Sunchaser Duo-Therm Rotary XL 55812.041, Duo-Therm Classic 54812.041, Duo-Therm Classic 54815.041, Duo-Therm Classic 54812.042, Duo-Therm Rotary XL 55812.042 Installation And Operating Instructions Manual

...
Page 1
INSTALLATION
and OPERATING
INSTRUCTIONS
ROOF MOUNT
AIR CONDITIONER
Rotary XL (558 Series)
and Classic (548
QUICK START
SHUR START
MODELS
MODELS
54812.041
54812.042
55812.041
55812.042
54815.041
54815.042
54815.043
54815.044
55815.041
55815.042
READ THESE INSTRUCTIONS CAREFULLY, KEEP FOR FUTURE REFERENCE.
AVIS:
Cet appareil
doit
etre
repare
seulement par
un reparateur
autorise.
Modification de
I’appareil pourrait
etre
extremement
dangereuse.
CAUTION
MODIFICATION OF THIS APPLIANCE
CAN
BE
EXTREMELY
HAZARDOUS.
ALWAYS CONSULT
THE MANUFACTURER BEFORE MAKING CHANGES.
et pourrait
Causer
mal ou mort.
Form No. 19-1112-2 7-14-80
Page 2
SPECIFICATIONS
* For
two units
USE
5000 watt generator
DUO-THERM TESTED UNDER ARI STANDARD 250-74
UL STANDARD 484
.
CSA STANDARD 22.2 No.
0,46
and 119
14” x 14” OPENING FROM ROOF VENT REMOVAL
Right
1.
Normally, roof mount air conditioners are installed where an existing roof vent has been removed. This creates the
14” x 14” opening required for installation (Fig. 1). If an opening has to be cut, be sure to check for proper clearance on the inside of the RV for the air box (Fig. 2) and on the outside for the unit. (Fig. 3).
AIR
CONDITIONER DIMENSIONS
7
ROOF FLASHING DIMENSIONS
(On
Top of Vehicle)
7 I
FIG. 2
Left
RIGHT
Air Box Perimeter
I
LEFT
MINIMUM DISTANCE TO ANY
VERTICAL SURFACE (Example:
Luggage Rack) FOR CONDENSER
AIR FLOW
14” x 14” OPENING
FIG. 3
-2-
Page 3
INSTALLATION LAYOUT
Fig. 4
AIR CONDITIONING UNIT
NOTE:The anchor bolts, supplied as standard equipment, will cover a range of 2
3/8"
to 4
1/8" roof thickness. For roof thicknesses, other than the standard, special Bolt Kits can be obtained by
special order. For roof sections thinner than the standard, bolts can be cut off, care must be taken so that threads are not damaged. Bolt Kits are available as follows:
Threaded Hole
ROOF
KIT PART NO.
THICKNESS RANGE
3-14870(std)
2-3/8"
to 4-
1/8"
3-14867(opt)
1 to 2-3/8”
314868(opt)
3-3/4" to 5-1 /4"
314869(opt)
5-
1/4" to 6- 1/8"
(B)
Machine Screw
1
(Cl
Hex Nut
2
(D)
Nut & Lockwasher 4
Total No.
x
v B
@
e
63
(E)
Self Taping Screw 4
(Blunt Point)
(F)
Wire Connector
2
(G)
Anchor Bolt (Straight)
1
(H)
Anchor Bolt (Hook) 3
OPTIONAL HEAT PACKAGE AVAILABLE FROM DEALER
PART NUMBER 3-15603 SOLD IN U.S.A. ONLY (UL Listed)
AIR BOX ASSEMBLY 3-13577 FOR CANADA
(CSA
Certified)
MOUNTING PARTS
Roof
Flashing
Adhesive .
Return Air
J
Conduit Attached to Unit
\
Control
BOX
./
Guide Flanges
7
Power Supply Line
\
Framing Stock
Page 4
2.
4.
6.
Framing is required to provide adequate support and a smooth surface for sealing. Under no circumstances should the roof be constructed to create a low spot where water will accumulate. Any opening between the roof and ceil­ing should be framed to prevent hot or cold air from being drawn from the cavity. (Be sure to provide opening for electrical supply line.) (See Fig. 4).
In the carton you will find the “return air duct”, an alumin-
um piece of sheet metal folded flat. Unfold and form into a square (approximately 14” x 14”) to line the roof opening.
Form tabs approximately 1” wide along top edge to rest
against the roof.
Place duct through opening then mark and remove any excess that protrudes beyond the ceiling. (Hole is provided for supply line.) (See Fig. 4).
Run power line to roof opening:
If vent fan was removed,
the existing wire may be used provided it complies with all National, State and Local wiring codes.
NOTE: Be
sure power supply is OFF.
The power line should be a
separate circuit using 12 AWG size wire and maximum
circuit protection (20 AMP time delay).
Installation of roof flashing:
(Reference Fig. 4) CAUTION:
Be sure all roof seams are sealed and surface is clean be­fore proceding.
a. Peel
off the protective wax paper from the adhesive
a.
on the bottom of roof flashing.
Place roof flashing over 14” x 14” opening - flanges on bottom will help assure proper alignment. Be sure marking “REAR” is toward rear of vehicle.
b.
Once you are sure of proper alignment, press down around outer edges to help hold in place. Seal will
be completed when unit is torqued down.
Install air conditioner on roof flashing: (Reference Fig. 4) Using the roof flashing guide flanges, position the air condi-
tioner over the corresponding openings, CAUTION: Do not damage the foam tape sealer on the flashing as this
makes
the sear between it ande unit. The outside
installation
is now completeand any minor positioning can be made
from inside.
(Ceiling Template)
7.
Ceiling Template Installation: Open the plastic bag of mounting parts and use the Installation Layout on Page 3 for
reference.
a.
The control box which is permanently connected to
the unit is wrapped in cardboard and stored in the
return air opening for shipping. Pull down, being
careful not to damage coil fins, and discard wrapper.
Let hang until ceiling template is installed.
b.
Install the straight anchor bolt
(G)
into the threaded hole located opposite the discharge air opening in the bottom of the unit. Screw the end with
3/8”
of
thread in until finger tight. (See Fig. 5).
C.
Slide the ceiling template over this bolt andengage the discharge air duct to check for proper alignment.
(The
upper
duct fits inside
the lower.)
Perforated
tabs may be removed for
thin
roof
sections.Remove both tabs for roofs 1” to 2” thick; remove 1 tab for roofs 2” to
3”thick,
and as received for roofs
3” to 4
1/4"
thick.
For roof thickness greater
than 4
1/4",
a duct adaptor (Part No. 3-13606) is
available upon request.
d.
If alignment is correct, proceed with installation; if slight adjustments are necessary, make these before continuing.
e.
Put Nut
(D)
on straight anchor bolt finger tight to
hold template while installing the three (3) hook bolts
(H)
in the remaining corners. The nuts may
be installed finger tight on the bolts to aid in holding the template. (See Fig. 5).
f.
g.
Secure ceiling template with four (4) wood screws (A), two (2) in each end. (See Fig. 5).
Evenly tighten the four (4) anchor bolt nuts (D) to secure the unit and insure a proper roof seal. Since these nuts have lock washers, do not over tighten, 75 in. Ibs. or 6
1/4
ft. Ibs. torque is recommended.
Hook Bolt (H)
/
Wood Screws (A)
Page 5
8.
9.
10.
Control Box Installation: Fasten the control box to the
11.
Install Air Box: (Reference Fig. 7)
Mounting requires
ceiling template with two blunt point screws (E).
(See
four (4) wood screws (A); one (1) machine screw (B); and
Fig. 6 ).
Install one screw (A) in the junction box (part
two (2) hex nuts (C) to install the air box. (Reference
of the control box) which holds it to the ceiling.
Fig. 4).
Connect Power Supply: As mentioned previously, all wiring must comply with the American National Standard Insti­tute, National Electrical Codes and all local codes. NOTE: All required installation hardware is supplied.
a.
Remove the
return
air grille held by two (2) quarter
turn fasteners.
b.
a.
The supply line should be routed to the junction box and secured by the cable connector provided. Six inch tails are sufficient for connection to unit wires and ground screw. (See Fig. 6).
Remove the small cover plate at the end opposite the return air grille, Care must be used not to break the two mounting legs as this piece will be reinstalled
later.
C.
b.
Connect the white wire in the junction box to the white or neutral wire from the supply line with one of the twist type connectors provided.
NOTE: If optional heat package is to be installed, do so before air box is installed. Refer to instructions
provided with heat package accessory 3-15603.
d.
Install air box over two weld studs on ceiling template and secure with nuts (C).
C.
Connect the black wire in the junction box to the
black or hot
wire from the supply line with the other
twist connector.
e.
Install machine screw (B) in hole that was uncovered
by small plate. Tighten screw and nuts.
d.
Connect the ground wire to the identified ground screw. (See Fig. 6 ).
f.
Install four (4) wood screws (A) that hold air box tight to the ceiling.
e.
Install junction box cover with two blunt point screws (E). (See
Fig. 6).
Reinstall cover plate and return air grille.
h.
You are now ready for operational check and many hours of comfort!
Place thermostat sensor tube in ceiling template bracket with small rubber grommet. (See Fig. 6 ).
Thermostat Sensor Tube
/
Bracket and Grommet
7
Plug for Optional
I
Electric Heater
Wood Screw
(A)
Wood Screw
(A)
Machine Screw (B)
Page 6
12.
FOR COOLED AND DEHUMIDIFIED AIR set the thermo-
stat dial to the desired temperature. The warmest setting
(WARM) on the dial is approximately 95 degrees;
the
coolest setting (COLD) is approximately 70 degrees. Place blower selector switch in desired position. High-cool,
medium-cool or low-cool positions are used when air condi­tioning is desired. In these positions, the blower will operate continuously and the compressor will come on when the thermostat calls for cooling and off when the desired tem­perature has been
reached.
FOR CIRCULATED AIR ONLY place the selector switch in
the desired position. High Fan, Medium Fan and Low Fan positions will circulate
inside
air and not operate the com-
pressor for cooling.
FOR HEATED AIR, with the optional heat package instal­led, place selector switch in the desired position. High Heat,
Medium Heat and Low Heat positions will circulate the
air and allow the heater to cycle on the thermostat that has been set at the desired temperature. Since actual BTU out­put is not affected by blower speed, it is recommended that
Low Heat position be used. NOTE: On units that do not have the optional heat package installed, these positions will act to circulate the inside air only.
Adjust the louvers at the air discharge openings for best air
zb&ib;tion.
(These louvers should never be completely
TO COMPLETELY SHUT DOWN THE UNIT, place the blower switch in the “OFF” position.
NOTE: Shur-Start models have a delayed start kit installed.
When the unit is turned on, the fan will start and in approxi-
mately two (2) minutes, the compressor will start. After the
compressor has shut down, it will not restart for approxi-
mately two (2) minutes. This allows pressures to equalize in the refrigerant system and eases the starting load for the compressor.
Quick-Start models do not have the delayed start feature. When the unit is turned on, the fan and compressor start at the same time. After shutdown, wait three (3) to four (4)
minutes before restarting unit to allow pressure equalization.
13.
Air Filter - Your air conditioner will operate more effi-
ciently with a clean filter. Periodically remove and wash
the filter with soap and warm water, let dry and reinstall.
Replacement filters are available from your R.V. Dealer, DUO-THERM Service Center or Distributor. Order Part No. 3-8166.
Motor Lubrication
-
The motor has sealed-bearings and with normal usage will not require oiling. On some motors oilers may be included and can be lubricated with
non-
detergent SAE 20 motor oil if you desire. Protective Cover
-
To keep outdoor portion of your air
conditioner free from foreign material during the
off­season, a protective vinyl cover is available as an option­al item.
Order Part Number 3-9937 for the 54812,
54815, 55812 and 55815 Series.
NOTE: Be sure to
remove cover before operating the unit.
If service work is needed refer to the 19-1073 Service Directory supplied, with the unit for the name of the_ nearest authorized service enter. When requesting service, always give complete model and serial numbers located on the plate
at
the rear of the
outdoor portion of the air
conditioner.
Page 7
WIRING DIAGRAM
COMPRESSOR
I
I
I
FACTORY WIRING
-
PL_
GRN
WHT
FIELD WIRING
---_
BLK
115 V.A.C. 60~ If
SHUR START ONLY
I-
CIRCUIT DIAGRAM
FAN
CAP
GRD.
Therm.
Page 8
DUO-THERM, Division of Motor Wheel Corp.,
LaGrange,
Indiana 46761
Loading...