 of the VDEW Guideline (4th edition 2001). A constantly accessible isolation point is therefore not required (see section
2.1.2 Switching point with isolating function). Observation of the cut-off values of the threephase undervoltage protection is undertaken by means of a routine check test on each device
City, Date Roland Burkhardt,CEO
Konstanz, 2005-22-03
Page 84
170
General exclusion of liability
Although the accuracy and completeness of the information contained in these instructions have been checked with the utmost care, no liability can be accepted for errors or omissions.
· Sunways AG reserves the right to modify the hardware and software features described here at any time, without prior notice.
· These instructions may not be duplica­ted, passed on, copied or translated in to other languages, either in whole or in part, in any form or by any means, without prior written permission of Sunways AG.
· Sunways AG does not provide any war­ranty for damages due to defective or lost data, incorrect operation or mal­functioning of the solar inverter, the software, additional equipment or PCs.
All rights reserved. © Sunways AG
The products specified in the title are copyright-protected and are sold with licences. No part of this document may be reproduced in any form, without prior written permission of Sunways AG and the Sunways licensors.
Registered trademarks
Sunways Sunways NT 6000, NT 5000, NT 4000 and NT 2600 and the Sunways logo are registered trademarks of Sunways AG, Constance.
HERIC
®
is a registered trademark of
Fraunhofer, Munich.
Page 85
200
Page 86
Sunways AG Photovoltaic Technology Macairestraße 3 - 5 D-78467 Konstanz Telefon + 49 7531 996770 Fax + 49 7531 99677444 E-Mail info@ sunways.de www.sunways.de
Technische Hotline +49 7531 99677577
9-1-27-0-0 Version 05/05
Loading...