Sundrax DALIGate DIN Series, DGD-1-DE4DALI, DGD-1-DE2DALI User Manual

Page 1
User manual
DALIGate DIN
DGD-1-DE2DALI, DGD-1-DE4DALI
Version 1.11
March 22, 2018
Page 2
Table of contents
•ArtNet settings
•DALI control
•Network settings
Operation Technical maintenance Connection scheme
1 1 2 2 3 3 4 5 6 7 7 8
Page 3
Visual appearance
1
Pic.1 DALIGate DIN device appearance
Specifications
Supported protocols: ArtNet, sACN, DMX512, RDM, DALI Data refresh rate: 44 Hz DMX ports: 1 isolated DMX connectors: Terminal blocks 15EDGVC Controllable output lines: 2 or 4 DALI Ethernet port: 10/100 Base-TX Power supply:
~90-250 VAC, 50/60 Hz or
15V
Mains Fuse: 0.5 A Operating Temperature: -40...+70°C IP Rating: IP 20 Dimensions, mm: 142(D) x 105(H) x 75(W)
ON
1
1 DMX 512 input 4 Trigger inputs 7 Power input 2 DMX512 terminator 5 LED indicators 8 Ethernet port 3 DALI outputs 6 Fuse 9 Ground terminal
6
1 2 3 3 4 5
7 3 3 8 9
Page 4
Safe operation
WARNING!
The device uses hazardous voltage AC 230 V
General information
2
In installation, operation, preventive maintenance and repairs of
the device, the requirements of the safety rules must be followed.
To ensure safe and reliable operation of the devices, please ob-
serve the following requirements:
• Use the device only for its intended purpose;
• Do not use devices that shows signs of malfunctioning;
• Avoid strong physical impacts on the device;
• Protect devices and cables from contact with moisture or other
corrosive liquids;
• Prevent any improper disconnection of the Ethernet cable from
the device being disconnected.
Whenever a fault is detected in the device, please contact the
manufacturer.
DALIGate DIN is DIN rail mounted converter that converts Art­NET/sACN/DMX signal into DALI protocol to include DALI light­ing fixtures into controllable lighting network.
With DIN rail mounting hassle-free installation and ArtNET/ sACN/DMX input, DALIGate DIN is ideal as indoor solution for mixed lighting control purposes in theatres, small venues, architec­tural installations, industrial, warehouse, and agricultural lighting.
Key features
• 2 DALI interfaces
• No external power supply for DALI is needed
• Simple web interface
• Selectable ArtNET/sACN or DMX512 control
Page 5
3
Installation
1. Ensure the device has no damage due to transportation.
2. Mount device on DIN rail.
3. Connect Ethernet cable.
4. Connect DMX line input (if necessary) and DALI lines outputs.
5. Connect the power cable.
6. After few seconds, port status LEDs will indicate the state.
Open device’s web-interface on the computer connected to the same network as the DALIGate device.
7. Open the Network Settings tab.
8. STATIC IP ADDRESS field will display the address of the de-
vice, SUBNET MASK field will display the network mask. If neces­sary, fill the IP and Subnet fields for the required network settings (by default, device has IP 2.0.0.100 and Subnet 255.0.0.0). Click “Save settings” so that the new settings take effect.
Before mounting and power up, it is necessary to verify protec-
tive earthing and cable connections.
Web interface
DALIGate DIN devices support configuring most of their parameters through the Web-interface using HTTP protocol (TCP port 80).
Page 6
4
Pic.2 ArtNet settings
Device name – edit device name;
Device description – editable device description;
Input data protocol – switching input data source: ArtNet, sACN,
DMX512.
Channel 1 and Channel 2 configuration:
Subnet *16 +
Universe
Art-Net subnet number (0-15),
Art-Net universe number (0-15);
or sACN universe number (1-65279)
Start Address DMX start address for the channel
Mode
Conversion mode:
BROADCAST, GROUP, INDIVIDUAL
To save the changes in ArtNet settings, click “Save settings”.
ArtNet settings
To access the settings page enter the IP address of the device to the browser. ArtNet settings page will be displayed.
Page 7
5
DALI control
To edit the settings of one of DALI interfaces, click on the link “DALI1 CONTROL” or “DALI2 CONTROL”.
Pic.3 DALI control settings
Current DALI Network- shows the devices found on DALI line.
Short Address Individual address of DALI device (0-63)
Device Type Code of type, returning by device
Group Current group number (0-15) Check Checkbox for switching device individually on and off
Search – searching connected devices.
Refresh – refresh list of detected devices.
All devices ON – switch on all devices.
All devices OFF – switch off all devices.
ADDR N, GROUP M, Add to group, Remove from group­adding/removing device N to/from group M.
Page 8
6
Pic.4 Network settings
Network settings
To edit the network settings of the device, click on the link “Network Settings”.
Static IP address – main network address of the device;
Subnet mask – the mask of the IP subnet;
Default Gateway – network address of the gateway (if ability
to operate via the Internet is required);
To save the changes in Network settings, click “Save settings”.
Page 9
7
DALIGate devices start their normal operation in a few seconds after they have been powered up. Device always operates based on last saved settings. Viewing DALIGate settings does not affect normal operation until any of the settings have been saved. When changes are saved, the device applies the new settings immediately, without having to power it down.
Actual control of DALI devices is performed based on DALI interface conversion mode. If BROADCAST mode selected, value of START ADDRESS in ArtNet/sACN or DMX universe controls all devices on DALI line. If GROUP mode selected, 16 values beginning from START ADDRESS control the groups 0-15. If INDIVIDUAL mode selected, 64 values beginning from START ADDRESS control DALI devices 0-63.
Individual addresses of DALI devices are assigned during search procedure. After all devices found, they may be individually checked by clicking checkbox. Group number may be assigned to DALI device, to enable group conversion mode.
Operation
Maintenance the device, search and troubleshooting should be performed by service personnel. The device should be free from dirt, dents, connecting cables and wires must be intact and securely fastened.
Technical maintenance
Page 10
8
Connection Scheme
ArtNet/sACN/Other
ON
1
DMX
N
L
DALI
DALI
Ballasts/Drivers
with Dimming Control
(interface DALI)
DALI controllable equipment 1
DALI
controllable
equipment 2
DALI DALI
Page 11
9
Please send all your warranty-related questions to
support@sundrax.com
All Sundrax products are covered by a 36 months warranty.
Page 12
Sundrax Electronics,
6008, First Central 200
2 Lakeside Drive, Park Royal, London NW10 7FQ United Kingdom + 44 (0) 208 991 33 19 office@sundrax.com www.sundrax.com
Loading...