Sungrow EMS200 User Manual

Page 1
EMS200 Local Controller User Manual
EMS200-V12-UEN-Ver11-201812
Page 2
Page 3
Contents
1.1 Target Group ............................................................................. 1
1.2 How to Use this Manual ............................................................ 1
1.3 Symbol Explanations ................................................................. 1
3.1 Function Introduction ................................................................. 5
3.2 Appearance ............................................................................... 5
3.3 Dimension and Weight .............................................................. 6
5.1 Unpacking and Inspection ................................ ......................... 8
5.2 Requirements for Installation Location ...................................... 9
5.3 Installation ................................................................................. 9
5.3.1 Rack Mounting .......................................................................... 9
5.3.2 Wall Mounting .......................................................................... 10
6.1 General Safety Regulations .................................................... 12
6.2 Terminal Introduction ............................................................... 12
6.3 Communication Device Connection ........................................ 14
6.3.1 COM Port Connection ............................................................. 14
6.3.2 Internet Port Connection.......................................................... 15
6.4 Connection to System EMS .................................................... 15
6.5 Protection Earthing Connection ............................................... 16
6.6 Power Supply Connection ................................ ....................... 17
7.1 Checking before Commissioning ............................................. 19
7.2 Running Steps ................................................................ ......... 19
I
Page 4
8.1 Requirements for Operation Environment ................................ 20
8.2 Preparations for Login .............................................................. 20
8.3 Login Steps .............................................................................. 20
8.4 WEB Main Interface ................................................................. 21
8.5 WEB Menu ............................................................................... 22
8.6 Operating Information .............................................................. 22
8.6.1 Summary Information .............................................................. 23
8.6.2 PCS Information ...................................................................... 23
8.6.3 BMS Information ..................................................................... 24
8.6.4 Detail Information .................................................................... 24
8.7 Parameter Settings .................................................................. 24
8.7.1 System Parameters ................................................................. 25
8.7.2 Operating Parameters ............................................................. 26
8.7.3 Communication Parameters .................................................... 26
8.7.4 Slave Unit Parameters ............................................................ 27
8.7.5 Protection Parameters............................................................. 28
8.8 History Records ....................................................................... 29
8.8.1 Running Records .................................................................... 30
8.8.2 Event Records......................................................................... 30
8.8.3 Fault Records .......................................................................... 31
8.8.4 Alarm Records......................................................................... 31
8.9 System Information .................................................................. 32
User Password Changing ................................................................ 32
9.1 Safety Precautions ................................................................... 33
9.1.1 General Safety Rules .............................................................. 33
9.1.2 Five Safety Rules .................................................................... 33
9.2 Routine Maintenance ............................................................... 34
10.1 Overview .................................................................................. 35
10.2 Alarm Diagnosis ................................................................ ....... 35
II
Page 5
10.2.1 Alarm Information on Power Conversion System (PCS) ........ 35
10.2.2 Alarm Information on Battery ................................................. 37
10.2.3 Alarm Information on BCP ..................................................... 39
10.2.4 Other Alarms ......................................................................... 40
10.3 Fault Diagnosis........................................................................ 41
10.3.1 Fault Information on Power Conversion System (PCS) ......... 41
10.3.2 Fault Information on Grid ....................................................... 43
10.3.3 Other Faults........................................................................... 43
11.1 Technical Data ................................ ......................................... 45
11.2 Abbreviation Explanation ..................................................... 46
11.3 Quality Assurance ................................................................... 46
11.4 Contact Information ................................................................. 47
III
Page 6
IV
Page 7
"DANGER" indicates a hazard with a high level of risk which, if not avoided, will result in death or serious injury.
"WARNING" indicates a hazard with a medium level of risk which, if not avoided, could result in death or serious injury.
1 About this Manual
1.1 Target Group
This manual is intended for qualified persons responsible for the installation, operation, and maintenance of the local controller and users performing routine operations.
1.2 How to Use this Manual
Read this manual carefully before using the device. Keep the documentation in a convenient place for future reference.
All rights reserved including the pictures, markings, and symbols used. Any reproduction or disclosure, even partially, of the content of this manual is strictly prohibited without prior written authorization of our company. The content of the manual is constantly updated or revised, and the description in this manual may slightly deviate from the actual product or even have errors.
1.3 Symbol Explanations
To ensure personal and property safety in using the device or to use the device efficiently, this manual provides relevant instructions that are highlighted by corresponding symbols. Read the following symbols carefully for better using this manual.
1
Page 8
1. About this Manual User Manual
"CAUTION" indicates a hazard with a low level of risk which, if not avoided, could result in minor or moderate injury.
"NOTICE" indicates a situation which, if not avoided, could result in equipment malfunction or property damage.
"NOTE" indicates additional information, emphasized contents, or tips to help you solve problems or save time.
2
Page 9
Only electrically qualified persons can operate and wire the device.
After receiving the device, check whether the local controller is damaged due to transport. Should there be any problem, please contact us or the forwarding company.
Before performing any operations on the local controller, the operators must be familiar with all safety instructions and related regulations on installation, operation, and maintenance.
Correct moving, transport, installation, operation and maintenance are critical to safe and appropriate use of the local controller.
2 Safety Instructions
This chapter mainly introduces some important safety instructions about operating the local controller.
The local controller is designed and tested according to the international safety regulations. For this electrical and electronic device, safety instructions related to it must be complied with during installation, operation, and maintenance.
Incorrect operation or misoperation may cause:
personal injury
property damage
To prevent the personal injury and property damage and to ensure long-term operation of the local controller, read these symbols carefully.
Before Installation
3
Page 10
2. Safety Instructions User Manual
The local controller can only be used as described in this manual. Unauthorized alternation or using spare parts not sold or recommended by our company can cause fires, electric shock, or other damage.
Before the installation, disconnect all electrical connections and input switches upstream to ensure that the local controller is voltage-free.
Before the electrical connection, disconnect input switches upstream, and ensure that the local controller is voltage-free.
Only persons from the service department of our company or other qualified personnel can service the local controller.
The user is prohibited to perform maintenance, replacement, and other operations. Otherwise, serious personal injury or tremendous property loss may be caused.
Do not replace the internal components of the local controller without authorization. Our company shall hold no liability for the damage caused.
During Installation
Maintenance and replacement
4
Page 11
Front view Side view
Bottom view
A
B
C
Item
Name
Description
A
Indicator
Display running status of the local controller
B
Heat dissipation hole
- C Cable connection terminal
-
3 Product Description
3.1 Function Introduction
The local controller researched & developed by our company can be applied to the micro-grid system.
Local controller can collect running information of the PCS, BCP, and other devices in the system, and uploads the information to the energy management system via the background, so as to facilitate the management of energy storage system.
Main functions
Data collection Data forwarding Device management Micro-grid operation management
Receiving and executing local controller scheduling instructions
3.2 Appearance
5
Page 12
3. Product Description User Manual
Indicator
Name
Description
PWR
Power indicator
PWR indicator is on: power supply is normal PWR indicator is off: power supply is abnormal
RUN
Running indicator
RUN indicator flashes: running is normal RUN indicator is off: running is abnormal
BLE
Bluetooth indicator
Reserved function
FAULT
Fault indicator
FAULT indicator is on: the system fault occurs FAULT indicator is off: the connected inverter is fault-free
Width (W)
Height (H)
Depth (D)
Width (W)
Height (H)
Depth (D)
Weight
440
241
44
3kg
Tab. 3-1 Indicator
3.3 Dimension and Weight
Note: The unit is mm
6
Page 13
Procedure
Reference section
Unpacking and inspection
5.1
Select an optimum installation site and perform mechanical installation
5.3
Electrical connection
6
Checking before commissioning
7.1
Running steps
7.2
4 Installation Procedure
Tab. 4-1 Description of the installation procedure
7
Page 14
A
B
D
G
C
E
F
H
No
Name
Description
A
local controller
-
B
Enclosed documentation
User manual, delivery inspection records, packing list, warranty card, and quality certificate
C
Communication terminal resistor
12x120Ω Note: When the RS485 bus is connected to more
than 15 devices, it is recommended to connect 120-Ω terminal resistors in parallel to cables A and B on the two ends of the bus
D
Network Cable
Length: 1x2m
E
Hanger
2
F
Fastener combination
Cross recessed pan head tapping screws
G
OT terminal
RNBL5-4
H
Nylon cable tie
Fastening cables
5 Mechanical Installation
5.1 Unpacking and Inspection
Check for completeness of the scope of delivery according to the packing list in the carton.
Fig. 5-1 Scope of delivery
8
Page 15
User Manual 4. Mechanical Installation
440
241
5.2 Requirements for Installation Location
This section is intended to instruct the user to select an optimum installation location.
The local controller with protection degree IP20 can only be installed indoors.
The ambient temperature range is -30℃ to +60℃.
The humidity cannot exceed 95%. Otherwise, internal components can be damaged.
Take proper damp-proof and anti-corrosion measures.
5.3 Installation
The local controller can be installed at any indoor locations provided that the requirements above are met.
5.3.1 Rack Mounting
In the rack mounting manner, the standard 1U rack is used, and installation steps are as follows:
Step 1 The distance between the two hangers of the local controller is shown in
the following figure.
Step 2 Select an appropriately sized rack according to the distance, and insert
the local controller into the rack.
9
Page 16
4. Mechanical Installation User Manual
150.3 31.2
465
482
31.2
Consider the weight of the local controller during the whole installation process!
Tilting or falling of the device caused by inappropriate operations could result in personal injury!
It is recommended to install the local controller at a location 1.5m above the ground and reserve at least 0.5m for future maintenance.
Step 3 Fix the local controller according to the sequence of bolt, hanger, rack,
and nut.
5.3.2 Wall Mounting
Fix the local controller through the hangers at the four corners. Installation distances between the hangers are shown in the following figure.
Step 1 Prepare installation tolls including the impact drill, expansion solenoids,
washers, tapping screws, and torque screwdriver.
Step 2 Select an installation surface and mark drilling positions on the target
area considering distances between the local controller and ambient objects.
10
Page 17
User Manual 4. Mechanical Installation
Step 3 Install the expansion solenoids, washers, and tapping screws onto the
marked positions on the surface.
Step 4 Hang the local controller onto the tapping screws via the screw holes on
the hangers.
Step 5 Fasten the tapping screws by using the torque screwdriver with fastening
torque: 0.3N·m.
Check to ensure that the local controller is firmly in place.
11
Page 18
Incorrect cable connections could damage the local controller or even injure operators.
All cables must be undamaged, well insulated, appropriately sized, and securely connected.
ABC D E
G H
I LJF K
M N O
P
ETH2
ETH1
USB SD Debug RST
0V 1 2 3 4 5 6 7 8 9 10 11 1213 14 1516 0V
DIN
1 2 3
DO1
1 3
DO2
1 3
DO3
1 3
DO4
2 2 2
A1B1A2 B2 A3B3A4 B4 A5 B5A6 B6
+ - GND
PT1
+ - GND
PT2
+ -
AI1
+ -
AI2
+ -
AI3
+ -
AI4
H L
CAN
+ -
24V
AC(L) AC(N)
GPS/BDS RF
L1 L2
DO12
3
NO NC
COM
Item
Remark
Name
Description
A
ETH1/ETH2
Ethernet port
ETH2 can be connected to local controller via the switch, router, and other devices; and ETH1 is used for lower-layer devices (can be connected to BCP, PCS, and the like)
B
DIN
Digital input
Node input port DIN1: Not assigned DIN2: Emergency stop node DIN3-DIN5: Not assigned DIN6-DIN13: Optional DIN14-DIN16: Not assigned
C
USB-HOST
USB interface
Software upgrade interface
6 Electrical Connection
6.1 General Safety Regulations
6.2 Terminal Introduction
Tab. 6-1 Terminal description
12
Page 19
User Manual 5. Electrical Connection
Item
Remark
Name
Description
D
SD
SD card interface
Function is reserved
E
Debug
Debugging serial port
Used for debugging local controller
F
RST
Reset port
Used for hardware reset of local controller
G
DO1~DO4
Digital output
Relay output ports, where the relay specification is 250Vac/1A or 30V/1A DO-DO4: Not assigned
H
PT1, PT2, AI1~AI4
Analog input
Function is reserved
I
A1B1~A6B6
RS485 communicatio n port
Supports 6 inputs of RS485, and can be connected to slave devices or background
J
CAN
CAN communicatio n port
Function is reserved
K
24V
DC24V power supply port
Current ≤2.0A, and the switch-mode power supply used for this port should be insulated intensely
L
AC (100~240V)
AC power supply port
Connected to 100~240Vac (50/60Hz), and the current ≤0.5A
M
GPS/BDS
GPS antenna port
Function is reserved
N
RF
Wireless antenna port
Function is reserved
O
Grounding hole
Connecting protection ground cable
P
PLC(L1/L2)
PLC Communicatio n port
Function is reserved
Digital input/output ports (DIN and DO1~DO4) are configured to collect node data and control node communication.
The farthest communication distance of COM1 to COM6 (A1B1 – A6B6) is no more than 1000m.
13
Page 20
5. Electrical Connection User Manual
High voltage on the AC power supply port! Do not operate under voltage. Make sure the input side is completely voltage-free and the grounding cable is reliably grounded before cable connection.
SD card does not support hot plugging.
The RS485 communication cable must be shielded twisted pair cable and single-point grounded.
0.2mm² ≤ the maximum cross-sectional area of the shielded twisted pair ≤ 1.2mm², and the recommended stripped length of the cable is
8mm. Keep at least 0.5m away from the strong electricity. Avoid parallel cable
layout. Use the steel tube in area with strong interference. It is recommended to add an SPD if an outdoor device is connected to
the local controller. Otherwise, the local controller may be damaged by lightning.
The local controller supports a maximum of 6 RS485 buses. COM1 to COM 5 support connections to optional devices as well as PCS, battery BMS (BMS of Samsung battery only). COM6 is used to connect touch screen and other devices.
When more than 15 devices are connected to the RS485 bus, it is recommended to connect 12Ω resistors in parallel to A and B of the devices on two ends of the bus.
6.3 Communication Device Connection
Devices that can be connected to the local controller include PCS, BCP, and the like.
6.3.1 COM Port Connection
Devices are connected to serial ports of the local controller in the daisy chain manner by using the RS485 bus.
14
Page 21
User Manual 5. Electrical Connection
It is recommended that devices of different models need to be connected to the local controller separately. For example, connect the PCS and the battery BMS to different RS485 communication ports of the local controller.
Addresses of all devices connected to each input of the bus RS485 must be within set address range of the local controller and be different from each other. Otherwise, communication failure occurs.
The baud rate of all devices connected to each bus RS485 must be consistent with that of the local controller.
IP addresses of all devices must be on the same network segment as the local controller address, and be different from each other. Otherwise, communication failure occurs.
6.3.2 Internet Port Connection
The internet port of the local controller can be connected to the PCS. Connect both the local controller and to-be-connected devices to the switch through ETH1 and corresponding network ports, where Modbus-TCP communication protocol is supported.
6.4 Connection to System EMS
The local controller can be connected to the system EMS via the Ethernet port, and the communication protocol is standard Modbus-TCP.
The connection method is as follows: In the following, an example of the connection to the background monitoring
system through the Ethernet switch is used for description.
Step 1 Insert one end of the network cable (within the scope of delivery) to the
electricity port of the Ethernet switch and the other end to the port ETH2 of the local controller.
15
Page 22
5. Electrical Connection User Manual
IP addresses of ETH1 and ETH2 cannot be on the same network segment. Otherwise, communication error occurs.
Default IP address of ETH1 is IP192.168.0.100 Default IP address of ETH2 is IP192.168.1.100 ETH2 is used by default to set the WEB of the local controller, and the
IP address cannot activate the DHCP function.
The grounding cable must be well grounded. Otherwise: Lethal electrical shock occurs to the operator in a fault case! The device can be damaged by lightning!
Step 2 Set ETH2 IP address of the local controller to be on the same network
segment as that of the background monitoring system.
6.5 Protection Earthing Connection
Step 1 Prepare the grounding cable (recommended: outdoor copper-core cable
with cross-sectional area of 4mm2 to 6mm2 or 12AWG to 10AWG) and OT terminal.
Step 2 Crimp the grounding terminal shown in the following figure.
Step 3 Tighten the M4 screw to the grounding hole according to the sequence
shown in the figure below by using the wrench with fastening torque: 5± 1N·m.
16
Page 23
User Manual 5. Electrical Connection
E
Item
Definition
Note
A
Screw
M4
B
Spring washer
——
C
Flat washer
——
D
OT terminal
——
E
Grounding hole of the local controller
——
Cable
Recommended cross-sectional area
AC cable
Cross-sectional area: 1mm
2
to 1.5mm
2
DC cable
Cross-sectional area: 0.75mm
2
to1mm
2
DC(UPS)
AC
6.6 Power Supply Connection
The local controller supports DC24V DC input or AC100 to 240V (50/60HZ) AC input. This section will take the AC power supply for example.
Step 1 Prepare power cables and phoenix terminal. Specifications of the AC &
DC cables are shown in the following table:
Step 2 Remove the phoenix terminal at the power supply port of the local
controller, and crimp the power supply terminal.
Step 3 Insert the power supply terminal to the corresponding DC/AC power
supply port.
17
Page 24
5. Electrical Connection User Manual
The local controller can connect to the DC and AC power at the same time. The DC power can be connected to the UPS and used as the standby power supply.
18
Page 25
No.
Inspection item
Result
1
Whether all cables are undamaged, well insulated, and appropriately sized.
□
2
Whether all cable are securely in place.
□
3
Whether the power supply cable and the grounding cable are correctly connected.
□
No.
Commissioning steps
Result
1
Inspection before commissioning
□
2
The local controller is powered on
□
3
Connect the debugging PC to the ETH2 (default IP address of the port is 192.168.1.100) of the local controller by using the cable. Log into the local controller operation interface via the IE browser or the Google browser.
□ 4
Ensure that the device is firmly connected to the local controller.
□
5
Perform system networking configuration and communication parameter configuration on the WEB page, where the type of actual connected device, operation strategy, and the like are consistent with actual system requirements.
□ 6
The system starts commissioning. Observe whether the device communication parameter is normal.
□
Notice: Device addresses should be different for the same communication port.
Save operations. Otherwise, the settings are invalid.
7 Commissioning
7.1 Checking before Commissioning
7.2 Running Steps
Tab. 7-1 Commissioning steps
19
Page 26
Item
Requirement
System requirement
WIN7, WIN8, and WIN10
Browser version
IE10 to IE11 and CHROME43 to CHROME45
Minimum resolution
1366*768
CPU
The clock speed is above 2.5G Hz
Memory
More than 4GB
8 WEB Interface
8.1 Requirements for Operation Environment
8.2 Preparations for Login
Set IP address of the PC to be on the same network segment as that of the local controller.
Connect the PC to the port ETH2 of the local controller.
The default IP address of the port ETH2 is 192.168.1.100. IP address of the PC can be set to 192.168.1.125 when the subnet mask can be set to
255.255.255.0.
8.3 Login Steps
Step 1 Connect the local controller to the PC by using the Ethernet cable. Step 2 Enter the IP address, for example, 192.168.1.100, of the local controller
in the PC address bar to enter the login interface shown in the picture below.
Step 3 Enter the username and password, and click login.
20
Page 27
User Manual 8. WEB Interface
In the system, there are three types of users: "operator", "administrator", and "maintainer". Default password of the "operator" is 1111, and passwords of the other two types of users can be obtained from the SungrowSumsung Energy Storage Power Supply Co., Ltd.
A
C
D
E
B
F
G
H
I
Item
Name
Description
A
Username
Display the current login user
B
Operating information
Display detailed information of the system access device
C
Parameter settings
Set system running-related parameters
D
History Records
Display history running records, history alarms, history faults, and history events of the system
E
System information
Display the software version and used for changing user password
Step 4 Select the desired language on the upper righter corner of the interface.
8.4 WEB Main Interface
The WEB interface is shown in the following picture.
21
Page 28
8 WEB Interface User Manual
Item
Name
Description
F
Display of summary operating information
Current operating mode and summary operating information of the system
G
System schematic diagram
Schematic diagram of system running
H
Language option
Used for switching between Chinese and English interfaces
I
Fault and alarm
Detailed fault and alarm information of the system
WEB Main
Interface
Operating
Information
Parameters
Settings
History
Records
System
Information
Summary
Information
Running Records
Event Records
Fault Records
Alarm Records
PCS
Information
BMS
Information
System
Parameters
Operating
Parameters
EMS Comm Parameters
Slave Unit
Parameters
Protection
Parameters
Detailed
Informatioin
When the local controller is connected to different systems and devices, the operating information interface is different.
When the connected device is set to the "enable" and "disable" states, device types and device names displayed on the operating information
8.5 WEB Menu
The WEB Menu includes four main function modules: "Operating Information", "Parameter Settings", "History Records", and "System information".
Specific classifications of the administrator menu is shown in the following figure.
8.6 Operating Information
22
Page 29
User Manual 8. WEB Interface
interface are also different. Please refer to the actual interface.
The "Operating Information" indicates detailed information of the system and the connected device, and includes:
"Summary Information", "PCS Information", "BMS Information", and "Detail Information".
8.6.1 Summary Information
The summary information interface differs due to different system configuration interface parameters. Please refer to the actual interface, and details are not described herein.
8.6.2 PCS Information
The PCS Information includes: detailed information of each PCS connected to the system.
23
Page 30
8 WEB Interface User Manual
8.6.3 BMS Information
The BMS Information includes: detailed information of each battery connected to the system.
8.6.4 Detail Information
The Detail Information includes operating information of the whole system, for example, total active power of
the PCS.
8.7 Parameter Settings
The "Parameters Settings" are used to set parameters relevant to system running and include "System Parameters", "Operating Parameters", "local controller Comm Parameters", "Slave Unit Parameters", and "Protection
24
Page 31
User Manual 8. WEB Interface
Parameter
Description
Time setting
Set the system time with the format minute/hour/day/month/year
Energy adjust
Set the energy adjustment value
Load default param
Enter the set password 1111 to restore factory defaults
User param bak
Enter the set password 1111 to backup current system configuration information
User param recovery
Enter the set password 1111 to recover parameters set by the user
system reboot
Enter the set password 1111 to reboot the system
Notice: Do not reboot the system in running state
Parameters".
8.7.1 System Parameters
The System Parameters include the following settings:
25
Page 32
8 WEB Interface User Manual
Parameter
Description
NTP parameters
After checking "enable NTP time synchronization", synchronize the time to the NTP server (such as PC and Internet server) Set server address and port number
Parameter
Description
Mode setting
Set to "Running Mode", "Power Control Mode", "Grid Power", or "Off-Grid power"
Q-ac regulation
That includes "Close", "Power Factor", and “Q-ac Power”
BMS control
Setting closing or opening of the BMS switch
Start type
Set the active or passive mode
Start & stop control
Set to start or stop
Parameter
Description
Network 1 parameters
Default IP address: 192.168.1.100
Network 2 parameters
Default IP address: 192.168.0.100
parameters
Set the Modbus parameter and TCP port number
8.7.2 Operating Parameters
Different parameters are set for the system configuration interfaces, and the running parameter interfaces are different accordingly. Please refer to the actual interfaces, and details are not described herein.
The Operating Parameters include the following settings.
Note: The table above includes all parameters that can be set, but actual configurable parameters and interfaces may vary as per system configuration.
8.7.3 Communication Parameters
The communication parameters include the following settings:
26
Page 33
User Manual 8. WEB Interface
Parameter
Description
IEC-104 parameters
Timeout T1: acknowledgement timeout of the control packet. Timeout T2: Response timeout of the monitoring
packet, where T2<T1. Parameters k and w: K is the largest number, and
W is latest acknowledgement number. The sender stops sending after sending K packets, and the receiver performs acknowledgement after receiving w packets. Range: 1 to 32767 Recommended: w<k*2/3, where k is 12, and w is 8.
Communication port configuration
According to the specific connected communication cable, select the type of the device connected to the corresponding port. If the PCS communication cable is connected to
the serial port 1, the PCS is selected as the device type for the serial port 1. The start ID is set to 1, and the end ID is set to 247.
If a device connects to 2 serial ports, start IDs
and end IDs of the two serial ports should be different from each other.
Maximum device number
Used for setting numbers of devices of different types in the system according to the actual situation. The set number should be equal to the number of actually connected devices.
8.7.4 Slave Unit Parameters
The Slave Unit Parameters are used to set communication address of the connected device. For example, for the PCS communication method, select an internet port mode, and set IP address, port number, and Modbus ID for each device.
27
Page 34
8 WEB Interface User Manual
Parameter
Description
SOC Parameters
Disabled If it is enabled, the local controller controls charge and discharge power of the system according to battery SOC information read from the BMS, so as to keep the battery SOC operating within the set section.
SOC upper limit 1 (2) level: battery charge SOC 1 (2) level upper limit
SOC lower limit 1 (2) level: battery discharge SOC 1 (2) level upper limit
SOC lower limit 1 (2) recovery: battery lower limit 1 (2) level alarm recovery value
SOC hysteresis control
SOC control delay time (s): delay of triggering battery SOC alarm
SOC control recover time (s): SOC alarm recovery delay
Vbat Parameters
Disabled If it is enabled, the local controller controls charge and discharge power of the system according to battery SOC information read from the PCS, so as to keep the battery voltage within the set section. In case of grid connection, the battery SOC or the voltage
charge and discharge sections is at the lower limit 1 to the upper limit 1.
In the off-grid case, the battery SOC or the voltage section is
above the lower limit level 2.
Vbat upper limit 1 (2) level: battery charge voltage 1 (2) level upper limit
Vbat lower limit 1 (2) level: battery discharge voltage 1 (2) level upper limit
8.7.5 Protection Parameters
The local controller protection parameters include the following settings:
28
Page 35
User Manual 8. WEB Interface
Parameter
Description
Vbat lower limit 1 (2) recovery: battery lower limit 1 (2) level alarm recovery value
Vbat hysteresis control
Vbat control delay time(s): delay of triggering battery voltage alarm
Vbat control recovery time (s): Vbat alarm recovery delay
Air Condition Param
Set alarm temperature thresholds
8.8 History Records
The History Records include "Running Records", "Event Records", "Fault Records", and "Alarm Records". A maximum of 10,000 history records can be stored, and the records can be exported in the CSV format.
29
Page 36
8 WEB Interface User Manual
8.8.1 Running Records
The Running Records include a maximum of 10,000 history records. During running, the system automatically records once every minute. The records within specified time can be queried, and the CSV export format is supported.
8.8.2 Event Records
The Event Records include a maximum of 10,000 history records. When status changes occur, the system automatically records. Records within specified time can be queried, and the CSV export format is supported.
30
Page 37
User Manual 8. WEB Interface
8.8.3 Fault Records
The Fault Records include a maximum of 10,000 history records. When faults occur, the system automatically records. The records within specified time can be queried, and the CSV export format is supported.
8.8.4 Alarm Records
The Alarm Records include a maximum of 10,000 history records. When alarms occur, the system automatically records. The records within specified time can be queried, and the CSV export format is supported.
31
Page 38
8 WEB Interface User Manual
User type
Permission
Operator
Can view running information, but cannot set parameters.
Maintainer
Can view running information and set parameters, but cannot change passwords of subordinate users.
Administrator
Can view running information, set parameters, and change passwords of subordinate users. Note: Ask Sungrow for the administrator account and password.
8.9 System Information
The System Information includes: changing passwords of all types of users and displaying software version.
User Password Changing
32
Page 39
Only approved qualified persons can service the local controller. Do not leave any screws, washers, or other metallic parts inside the
local controller. Otherwise, the device can be damaged.
After the local controller stops, wait at least 5 minutes before operating it.
9 Routine Maintenance
Affected by ambient temperature, humidity, dust, vibration, and the like, the internal components of the local controller will be aging and be worn out. Consequently, potential faults occur in the local controller. Therefore, it is necessary to maintain the local controller regularly to ensure normal and long-term operation.
All operations that can keep the local controller be in good working conditions fall within the maintenance scope.
9.1 Safety Precautions
9.1.1 General Safety Rules
9.1.2 Five Safety Rules
Observe the following five rules during maintenance or troubleshooting to ensure personal safety.
Disconnect the local controller from all external connections and internal power supplies.
Ensure that the local controller will not be powered on accidentally.
Verify that the local controller interior is completely voltage-free with a multimeter.
Perform necessary grounding connections.
33
Page 40
9 Routine Maintenance User Manual
Item
Method
Operation environment
Check to ensure that there is no strong EMI device
around the local controller.
Check to ensure that there is no hot source around the
local controller.
Check to ensure that there is no corrosive materials
around the local controller.
Hardware maintenance
Check to ensure that the power supply voltage is normal. Check to ensure that the cables are connected firmly. Check to ensure that the cable is grounded well.
System cleaning
Clean the enclosure, circuit board, and components. Clean the heat dissipation holes and the cover.
Terminal and cable connection
Check if the screws of the control terminals are loose,
and refasten them with screwdriver if necessary.
Check if the connection copper bar or screws are
discolored.
Check the wiring layout and the device terminal
connections.
Software maintenance
Log into the WEB to check the device communication
status.
Log into the WEB to check parameter settings of the
local controller.
Log into the WEB to check the software version of the
local controller.
Cover the possible live components with insulation cloth during operation.
9.2 Routine Maintenance
The following maintenance work is recommended.
34
Page 41
The ground cable must be grounded well, otherwise, Fatal electric shock may occur to the operators!
Alarm
Possible causes
Measures
PCS Fault/Alarm/EMGStop
1. A fault or an alarm occurs.
1. Troubleshoot the PCS according to the PCS manual.
2. An emergency stop occurs on the PCS.
2. Check whether the PCS is in emergency stop state.
PCS Comm Fault Alarm
Communication between the PCS and the local controller failed.
1. Check whether the communication connection between the PCS and the local controller is firmly in place.
10 Troubleshooting
10.1 Overview
The common faults and troubleshooting are shown in the table below. If problems cannot be resolved according to this manual, please contact us. We need the following information in order to provide you with better assistance.
The SN, the manufacture date, and the software version of the local controller
The manufacturers, the models, and the configuration information of the devices connected to the local controller
Brief fault description
Pictures of the fault site
10.2 Alarm Diagnosis
10.2.1 Alarm Information on Power Conversion System (PCS)
35
Page 42
10 Troubleshooting User Manual
Alarm
Possible causes
Measures
2. Check whether the IP address and Modbus address of the PCS are correctly set.
PCS AC- side Disconnect
AC circuit breaker of the PCS is open.
Close the AC circuit breaker.
PCS Direct Grid V-Diff too Large Alarm
In the case that multiple PCSs are directly connected in parallel on the AC side, battery voltages on the DC side differ from each other, and the difference exceeds the set value.
1. Check whether the parameter is set to an appropriate value.
2. Check whether "Balance Control Enable" is enabled.
3. Check whether voltage equalization is invalid.
PCS not Ready Alarm
1. The PCS is faulty.
1. Check whether PCS has a fault.
2. An emergency stop occurs on the PCS.
2. Check whether the PCS is in the emergency stop state.
3. PCS container node collects node fault.
3. Check whether the dry contact in the PCS container is faulty.
4. The BCP is faulty.
4. Check whether faults occur in the BCP.
5.The number of racks in normal operation is less than the lower limit.
5. Check whether The number of racks in normal operation is less than the lower limit. Note: When the alarm occurs, the corresponding devices (including the PCS, PCS container, battery, and battery container) cannot operate.
Note: * applicable only to SC1000 whose AC side is directly connected in parallel.
36
Page 43
User Manual 10 Troubleshooting
Alarm
Possible causes
Measures
Note
One or More Low Battery Level1
Battery voltage/SOC is lower than the "Vbat Lowlimit1".
1. Reduce discharging power.
In the on-grid mode, the local controller will limit the discharging power of the PCS until it drops to 0, but the charging power is not affected.
In the off-grid mode, the user-side EMS needs to control external load power.
2. Check whether the protection parameter is set to an appropriate
One or More High Battery Level1
Battery voltage/SOC is higher than the "Vbat Uplimit1".
1. Reduce charging power
In the on-grid mode, the local controller will limit the charging power of the PCS until it drops to 0, but the discharging power is not affected. In the off-grid mode, the user-side EMS needs to limit the external power to be fed into the system.
2. Check whether the protection parameter is set to an appropriate value.
One or More Low Battery Level2
Battery voltage/SOC is lower than the "Vbat Lowlimit2".
1. Stop discharging.
In the on-grid mode, the local controller will control the PCS to enter the standby state (or control the PCS to perform
10.2.2 Alarm Information on Battery
37
Page 44
10 Troubleshooting User Manual
Alarm
Possible causes
Measures
Note
2. Check whether the protection parameter is set to an appropriate value.
zero-power operation if there is no standby state), but the charging power is not affected. In the off-grid mode, the local controller will control the system to shut down.
One or More High Battery Level2
Battery voltage/SOC is higher than the "Vbat Uplimit2".
1. Stop charging
In the on-grid mode, the local controller will control the PCS to enter the standby state (or control the PCS to perform zero-power operation if there is no standby state), but the charging power is not affected. In the off-grid mode, the user-side EMS needs to stop the external power being fed into the system.
2. Check whether the protection parameter is set to an appropriate value.
Battery Group DC V-Diff too Large
For multiple of BCPs, or the system in which battery DC sides are directly connected in parallel, "Battery Direct Connect Voltage Value" is greater than the set value.
1. Check whether the parameter is set to an appropriate value.
When the alarm occurs, the local controller does not respond to the instruction sent by the customer EMS to close the BMS contactor.
2. Check whether the system voltage difference between battery racks whose DC sides are connected in parallel is relatively large.
38
Page 45
User Manual 10 Troubleshooting
Alarm
Possible causes
Measures
Note
Low online rack num
For the standard battery, the alarm occurs when the online Rack number is lower than the set "Rack Num".
1. Check whether the batteries are faulty.
-
2. Check whether the related parameter of the local controller is appropriately set.
BMS Comm Fault Alarm
Communication between the BMS and the local controller failed.
1. Check whether the communication cable connecting the BMS and the local controller is firmly in place.
-
2. Check whether the IP address and Modbus address of the BMS are correctly set.
3. Check whether the serial port via which the BMS is connected to the local controller is correctly configured.
BMS Fault Alarm
The battery system or Rack is faulty.
Refer to the measures for battery fault.
-
BMS Alarm
The battery system or Rack gives an alarm.
Refer to the measures for battery alarm.
-
Alarm
Possible causes
Measures
BCP Alarm(including BCP fault, alarm, emergency stop)
A fault or an alarm occurs in the external devices connected to the BCP, such as air conditioner and smoke sensor.
Check whether the devices connected to the BCP, such as the air conditioner and smoke sensor run in the normal state. If a fault such as smoke sensor overtemperature occurs or fire fighting is
10.2.3 Alarm Information on BCP
39
Page 46
10 Troubleshooting User Manual
Alarm
Possible causes
Measures
triggered, the local controller shuts down this battery rack and the BCP
BCP Comm Fault Alarm
Communication between the BCP and the local controller failed.
1. Check whether the communication cable connecting the BCP and the local controller is firmly in place.
2. Check whether the IP address and Modbus address of the BCP are correctly set.
3. Check whether the serial port via which the BMS is connected to the local controller is correctly configured.
Alarm
Possible causes
Measures
Node collector Comm Fault Alarm
Communication between the PCS dry contact and the local controller failed.
1. Check whether the communication cable connecting the node and the local controller is firmly in place.
2. Check whether the IP address and Modbus address of the node contactor are correctly set.
Node Collector Node Abnormal
The PCS dry contact collects node signals.
Check whether the device connected to the corresponding dry contact is normal. The dry contact can be configured for alarm or fault collection. When it is configured for alarm, the node reports alarm information. When it is configured for fault collection, the node can control all PCSs in the container to shut down via
10.2.4 Other Alarms
40
Page 47
User Manual 10 Troubleshooting
Alarm
Possible causes
Measures
the local controller.
Node 1/2/3/4/5/6/7/8 Alarm
Dry contact of the local controller collects node signals.
Check whether the device connected to the corresponding dry contact is normal. The dry contact can be configured for alarm or fault collection. When it is configured for alarm, the node reports alarms.
Air Condition Temperature Abnormal
The actual temperature in the battery container is higher than "Air Condition T Uplimit Value" or Air Condition T Lowlimit Value ".
1. Check whether the air conditioner in the battery container is faulty.
2. Check whether the parameters such as "Air Condition T Uplimit Value" or Air Condition T Lowlimit Value ". are appropriately set.
Master Alloc Abnormal Alarm
When multiple PCSs are directly connected in parallel on the AC side, there is no master or more than one master.
Check the setting of master and slave.
Fault
Possible causes
Measures
PCS fault
1. The grid is powered off and the PCS is faulty.
1. Check the grid state, and check whether the voltage frequency is normal.
Note: * applicable only to SC1000 whose AC side is directly connected in parallel.
10.3 Fault Diagnosis
10.3.1 Fault Information on Power Conversion System (PCS)
41
Page 48
10 Troubleshooting User Manual
Fault
Possible causes
Measures
2. PCS AC circuit breaker is open.
2. Check whether the PCS AC circuit breaker is closed.
PCS comm fault
The grid is powered off and the PCS fails to communicate with the local controller.
1. Check the grid state, and check whether the voltage frequency is normal.
2. Check whether the communication cable connecting the PCS and the local controller is firmly in place.
3. Check whether the IP address and Modbus address of the PCS are correctly set.
PCS Address Conflict
Multiple PCSs have the same Modbus address.
Check the Modbus address setting.
PCS not Ready Fault
Refer to " PCS not Ready Alarm".
Micro start timeout
1. The PCS is in the local mode.
1. Check whether the PCS is in the local mode.
2. Communication between the PCS and the local controller is abnormal.
2. Check whether the communication between the PCS and the local controller is normal.
Micro Start Fail
1. The PCS is connected to the grid.
1. Disconnect the PCS from the grid.
2. The Soft-Start Voltage is abnormal.
2. Check whether the Soft-Start Voltage is normal.
3. The micro-grid voltage range is inappropriate.
3. Check whether the micro-grid voltage range of the local controller is appropriately set.
Stop timeout
1. The PCS is in the local mode.
1. Check whether the PCS is in the local mode.
2. Communication between the PCS and the local controller is abnormal.
2. Check whether the communication between the PCS and the local controller is normal.
42
Page 49
User Manual 10 Troubleshooting
Fault
Possible causes
Measures
Grid Start Timeout
1. The PCS is in the local mode.
1. Check whether the PCS is in the local mode.
2. Communication between the PCS and the local controller is abnormal.
2. Check whether the communication between the PCS and the local controller is normal.
Grid Start Fail
1. The gird is abnormal.
1. Check whether the grid frequency or voltage is abnormal.
2. The grid voltage range is inappropriate.
2. Check whether the grid voltage range is appropriately set.
Fault
Possible causes
Measures
Upper Computer Comm Err.
Communication between the local controller and the user-side EMS times out.
1. Check whether the communication cable between the local controller and EMS is firmly in place.
2. Check whether the communication between the EMS and the local controller is normal.
Self Check Timeout
PCS is running in the local mode.
Check whether the PCS is in the local mode.
Self Check Fault
1. The gird is abnormal.
1. Check the grid status.
2. PCS is faulty or shuts down due to emergency.
2. Check whether the PCS is faulty or has shut down due to emergency.
3. The battery is faulty.
3. Replace the faulty battery.
4. Container node is faulty.
4. Check the status of the container node.
Master Alloc Abnormal
Refer to the "Master Alloc Abnormal Alarm".
10.3.2 Fault Information on Grid
10.3.3 Other Faults
43
Page 50
10 Troubleshooting User Manual
Fault
Possible causes
Measures
Nodes 1-8 Fault
Dry contact collection port of the local controller collects node signals.
Check whether the device connected to the corresponding dry contact is normal. The dry contact can be configured for alarm or fault collection. When it is configured for fault collection, the node can control the system to shut down via the local controller.
Power-on failure
1. The power supply port of the local controller is not connected to the power source.
1. Check whether the power cable connecting the local controller is firmly in place.
2. The power source is faulty.
2. Replace the power source.
3. The local controller is faulty.
3. Contact us.
Failure to communicate with background
1. Communication between the local controller and the
background failed.
1. Check whether the Ethernet port of the local controller is firmly in place to the PC or router.
2. The network parameter is incorrectly
set.
2. Check whether the network parameter is correctly set.
3. The forwarding protocol is incorrectly
configured.
3. Check whether the forwarding protocol is correctly configured.
44
Page 51
Port
Ethernet
2 inputs, 10/100M
RS485
6 inputs Support baud rates 9600 to 38400
USB
Reserved function CAN
SD
Digital input
16 inputs
Digital output
4 inputs
Analog input
Reserved function
Device connection
Max. device number
Maximum device numbers:
60 PCSs 60 BMSs 60 groups 60 sub-systems
Communication manner
RS485 and Ethernet
Max. communication distance
RS485: 1000m(COM1~COM6)
Ethernet: 100m
Other parameter
Display
WEB and LED indicator
Language
Chinese , English
Power supply
AC100 to 240V(50/60HZ) or DC12 to 24V
Power consumption
Typically 5W and 10W at most
Mechanical parameter
Dimension (W*H*D)
440x241x44mm
Weight
3kg
Protection degree
IP20
Installation method
Wall mounting and rack mounting
Altitude
≤4000m
Environmental parameter
Operation temperature
-30℃ to +60℃
Storage temperature
-40℃ to +85℃
Operation humidity
0 to 95% and no condensation
11 Appendix
11.1 Technical Data
45
Page 52
11 Appendix User Manual
Abbreviation
Explanation
PCC
Point of Common Coupling
BMS
Battery Management System
CAN
Control Area Network
CC
Constant Current
CP
Constant Power
CV
Constant Voltage
DOD
Depth of Discharge
MCCV
Maximum Charge Current
MDCV
Maximum Discharge Current
RH
Relative Humidity
SOC
State of Charge
SOH
State of Health
NTP
Network Time Protocol
11.2 Abbreviation Explanation
11.3 Quality Assurance
Evidence
Within the warranty period, SungrowSamsung (Hefei) will require the customer to present the purchase invoice and date. The trademark on the product shall be clearly visible. Otherwise, SungrowSamsung shall hold no liability.
Conditions
If the product covered by warranty becomes defective during warranty period, SungrowSamsung (Hefei) will provide a totally-free repair or exchange.
The unqualified product that is replaced shall be returned to SungrowSamsung (Hefei).
Customers shall leave proper time for us to repair the failed device.
Damage and claims arising from the followings are not covered by the warranty of SungrowSamsung (Hefei):
Transport damage
46
Page 53
User Manual 11 Appendix
Company:
Sungrow-Samsung SDI Energy Storage Power Supply Co., Ltd.
Website:
www.sungrowsamsung.com
Email:
Address:
No. 788 Mingchuan Rd., Baiyan Science and Technology Park, New & High Technology Industrial Development Zone, Hefei, P. R. China.
Telephone:
+86 551 6532 6000
Incorrect installation
Incorrect alternation
Inappropriate operation
Use of this product in harsh environment beyond the specification in this manual
Damage caused by abnormal natural environment
11.4 Contact Information
Should you have any questions or queries about this product, please contact us through the following information. We will be more than happy to assist you!
47
Loading...