*Do not touch any electrical switch; do not use any phone in your building.
*Immediately call your gas supplier from a neighbors phone. Follow the
gas supplier's instructions.
*If you cannot reach your gas supplier, call the fire department.
WARNING: Improper installation, adjustment, alteration,
service or maintenance can cause property damage, injury
or death. Read the installation, operating and maintenance
instructions thoroughly before installing or servicing this
equipment.
INSTALLER: This manual is the property of the owner. Please present this manual to the owner when you leave the job site.
This heater is a self-contained infrared floor model heater for use in the temporary heating of buildings under construction,
repair or alteration.
GENERAL HAZARD WARNING:
WARNING: FIRE, BURN, INHALATION,
AND EXPLOSION HAZARD. KEEP SOLID COMFAILURE TO COMPLY WITH THE PRECAUTIONS AND INSTRUCTIONS PROVIDED WITH
THIS HEATER, CAN RESULT IN DEATH, SERIOUS BODILY INJURY AND PROPERTY LOSS
OR DAMAGE FROM THE HAZARDS OF FIRE,
EXPLOSION, BURN, ASPHYXIATION, CARBON MONOXIDE POISONING, AND/OR ELECTRICAL SHOCK.
BUSTIBLES, SUCH AS BUILDING MATERIALS,
PAPER OR CARDBOARD, A SAFE DISTANCE
AWAY FROM THE HEATER AS RECOMMENDED
BY THE INSTRUCTIONS. NEVER USE THE
HEATER IN SPACES WHICH DO OR MAY CON-
TAIN VOLATILE OR AIRBORNE COMBUSTI-
BLES, OR PRODUCTS SUCH AS GASOLINE,
SOLVENTS, PAINT THINNER, DUST PARTICLES
OR UNKNOWN CHEMICALS.
ONLY PERSONS WHO CAN UNDERSTAND
AND FOLLOW THE INSTRUCTIONS SHOULD
SERVICE THIS HEATER.
WARNING: NOT FOR HOME OR RECRE-
IF YOU NEED ASSISTANCE WITH THIS
ATIONAL USE.
HEATER OR INFORMATION SUCH AS AN
INSTRUCTIONS MANUAL, LABEL, ETC. CONTACT THE MANUFACTURER.
INSTALLATION REQUIREMENTS
The heater is designed and approved for use as a construction heater in accordance with Standard ANSI Z83.7 - CGA 2.14.
CHECK WITH YOUR LOCAL FIRE SAFETY AUTHORITY IF YOU HAVE ANY QUESTIONS ABOUT APPLICATIONS. Other standards
govern the use of fuel gases and heat producing products in specific applications. Your local authority can advise you about
these.
This heater is intended for use in the temporary heating of buildings or structures under construction, alteration or repair.
Installation of this heater must be in accordance with all applicable codes shown in the instructions and/or the local codes
and authorities having jurisdiction. Heaters shall be installed by a licensed contractor or licensed installer. Clearances to
combustibles as outlined in this manual should always be observed.
Every heater shall be located with respect to building construction and other equipment so as to permit access to the
heater. Each installer shall use good installation practices when locating the heater and must give consideration to service
accessibility. The heater should be inspected before each use, and at least annually by a qualified service person.
This heater is for INDOOR INSTALLATION ONLY. While the products of combustion are expelled into the building, national
codes require ventilation in the building to dilute these products of combustion. This ventilation may be provided by gravity
or mechanical means. Refer to Section 7 “VENTILATION AND COMBUSTION AIR” on page 6 of this manual for minimum
requirements for ventilation and combustion air.
The heater must not be installed where it is directly exposed to water spray, rain and/or dripping water.
Copies of the National Fuel Gas Code (ANSI Z223.1 - latest edition) are available from the American Gas Association Laboratories, 8501 E. Pleasant Valley Road, Cleveland, OH 44131. All NFPA codes are available from the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269.
rev: 11/15/061
Hot surfaces! Do NOT move,
handle or service heater
while operating.
Allow at least 10 minutes
before touching any surfaces.
Failure to do so may result
in serious injury.
SECTION 2: SPECIFICATIONS
MODEL NOGAS TYPEINPUT BTU/HRORIFICE SIZE
RCH100NATURAL100,000#12 (.1890)
WARNING
BURN HAZARD
Table 1: Model input rating
WARNING
FIRE HAZARD
Heater must be on a stable
and level surface.
Failure to do so may result
in death, serious injury or
property damage.
RCH100PROPANE95,000
Gas Pipe connection: 1/2” NPT Female
MODEL SUFFIXES:
NNatural Gas
LPropane Gas
6CStanding Pilot Ignition, 100% Safety Shutoff, Manual Valve (White-Rodgers)
9AStanding Pilot Ignition, 100% Safety Shutoff, Thermostatic Controlled Valve (Robertshaw)
9BStanding Pilot Ignition, 100% Safety Shutoff, Thermostatic Controlled Valve (Robertshaw) with Suspension
assembly and Tip-over switch
7/64 (.1094)
Table 2: Model Dimensions
DIMENSIONSRCH100
HEATER15"Dia. x 32-1/4"
PACKAGED18-1/2" x 18-1/2" x 34"
SHIPPING WEIGHTS40 LBS.
SECTION 3: INSTALLATION OF THE THERMOSTAT BULB (RCH100 9A & 9B models)
The thermostat bulb is not factory installed to avoid shipping damage. To install the thermostat bulb, insert the sensing
bulb into the retianer bracket. Secure bulb by gently squeezing the tabs of the bracket, taking care not to crimp the bulb
capillary. See Figure 1 ”Thermostatic Bulb Retainer detail.” on page 3
2
RCH100 Installation and Operation Instructions
.
Figure 1: Thermostatic Bulb Retainer detail.
Control Gas Valve
Bulb Retainer Bracket
Temperature Sensing Bulb
Bulb Capillary
SECTION 4: MINIMUM CLEARANCES TO COMBUSTIBLES
The heater shall be operated only on a NON-COMBUSTIBLE, level floor. Minimum clearances to combustible walls and ceilings are listed below:
Table 3: RCH100 Clearances to combustibles
MODEL RCH100FRONTSIDESREARTOP
WITHOUT REFLECTOR---60"---54"10 FEET
CLEARANCE FROM
PROPANE CYLINDER
SECTION 5: GAS CONNECTIONS AND REGULATION
5.1. The installation must conform with local codes, or in absence of local codes, with the standard for the storage and
handling of Liquefied Petroleum Gases, ANSI/NFPA 58 and the Natural Gas and Propane Installation Code, CSA
B149.1.
5.2. This heater is intended for construction heating and it must never
5.3. Connect to the supply tank or manifold in accordance with the latest edition of National Fuel Gas Code (ANSI Z223.1/
NFPA 54) and local building codes. Authorities having jurisdiction should be consulted before the installation is made.
5.4. Pipe joint compounds must be resistant to the action of liquefied petroleum gases.
5.5. Where local codes do not prohibit, a C.S.A or U.L. approved flexible connection is recommended between the rigid piping and the heater. A union and an approved shut-off valve should be installed before the control valve inlet. The shutoff valve should be installed within 6 feet of the union.
be used for residential/domestic heating.
5.6. This appliance is equipped with a manual gas valve and an appliance regulator. The maximum supply pressure to the
appliance is 14" W.C. or 1/2 P.S.I. If the line pressure is more than the maximum supply pressure, then use a line regulator which corresponds to the supply pressure.
5.7. After gas connections have been made, make sure the heater and all gas outlets are turned off before the main gas
supply is turned on. Turn the gas pressure on and check for leaks. To check for leaks, apply a solution of soap suds to
all connections and joints or check by one of the methods listed in Appendix D of ANSI Z223.1/NFPA 54 (latest edition) Natural Fuel Gas Code. DO NOT USE AN OPEN FLAME OF ANY KIND TO TEST FOR LEAKS.
rev: 11/15/063
SECTION 6: INSTRUCTIONS FOR PRESSURE TEST GAUGE CONNECTION
6.1. Supply Pressure: Installer to provide a 1/8" N.P.T. plugged tapping, accessible for test gauge connection immediately
upstream of the gas supply connection to the heater.
6.2. Manifold Pressure: Turn gas valve to "OFF" position. Remove 1/8" plug from manifold downstream from the valve and
connect 1/8" nipple to the tapped hole. Connect gauge to nipple. Turn on the gas supply.
6.3. With the main burner operating, check burner manifold pressure using a water manometer (see Table 4 on page 4 for
correct setting pressures). If adjustment is required, remove cover screw of the appliance regulator. Using a small
screwdriver, turn adjustment screw clockwise to increase or counter-clockwise to decrease gas pressure to
burner. Replace cover screw.
6.4. Gauges which measure in pounds per square inch or ounces per square inch are not accurate enough to measure or
set the manifold pressure. Use a water manometer.
Table 4: Gas supply pressures
GAS TYPEMANIFOLD PRESSUREMINIMUM*MAXIMUM
Natural3.5" W.C. 5" W.C.14" W.C.
Propane 10" W.C.11" W.C.14" W.C.
*Minimum permissible gas supply pressure for purpose of input adjustment.
SECTION 7: INFORMATION FOR LP GAS FLOOR MODEL HEATERS ONLY
Heaters used with LP gas must be installed in accordance with the latest edition of the National Fuel Gas Code -NFPA54,
Standard for the Storage and Handling of LP Gas - NFPA 58, all state and local codes or the authority having jurisdiction.
See Section 7.1 “LP models only - Regulator and hose assembly instructions” on page 5 for specific LP connection information.
The heater must be connected to the tank or cylinder by a UL Listed hose assembly or hard piping. A 10 foot assembly of UL
Listed hose is available from Sunstar under Part No. 3052200. A single stage LP gas regulator (operation range: 10-150
PSIG inlet and 11.0" W.C. outlet) having a POL fitting with an excess flow valve is included with each hose assembly Part
No. 3052400.
The hose assembly must be visually inspected prior to each use of the heater. If it is evident there is excessive abrasion or
wear, or the hose is cut, it must be replaced prior to the heater being put into operation. The replacement hose must a UL
Listed hose assembly.
The volume of a given quantity of liquid LP gas in a container is directly related to its temperature. As a result, the vaporization rate of a tank or cylinder will decrease as the temperature drops and as the percentage of liquid in the container
becomes smaller. Table 5 on page 4 shows the approximate vaporization rate of a 100 lb. cylinder.
Table 5: Maximum Continuous Flow in BTU/Hr. At Various Temperatures (Degrees F)
Lbs. of Propane in
Cylinder
100167,000214,000277,000300,000
80137,000180,000214,000236,000
60109,000140,000176,000197,000
40**105,000131,000141,000
30****107,000118,000
20oF40oF60oF70oF
** Rate of vaporization drops below the heater input rate.
4
RCH100 Installation and Operation Instructions
WARNING: Due to the continuous length of time the heater might be in operation, a 100 lb. LP gas
cylinder may not be sufficient in size. Manifolding several cylinders together is a practical way of
increasing the time of operation of these heaters. Operation of the heater with insufficient sized cylinders or when the liquid level becomes too low will result in poor heater performance and can
cause sooting. Consult your LP gas dealer for proper sizing of container.
Always turn the gas off at the tank or cylinder when the heater is not in use. When in operation, keep the heater a safe distance from the LP gas container and combustible materials as indicated on the heater and in the instructions. Fasten LP
cylinders securely so they cannot be knocked over.
When the heater is to be stored indoors, the connection between the propane supply cylinder(s) and the heater must be disconnected and the cylinder(s) removed from the heater and stored in accordance with the Standard for the Storage and
Handling of Liquefied Petroleum Gases, ANSI/NFPA 58 and CSA B149.1, Natural Gas and Propane Installation Code.
7.1. LP models only - Regulator and hose assembly instructions
WARNING
EXPLOSION HAZARD
High gas pressure will cause an
explosion.
Regulator must be connected to LP
gas cylinder. Maximum operating
pressure 1/2 PSI or 14 W.C.
Failure to do so may result in death,
serious injury or property damage.
7.1.1. Attach the POL fitting on the regulator to the LP gas tank / cylinder as shown in Figure 2 ”Regulator and hose
assembly” on page 6. Use a wrench to tighten the connection.
Note:
This fitting has left hand threads (like a gas barbecue and tank). Screw the POL fitting counter-clockwise.
CAUTION: DO NOT try to overtighten this connection. Overtightening may damage the “Excess flow control safety device” in
the POL fitting regulator.
7.1.2. Remove the plastic cap from the end of the 3/8” flare fitting. Connect the 3.8” flare swivel nut on the end of the regulator/hose assembly to the 3/8” flare tube fitting on the burner assembly, as shown in Figure 2 ”Regulator and
hose assembly” on page 6. Use two wrenches to tighten this connection, screwing the swivel nut clockwise onto the
supported 3/8” flare fitting.
7.1.3. After all the connections are made, they must be checked for leaks prior to operation. The following instructions
describe the leak checking procedure.
i.Make sure the control knob on the heater is turned to “OFF” prior to opening the valve on the LP tank/cylinder.
ii.Open the tank/cylinder valve fully (turn tank knob counterclockwise). Apply a rich soap and water solution to the POL
fitting into the tank/cylinder as well as the 3/8” flare swivel fitting at the heater. Bubbles indicate leaks which must be
fixed before the heater is operated.
iii.Tighten the joints to stop any leaks. Repeat steps i. and ii. after any tightening. If you are unable to stop the leaks, DO
NOT operate the heater. Contact your local LP dealer.
rev: 11/15/065
Figure 2: Regulator and hose assembly
10 ft min.
ON OFF
TURN BY HAND ONLY
NEVER USE TOOLS
FROM PILOT POSITION
SLIGHT PUSH TO
TURN OFF
FULL PUSH TO
LIGHT
3/8 Flare swivel nut
burner assembly
3/8 Flare fitting x 1/2 NPT
SECTION 8: VENTILATION AND COMBUSTION AIR
POL fitting
Regulator assembly
WARNING
FIRE HAZARD
Never use an open flame
to check for gas leaks.
DO NOT operate a heater
that has a leak
Any leaks must be repaired
before use.
Failure to do so may result
in death, serious injury or
property damage.
To LP gas
Cylinder or
tank
WARNING
POISON HAZARD
Do not restrict air. Poisonous
Carbon monoxide will be
produced.
Minimum ventilation 418 cfm.
must be provided.
Failure to do so may result
in death or serious injury.
This heater requires ventilation in the building to dilute the products of combustion and provide fresh air for combustion.
The minimum recommended vent flow required is 418 cfm.
The combustion air enters through the heater base and must
heater base. All ventilation in the building must be at a level above the height of the heater.
6
not be restricted. DO NOT block or enclose any part of the
RCH100 Installation and Operation Instructions
SECTION 9: HANGING INSTRUCTIONS FOR RCH100-9B
The RCH100-9B model is supplied with a suspension ring accessory and tip-over switch. Please see Figure 3 ”RCH100-9B
Suspension Assembly” on page 7 for the approved method for suspending the RCH100-9B. The suspended weight of the
heater is 40lb.
Figure 3: RCH100-9B Suspension Assembly
3 x 3/8 Suspension holes
#10-24 Screws &
Locknuts (4 each)
Suspension Leg
(2 each)
1/4-20 Screws &
Locknuts (4 each)
Upper Suspension Ring
Closed loop
hardware
Tilt Switch
Heater Rear View
The RCH100-9B heater is equipped with a tip-over switch as standard, the tip-over switch is connected to the thermocouple
and will safely turn off the heater if it is tipped between 25 and 40 degrees from the vertical in any direction. To reset the
tip-over switch the heater must be returned to its vertical upright position. See Figure 4 ”Tip-over Switch Details” on page 7
for details of the tip-over switch connection.
Thermocouple #K16JA18 Junction Block (from
gas control arm)
rev: 11/15/067
Figure 4: Tip-over Switch Details
Weld Nut (from
shroud asm.)
Blue
Blue
Tilt Switch
LH Shroud Asm.
#8x3/4 Screw (from
switch asm.)
SECTION 10: LIGHTING AND SHUTDOWN INSTRUCTIONS
10.1. MODELS WITH IGNITION SUFFIX "-6C"
10.1.1. Turn gas control knob to "OFF" position. Allow 5 minutes for any gas to escape before lighting.
10.1.2. Turn gas control knob to "PILOT" position. Push down on gas control knob and light the pilot with a match. (See Figure 5 ”Pilot lighting hole location” on page 8). Hold this knob down for approximately 60 seconds after lighting the
pilot.
10.1.3. When the gas control knob is released, the pilot should continue to burn. If the pilot goes out, repeat Steps 1 and 2
again. Close the pilot hole swivel door after the pilot is lit.
10.1.4. Push the knob down slightly and rotate the gas control knob from "PILOT" to "ON". The main burner will ignite.
10.1.5. If the main or pilot burners extinguish, depress and turn the gas control knob to the "OFF" position, wait 5 minutes
and repeat the above lighting procedure.
CAUTION: DO
NOT OPERATE MAIN BURNER AT ANY SETTING LESS THAN FULL "ON" POSITION. SOOTING WILL OCCUR!
10.2. MODELS WITH IGNITION SUFFIX "-9A" and “-9B”
10.2.1. Turn gas control knob to "OFF" position. Allow 5 minutes for any gas to escape before lighting.
10.2.2. Turn gas control knob to "PILOT" position. Push down on gas control knob and light the pilot with a match. (See Figure 5 ”Pilot lighting hole location” on page 8.) Hold this knob down for approximately 60 seconds after lighting the
pilot.
10.2.3. When the gas control knob is released, the pilot should continue to burn. If the pilot goes out, repeat Steps 1 and 2
again. Close the pilot hole swivel door after the pilot is lit.
10.2.4. Rotate the gas control knob from "PILOT" to "ON". The main burner will ignite.
10.2.5. If the main or pilot burners extinguish, depress and turn the gas control knob to the "OFF" position, wait 5 minutes
and repeat the above lighting procedure.
10.2.6. Turn the temperature control knob to the desired setting.
CAUTION: DO
NOT OPERATE MAIN BURNER AT ANY SETTING LESS THAN FULL "ON" POSITION. SOOTING WILL OCCUR!
Figure 5: Gas control knob setting position
Suffix -6C
ON
PILOT
NEVER USE TOOLS
ONOFF
TURN BY HAND ONLY
TURN OFF
FULL PUSH TO
SLIGHT PUSH TO
FROM PILOT POSITION
LIGHT
Control
OFF
ON
ONOFF
PILOT
TURN BY HAND ONLY
NEVER USE TOOLS
SLIGHT PUSH TO
FROM PILOT POSITION
CorrectIncorrect
Figure 6: Pilot lighting hole location
Pilot Lighting Hole
TURN OFF
LIGHT
FULL PUSH TO
OFF
Suffix -9A & 9B
Control
O
T
L
ON
T
O
L
I
OFF
P
I
P
OFF
ON
CorrectIncorrect
Swivel Door
8
RCH100 Installation and Operation Instructions
SECTION 11: CLEANING AND ANNUAL MAINTENANCE
This heater must be cleaned and serviced at least once before the start of each heating season or at any time the infrared
emitter show signs of collecting any foreign material on its surface. Maximum heating efficiency and clean combustion will
be maintained by keeping the emitter and burner clean. To clean the heater follow these instructions:
11.1. Turn off the gas supply to the heater.
11.2. Remove and clean the burner.
11.2.1. Remove the front cross brace and radiation shield from heater.
11.2.2. Disconnect the pilot burner and pilot shield from burner assembly. Rotate the swivel clamp (at the bottom of the
burner) away from the brass orifice holder.
11.2.3. Lower and remove the complete gas control arm from the heater.
11.2.4. Remove the four (4) nuts from each burner alignment bracket.
11.2.5. Lower the burner and remove from the heater.
11.2.6. Remove four (4) pan head screws holding burner cap in place.
11.2.7. Burner ports are formed by grooves on underside of burner cap; burner ports may be cleaned with a wire brush.
11.2.8. Removal of burner cap also makes mixing tube of burner accessible for cleaning with a round wire brush.
11.2.9. After cleaning, re-assemble burner cap on burner base with the four (4) pan head screws.
11.2.10.Re-install the Burner control arm and remaining components in reverse order.
11.3. If the emitter shows any accumulation of material in the ports, remove the heater top and the expanded metal guard
to expose the emitter and use a high pressure air hose to blow the ports clean. If this does not clean the holes, remove
the four (4) screws holding the emitter to its mounting ring and remove the emitter so that it can be cleaned both
inside and out with a wire brush and then blown out with a high pressure air hose.
11.4. Inspect the pilot burner and remove any foreign material with a brush or an air hose.
11.5. Reassemble the heater, test all connections for leaks and test the heater to be sure it is now operating properly.
Figure 7: Burner swivel retainer detail
Main Burner
Assembly
Control Arm Assembly
Swivel Clamp
Main Burner
Orifice
SECTION 12: REPLACING PARTS
At all times when parts are being replaced, ensure that both gas and electrical supplies are disconnected. Various parts are
available from the factory for replacement by a licensed service person. Refer to exploded parts guide in Section 12 for all
replacement parts.
Date of Installation _______________________
Heater Model Number RCH100 _____ - ______N = Natural Gas, L = Propane Gas
Heater Serial Number _____________________
rev: 11/15/069
SECTION 13: REPLACEMENT PARTS LIST - RCH100
Table 6: Replacement parts
ITEM
No.
203333080Nipple 1/2 x 2 - 1/2”1
302127110Nut, Hex 5/16-181
402167040Locknut, #8-32 KEPS4
502166060PHMS, #8-32 x 3/4”4
602167020Locknut, #10-24 KEPS5
702155060HWHMS, #10-24 x 1/2”12
802192010HWHSMS, #10 x 1/2”4
902152010HHTCS, #10-24” x 3/8”2
1004362050Heat Exchanger Assembly1
1104593050Guard, Expanded Metal1
1243901000Head, 15” dia (top of heater)1
1343901980Head 15” dia. (upper base)1
1443901990Head 15” dia (lower base)1
1543902050Base Shroud Assembly - LH2
1643904000Brace, Cross1
1743905000Shield, Radiation1
1841357030Instruction Manual (Not Shown)1
1943633060Burner Asssembly (complete w/cap)1
2043633005Burner Sub-Assembly1
2141859000Burner Cap1
2243903000Burner Bracket4
2343637050Pilot Shield Assembly (outer)1
2443900010Control Arm Complete-LP Gas (Suffix L6C)1
2543900020Control Arm Complete-NG Gas (Suffix N6C)1
2603258910Main Burner Orifice-LP Gas (7/64”)1
2703258120Main Burner Orifice-NG Gas (#12)1
2803399030Pilot Burner Assembly - LP Gas (#J129DDA4212)1
2903399020Pilot Burner Assembly - Nat Gas (#J129DDA3223)1
3003345020Pilot Orifice ftg - LP Gas (#Y90AA4212)1
3103345010Pilot Orifice ftg - Nat Gas (#Y90AA3223)1
3203437000Pilot Burner Less fittings (#J129DDA-ID)1
3303401030Thermocouple (#K16BA18)1
33a03401070Thermocouple with tip-over switch junction block (#K16JA-24)1
3430091010Gas Valve (White Rodgers #764-2)1
3530241010Male Fitting 3/8 Flared Tube x 1/2 MPT-LP Gas1
3641799010Pilot Tubing1
3742889010Orifice Fitting 9/16-18 UNF x 1/2NPT1
3803307100Regulator, 1/2 x 1/2 NPT (#RV48)-Nat Gas1
3903333140Nipple, 1/2 x 41
PART NO.DESCRIPTIONQUANTITY
10
RCH100 Installation and Operation Instructions
Table 6: Replacement parts
ITEM
No.
39a03333080Nipple 1/2 x 2-1/2 - Nat Gas1
4003336080Tee 1/21
4103338130Bushing 1/2 x 1/81
4203339020Pipe Plug 1/8 (pressure tap)1
4330522000Hose & Regulator Assembly - LP Gas (Not Shown)1
4430523000Hose Assembly 3/8” x 120” - LP Gas (Not Shown)1
4530524000Regulator, POL x 3/8 - LP Gas (Not Shown)1
4643900030Control Arm Complete - LP Gas (Suffix L9A)1
4743900040Control Arm Complete - Nat Gas (Suffix N9A)1
4830528030Adapter, Extension 1/2FPT x 1/2MPT - Nat Gas1
4930640000Gas Valve (Robertshaw) LP Gas @ 10” WC1
5030640010Gas Valve (Robertshaw) Nat Gas @ 3.5” WC1
5141870050Bulb Retainer1
5243137020Pilot Tubing (Robertshaw)1
5303841020Tip-Over Switch (RCH100-9B only)1
PART NO.DESCRIPTIONQUANTITY
MODEL NUMBER SUFFIXES
N - Natural Gas
L - LP Gas
6 - 100% Gas Shutoff Control - Manually Operated (Baso valve)
6C - 100% Gas Shutoff Control - Manually Operated (White-Rodgers valve)
9A - 100% Gas Shutoff Control - Thermostatically Operated (Robertshaw Valve)
9B - 100% Gas Shutoff Control - Thermostatically Operated (Robertshaw Valve)
rev: 11/15/0611
35
46
46a
52
51
48
Natural & Propane Gas
47
Control
Model Suffixes: N9A & L9A
47a
N9B & L9B
38
39a
34
29
32 33
49 50
2
Figure 8: Replacement parts
31
33a
26 27
37
41 42
40
29 31
33a
32 33
36
27
37
41 42
3
12
10
11
Natural Gas
25
Control
PModel Suffix: N6C
15a
15
53
40
39
13
1
23
7
6
8
22
21 4
6
5
3028
33 32
17
9
LP Gas
Control
Model Suffix: L6C
33a
16
36
7
35
24
34
14
39
7
20
19
26
15
15a
37
41 42
40
IMPORTANT
PLEASE ORDER BY PART NUMBER - NOT BY ITEM NUMBER. ALSO REFER TO COMPLETE MODEL NUMBER WHEN ORDERING. ALL REPLACEMENT PART PRICES AVAILABLE WHEN ORDERING.
12
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.