suntouch TapeMat D12 series, TapeMat C12 series, TapeMat C15 series Installation Instructions Manual

Installation Manual
TapeMat
®
Please be aware local codes may require this product and/or the thermostatic control to be installed or connected by an electrician. Please leave this manual with the end user.
Includes Custom TapeMat® and ShowerMat™
Series D12, C12 & C15
Assembled in the
USA
IOM-WR-TapeMat 1526 2 of 32
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information can result in death, serious personal injury, property damage, or damage to the equipment.
Keep this Manual for future reference.
Specifications for TapeMat:
Floor heating mats are a simple way to heat an indoor space. This instruction manual is provided as a guide to installing TapeMats, including design considerations, installation steps, limitations, precautions, and floor covering guidelines.
TapeMat is a complete heating mat consisting of a series heating wire and a power lead for connection to the electric power supply.
The heating wire length cannot be cut to fit.
Controls:
TapeMats must be controlled by a SunStat® floor sensing thermostat. (Listed separately)
Voltage:
120 VAC, 240 VAC, 1-phase (see Table 2)
Watts:
D12 and C12 Series - 12 W/ft2 (41 Btu /h/ft2), C15 Series 15 W/ft2 (51 Btu/h/ft2)
Maximum circuit load:
15 A
Maximum circuit overload protection:
20 A breaker
GFCI:
(Ground Fault Circuit Interrupter) required for each circuit (included in the SunStat control)
Listing:
UL Listed for U.S. and Canada under UL 1693 and CAN/CSA C22.2 No. 130.2-93,
File No. E185866
Application:
Indoor floor heating only (-X on the nameplate label indicates CUL Listing for this
application).
Suitable for installation in a shower area (see Step 3.10 for restrictions). (-W on the nameplate label indicates CUL Listing for Wet Location in Canada per Canadian Electrical Code, Part I (CEC).
Embedded in polymer-modified cement based mortar only (see Phase 4). D12 and C12 Series - May be installed under masonry or non-masonry surfaces as indicated in this manual.
C15 Series - May only be installed under masonry surfaces as indicated in this manual.
Minimum bend radius:
1 inch
Maximum exposure temperature: (Continuous and storage) 194ºF (90ºC)
Minimum installation temperature:
50ºF (10ºC)
Installation must be performed by qualified persons, in accordance with local codes, ANSI/ NFPA 70 (NEC Article 424) and CEC Part 1 Section 62 where applicable. Prior to installation, please consult the local codes in order to understand what is acceptable. To the extent this information is not consistent with local codes, the local codes should be followed. However, electrical wiring is required from a circuit breaker or other electrical circuit to the control. It is recommended that an electrician perform these installation steps. Please be aware local codes may require this product and/or the control to be installed by an electrician.
Double­sided Tape
Heating Wire
Factory Splice
Power lead
Mat Mesh
3 of 32 © 2015 Watts Water Technologies
Expected floor temperature
Heating performance is never guaranteed. The floor temperature attainable is dependent on how well the floor is insulated, the temperature of the floor before start up, and the overall thermal drain of the floor mass. Insulation is required for best performance. Refer to Phase 4 for important design considerations.
Important Safety Information
This is a safety-alert symbol. The safety alert symbol is shown alone or used with a signal word (DANGER, WARNING, or CAUTION), a pictorial and/or a safety message to identify hazards.
When you see this symbol alone or with a signal word on your equipment or in this Manual, be alert to the potential for death or serious personal injury.
This pictorial alerts you to electricity, electrocution, and shock hazards.
This symbol identifies hazards which, if not avoided, could result in death
or serious injury.
This symbol identifies hazards which, if not avoided, could result in minor
or moderate injury.
This symbol identifies practices, actions, or failure to act which could result
in property damage or damage to the equipment.
Table of Contents
Important Safety Information .....................3
Phase 1 - Preparations ..............................5
Phase 2 - Electrical Rough-in ....................9
Phase 3 - TapeMat Installation ................11
Phase 4 - Floor Coverings ....................... 17
Phase 5 - Control Installation ..................20
Appendices ..............................................22
Troubleshooting .......................................29
Warranty ................................................... 31
These are the three most common installa tions:
1.
Wood framing:
With the mat installed on a well-insulated wood subfloor, and thin-set mortar
and tile on top, most floors can be heated up to 20°F warmer than they would otherwise be.
2. Insulated concrete slab:
With the mat installed on an insulated concrete slab, and thin-set mortar and tile on top, most floors can be heated up to perhaps 15°F warmer than they would otherwise be.
3.
Uninsulated concrete slab:
With the mat installed on an uninsulated concrete slab, and thin-set mortar and tile on top, most floors can be heated up to perhaps 10°–15°F warmer than they would otherwise be.
Please consult a designer or the factory if questions remain about the surface tempera ture that can be expected from the cables in any particular construction.
IOM-WR-TapeMat 1526 4 of 32
NEVER install TapeMat under carpet, wood, vinyl, or other non-masonry flooring without
embedding it in thin-set, thick-set, or self-leveling mortar.
NEVER install TapeMat in adhesives or glues intended for vinyl tile or other laminate flooring, or
in pre-mix mortars. It must be embedded in polymer-modified, cement based mortar.
NEVER cut the heating wire. Doing so will cause dangerous overheating and will void the
warranty. The power lead may be cut shorter if necessary, but never remove completely from the heating wire.
NEVER bang a trowel or other tool on the heating wire. Be careful not to nick, cut, or pinch
the wire causing it to be damaged.
NEVER use nails, staples, or similar to fasten the heating wire to the floor.
NEVER attempt to repair a damaged heating wire, splice, or power lead using unauthorized
parts. Use only factory authorized repair parts and methods.
NEVER attempt to repair a damaged shower mat. It must be replaced.
NEVER splice one mat heating wire to another mat heating wire to make a longer mat. Multiple
mat power leads must be connected in parallel in a junction box or to the thermostat.
NEVER install one mat on top of another or overlap the heating wire on itself. This will cause
dangerous overheating.
NEVER forget to install the floor sensor included with the thermostat.
NEVER install TapeMat in any walls, or over walls or partitions that extend to the ceiling.
NEVER install mats under cabinets or other built-ins having no floor clearance, or in small
closets. Excessive heat will build up in these confined spaces, and the mat can be damaged by fasteners (nails, screws, etc.) used to install built-ins.
NEVER remove the nameplate label from the power leads. Make sure it is viewable for
inspection later.
NEVER extend the heating wire beyond the room or area in which it originates.
NEVER allow a power lead or sensor wire to cross over or under a heating cable. Damage
could result.
NEVER put the system into full operation until the tile or flooring installer verifies all cement
materials are fully cured (typically two to four weeks).
Table 1
As with any electrical product, care should be taken to guard against the potential risk of fire, electric shock, and injury to persons. The following cautions must be observed:
Local building or electrical codes may require modifications to the information provided. You are required to consult the local building and electrical codes prior to installation. If this information is not consistent with local building or electrical codes, the local codes should be followed.
ALW AYS completely embed the heating wire and factory splices in the floor mortar.
ALW AYS maintain a minimum of 2.5" spacing between heating wires.
5 of 32 © 2015 Watts Water Technologies
Installation must be performed by qualified personnel, in accordance with local codes and standards. A licensed electrician is recommended.
Phase 1 - Preparations
ALWAYS pay close attention to voltage and amperage requirements of the breaker, the
thermostat, and the TapeMat. For instance, do not supply 240 VAC power to 120 VAC TapeMat as damage will result.
ALW AYS make sure all electrical work is done by qualified persons in accordance with local
building and electrical codes, Section 62 of the Canadian Electrical Code (CEC) Part I, and the National Electrical Code (NEC), especially Article 424.
ALW AYS use copper only as supply conductors to the thermostat. Do not use aluminum.
ALW AYS seek help if a problem arises. If ever in doubt about the correct installation procedure
to follow, or if the product appears to be damaged, the factory must be called before proceeding with the installation.
Before installing TapeMat, make sure to fully inspect the products and carefully plan the site.
Items Needed
Materials:
• SunStat thermostat control with floor sensor.
• SunStat Relay control (if required)
Control electrical box (UL Listed, extra deep, see control instructions for size and type required)
• Junction electric box (if required, see Step 2.2)
• Wire nuts (Must be UL Listed and proper size)
• Flexible or rigid conduit (if required, see Step 2.4, must be UL Listed and proper size)
• 12-gauge or 14-gauge electrical wiring cable (consult local code)
• Nail plate (see Step 3.8)
Tools:
• Digital multi-meter for ohms testing; must read up to 20,000 ohms to measure sensor
• Drill with 1/2" & 3/4" bits
• Hammer and chisel
• Hot glue gun and hot glue (craft grade)
• Wire strippers
• Phillips screwdriver
• Fish tape
• Hole saw
• Floor covering installation tools
Floor sensor is
included in the
SunStat thermostat
packaging. This must
be installed in the
floor with the mat.
IOM-WR-TapeMat 1526 6 of 32
It is important to select the proper size mat for the given area. Mats cannot be cut shorter in order to fit a given area. Doing so will damage the heating wire and prevent the system from working.
Please check the product label for exact ratings. This table is for reference only.
Table 2 - Mat Sizes
Inspect mat, control, and sensor
To prevent the risk of personal injury and/or death, make sure power is not applied to the product until it is fully installed and ready for final testing. All work must be done with power turned off to the circuit being worked on.
STEP 1.1
Remove the TapeMat, SunStat Control, and sensor from their packages. Inspect them for any visible damage and verify everything is the correct size and type according to the plan and the order. Do not attempt to install a damaged product.
120 VAC TapeMat
2 ft Wide
Mat
Ft
2
Mat Size
(W x L)
Model
Number
Amp
Draw
Ohms
10 2' x 5' 12000524 1.0
109 - 134
15 2' x 7'-6" 12000724
1.5 76 - 94
20 2' x 10' 12001024
2.0 57 - 71
25 2' x 12'-6" 12001224
2.5 43 - 54
30 2' x 15' 12001524
3.0 34 - 42
35 2' x 17'-6" 12001724
3.5 29 - 36
40 2' x 20' 12002024
4.0 25 - 32
45 2' x 22'-6" 12002224
4.5 22 - 28
50 2' x 25' 12002524
5.0 20 - 26
60 2' x 30' 12003024
6.0 17 - 21
70 2' x 35' 12003524
7.0 14 - 18
80 2' x 40' 12004024
8.0 12 - 16
90 2' x 45' 12004524
9.0 11-14
100 2' x 50' 12005024
10.0 10-13
3 ft Wide
15 3' x 5'
12000536 1.5 76 - 95
20 3' x 6'-8"
12000636 2.0 58 - 72
25 3' x 8'-4"
12000836 2.5 44 - 55
30 3' x 10'
12001036 3.0 34 - 42
45 3' x 15'
12001536 4.5 22 - 28
60 3' x 20'
12002036 6.0 17 - 22
240 VAC TapeMat
2 ft Wide
Mat
Ft
2
Mat Size
(W x L)
Model
Number
Amp
Draw
Ohms
20 2' x 10'
24001024 1.0 221 - 271
30 2' x 15'
24001524 1.5 153 - 188
40 2' x 20'
24002024 2.0 115 - 142
50 2' x 25'
24002524 2.5 87 - 108
60 2' x 30'
24003024 3.0 68 - 84
70 2' x 35'
24003524 3.5 58 - 72
80 2' x 40'
24004024 4.0 51 - 63
90 2' x 45'
24004524 4.5 45 - 56
100 2' x 50'
24005024 5.0 40 - 51
120 2' x 60'
24006024 6.0 34 - 42
140 2' x 70'
24007024 7.0 29 - 36
160 2' x 80'
24008024 8.0 25 - 32
180 2' x 90'
24009024 9.0 22-28
200
24010024 10.0 20-26
3 ft Wide
30
3' x 10' 24001036 1.5 154 - 190
40
3' x 13'-4" 24001336 2.0 116 - 143
50
3' x 16'-8" 24001636 2.5 88 - 109
60
3' x 20' 24002036 3.0 68 - 84
90
3' x 30' 24003036 4.5 45 - 56
120
3' x 40' 24004036 6.0 34 - 43
120 VAC ShowerMat
Mat
Ft
2
Mat Size
(W x L)
Order
Number
Model
Number
Amp
Draw
Ohms
10 36" x 60" 81017075 C12120010ST-S3660 1.0 109 - 137 10 48" x 48" 81017076 C12120010ST-S4848 1.0 109 - 137
7 of 32 © 2015 Watts Water Technologies
Do not remove this nameplate label. The electrical inspector will need to see this.
STEP 1.2
Record the product information in Ta ble 4. Give this information to the homeowner to keep in a safe place.
The Mat model number, serial number, voltage, and resistance range are shown on a nameplate label attached to the power leads.
Black Lead
White or Blue Lead
Ground Lead
Black Lead
White or Blue Lead
Ground Lead
Black Lead
White or Blue Lead
Ground Lead
200 ohm
setting
Black wire
to COM
Red wire
to 
Readings between the Black and Ground and the White (or Blue for 240 VAC) and Ground power lead wires should measure “open”, or “O.L”, or the same as displayed when the test leads are not touching anything.
Press the test lead tips to the Black and White (or Blue for 240 VAC) power lead wires. This reading should correspond to the factory resistance range on the nameplate label attached to the Power lead.
Temperature Typical Values
55°F (13°C) 17,000 ohms
65°F (18°C) 13,000 ohms
75°F (24°C) 10,000 ohms
85°F (29°C) 8,000 ohms
Table 3 - Floor Sensor Resistance Values
STEP 1.3
Use a digital multi-meter set to the 200Ω or 2000Ω (2kΩ) range to measure the resistance between the conductors of the mat power leads. Record these resistances in Table 4 under “Out of the box before installation”.
The resistance should measure within the resistance range on the nameplate label. If it is a little low, it may be due to low air temperatures or meter calibration. Consult the factory if in doubt.
Measure the resistance between either of the white or black leads and ground lead. This measurement should be “open”, usually indicated by an “OL” or a “I”. This is the same as displayed when the test leads are not touching anything.
If there is any change in the reading, record this information and contact the factory before continuing. This could indicate damage, test lead problems, or a number of other issues. Try “pinning” the test leads to the cable lead wires against a hard non-metal surface if the readings continue to fluctuate.
Change the meter to the 20,000 ohms (20 kΩ) range. Measure between the lead wires of the control sensor. This resistance varies according to the temperature sensed. Tab le 3 provides approximate resistance-to-temperature values for reference.
IOM-WR-TapeMat 1526 8 of 32
Mat 1 Mat 2 Mat 3
Mat serial number
Mat model
Mat voltage
Factory mat resistance range
OUT OF THE BOX BEFORE INSTALLATION (OHMS)
Mat black to white (black to blue for 240VAC)
Mat black to ground
Mat white to ground (blue to ground for 240VAC)
Sensor wire
AFTER MAT AND SENSOR ARE FASTENED TO FLOOR (OHMS)
Mat black to white (black to blue for 240VAC)
Mat black to ground
Mat white to ground (blue to ground for 240VAC)
Sensor wire
AFTER FLOOR COVERINGS ARE INSTALLED (OHMS)
Mat black to white (black to blue for 240VAC)
Mat black to ground
Mat white to ground (blue to ground for 240VAC)
Sensor wire
Retain this log to retain the warranty! Do not discard!
Table 4 - Mat and Sensor Resistance Log
INSTALLATION NOTES
9 of 32 © 2015 Watts Water Technologies
Phase 2 - Electrical Rough-in
To prevent the risk of personal injury and/or death, make sure power is not applied to the product until it is fully installed and ready for final testing. All work must be done with power turned off to the circuit being worked on.
STEP 2.1: Circuit Breaker (Overcurrent Protection)
TapeMat(s) must be protected against overload by a circuit breaker. GFCI type (ground fault circuit interrupter) or AFCI type (arc-fault circuit interrupter) breakers may be used if desired, but are not necessary when using SunStat controls with integral GFCI
The rating of the breaker (see Table 5) is determined by the amp draw of the heating mats. Add the amp ratings of all mats to be connected to the SunStat control (see Table 2 or the Nameplate Label on the mat). If the total is less than 12 amps, use a 15 or 20 A breaker (preference is 15 A). If the total is between 12 and 15 amps, use a 20 A breaker. If the total is over 15 A, another circuit will be required with its own breaker and SunStat control.
Circuit Breakers and Supply Wire
Mat(s) Supply Wire Breaker VAC total amps (AWG)* qty type** rating 120 up to 12 amps 14 1 SP 15 or 20 A 120 up to 15 amps 12 1 SP 20 A 240 up to 12 amps 14 1 DP 15 or 20 A 240 up to 15 amps 12 1 DP 20 A
* Recommended only. Follow local codes for wire gauge size. ** SP= single-pole, DP=double-pole
Table 5
STEP 2.2: Install Electrical Boxes
SunStat Thermostat:
Install an extra-deep electrical box for the SunStat thermostat. Follow the instructions included with the SunStat for complete information on location and wiring. The thermostat must be located at least 4 feet (1.2 meters) away from shower openings to avoid being exposed to water or touched by a person while in the shower area.
SunStat Relay:
Install an extra-deep electrical box for any SunStat Relay(s). The SunStat Relay is used when more than 15 amps must be controlled by one SunStat Thermostat. Follow the instructions included with the SunStat Relay for complete information on location and wiring.
Junction Boxes:
If a mat is to be located so its Power lead is not long enough to reach the SunStat Control or SunStat Relay directly, a junction box must be installed. Do not attempt to make a connection to other wiring without a junction box. Use a standard junction box with a cover, mounting it below the subfloor, in the attic, in the wall, or in another location easily accessible after all coverings are complete. If the SunStat sensor wire is not long enough to reach the SunStat Control directly, it may be extended. A junction box may be required by local code to make this connection. Follow the installation instructions included with the SunStat Control for details.
For construction with an existing wall or where the wall is covered, cut the necessary openings to mount the electrical boxes listed above. Wait to install the boxes until all wiring is fed into these locations to make it easier to pull the wire.
It may be possible to tap into an existing circuit as long as there is adequate capacity for the mat(s) and any additional ap­pliance, such as a hair dryer or vacuum cleaner. Avoid circuits which have lighting, motors, exhaust fans, or hot tub pumps due to possible interference.
IOM-WR-TapeMat 1526 10 of 32
STEP 2.3:
Bottom Plate Work
Drill or chisel holes at the bottom plate as indicated. One hole is for routing the power lead conduit and the other is for the thermostat sensor. These holes should be directly below the electrical box(es).
Power lead
conduit
Wire
Clip
Power
lead
Sensor wire
Sensor wire
If going in to an existing wall, cut out dry wall and chisel out bottom plate to route wires to control.
STEP 2.4: Install Power Lead Conduit and Thermostat Sensor
Power Lead Conduit:
The shielded power lead can be installed with or without electrical conduit (recommended for added protection against nails or screws) depending on code requirements. Remove one of the knock-outs in the electrical box to route the power lead. If electrical conduit is not required by code, install a wire collar to secure the power leads where they enter the box. If conduit is required by code, install 1/2" (minimum) conduit from the bottom plate up to the electrical box. For multiple power leads (multiple mats) install 3/4" conduit.
Thermostat Sensor:
The SunStat Control sensor can be installed with or without electrical conduit depending on code requirements. Conduit is recommended for added protection against nails or screws. Do not place the sensor in the same conduit as the power leads to avoid possible interference. Open a separate knock-out in the bottom of the thermostat box. Feed the sensor (and conduit, if used) through the knock-out, down through the cut-out in the bottom plate, and out into the floor where the heating mat will be installed. If the sensor wire needs to be secured to the wall stud, wait until after the mat and sensor are completely installed on the floor.
STEP 2.5: Rough-in Wiring:
Install appropriate 12 or 14 AWG electrical wire from the circuit breaker or branch circuit source to the SunStat Control electrical box (and SunStat Relay box(es) if needed) following all codes, see Ta ble 5.
If SunStat Relay(s) are used, feed appropriate wire between the SunStat Relay(s) and the SunStat Control. See SunStat Relay instructions for details of wire size and type.
Loading...
+ 22 hidden pages