This manual applies to inverter SG2KTL-S, SG2K5TL-S SG3KTL-S, SG3K6TL-S,
SG4KTL-S, SG3KTL-D, SG3K6TL-D, SG4K6TL-D and SG5KTL-D. We hope that the
device will meet your satisfaction when you use it with your PV plant system.
Purpose
The purpose of this manual is to provide detailed product information and
instructions for the use of SG2KTL-S, SG2K5TL-S SG3KTL-S, SG3K6TL-S, SG4KTL-S,
SG3KTL-D, SG3K6TL-D, SG4K6TL-D and SG5KTL-D PV grid-connected inverter.
Related Documents
The manual cannot include complete information about the PV system. You will get
the additional information about other devices at www.sungrowpower.com or via
the webpage of device manufacturer.
Target Group
The manual is aimed at technical personnel who are responsible for inverter
installation and commissioning in the PV power system.
How to Use This Manual
Read this manual and other related documents before any work on the inverter.
Documents must be stored carefully and available at all times.
The contents of the manual will be periodically updated or revised due to the
product development. It is probably that there are changes of manual in the
subsequent inverter edition. The latest manual can be acquired via visiting web
page at www.sungrowpower.com.
I
Page 4
Symbols Explanation
This manual contains important safety and operational instructions that must be
accurately understood and followed during the installation and maintenance of the
equipment.
To ensure optimum use of this manual, note the following explanations of symbols
used.
DANGER indicates a hazard with a high level of risk which, if not avoided,
will result in death or serious injury.
WARNING indicates a hazard with a medium level of risk which, if not
avoided, could result in death or serious injury.
CAUTION indicates a hazard with a low level of risk which, if not avoided,
could result in minor or moderate injury.
NOTICE indicates a situation which, if not avoided, could result in
equipment or property damage.
NOTE indicates additional information, emphasized contents or tips to
help you solve problems or save time.
Symbols on the Inverter Body
Wait at least 10 minutes after disconnecting the inverter from the
utility grid and the PV input before touching any inner live parts.
Hot surface! Do not touch device hot surface when the device is
running.
II
Page 5
Read over the user manual before any work on the inverter!
The installation and service of the inverter unit can only be
performed by qualified personnel.
III
Page 6
Contents
About This Manual .......................................................................... I
11.1 Technical Data ..................................................................................................... 68
11.1.1 Single MPPT Inverter Data ................................................................................ 68
11.1.2 Double MPPTs Inverter Data ............................................................................ 72
11.2 Exclusion of Liability .......................................................................................... 76
11.3 About Us ................................................................................................................ 77
VI
Page 9
1 Safety Instructions
1.1 IMPORTANT SAFETY INSTRUCTIONS
SG2K5TL-S, SG3KTL-S, SG3K6TL-S, SG4KTL-S, SG4K6TL-D and SG5KTL-D inverter are
designed and tested in accordance with the international safety requirements. But
as with all electrical and electronic equipments, certain precautions should be
observed during installation, operation and maintenance work.
There is a risk of inverter damage or personnel injury!
Various interfaces are provided on the bottom of the inverter. Do not open
the enclosure at any time. Loss of any or all warranty rights may follow if
otherwise.
Operation or work performed incorrectly can result in damage to:
y
The life and well-being of the operator or a third party
y
The inverter and other properties that belong to the operator or a third party
To reduce the risk of injury and ensure the normal operation of the inverter, you
must read over and follow all the instructions, cautions and warnings.
All installation and electrical work must only be performed by qualified
personnel. They have
y been trained specially;
y already completely read through and understood the manual and other
related documents;
y been familiar with safety requirements for electrical system.
Technical personnel mentioned above may perform the following work:
y
Secure the inverter to the wall
y
Connect the inverter to the PV power system
y
Connect other devices to the PV power system
y
Commission the inverter
y
Maintain and service the inverter
1
Page 10
1 Safety Instructions User Manual
Before Installation
There is a risk of injury if the product is mishandled!
y Always follow the instructions in the manual when moving and
positioning the inverter.
y The weight of the equipment can cause injuries, serious wounds, or
bruising if mishandled.
During Installation
Prior to securing the inverter to the wall, it is crucial to make certain that the inverter
is not electrically connected.
System performance can be impaired by poor ventilation!
The equipment requires well ventilation during operation. It is essential to
keep the unit upright and nothing covering the heat sink to let the
equipment interior well cool down.
During Electrical Connection
Lethal voltage exists!
PV arrays will produce electrical energy when exposed to sunlight and thus
can cause an electrical shock hazard.
y Wiring of the PV arrays should only be performed by qualified personnel.
All cables must be firmly attached, undamaged, properly insulated and
adequately dimensioned.
2
Page 11
User Manual 1 Safety Instructions
During Inverter Operation
There is a risk of inverter’s damage or personal injury!
Do not disconnect DC connectors while the inverter is under AC load! First
de-energize the equipment from the dual power sources and then verify
that there is no voltage existing.
There is a risk of burns!
Avoid touching device hot parts (such as the heat sink) during operation.
Only the LED indicator panel and the optional DC switch can be touched
during inverter operation.
Maintenance and Service
y Any malfunction that may impair the inverter safety operation must be
repaired immediately before the inverter is restarted.
y Inverter contains no customer serviceable parts inside. Please contact
local authorized personnel if any service work is required.
Servicing of the device in accordance with the manual should never be
undertaken in the absence of proper tools, test equipments or the more
recent revision of the manual which has been clearly and thoroughly
understood.
3
Page 12
1 Safety Instructions User Manual
There is a risk of inverter damage or personal injury due to incorrect service
work!
Always keep in mind that the inverter is power supplied by dual power
source: PV arrays and utility grid.
Before any service work, observe the following procedures.
y Disconnect the inverter from the utility grid side first and then PV arrays;
y Wait at least 10 minutes for inner capacitors to discharge completely;
y Verify that no voltage and current existing with appropriate testing
devices.
Keep non-related persons away!
A temporary warning sign or barrier must be posted to keep non-related
persons away while performing electrical connection and service work.
Do not open the enclosure when the inverter is under voltage. There is a high likely
risk of explosion in very specific cases of malfunction. The enclosure will protect
persons and property from such an explosion, only if it is correctly sealed.
There is a risk of inverter damage if it is improperly serviced.
Use accessories and spare parts approved by the inverter manufacturer
only. Never modify the inverter or other components of the inverter. The
loss of any or all warranty rights may follow if otherwise.
There is a risk of inverter damage due to electrostatic discharge!
The printed circuit boards contain components sensitive to electrostatic
discharge. Wear a grounding wrist band when handling the boards. Avoid
unnecessary touch of the boards during replacement.
4
Page 13
User Manual 1 Safety Instructions
Others
The selected country settings can be changed by qualified personnel only!
Alternation of the country settings may cause a breach to the
type-certificate marking
All safety instructions, warning labels and nameplate on the inverter body:
y must be clearly visible;
y must not be removed, covered or pasted.
These regulations should also be followed:
y the regulations related to the electricity fed into grid;
y the safety instructions related to PV arrays;
y the safety instructions related to other electrical devices.
5
Page 14
A
k
2 Product Introduction
2.1 Intended Usage
SG2K5TL-S, SG3KTL-S, SG3K6TL-S, SG4KTL-S, SG4K6TL-D and SG5KTL-D (They will be
referred to as inverter hereinafter unless otherwise specified), single-phase without
transformer string inverter, is a crucial unit between the PV arrays and the utility grid
in the small-scaled PV power system.
Inverter is dedicated to converting direct current power generated by the PV
modules into alternating current, which conforms to parameters of local utility grid,
and feeds the alternating current into the utility grid. An example about intended
usage of the inverter is shown in Fig. 2-1.
Where the positive or negative terminal of PV strings needs to be grounded,
inverter cannot be connected to PV modules of this type.
L
N
D
PE
BC
Fig. 2-1 Application of Inverter to the PV Power System
Item Description Remar
A PV strings
B Inverter
Metering
C
device
6
Monocrystalline silicon; polycrystalline silicon and
thin-film of protection class II without grounding
SG2K5TL-S, SG3KTL-S, SG3K6TL-S, SG4KTL-S, SG4K6TL-D
and SG5KTL-D.
Meter cupboard with power distribution system
Page 15
User Manual 2 Product Introduction
k
Item DescriptionRemar
D Utility grid TT, TN
For TT utility grid, N line voltage to ground must be less than 30V.
Any other or additional usage other than the intended usage is not
permitted.
Inverter only accepts PV modules of Protection Class II as its input.
Inverter may only be connected to utility grid via distribution board. Local
loads (home appliance, lights, motor loads, etc.) cannot be connected
between the inverter and AC circuit breaker on the distribution board.
2.2 Product Description
2.2.1 Product Appearance
Fig. 2-2 Product Description
Item Name Description
1 LED indicator panel Indicate the working statues of the inverter.
2 DC terminals
3 DC switch (Optional)
4 RS485 terminal
5 AC terminal
7
There is a pair or two pairs of DC terminals
between PV arrays and inverter.
Optional component. It is designed for safely
disconnecting DC current.
It is provided for connecting LCD display panel,
WiFi or HEMU module.
Inverter feeds power to utility grid via this
terminal.
Page 16
2 Product Introduction User Manual
Item Name Description
6 Mounting rack It is used to hang inverter onto the backplate.
HEMU module mainly provides the following functions: zero export, LCD
display, partial export, reactive power control and so on.
As a human-computer interaction interface, the LED indicator on the inverter front
panel indicates the working statues of the inverter.
Fig. 2-4 LED Indicator Panel
Name Description
LED indicator
8
User can observe the indicator’s flashing color to get the current
state of inverter. Detailed definition is shown in Tab. 2-2.
Page 17
User Manual 2 Product Introduction
Tab. 2-2 Description of LED Indicator
State Description
Green&
Red
Green
Red Flicker once every 0.3 second
Flicker once in turn every 1
second
Flicker once every 0.2 seconds to
2 seconds ( The greater the
inverter current power, the
faster the green light flashing)
Non-running or Non-fault (For
example, the inverter is in standby
state.)
Inverter is running.
A malfunction happens, or protection
function triggers.
The red and green LEDs will be on at the same time when the inverter is
in the upgrade status. If the red and green LEDs are on at the same time
in other status, please contact the service provider for troubleshooting.
2.3 Technical Description
2.3.1 Circuit Description
Fig. 2-6 and Fig. 2-6 show the main circuit of inverter.
The inverter boost circuits raise DC input voltage. The MPP trackers ensure the
maximum power from PV arrays can be utilized. Then the inverter circuit converts
DC power to AC power. Meanwhile inverter is equipped with protective circuit to
guarantee its safety operation which can triggers the AC relay if required.
Additionally, inverter provides WiFi interface for communication.
Fig. 2-5 Main Circuit Diagram of single MPPT inverter
9
Page 18
2 Product Introduction User Manual
Fig. 2-6 Main Circuit Diagram of double MPPTs inverter
2.3.2 Functions Description
Inverter functions can be grouped as the following:
y
Conversion function
Inverter converts the direct current power into the alternating current power,
which conforms to the grid requirement of its installation country.
y
Data storage and display
Inverter archives essential data including running information and fault records.
y
Parameters configuration
Inverter provides various parameters configuration for optimal operation. You
can choose the type of country by APP, if you need a more professional setting,
please contact Sungrow.
y
Communication interface
WiFi module for connecting other monitoring devices to the PV system is
included.
y
Protection functions include
− short circuit protection
− grounding insulation resistance surveillance
− inverter output voltage surveillance
− inverter output frequency surveillance
− residual current protection
− DC injection of AC output current surveillance
− anti-islanding phenomena protection
− ambient temperature surveillance
10
Page 19
User Manual 2 Product Introduction
− DC over-voltage protection
− over-current protection
− over-temperature protection
2.3.3 Temperature-related Power Derating
The following graph shows the automatic reduction in output power in relation to
ambient temperature.
11
Page 20
2 Product Introduction User Manual
12
Page 21
User Manual 2 Product Introduction
*The derating curve shown in the graph above is obtained by the test in high
temperature environmental chamber.
−
13
Page 22
3 Unpacking and Storage
3.1 Unpacking and Inspection
The unit is thoroughly tested and strictly inspected before delivery. Although sturdy
packaging is used, damages may still occur during shipping.
y
Check the packing for any visible damages upon receiving.
y
Check the inner contents for damage after unpacking.
y
Check the completeness of the delivery contents according to the supplied
packing list.
If there are visible damages to the packaging or the inner contents, or something
missing, please contact the unit dealer.
Do not dispose of the original packaging. It is the best choice to store the inverter in
the original packaging.
Fig. 3-1 Single Inverter Packing
* The dimensions shown in the image here is for reference only.
Two nameplates are attached to one side of the inverter and the carton respectively.
They provide information on the type of inverter, the most important specifications,
marks of certification institutions, website and serial number which are available
and identified by Sungrow.
Fig. 3-2 Nameplate of Inverter
* Image shown here is for reference only. Actual product you receive may differ.
Item DescriptionItemDescription
SUNGROW logo and product
1
type
2 Technical data of inverter 4 Company name, website and origin
Tab. 3-1 Description of Icons on the Nameplate
Marks of certification institutions of
3
inverter
Icon Description
Do not dispose of the inverter with the household waste.
Refer to the corresponding instructions.
C-tick mark of conformity. The inverter is in compliance with
directives of C-tick.
CE mark of conformity. The inverter is in compliance with directives
of CE.
TUV mark of conformity.
The inverter is in compliance with directives of TUV.
15
Page 24
3 Unpacking and Storage User Manual
3.3 Delivery Contents
Fig. 3-3 Delivery Contents
Item Description
A Inverter unit
B It is used to mount the inverter onto the wall
C Expansion bolts for fastening the backplate onto concrete wall
D Fastener set for installing the inverter onto metal frame
E PV input connectors, including positive and negative connectors
F WiFi, for wireless communication(Optional)
G Quick user manual and CD
H Packing list and product test report
I Quality certificate
J T-type terminals. It is only for SG3K6TL-S/SG4KTL-S.
16
Page 25
User Manual 3 Unpacking and Storage
3.4 Storage of Inverter
If you do not install the inverter immediately, you should choose an appropriate
location to store it.
y
The unit must be stored in original packaging and the desiccant must be left in
the packaging.
y
The unit must be stored in a clean and dry place to protect against dust and
moisture.
y
The storage temperature should be always between -30 °C and +85 °C. And the
storage relative humidity should be always between 0 and 100%.
y
It is very important to keep the packaging away from chemicals. Otherwise it will
lead to corrosion.
y
During the storage time, check periodically for visible damages by rats. Replace
the packaging if necessary.
y
If there is more than one inverter to be stored, the maximum layers for original
paper packaging are five.
After long-term storage or decommissioning, local installer or Service
Dept. of Sungrow should perform a comprehensive test before
connecting the inverter into PV power system.
17
Page 26
4 Securing Inverter to the Wall
4.1 Selecting Installation Location
Selecting an optimal installation location for the inverter is decisive for its operating
safety as well as its expected efficiency and service life.
1. Take the load capacity of the wall into account. The wall (such as concrete wall or
metal structure) should be strong enough to hold the weight of the inverter over a
long period of time.
2. Install the unit where is accessible to install, electrical connect and service.
3. Do not install the inverter where
contains flammable materials or
flammable gas in the vicinity of the
unit installation site.
Flammable material or
gas near the installation
4. Do not install the unit on wall of
flammable materials.
18
Page 27
User Manual 4 Securing Inverter to the Wall
5. Install the unit at eye level for easy
button operation and display read.
6. It is suggested that the inverter be
installed vertically with upside up
for good heat dissipation.
7. Never install the inverter horizontally, or with a forward tilt or with a backward tilt
or even with upside down.
8. The inverter unit with IP65 can be installed indoors or outdoors.
19
Page 28
4 Securing Inverter to the Wall User Manual
9. The ambient temperature should
range from -25°C to 60°C. The power
output will reduce when the ambient
Max. ambient temperature:
+60°C
temperature exceeds 45°C.
10. The relative humidity of chosen
Min. ambient temperature:
-25°C
installation site should never exceed
100%. Moisture may result in corrosion
and damage to the internal device
components.
Max. relative humidity:
100%
11. Avoid exposing the inverter to direct sunlight, rain or snow to extend its service
life despite of IP65 rating. Shaded site of the building would be better.
12. Take enough space for
convection into consideration
during installation. For details,
see ”6.2 Distance between the
inverter and the
smartphone/router”.
20
Page 29
User Manual 4 Securing Inverter to the Wall
13. Do not install the inverter in a closed cabinet. Otherwise, the inverter will not
operate normally.
14. Do not install the inverter where children can reach.
15. Do not install the inverter in residential area. Noise can be produced during the
running of the inverter and may affect your daily life.
4.2 Moving Inverter to Installation Site
If the inverter is to be installed, remove the unit from the packaging and move it to
the chosen installation site. During the moving process, the instructions below
should be obeyed.
1. Beware of the weight of the inverter.
2. Grasp the equipment with both hands by means of handles.
3. Do not release the equipment unless it has been firmly secured to the wall.
4.3 Installation Procedure
Inverter is installed onto the wall by means of backplate in the packaging. If you
don’t use the supplied backplate, you can drill holes according to its dimension
below.
21
Page 30
4 Securing Inverter to the Wall User Manual
Fig. 4-1 Fastener(unit: mm)
Fig. 4-2 Dimensions of Expansion Bolt Set for Concrete Wall (unit: mm)
Fig. 4-3 Dimensions of Fastener Set for Metal Frame(unit: mm)
Please select the appropriate length of the expansion screw according to
the thickness of the wall insulation layer. The dimensions shown in the
image here is for reference only.
In the following, we will introduce how to secure the inverter to the wall using the
provided backplate.
Concr ete Wall
Step 1 Remove the backplate and expansion bolts from the packaging.
Step 2 WiFi connection.(If you purchase WiFi module)
1. Plug SolarInfo WiFi into the corresponding terminal under the inverter.
22
Page 31
User Manual 4 Securing Inverter to the Wall
2. Fasten the screws with appropriate torque.
Step 3 Screw a M5 screw onto the chosen concrete wall.
In order to avoid electrical shock or other injury, inspect if there is electricity
or plumbing installation before drilling holes.
Step 4 Fasten the backplate to the wall with the supplied expansion bolt set. The
torque for fastening the nut should be at least 10 Nm.
Step 5 Hang the inverter onto the backplate and lock the device.
23
Page 32
4 Securing Inverter to the Wall User Manual
The lock is an optional accessory. Users need to purchase it.
Metal Frame
Step 1 Remove the supplied backplate from the packaging.
Step 2 WiFi connection. (If you purchase WiFi module)
Step 3 Screw a M5 screw onto the chosen mental frame.
If the shape of the metal frame doesn’t fit the holes on the backplate, you
need to re-drill holes on the backplate at appropriate position according
to the chosen frame.
Step 4 Choose the best installation site according to the abovementioned
requirements. Fasten the backplate to the mental framel with the supplied
expansion bolt set. The torque for fastening the nut should be at least 10
Nm.
Step 5 Hang the inverter onto the backplate and lock the device.
24
Page 33
User Manual 4 Securing Inverter to the Wall
25
Page 34
5 Electrical Connection
5.1 General Safety Instruction
Once the inverter is firmly attached to the appropriate location, it can be connected
into the PV power system.
Prior to any electrical connection, keep in mind that the inverter has dual power
supplies. It is mandatory for technical personnel to wear personal protective
equipments: helmet, footwear and gloves during the electrical work.
Improper operation during the wiring process can cause fatal injury to
operator or unrecoverable damages to the inverter.
All electrical installations must be in accordance with local and national
electrical codes.
Only after being approved by the utility company and installed by qualified
personnel can you connect the inverter to the utility grid.
All cables must be firmly attached, undamaged, properly insulated and
adequately dimensioned.
These regulations should also be followed:
y The regulations related to the electricity fed into the grid
y The safety instructions related to the PV arrays
26
Page 35
User Manual 5 Electrical Connection
5.2 Terminals Description
All electrical terminals are located at the bottom of unit. Fig. 5-1 shows the
connection area.
Enough space should be kept for electrical connection at the bottom of
the inverter when choosing the installation site.
Fig. 5-1 Terminals Description
* Image shown here is for reference only. Actual product you receive may differ.
Tab. 5-1 Terminals Specification
Item TerminalsDescription
1 DC MC4 terminals for PV input.
2 WiFi --3 PE A second PE terminal
4 AC AC terminals to the power grid.
5.3 Overview of Electrical Connection
Electrical connections of the inverter include DC connection, AC connection and
communication connection.
27
Page 36
5 Electrical Connection User Manual
k
Fig. 5-2 Electrical Connection Diagram
Item DescriptionRemar
A AC circuit breaker
B Utility grid
C SolarInfo WiFi It is used for wireless communication.
D PV arrays
Used as a protective device during electrical
connection. User equips this device according to
the maximum output voltage and current.
Nominal line-to-neutral voltage of the utility grid is
230V.
-S series: one input area with one pair of terminals.
-D series: two input areas with two pairs of
terminals.
5.4 Connecting Inverter to AC Grid
The inverter is connected to the grid via 3 wires (L, N, and PE). Feeding power is
always single-phase via AC terminal at the bottom of the unit.
An appropriately sized AC circuit breaker is suggested as the protection equipment
in AC connection, as shown in Fig. 5-2.
5.4.1 AC Side Requirements
Only after being approved by the local grid company can you connect
the inverter to the grid.
Prior to connecting the inverter to the utility grid, verify whether the grid voltage
and frequency are within the range of inverter output parameters (refer to
Appendix). Consult the local grid company for solution if otherwise.
28
Page 37
User Manual 5 Electrical Connection
AC Side Circuit Breaker
An independent two-pole circuit breaker for the inverter must be installed at the
output side to ensure that the inverter can be securely disconnected under load.
Inverter Type Specification Recommended of AC Circuit Breaker
SG2KTL-S 25A
SG2K5TL-S 25A
SG3KTL-S 25A
SG3K6TL-S 25A
SG4KTL-S 32A
SG3KTL-D 25A
SG3K6TL-D 25A
SG4K6TL-D 32A
SG5KTL-D 32A
y It is not allowed for several inverters to use the same circuit breaker.
y It is not allowed to connect loads between the inverter and the circuit
breaker.
Residual Current Device
With an integrated universal current-sensitive residual current monitoring unit
inside, the inverter is able to distinguish the fault current from normal capacitive
leakage current. The inverter will disconnect immediately from the mains when a
fault current out of the limit value has been detected.
However if an external RCD or residual current breaker is mandatory, the switch
must be triggered at a failure current of 300mA or higher.
5.4.2 Assembling AC Cables to Connector
Inverter is equipped with water-proof direct plug-in connectors for AC connection,
which match AC terminals at the bottom of the inverter.
“L”, “N” and “PE” should be equipped with correctly colored cables for
distinguishing. Please refer to related standards for specific wiring color.
AC Cable Requirements
Select AC cable specifications and types considering the following facts:
29
Page 38
5 Electrical Connection User Manual
y
The grid impedance of the AC cable must correspond to the specification to
avoid unintended disconnection from the grid or derating of the output power.
y
The cable cross-sectional areas and recommended value are shown in the
following table, avoiding power loss in the cables of more than 1% of the
nominal power.
Layout type (inside wall, underground, free air etc.);
y
UV resistance and so on.
5.4.3 AC Wiring Procedure
Step 1 Loosen all four screws on the AC terminal lid and remove the lid.
Step 2 Unscrew Thread-Lock Sealing Nut, pull out the Waterproof Sealing Insert
from the opening.
Step 3 Strip off insulation layer of all AC cables. The length of strip insulation is
approximate 18mm.
30
Page 39
User Manual 5 Electrical Connection
k
No. DescriptionRemar
A Protective layer
Length of insulation to be
B
stripped off
C Insulation layer -
Step 4 Lead the AC cable through the Thread-Lock Sealing Nut, and the cable gland.
Step 5 Fix all cables to the corresponding terminals according to markings on the
Accepted cable external diameter ranges from
10mm to 14mm.
18 mm
connector with a screwdriver, especially the “PE” cable.
L and N line must not be swapped, otherwise it may permanently destroy
the inverter.
Step 6 Connect “PE” cable to the grounding electrode. Where there are multiple
inverters in the PV power system, connect “PE” cables of all inverters and the
mounting frame of PV arrays to the same copper bus bar, which may
establish equipotential connection.
Step 7 Pull cables outward to check whether they are firmly installed.
Step 8 Fix all four screws to the AC terminal lid. Insert the Waterproof Sealing Insert
back to AC opening and tighten the Thread-Lock Sealing Nut firmly to the
cable gland.
31
Page 40
5 Electrical Connection User Manual
Step 9
Make sure the AC and DC circuit breaker are disconnected.
Step 10 Connect phase cable and “N” cable to AC circuit breaker.
Step 11 Connect AC circuit breaker to utility grid.
Step 12 Make sure all AC cables are firmly installed.
5.5 Connecting Inverter to PV Arrays
Lethal voltage exists!
PV arrays produce electrical energy when exposed to light and thus can
create an electrical shock hazard. Wiring should only be performed by
qualified personnel.
Before connecting the PV arrays to the inverter, make sure that the
impedances between the positive terminal of the PV string and Earth and
the impedances between the negative terminal of the PV string and Earth
are larger than 200Kohm.
There is a risk of inverter damage! The following requirements should be met;
otherwise they will lead to loss of any and all warranty rights.
y Make sure that the maximum short circuit current of each DC input is less than
inverter allowable limit.
y Make sure that the maximum open voltage of each string is less than 1000V.
Voltage over 1000V can damage the inverter.
If the input line is changed, such as input line falls off, etc. You need to
reset the work mode.
5.5.1 PV Inputs Configuration
For -S series inverters, there’s one input area with one MPP tracker. They can be
configured in parallel mode only.
For –D series inverters, there’re two PV input areas, each owning its MPP tracker. The
32
Page 41
User Manual 5 Electrical Connection
two PV inputs can be configured in independent mode or parallel mode.
PV Configuration Mode-Independent Mode
For independent mode, the two PV inputs work independently, each with its own
MPPT. Therefore the two PV inputs can be different from each other in PV module
types, numbers of PV panels in PV string, tilt angles and orientation angle of PV
modules.
As shown in the following diagram, the inverter should be configured to
independent mode due to different orientation angle between the two PV inputs.
To make sure the maximum DC power, PV strings connected to
individual input area should have a homogenous structure, i.e. the
same type, identical tilt and identical orientation.
Type Area
SG3KTL-D
SG3K6TL-D
SG4K6TL-D
SG5KTL-D
Total DC
Input Power
Limit
DC1
3300W 600V
DC2 12A
DC1
3900W 600V
DC2 12A
DC1
4900W 600V
DC2 12A
DC1
5400W 600V
DC2 12A
33
Open-circuit
Voltage Limit
for Each Input
Short-circuit
Current Limit for
Each Input
12A
12A
12A
12A
Page 42
5 Electrical Connection User Manual
Only the current is limited for a single input and the power is not
limited.
PV Configuration Mode-Parallel Mode
For parallel mode, all PV strings with the same type, the same number of PV panels,
identical tilt and identical orientation in series can be connected to the same single
input area.
• SG3K6TL-S/ SG4KTL-S
Connect the 2 PV strings in parallel using T-type terminals and then connect them to
inverter DC input.
Type
SG3K6TL-S 3900 W 600V 20A
SG4KTL-S 4300 W 600V 20A
Total DC Input
Power Limit
Open-circuit
Voltage Limit
Short-circuit
Current Limit
To avoid input power unbalance of the two inputs or input
load-restriction, ensure the two PV input cables are of the same model.
All DC cables are equipped with water-proof direct plug-in connectors, which match
the DC terminals at the bottom of the inverter.
The positive and negative connectors are marked with polarity symbols
and should be equipped with correctly colored cable.
e.g. Red cable should be connected with DC positive terminal while the
blue one be connected with the negative.
DC Cable Requirements
Type Cross-Section
Area Range
SG2KTL-S/SG2K5TL-S/
SG3KTL-S
SG3K6TL-S/SG4KTL-S 2.5...6mm2 5…8mm 600 V
SG3KTL-D/SG3K6TL-D
/SG4K6TL-D/SG5KTL-D
2.5...6mm
2.5...6mm
2
2
Outer
Cable
Diameters
5…8mm 600 V
5…8mm 600 V
Max.
Withstand
Voltage
Max.
Withstand
Current
Same with
short-circuit
current.
Same with
short-circuit
current.
Same with
short-circuit
current.
35
Page 44
5 Electrical Connection User Manual
f
The DC cables must be flexible wires.
DC Connector Assembling Procedure:
Make sure that all the DC and AC cables to the inverter are not live before
you start the electrical work.
Step 1 Strip of
7mm insulation layer from all
DC cables.
Step 2 Assemble cable ends with crimp
contacts by crimping pliers.
Step 3 Lead cable through cable gland.
Step 4 Insert the crimp contact into the
insulator until it snaps into place.
Then pull gently to check if it is
correctly engaged.
Step 5 Screw the cable gland to front
insulator with tightening torque
2.5…3 Nm.
36
Page 45
User Manual 5 Electrical Connection
For further assembly and connection instruction, please visit the
webpage of the device manufacturer.
Step 6 Make sure the connection cable of PV string for the correct polarity.
The inverter will not function properly if the DC polarities are reversed.
Step 7 Disconnect the DC switch.
Step 8 Configure PV configuration mode according to actual PV conditions. Please
refer to ”5.5.1 PV Inputs Configuration”.
5.5.3 DC Wiring Procedure
Make sure that none of the DC or AC cables connected to the inverter is live
before the electrical work.
Connect the inverter to PV array as the following procedures:
Step 1 Rotate the optional DC switch at the bottom to the “OFF” position.
Step 2 Check the connection cable of PV string for the correct polarity and that the
open-circuit voltage does not exceed the inverter input limit 550V, even
under the lowest operating temperature. Refer to module specification
supplied by module manufacturer for detailed information.
37
Page 46
5 Electrical Connection User Manual
480.0
+
-
y Check the positive and negative polarity of the PV cells. After confirmation,
you can insert the DC connectors into the input terminals on the bottom of
the inverter.
y For the same MPPT, reverse connection of a single string is prohibited. A
permanent failure of the system or inverter may follow if otherwise.
Step 3 Plug the positive and negative DC connectors into corresponding terminals
until there is an audible click.
* Image shown here is for reference only. Actual product you receive may differ.
5.6 Grounding of Inverter
Because of the transform-less design of the inverter, DC positive pole and
DC negative pole are not permitted to be grounded. A permanent destroy to
the inverter may follows if otherwise.
All non-current carrying exposed metal parts of the equipment and other
enclosures in the PV power system should be grounded (e.g., PV arrays frame and
inverter enclosure).
38
Page 47
User Manual 5 Electrical Connection
k
Where there is only one inverter in the PV power system, connect the “PE” cable to
the installation ground.
5.6.1 Second Protective Earth Terminal
The inverter is equipped with second protective earth terminal as specified in EN
50178. There is a second PE terminal at the bottom of the inverter. Users may choose
to connect PE connection.
Second PE Connection
ItemDescriptionRemar
A Screw
B Lock washer C Washer D Cable socketE Yellow-green cable6mm2(9AWG)
M4×12mm
Fig. 5-3 Connection of the Second PE Connection
*The connection parts are not included in the delivery scope.
39
Page 48
6 Communication
6.1 Communication System
The communication connection between the inverter and mobile
smartphone/router can be established via SolarInfo WiFi. If you have problems,
please refer to "10 FAQ for SolarInfo WiFi Installation and Configuration".
6.2 Distance between the inverter and the
smartphone/router
6.2.1 Linear distance
If there are no obstructions between the inverter and smartphone/router, the
maximum linear distance between them can be 150m.
If smartphone is connected to the router, the effective distance between
them depends on the technical parameters of the route and the external
environment.
40
Page 49
User Manual 6 Communication
Impacts of common materials on the wireless signal
Material
Wireless signal
strength
Possible Environment
Wood
Plaster\Asbestos
Glass
Water
Brick wall
Marble
Reinforced
concrete
Metal
cordless
smartphones,
microwave
ovens
Compartment
Wall
Window
Aquarium, pool
Partition
Floor
Floor panels, wall
Iron sheet
6.2.2 Inverter and smartphone / router on different floors
Inverter can be located inside the same house with the smartphone or router, yet
the distance between them must not be more than one floor.
41
Page 50
6 Communication User Manual
m
<20
>0.4m
<3m
Image shown here is for reference only. The inverter can be installed
indoors or outdoors.
6.2.3 Inverter and smartphone / router on the same floor, in
different rooms
42
Page 51
User Manual 6 Communication
1. Keep the inverter in parallel with the external antenna of the router.
2. The WiFi module can not be blocked by metal.
3. In order to avoid wireless electromagnetic interference, please keep
the inverter away from equipment such as cordless smartphones,
microwave ovens and so on.
4. Do not install the inverter in confined environment, such as the
basement.
6.3 SolarInfo Home APP
6.3.1 Acquisition and installation
Download the SolarInfo Home APP and install it into your smartphone. You can
select the APP version for iOS or Android.
For iphone(iOS)
The address for downloading SolarInfo Home APP
is
https://itunes.apple.com/us/app/solarinfo-home/i
d906260039?l=zh&ls=1&mt=8. You can also use
your smartphone to scan the OR code as shown
on the right to download and install it.
Search SolarInfo Home in your APP Store to download and install it.
43
Page 52
6 Communication User Manual
For other smartphone(Android)
The address for downloading SolarInfo Home APP is
https://play.google.com/store/apps/details?id=com.sungrow.home.or
Http://www.solarinfobank.com/app/SolarInfoHome_v1.0.apk.You can also use your
smartphone to scan the following OR codes to download and install it.
Search SolarInfo Home in your PlayStore to download and install it.
44
Page 53
User Manual 6 Communication
Search
Install
solarinfo home
Download
To perform the operations in the following sections, make sure the
distances between the smartphone and the inverters, inverters and the
routers are within the valid range.
SolarInfo Home APP supports two kinds of operation:“Remote
[Login]”and “[Direct visit]”.
In “Remote [Login]” mode, you need configure the inverter to connect it
to your router and complete registration. Then you can log into SolarInfo
Home via the Internet to check the device running information
anywhere.
In “[Direct visit]” mode, you can connect your smartphone to the inverter
directly via WiFi to check the device running information anywhere.
45
Page 54
6 Communication User Manual
6.3.2 SolarInfo Home APP Online Registration
Submit
SolarInfo Home
NOTE
Please enter your e-mail
account and the password.
Slide left
Slide right(Yes)
A
*******
123456
Inverter
Nameplate
Next
OK
Slide left
Press HOME button
46
Page 55
User Manual 6 Communication
6.3.3 Check the running information and connect inverter to your
router in “[Direct visit]”mode.
1. Check the running information
47
Page 56
6 Communication User Manual
2.Select the country you are in and connect inverter to your router
Click and select the
Setting
NOTE
Please do not name your router started with "SG".
Otherwise you cannot find it.
Select your router
country you are in
Enter router’s password
48
Page 57
User Manual 6 Communication
6.3.4 Check the running information in “Remote [Login]”mode.
If you want to check the running information via Internet in “Remote [Login]” mode,
please follow the steps below.
Press HOME button
NOTE
The account and password are
what you have created in
Chapter 2.2.
Settings
Change Off to On
NOTE
The router must be connected
to the Internet.
1
Input your account
and password
2
Login
1
Select your router
2
Press HOME button
SolarInfo Home
49
Page 58
7 Commissioning
7.1 Verify before Commissioning
Before starting up the inverter, you should check the following items.
1. Inverter unit is accessible for operation, maintenance and service.
2. Re-check whether the inverter is firmly secured to the wall.
3. Room for ventilation is provided for one inverter or more than one inverter.
4. Nothing is left on top of the inverter.
5. Inverter and accessories are correctly connected.
6. Cables are routed in safe place or protected against mechanical damages.
7. Specification of AC circuit breaker is reasonable.
8. Terminals unused underneath the inverter are sealed.
9. Warning signs & labels are suitably affixed and durable.
7.2 Commissioning Procedure
Step 1 Make sure all the above mentioned items meet the requirements.
Step 2 Connect the external AC circuit breaker.
Step 3 Rotate the optional DC switch to the “ON” position.
Provided that there is sufficient sunlight:
y
PV arrays initialize and supply DC power to inverter;
y
DC-link starts to charge and check the state of the utility grid;
y
If the conditions are OK, inverter feeds AC power to grid and enters into the
running state.
Step 4 Observe the status of LED indicator.
50
Page 59
User Manual 7 Commissioning
State Description
Green&
Red
Green
Red Flicker once every 0.3 second
Flicker once in turn every 1
second
Flicker once every 0.2 seconds to
2 seconds ( The greater the
inverter current power, the
faster the green light flashing)
Non-running or Non-fault (For
example, the inverter is in standby
state.)
Inverter is running.
A malfunction happens, or protection
function triggers.
The red and green LEDs will be on at the same time when the inverter is
in the upgrade status. If the red and green LEDs are on at the same time
in other status, please contact the service provider for troubleshooting.
51
Page 60
8 Disconnecting, Dismantling and
Disposing of the Inverter
8.1 Disconnecting the Inverter
For maintenance or other service work, the inverter must be switched off.
Proceed as follows to disconnect the inverter from the AC and DC power source.
Lethal voltages or damages to the inverter will follow if otherwise.
Step 1 Disconnect the external AC circuit breaker and prevent it from reconnecting.
Step 2 Rotate DC switch to the “OFF” position and then turn off the upstream DC
circuit break or pull off the MC4 terminal.
Please strictly follow the sequence of the above procedures. Inverter will
not work normally if otherwise.
Step 3 Wait about ten minutes until the capacitors inside the inverter are
discharged.
Step 4 Measure to confirm that the inverter AC output at the AC circuit breaker is
voltage free.
Step 5 Pull AC connector out of the inverter.
Step 6 Release the locking part of DC connectors by pressing on the ribbing of the
locking hooks with nipper pliers and pull it outwards.
For further disconnection and conductor reconnection instruction,
please visit the webpage of device manufacturer.
52
Page 61
User Manual 8 Disconnecting, Dismantling and Disposing of the Inverter
8.2 Dismantling the Inverter
Refer to Chapter 6 for the inverter disconnection of all cables in reverse steps.
There is a risk of burn injuries and electric shock!
Wait at least 10 minutes after disconnecting the inverter from the utility
grid and the PV input before touching any inner live parts.
Open the theftproof padlock and dismantle the inverter referring to Chapter 4 in
reverse steps.
If necessary, remove the backplate from the wall.
If the inverter will be reinstalled in the future, please refer to “3 Unpacking
and Storage” for a proper conservation.
8.3 Disposing of the Inverter
Users should take the responsibility for the disposal of the inverter.
Some parts and devices of the inverter, such as, LED indicators, batteries,
capacitors, may cause environment pollution.
Disposal of the inverter must comply with the related local regulations to
avoid the potential pollution.
53
Page 62
9 Troubleshooting and
Maintenance
9.1 Troubleshooting
9.1.1 LED Indicator Troubleshooting
See “Tab. 2-2Description of LED Indicator” for the definition of LED’s status.
Type of fault Troubleshooting
LED indicator
cannot be lit.
Green indicator
goes out.
1. Disconnect the AC circuit breaker.
2. Rotate the optional DC switch to the “OFF” position.
3. Check the polarity of DC input.
1. Disconnect the AC circuit breaker.
2. Rotate the optional DC switch to the “OFF” position.
3. Check the correctness of the inverter electrical connection.
Refer to 5 Electrical Connection.
4. Check whether the voltage of DC input exceeds the inverter
start-up voltage.
5. If all above conditions are OK, please contact Sungrow.
Should you have any questions in operating the inverter, please contact
us:
We need the following information to provide you the best assistance:
y
Type of the inverter
y
Serial number of the inverter
y
Fault name (Each fault has a corresponding fault code, for example, 01 represents
sampling fault.)
y
Brief description of the fault phenomenon
54
Page 63
User Manual 9 Troubleshooting and Maintenance
9.1.2 Troubleshooting of Faults in the smartphone application
interface
When faults occur, “Fault” state can be shown in the smartphone application
interface.
Fault
Code
002
003
004
005
006
007 Transient AC overcurrent
008
009
Description Troubleshooting
1. Check the voltage of the grid.
The grid voltage exceeds
inverter allowable upper
limit.
Grid transient voltage
exceeds the permissible
range
The grid voltage is below
inverter’s allowable lower
limit.
The grid voltage is too
low.
The AC output current
exceeds inverter
allowable upper limit.
The grid frequency
exceeds inverter
allowable upper limit.
The grid frequency is
below the inverter
allowable lower limit.
2. If the grid voltage exceeds the permissible
range of inverter protection parameters, ask
utility grid company for solution.
3. If the grid voltage is within the permissible
range, contact Sungrow Service Dept..
1. This is a short-term fault due to grid
condition. Wait a moment for inverter recovery.
2. If the fault still exists, please contact
Sungrow Service Dept..
1. Check the grid voltage.
2. If the grid voltage exceeds the permissible
range of inverter protection parameters, ask
utility grid company for solution.
3. If the grid voltage is within the permissible
range, contact Sungrow Service Dept..
1. This is a short-term fault due to grid
condition. Wait a moment for inverter recovery.
2. If the fault still exists, please contact
Sungrow Service Dept..
1. The inverter will resume if the output current
falls below the protection value.
2. If the fault still exists, please contact
Sungrow Service Dept..
1. The inverter will self-recover after several
seconds.
2. If the fault still exists, please contact
Sungrow Service Dept..
1. Check the grid frequency.
2. If the grid frequency exceeds the permissible
range of inverter protection parameters, ask
utility grid company for solution.
3. If the grid frequency is within the permissible
range, contact Sungrow Service Dept..
55
Page 64
9 Troubleshooting and Maintenance User Manual
Fault
Code
010 Islanding
011
012
014
015
016
019
020 The bus voltage is high.
021
022
036
Description Troubleshooting
The DC component of AC
current exceeds inverter
limit.
A failure current is
detected.
The average grid voltage
exceeds the permissible
range for over 10
minutes.
The grid voltage exceeds
the permissible range
The bus voltage or power
is high.
The transient bus voltage
is high.
PV1 input overcurrent is
detected
PV2 input overcurrent is
detected
The temperature of
radiator is too high
1. Check whether AC circuit breaker is
triggered.
2. Check whether AC cables are all firmly
connected.
3. Check whether grid is not in service.
4. If all conditions are OK and this fault still
occurs in the LCD screen, contact Sungrow
Service Dept..
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Check the PV strings for ground fault.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Wait a moment for inverter recovery.
2. Check the voltage of the grid. If the grid
voltage exceeds the permissible range of
inverter protection parameters, ask utility grid
company for solution.
3. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Check the model of the AC cables.
2. Wait a moment for inverter recovery.
3. If the grid voltage exceeds the permissible
range, ask utility grid company for solution.
4. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
Check the layout and the wiring of PV1 input.
Check the layout and the wiring of PV2 input.
1. Check whether the placement of inverter is
correctly.
56
Page 65
User Manual 9 Troubleshooting and Maintenance
Fault
Code
037
038 Relay fault is detected
039
041
047
048 Sampling channel failure
053
054
056
Description Troubleshooting
The internal temperature
of inverter is too high
The insulation resistance
is low. (ISO-flt)
Leakage current self-test
abnormality
The PV configuration
mode set in the
smartphone application
interface is not in
accordance with the
configuration in the
connection cabinet.
Auxiliary DSP detects grid
voltage exceeds set
protection value
Auxiliary DSP detects grid
frequency exceeds set
protection value
Auxiliary DSP detects
leakage current exceeds
set protectino range
2. Check whether the inverter operating
ambient temperature is more than the range
indicated in the specification.
3. Check whether AC output power exceeds
the nominal power.
4. If the fault still exists, please contact
Sungrow.
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Check whether the positive and negative of
PV panels is short-circuited with ground lead.
2. Wait a moment for inverter recovery.
3. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Disconnect the inverter.
2. Re-select PV configuration mode and
re-connect PV strings.
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Check the grid voltage.
2. If the grid voltage exceeds the permissible
range of inverter protection parameters, ask
utility grid company for solution.
3. If the grid voltage is within the permissible
range, contact Sungrow Service Dept..
1. Check the grid frequency.
2. If the grid frequency exceeds the permissible
range of inverter protection parameters, ask
utility grid company for solution.
3. If the grid frequency is within the permissible
range, contact Sungrow Service Dept..
1. Check whether there is a grounded fault of
the PV string.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
57
Page 66
9 Troubleshooting and Maintenance User Manual
Fault
Code
057
058
059
060
070 Fans are defective
087
088 Arc anomaly fault
089 Arc detection OFF warn
100
101
102
106
200 The bus voltage is high.
Description Troubleshooting
Auxiliary DSP AC current
sampling channel
anomaly
Auxiliary DSP detects AC
current DC injection
exceeds inverter set
protection range
Main and auxiliary DSP
communication anomaly
Main and auxiliary DSP
sampling difference
Arc self-detection
anomaly warn
The AC output current
exceeds inverter
protection limit.
The grid frequency
exceeds inverter
allowable upper limit.
The grid frequency is
below the inverter
allowable lower limit.
The inverter is not
grounded
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
Stop the inverter and disconnect the AC & DC
cables. Check whether the fan duct has been
blocked. If not, replace fans.
Wait a while. Contact Sungrow if device is still
in self-detection warn state.
1. Stop the inverter and disconnect the AC &
DC cables. Check cable connection for aging
and looseness. Re-power on and remove the
arc warn manually.
2. Contact Sungrow if this fault still occurs.
Remove the warn by enable arc detection
function or keep the warn by closing arc
detection function.
1. The inverter will resume if the output current
falls below the protection value.
2. If the fault still exists, please contact
Sungrow Service Dept..
1. Check the grid frequency.
2. If the grid frequency exceeds the permissible
range of inverter protection parameters, ask
utility grid company for solution.
3. If the grid frequency is within the permissible
range, contact Sungrow Service Dept..
Check whether there is a reliable inverter
grounding line, if there is access to the ground,
and the fault still exists, please contact
Sungrow Service Dept..
1. Wait for inverter recovery after bus voltage
lower.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
58
Page 67
User Manual 9 Troubleshooting and Maintenance
Fault
Code
201
202 PV current overcurrent
205
307 DC power is too high
Description Troubleshooting
The bus voltage is too
low.
AC output relay
abnormal
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Wait for inverter recovery after DC current is
reduced.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
Check whether the configuration of PV is in the
range indicated in the specification. If the fault
occurs repeatedly, contact Sungrow Service
Dept..
9.2 Fault Repair
If the inverter can not work normally, you can contact the service provider for
troubleshooting.
Visit http://www.sungrowservice.com to fill in and submit the relevant information
(such as “ Inverter Information”, “Customer Information / Service Address”,
“Attachments” and so on).
9.3 Routine Maintenance
Items Methods Period
Check the temperature and dust of the inverter.
System
clean
Clean the inverter enclosure.
Check the humidity and dust of the environment.
Meanwhile check whether the filter function of
the air inlet is ok. Clean the air inlet and outlet,
when necessary.
59
Six months to a year
(it depends on the
dust contents in air.)
Page 68
10 FAQ for SolarInfo WiFi
Installation and Configuration
10.1 FAQ Index Table
No. Title
1001 Configurable terminal devices cannot find WiFi after installation
1002 Router password is correct or not
1003 Cannot find the assigned Router
1004 Communication strength is weak (Installation notice)
1005 User performs certain advanced operation to the Router
1006 2 Routers nearby have the same SSID
1007 Data cannot be uploaded to the Server after correctly connected to
Router
1008 Check the WiFi underlying data when all operations are failed
1009 Router SSID contains special characters and cannot connect to WiFi
1010 WiFi cannot find Router when Router max. rate is set to be 300Mbps
1011 Impacts of materials on the wireless signal
10.2 Question Description and Solution
No. 1001: Configurable terminal devices cannot find WiFi after installation
Applicable: All
Fault t ype: general
60
Page 69
User Manual 9 FAQ for SolarInfo WiFi
Question description: configuration end cannot find WiFi after installation
Solution:
1) Check if the device begins operation
2) Check if WiFi is installed correctly
3) The configuration end and WiFi should not be too far away. Move them together
to check if the search can be done.
4) If all above-mentioned items are checked and the distance is close enough, yet
this fault still occurs, it can be verified that the WiFi module is damaged.
No. 1002: Router password is correct or not
Applicable: All
Fault t ype: general
Question description: the signal strength and other items meet requirement, but
WIFi cannot connect to Router
Solution: make sure the router password is correct. Note if there are capital and
small letters.
No. 1003: Cannot find the assigned Router
Applicable: All
Fault t ype: general
Question description: smartphone or laptop cannot find the assigned Router
Solution:
1) Click the refresh button on the middle right to refresh
2) Make sure the Router is not far away from the WiFi and there is no iron materials
between them
3) Make sure there is no SSID hidden configuration of the Router
4) Router name cannot be started with “SG-”
61
Page 70
9 FAQ for SolarInfo WiFi User Manual
No. 1004: Communication strength is weak (Installation notice)
Applicable: All
Fault type: Improper installation method
Question description: Signal strength bar is less than one
Solution:
1) Make sure the device is at least 30CM higher than the floor
2) Make sure the device is at least 40CM from the wall
3) Make sure the device is installed internally between the PC cell or installation
frame and the ground
4) Make sure the device is parallel to the external antenna of the Router and vertical
as possible
5) Device is not covered by metal or reinforced concrete.
6) Installation position is shown below:
62
Page 71
User Manual 9 FAQ for SolarInfo WiFi
20m
<
Prevention measure: operate as described in the figure above.
No. 1005: User performs certain advanced operation to the Router
Applicable: All routers
Fault type: Improper operation
Question description: user perform some advanced settings to the Router, for
example, MAC address filtering, IP range limitation, access number limitation, SSID
limitation, DHCP enable, hidden of the Router SSID or other advanced settings.
Solution: Check with the user if there are such advanced settings. Cancel these
settings if any.
Prevention measure: operate as described above or reset the Router to factory
settings.
63
Page 72
9 FAQ for SolarInfo WiFi User Manual
Check the “Enable DHCP Server”; set the “DHCP IP Address Range” as wide as
possible, otherwise the accessed user numbers may decrease and cannot connect
to WIFI.
“Wireless filter policy” is to set which devices are allowed to be connected to the
Router. Do not set this parameter. You may not able to connect to the Router if
otherwise.
This setting may hide the Router SSID and the Router may not be searched later
64
Page 73
User Manual 9 FAQ for SolarInfo WiFi
No. 1006: 2 Routers nearby have the same SSID
Applicable: All
Fault type: 2 routers with the same name
Question description: two routers nearby have the same router name. Cannot
connect to the target Router even if the password is correct
Solution: Change the SSID of the Router that can be changed
Prevention measure: User confirmation
No. 1007: Data cannot be uploaded to the Server after correctly connected to Router
Applicable: All
Fault type: No data can be viewed from the Server
Question description: cannot find inverter data when the WiFi is correctly connected
to the Router and correctly registered.
Solution:
1) Make sure Router can correctly connect to Internet
2) Close the Router firewall
3) Check if there is advanced Router configuration
Prevention measure: confirm following the above solutions
No. 1008: Check the WiFi underlying data when all operations are failed
Applicable: All
Fault type: Configuration or WiFi module damage
Question description: Configuration or WiFi module damage
Solution: Read module data by EMW-TOOL software
Prevention measure: strict production inspection and strict configuration operation
65
Page 74
9 FAQ for SolarInfo WiFi User Manual
No. 1009: Router SSID contains special characters and cannot connect to WiFi
Applicable: All
Fault type: WiFi software bug
Question description: Router SSID contains special characters and cannot connect
to WiFi
Solution: modify WiFi software
Prevention measure: modify WiFi firmware
No. 1010: WiFi cannot find Router when Router max. rate is set to be 300Mbps
Fault type: compatibility of mode n
Question description: WiFi cannot find Router when Router max. rate is set to be
300Mbps
Solution: Modify WiFi software
Prevention measure: modify WiFi
66
Page 75
User Manual 9 FAQ for SolarInfo WiFi
No. 1011: Impacts of materials on the wireless signal
Fault type: interference
Question description: wireless transmission device and impacts of materials on the
Wireless signal
Material
Wireless signal
strength
Possible Environment
Wood
Compartment
Plaster\Asbestos
Wall
Glass
Window
Water
Aquarium, pool
Brick wall
Partition
Marble
Reinforced
concrete
Metal
Floor
Floor panels, wall
Iron sheet
cordless
smartphones,
microwave
ovens
Solution: Make sure there is no abovementioned materials between or near the
smartphone or router and the inverter
Prevention measure: Make sure there is no abovementioned materials between or
near the smartphone or router and the inverter
67
Page 76
11 Appendix
11.1 Technical Data
11.1.1 Single MPPT Inverter Data
SG2KTL-S/ SG2K5TL-S
Technical
Specifications
SG2KTL-S SG2K5TL-S
Input Side Data
Max. PV input power 2300W 2800W
Max. PV input voltage 600V 600V
Startup voltage 150V 150V
Nominal input
voltage
MPP voltage range 125…560V 125…560V
MPP voltage range for
nominal power
No. of MPPTs 1
Max. number of PV
strings per MPPT
Max. PV input current 11A 11A
Max. current for input
connector
Short-circuit current
of PV input
345V
210…520V 240…520V
1 1
20A
12A 12A
Output Side Data
Nominal AC output
power
Max AC output
apparent power
Max. AC output
current
Nominal AC voltage 230Vac(Single phase)
AC voltage range
Nominal grid
frequency
Grid frequency range 45Hz…55Hz/55Hz…65Hz (May vary as per corresponding
2000W 2490W (cosΦ=1)
2150VA 2490VA
9.5A 11.5A
180…276Vac (May vary as per corresponding country’s grid
standard)
50Hz/60Hz
68
Page 77
User Manual 9 Appendix
Technical
Specifications
THD <3% (Nominal power)
DC current injection <0.5% In
Power factor
SG2KTL-S SG2K5TL-S
country’s grid standard)
>0.99@default value at nominal power
(adj. 0.8 over-excited~0.8 under-excited)
Protection
Anti-islanding
protection
AC short circuit
protection
Leakage current
protection
DC switch
DC fuse
Overvoltage
protection
Yes
Yes
Yes
Optional
No
Varistors
System Data
Max. efficiency 98.00% 98.00%
Max. European
efficiency
Isolation method Transformerless
Ingress protection
rating
Night power
consumption
Operating ambient
temperature range
Allowable relative
humidity range
Cooling method Natural cooling
Noise level
Max. operating
Altitude
Communication WiFi
DC Terminals MC4
AC Terminals Plug and play connector
Max. PV input power 3300W 3900W 4300W
Max. PV input voltage 600V 600V 600V
Startup voltage 150V 150V 150V
Nominal input
voltage
MPP voltage range 125…560V 125…560V 125…560V
MPP voltage range for
nominal power
No. of MPPTs 1
Max. number of PV
strings per MPPT
Max. PV input current 11A 18A 18A
Max. current for input
connector
Short-circuit current
of PV input
345V
280…520V 210…520V 240…520V
1 2 2
20A
12A 20A 20A
Output Side Data
Nominal AC output
power
Max AC output
apparent power
Max. AC output
current
Nominal AC voltage 230Vac(Single phase)
AC voltage range
Nominal grid
frequency
Grid frequency range
THD <3% (Nominal power)
DC current injection <0.5% In
Power factor
3000W 3680W 4000W
3150VA 3680VA 4210VA
13.7A 16.0A 18.3A
180…276Vac (May vary as per corresponding country’s grid
standard)
50Hz/60Hz
45Hz…55Hz/55Hz…65Hz (May vary as per corresponding
country’s grid standard)
>0.99@default value at nominal power
(adj. 0.8 over-excited~0.8 under-excited)
Protection
Anti-islanding
Yes
70
Page 79
User Manual 9 Appendix
Technical
Specifications
protection
AC short circuit
protection
Leakage current
protection
DC switch
DC fuse
Overvoltage
protection
SG3KTL-S SG3K6TL-S SG4KTL-S
Yes
Yes
Optional
No
Varistors
System Data
Max. efficiency 98.00% 98.00% 98.00%
Max. European
efficiency
Isolation method Transformerless
Ingress protection
rating
Night power
consumption
Operating ambient
temperature range
Allowable relative
humidity range
Cooling method Natural cooling
Noise level
Max. operating
Altitude
Communication WiFi
DC Terminals MC4
AC Terminals Plug and play connector
Max. PV input power 3300W 3900W
Max. PV input voltage 600V 600V
Startup voltage 150V 150V
Nominal input
voltage
MPP voltage range 125…560V 125…560V
MPP voltage range for
nominal power
No. of MPPTs 2
Max. number of PV
strings per MPPT
(DC1/DC2)
Max. PV input current
(DC1/DC2)
Max. current for input
connector
Short-circuit current
of PV input (DC1/DC2)
345V
150…520V 180…520V
1/1
11A/11A
20A
24A(12A/12A)
Output Side Data
Nominal AC output
power
Max AC output
apparent power
Max. AC output
current
Nominal AC voltage 230Vac(Single phase)
AC voltage range
Nominal grid
frequency
Grid frequency range
THD <3% (Nominal power)
DC current injection <0.5% In
Power factor
3000W (cosΦ=1) 3680W (cosΦ=1)
3150VA 3680VA
13.7A 16.0A
180…276Vac (May vary as per corresponding country’s grid
standard)
50Hz/60Hz
45Hz…55Hz/55Hz…65Hz (May vary as per corresponding
country’s grid standard)
>0.99@default value at nominal power
(adj. 0.8 over-excited~0.8 under-excited)
Protection
Anti-islanding
Yes
72
Page 81
User Manual 9 Appendix
Technical
Specifications
protection
AC short circuit
protection
Leakage current
protection
DC switch
DC fuse
Overvoltage
protection
SG3KTL-D SG3K6TL-D
Yes
Yes
Optional
No
Varistors
System Data
Max. efficiency 98.00% 98.00%
Max. European
efficiency
Isolation method Transformerless
Ingress protection
rating
Night power
consumption
Operating ambient
temperature range
Allowable relative
humidity range
Cooling method Natural cooling
Noise level
Max. operating
Altitude
Communication WiFi
DC Terminals MC4
AC Terminals Plug and play connector
Certification
97.50% 97.50%
IP65
<1 W
-25℃…+60℃(>45℃ derating)
0…100%
≤30dB
4000m(>2000m derating)
IEC61000-6-2,IEC61000-6-3,AS/NZS3100,AS4777.2,AS4777.3,
VDE-AR-N-4105,VDE0126-1-1,CE,G83/2,C10/11,EN50438,CG
C
Mechanical Data
Dimensions(W×H×D)360×390×133mm
Mounting method Wall bracket
Weight 11kg
73
Page 82
9 Appendix User Manual
SG4K6TL-D/SG5KTL-D
Technical
Specifications
SG4K6TL-D SG5KTL-D
Input Side Data
Max. PV input power 4900W 5400W
Max. PV input voltage 600V 600V
Startup voltage 150V 150V
Nominal input
voltage
MPP voltage range 125…560V 125…560V
MPP voltage range for
nominal power
No. of MPPTs 2
Max. number of PV
strings per MPPT
(DC1/DC2)
Max. PV input current
(DC1/DC2)
Max. current for input
connector
Short-circuit current
of PV input (DC1/DC2)
345V
220…520V 240…520V
1/1
11A/11A
20A
24A(12A/12A)
Output Side Data
Nominal AC output
power
Max AC output
apparent power
Max. AC output
current
Nominal AC voltage 230Vac(Single phase)
AC voltage range
Nominal grid
frequency
Grid frequency range
THD <3% (Nominal power)
DC current injection <0.5% In
Power factor
4600W (cosΦ=1) 5000W (cosΦ=1)
4600VA 5000VA
20A 21.7A
180…276Vac (May vary as per corresponding country’s grid
standard)
50Hz/60Hz
45Hz…55Hz/55Hz…65Hz (May vary as per corresponding
country’s grid standard)
>0.99@default value at nominal power
(adj. 0.8 over-excited~0.8 under-excited)
Protection
Anti-islanding
protection
AC short circuit
Yes
Yes
74
Page 83
User Manual 9 Appendix
Technical
Specifications
protection
Leakage current
protection
DC switch
DC fuse
Overvoltage
protection
SG4K6TL-D SG5KTL-D
Yes
Optional
No
Varistors
System Data
Max. efficiency 98.00% 98.00%
Max. European
efficiency
Isolation method Transformerless
Ingress protection
rating
Night power
consumption
Operating ambient
temperature range
Allowable relative
humidity range
Cooling method Natural cooling
Noise level
Max. operating
Altitude
Communication WiFi
DC Terminals MC4
AC Terminals Plug and play connector
Certification
97.50% 97.50%
IP65
<1 W
-25℃…+60℃(>45℃ derating)
0…100%
≤30dB
4000m(>2000m derating)
IEC61000-6-2,IEC61000-6-3,AS/NZS3100,AS4777.2,AS4777.3,
VDE-AR-N-4105,VDE0126-1-1,CE,G83/2,C10/11,EN50438,CG
C
Mechanical Data
Dimensions(W×H×D)360×390×133mm
Mounting method Wall bracket
Weight 11kg
For SG5KTL-D, when the national selection is set to Australia,the nominal
AC output power of the inverter is 4600W and the max. AC output
current is 20A.
75
Page 84
9 Appendix User Manual
11.2 Exclusion of Liability
The content of these documents is periodically checked and revised where
necessary. Discrepancies therefore may exist. Readers are cautioned that Sungrow
reserves the right to make changes without notice. Please call us or visit our website
at www.sungrowpower.com for the latest information. No guarantee is made for the
completeness of these documents. Please contact our company or distributors to
get the latest version.
Guarantee or liability claims for damages of any kind are excluded if they are caused
by one or more of the following:
y
Improper or inappropriate use or install of the product
y
Install or operate the product in unintended environment
y
Install or operate the product without observing relevant safety regulations in
the deployment location
y
Ignore the safety warnings or instructions contained in all documents relevant to
the product
y
Install or operate the product under incorrect safety or protection conditions
y
Alter the product or supplied software without authority
y
Product malfunctions due to operation attached or neighboring devices running
out of the allowed limit values
y
Unforeseen calamity or force majeure
The use of supplied software produced by Sungrow Power Supply Co., Ltd. is subject
to the following conditions:
y
Sungrow Power Supply Co., Ltd. assumes no liability for direct or indirect
damages arising from the use of SolarInfo software. This also applies to the
provision or non-provision of support activities.
y
SolarInfo software used for commercial purposes is prohibited.
y
Decompiling, decoding or destroying the original program, including SolarInfo
software and the embedded software, is prohibited.
76
Page 85
User Manual 9 Appendix
11.3 About Us
Sungrow power supply is a China-leading manufacturer of various power
electronics products for renewable energy generation systems. Our products
include converters, inverters, battery chargers and other power supplies for
distributable generation system in both grid-connected and stand-alone
applications. The power rating of Sungrow products covers from several hundred
watt to large mega-watt systems.
The pursuit of Sungrow is to help our customers acquire stable and clean power
with minimum cost, maximum reliability and enhanced safety.
Contact Information
Should you have any questions or queries about this product, please contact us
through the following information. We will be more than happy to assist you!
Company: Sungrow Power Supply Co., Ltd.
Website: www.sungrowpower.com
Email: [email protected](China), [email protected](Overseas)
Add: No.1699 Xiyou Rd., New & High Technology Industrial Development
Add: No.1699 Xiyou Rd.,New & High Technology Industrial Development Zone, 230088,Hefei, P. R. China.
Post Zip: 230088
Web: www.sungrowpower.com
E-mail: [email protected]
Specifications are subject to changes without advance notice.