Sun Microsystems 6900, 6910, 3910, 3960, 3900SL Site Preparation Manual

...
Sun Microsystems, Inc. 4150 Network Circle Santa Clara, CA 95054 U.S.A. 650-960-1300
Sun StorEdge™3900 and 6900
Part No. 816-5256-10 July 2002, Revision A
Send comments about this document to: docfeedback@sun.com
Copyright 2002Sun Microsystems, Inc.,4150 NetworkCircle, SantaClara, California95054, U.S.A.All rightsreserved. Sun Microsystems, Inc.has intellectualproperty rightsrelating to technology embodied in the productthat isdescribed inthis document.In
particular,and without limitation, these intellectual property rightsmay includeone ormore ofthe U.S.patents listedat http://www.sun.com/patents and one or moreadditional patentsor pendingpatent applicationsin theU.S. andin othercountries.
This document and the productto whichit pertainsare distributedunder licensesrestricting their use, copying, distribution, and decompilation. No part of the product orof thisdocument maybe reproducedin any form by any means without prior written authorization of Sun and its licensors, if any.
Third-partysoftware, includingfont technology,is copyrighted and licensed fromSun suppliers. Parts of the product maybe derivedfrom BerkeleyBSD systems,licensed fromthe University of California. UNIX is a registered trademarkin
the U.S. and in other countries, exclusively licensed throughX/Open Company,Ltd. Sun, Sun Microsystems,the Sunlogo, AnswerBook2,Sun StorEdge,StorTools,docs.sun.com, SunEnterprise, SunFire, SunOS, Netra, SunSolve
and Solaris aretrademarks, registeredtrademarks, or service marks of Sun Microsystems, Inc. inthe U.S.and othercountries. AllSPARC trademarks are usedunder licenseand aretrademarks orregisteredtrademarks ofSPARCInternational, Inc.in theU.S. and other countries. Productsbearing SPARCtrademarks arebased uponan architecturedevelopedby SunMicrosystems, Inc.
All SPARCtrademarks areused underlicense andare trademarks or registered trademarksof SPARCInternational, Inc.in theU.S. andin other countries. Products bearingSPARCtrademarks arebased upon an architecture developedby SunMicrosystems, Inc.
The OPEN LOOK and Sun™ Graphical User Interface was developed bySun Microsystems,Inc. forits usersand licensees. Sun acknowledges the pioneering effortsof Xeroxin researchingand developing the concept of visual orgraphical userinterfaces forthe computerindustry.Sun holds a non-exclusive license fromXerox tothe XeroxGraphical User Interface, which license also covers Sun’s licensees who implement OPEN LOOK GUIs and otherwise comply with Sun’s written license agreements.
Use,duplication, ordisclosure bythe U.S.Government is subject to restrictionsset forthin theSun Microsystems, Inc.license agreementsand as providedin DFARS 227.7202-1(a) and 227.7202-3(a) (1995), DFARS 252.227-7013(c)(1)(ii) (Oct.1998), FAR12.212(a)(1995), FAR52.227-19,or FAR52.227-14 (ALTIII), asapplicable.
DOCUMENTATION IS PROVIDED "AS IS" AND ALL EXPRESS OR IMPLIED CONDITIONS, REPRESENTATIONS AND WARRANTIES, INCLUDING ANY IMPLIED WARRANTYOF MERCHANTABILITY,FITNESS FORA PARTICULARPURPOSE ORNON-INFRINGEMENT, ARE DISCLAIMED, EXCEPT TO THE EXTENT THAT SUCH DISCLAIMERS ARE HELD TO BE LEGALLY INVALID.
Copyright 2002 Sun Microsystems, Inc.,4150 NetworkCircle, SantaClara, California95054, Etats-Unis.Tousdroitsréservés. Sun Microsystems, Inc.a lesdroits depropriété intellectuels relatantsà latechnologie incorporéedans leproduit quiest décritdans ce
document. En particulier,et sans la limitation, ces droits depropriété intellectuelspeuvent inclureun ou plus des brevetsaméricains énumérés à http://www.sun.com/patentset unou lesbrevets plussupplémentaires ou les applications de brevet enattente dansles Etats-Uniset dans les autres pays.
Ce produit oudocument estprotégé parun copyrightet distribuéavec deslicences quien restreignentl’utilisation,la copie,la distribution,et la décompilation. Aucune partie de ce produit oudocument nepeut êtrereproduitesous aucuneforme, parquelquemoyen quece soit,sans l’autorisation préalable et écrite de Sun et de ses bailleurs delicence, s’ily ena.
Le logiciel détenu par des tiers, et qui comprendla technologierelative auxpolices decaractères, est protégépar uncopyright etlicencié pardes fournisseurs de Sun.
Des parties de ce produitpourront êtredérivées des systèmes Berkeley BSD licenciés par l’Université de Californie. UNIX est une marque déposée aux Etats-Unis et dans d’autres payset licenciéeexclusivement parX/Open Company,Ltd.
Sun, Sun Microsystems,le logoSun, AnswerBook2,Sun StorEdge,StorTools,docs.sun.com, SunEnterprise, SunFire, SunOS, Netra, SunSolve, et Solaris sont des marquesde fabriqueou desmarques déposées,ou marquesde service, de Sun Microsystems,Inc. auxEtats-Unis etdans d’autrespays. Toutesles marquesSPARCsont utilisées sous licence et sont des marques defabrique oudes marques déposées de SPARC International, Inc. aux Etats-Unis et dans d’autres pays.Les produitsportant lesmarques SPARCsont baséssur unearchitecturedéveloppée par Sun Microsystems,Inc.
Toutes les marquesSPARCsont utiliséessous licenceet sontdes marquesde fabrique ou des marquesdéposées deSPARCInternational, Inc. aux Etats-Unis et dans d’autrespays. Lesproduits protantles marques SPARCsont baséssur unearchitecture développéepar Sun Microsystems,Inc.
L’interfaced’utilisation graphique OPEN LOOK et Sun™ a été développéepar SunMicrosystems, Inc.pour sesutilisateurs etlicenciés. Sun reconnaîtles effortsde pionniersde Xeroxpour la rechercheet ledéveloppment duconcept desinterfaces d’utilisationvisuelle ougraphique pour l’industrie de l’informatique. Sun détient une license non exclusive do Xerox surl’interface d’utilisationgraphique Xerox,cette licence couvrant également les licenciées de Sun qui mettent en place l’interfaced ’utilisationgraphique OPENLOOK etqui enoutre seconforment aux licences écrites de Sun.
LA DOCUMENTATION EST FOURNIE "EN L’ÉTAT" ET TOUTES AUTRES CONDITIONS, DECLARATIONS ET GARANTIES EXPRESSES OU TACITES SONT FORMELLEMENTEXCLUES, DANSLA MESUREAUTORISEE PARLA LOIAPPLICABLE, YCOMPRIS NOTAMMENT TOUTE GARANTIE IMPLICITE RELATIVE A LA QUALITE MARCHANDE, A L’APTITUDE A UNE UTILISATION PARTICULIERE OU A L’ABSENCE DE CONTREFAÇON.
Please
Recycle

Contents

Planning Overview 1 Preinstallation Worksheet 1 Customer Obligations 3 Local Facility Safety 3
Handling Precautions 3 Secure Installation Requirements 4 Placement of a Sun Product 4
Facility Requirements 4
Environmental Specifications 5 Electrical and Power Specifications 5 Physical Specifications 6
Physical Dimensions 7 Clearance and Service Access 7
Cabling Requirements 9
iii
iv Sun StorEdge 3900 and 6900 Series 1.1 Site Preparation Guide • July 2002

Site Preparation and Planning

This manual describes the facility planning requirements for installing a Sun StorEdge™ 3900 or 6900 series system.
To determine the total components and storage systems your shipment will include, consult your local Sun sales representative.

Planning Overview

Follow the guidelines as outlined in this document when planning your installation.
“Customer Obligations” on page 3
“Local Facility Safety” on page 3
“Facility Requirements” on page 4
“Cabling Requirements” on page 9
For a product overview and installation instructions, refer to the Sun StorEdge 3900 and 6900 Series Version 1.1 Installation Manual. This document and a broad selection
of other Sun system documentation is located at the following web sites:
http://docs.sun.com/documentation

Preinstallation Worksheet

This worksheet is for gathering and recording the information required to successfully install a Sun StorEdge 3900 or 6900 series. Use this worksheet to preplan the data and Ethernet connections from the data host and Storage Service Processor.
1
Note – The number of IP addresses necessary for your installation depends on the
configurations you select. See the Sun StorEdge 3900 and 6900 Series 1.1 Reference and Service Manual for the number of IP addresses necessary for each of the supported
configurations.
Item Management Host Application Host TFTP Host
Host ID
Host name
Host IP address
Gateway IP address
Array IP address
Array name
TFTP host address
OS/patch revision level
Primary application
StorToolsrelease
Legend:
Required field
Optional field
Not applicable
2 Sun StorEdge 3900 and 6900 Series 1.1 Site Preparation Guide • July 2002

Customer Obligations

The customer is obliged to inform Sun Microsystems, Inc. of any and all ordinances and regulations that affect the installation. The customer is responsible for meeting all government codes and regulations concerning facilities. The customer is also responsible for compliance with the following requirements:
1. All local, national, and international codes covered in this specification. The subjects covered include fire and safety, building, and electrical codes.
2. Document and inform Sun Microsystems, Inc. of any deviations from this specification.

Local Facility Safety

Install the Sun StorEdge 3900 and 6900 series systems in accordance with the local safety codes and regulations at the facility site. Make sure you read the safety precautions in the Sun StorEdge 3900 and 6900 Series 1.1 Regulatory and Safety Compliance Manual. The following sections contain additional safety information for the local facility:
“Handling Precautions” on page 3
“Secure Installation Requirements” on page 4
“Placement of a Sun Product” on page 4
Note – Do not make mechanical or electrical modifications to the equipment. Sun
Microsystems, Inc. is not responsible for regulatory compliance of a modified Sun product.

Handling Precautions

Caution – A fully configured storage system cabinet can weigh in excess of 1400
pounds (627 kg). Any floor that this system will cross must be able to withstand this load.
3
The cabinet is equipped with wheels so that you can move it. Use enough personnel when moving the cabinet, especially on sloping loading docks and ramps, to gain access to a raised computer room floor. Move the cabinet slowly and deliberately, and make sure the floor is free of foreign objects and cables that the cabinet could roll over.
All personnel who are moving the cabinet should wear protective footwear.

Secure Installation Requirements

To minimize personal injury in the event of a seismic occurrence, you must securely fasten the cabinet to a rigid structure extending from the floor to the ceiling, or from the walls, of the room in which the cabinet is located.
Install the cabinet on a level surface. At each corner, on the base of the cabinet, are adjustable nonskid pads. These must be extended when the cabinet is installed to prevent the cabinet from rolling. These pads are not to be used to level the cabinet.

Placement of a Sun Product

If you have ordered a Sun StorEdge 3960 or 6960 series without the second cabinet, make sure you allow enough room to install a second cabinet in the event that you want to expand your system.
Do not block or cover the openings of your Sun product. Never place a Sun product near a radiator or heat register. Failure to follow these guidelines can cause overheating and affect the reliability of your Sun product.
Air cools the Sun StorEdge 3900 and 6900 series cabinets from front to back. Air enters at the front, circulates, and is expelled at both the top and bottom rear of the unit. The front and rear door clearances provide sufficient space for cooling. See
TABLE 5 and TABLE 6 for specific clearance specifications.

Facility Requirements

These sections contain the following information about the facility requirements for the Sun StorEdge 3900 and 6900 series:
“Environmental Specifications” on page 5
“Electrical and Power Specifications” on page 5
4 Sun StorEdge 3900 and 6900 Series 1.1 Site Preparation Guide • July 2002
“Physical Specifications” on page 6

Environmental Specifications

TABLE1 Facility Environmental Specifications
Specifications Operating Nonoperating
Temperature 41˚F to 95˚F (5˚C to 35˚C) -41˚F to 140˚F (-20˚C to 60˚C) Relative humidity 20% to 80% RH, noncondensing
80.6˚F (27˚C) maximum wet bulb
Altitude -1000 to 10,000 feet
(-305 to 3,048 meters)
Avoid temperature extremes and keep the work area clean. Maintain the operating conditions described the following table. The storage system should be in a computer room environment that provides control over environmental factors such as temperature, humidity, and airborne dust. A computer room installation can also help protect equipment from fire, flood, or other danger originating in the building.
TABLE2 Facility Environmental Specifications
5 to 95% RH noncondensing with maximum gradient 10% per hour
-1000 to 40,000 feet (-305 to 12,192 meters)
Environmental Factor Ambient Temperature Range Ambient Relative Humidity
Operating 70˚F to 73.5˚ F (21˚C to 23˚C) 45% to 50%
The operating environmental limits in
TABLE 1 reflect what the systems have been
tested to, in order to meet all functional requirements. The optimum operating condition in
TABLE 2 is the recommended operating environment. Operating
computer equipment for extended periods of time at or near the temperature or humidity extremes is known to significantly increase the failure rate of hardware components. In order to minimize any chance of down-time due to component failure, it is strongly recommended that customers plan and use the optimal temperature and humidity ranges.

Electrical and Power Specifications

All Sun StorEdge 3900 and 6900 series require two independent power sources. Each storage system cabinet has two power conditioners (distribution) for redundancy, which are mounted in the base of the cabinet. To maintain the power redundancy, each conditioner must be connected to independent power sources. power required for each conditioner.
TABLE 3 lists the
5
TABLE3 Power Specifications for the System Cabinet
Specification Rating
AC voltage rating 200 to 240 VAC AC voltage range 180 to 264 VAC Frequency range 47 to 63 Hz Current at 240 VAC 32A Power consumption, maximum:
• Sun StorEdge 3910 system
• Sun StorEdge 3960 system
• Sun StorEdge 6910 system
• Sun StorEdge 6960 system
4.2 kW
8.4 kW
4.2 kW
8.4 kW
The following is recommended for all installations:
All AC mains and supply conductors to power distribution boxes for both the
cabinet system and the desktop system must be enclosed in metal conduit or raceway, when specified by local, national, and/or other applicable government codes and regulations. The supply conductors and power distribution boxes (or equivalent metal enclosure) must be grounded at both ends.
The supplied storage systems require voltages within minimum fluctuation. The
facilities voltage supplied by the customer/end user must maintain a voltage of not more than (+/-) 5%.
The customer facilities must provide suitable surge protection.

Physical Specifications

This section contains the physical requirements for the Sun StorEdge 3900 and 6900 series systems.
6 Sun StorEdge 3900 and 6900 Series 1.1 Site Preparation Guide • July 2002

Physical Dimensions

TABLE4 Storage System Physical Specifications
Subsystem Height Width Depth Weight
Sun StorEdge 3900SL storage system single cabinet
Sun StorEdge 3900SL storage system with expansion cabinet
Sun StorEdge 3910 storage system
Sun StorEdge 3960 storage system
Sun StorEdge 6910 storage system
Sun StorEdge 6910SL storage system
Sun StorEdge 6960 storage system
Sun StorEdge 6960SL storage system
Note: The values given in this table are for the maximum hardware configuration available including the Sun StorEdge expansion cabinet in both the Sun StorEdge 3900SL, 3960, 6960, and 6960SL storage systems.
75 in.
109.5 cm
75 in.
109.5 cm
75 in.
109.5 cm 75 in.
109.5 cm 75 in.
109.5 cm 75 in.
109.5 cm 75 in.
109.5 cm 75 in.
109.5 cm
23.9 in.
60.7 cm
47.8 in. 122 cm
23.9 in.
60.7 cm
47.8 in. 122 cm
23.9 in.
60.7 cm
23.9 in.
60.7 cm
47.8 in.
121.4 cm
47.8 in.
121.4 cm
37 in. 94 cm
37 in. 94 cm
37 in. 94 cm
37 in. 94 cm
37 in. 94 cm
37 in. 94 cm
37 in. 94 cm
37 in. 94 cm
1465 lb 665 kg
2855 lb 1295 kg
1465 lb
665 kg 2855 lb
1295 kg 1210 lb
549 kg 1210 lb
549 kg 2895 lb
1314 kg 2895 lb
1314 kg

Clearance and Service Access

Side access can be required for some service procedures. Refer to the Sun StorEdge
7
3900 and 6900 Series 1.1 Reference and Service Guide for specific service procedures.
TABLE5 Clearance and Service Access for Sun StorEdge 3910 and 6910 Series
Location For Service Access
Front 48 in.
122 cm
Rear 36 in.
92 cm
Left 36 in.
92 cm
Right 36 in.
92 cm.
TABLE6 Clearance and Service Access for Sun StorEdge 3960 and 6960 Series
Location For Service Access
Front 96 in.
244 cm
Rear 60 in.
153 cm
Left 60 in.
153 cm
Right 60 in.
153 cm
8 Sun StorEdge 3900 and 6900 Series 1.1 Site Preparation Guide • July 2002

Cabling Requirements

This section contains the cabling requirements for the Sun StorEdge 3900 and 6900 series. When cabling the system, make sure you follow these guidelines:
Keep power and interface cables clear of foot traffic. Route cables inside walls,
under the floor, through the ceiling, or in protective channels or raceways. Route interface cables (excluding fiber-optic cables) away from motors and other sources of magnetic or radio frequency interference.
Do not exceed cable length limitations. The following table gives the cable
specifications and lengths.
TABLE7 Cable Specifications
Cable Type Connector Maximum Length
Shielded Ethernet, 10/100BASE-T, category 5
Serial (available only to qualified field service representatives)
Power (220V) Standard n/a
The power cables are the standard ones shipped with the Sun StorEdge Expansion Cabinet. The cables that connect the two cabinets together are standard Fibre Channel cables.
RJ-45 328.084 ft. (100 m)
RJ-45 82.021 ft. (25 m)
9
10 Sun StorEdge 3900 and 6900 Series 1.1 Site Preparation Guide • July 2002