Sub-Zero SZ-7512-P Operating Instructions Manual

SZ-7512-P
OPERATING
INSTRUCTIONS
4
To set other parameters.
Display will show ‘P5’ & flash to go other parameters, use UP / DOWN keys.
Press and DOWN(prg) key for 2 seconds.
hold
prg
Introduction: SZ-7512-P(Antifreeze thermostat)
Operating Instructions
The SZ-7512-P is a digital antifreeze thermostat with manual reset
O
facility and alarm (Buzzer) facility, this has a fixed differential of 2 C The SZ-7512-P can be used as a direct replacement to the following mechanical antifreeze thermostats :-
(a) Honeywell T675-B, (b) Danfoss-KP61, (c) Ranco-6953, (d) Johnson A19ACA-15C,(e) White Rodgers 16A60-9. The alarm is automatically set equal to the set point and can be
muted with the ‘RST’ key. The controller functions similar to the above mentioned
mechanical thermostats i.e. relay will go off when the set point is achieved and the same can be restarted only if the differential is reached and the ‘RST’ key is pressed.
1
INDEX
2
Para. Page
Description
P5 LP AL FS EP
3 4 5 6 7 8
9 10 12
13-14
To set the Set Point of the controller. How to set other parameters. Probe calibration. Keypad lock. Alarm - to activate buzzer. Restore factory defaults. End Programming & keypad functions. Operating messages. Wiring Diagram. Panel cutout & dimensions.
3
Function: T point of the controller.
o set the cut out
Display will change to set range flash. The set point range can now be changed by using the UP/DOWN keys. After setting the desired range, press the SET key and you will see“_ _ _" which confirms that the set point has been stored in memory.
Set point
Press and the SET key for 2 seconds.
hold
-50
O
C
50
O
C
3
O
C
Min
Max
Fac.
www.ascontrols.com
INDIA
P5 parameter
Function: To set probe calibration.
To change the P5 parameter, press the SET key.
Use UP/DOWN keys to set desired range. In time it may be possible that the display may be offset by a degree or so. To compensate for this error, you may need to add or minus the degrees required to achieve the correct temperature. Setting range
O O
is from -10 C to + 10 C
O
-10 C
Min Max
Fac.
O
+10 C
O
0 C
Example: The temperature on
O
the display is 28 C, whereas the
O
actual temperature is 30 C. You will need to set the P5 mode to 2, which means that once out of the programming mode, the display will show the temperature
O O O
30 C (28 C + 2 C).
5 6
LP parameter
Function : To lock keypad.
0 1 0
Min Max
Fac.
To change the LP parameter, press the SET key.
Use UP/DOWN keys to set desired range. This Parameter can lock the keypad so that tampering is not possible by by-standers.
When set to 0= keypad unlocked 1= keypad locked
When locked all parameters can only be viewed, but not modified.
7
AL parameter
0 1 1
Function: To activate / deactivate alarm.
To change the AL parameter, press the SET key.
Use the UP/DOWN keys to set alarm on or off. Once set to on, the buzzer will come on incase the temperature is equal to the set point.
1 = Activates Buzzer. 0 = Deactivates Buzzer.
Note=Alarm will be ON in probe fail condition irrespective of AL parameter
Min Max
Fac.
FS Parameter
Function : To restores default settings of the controller.
To change the FS parameter, press the SET key.
When set to 1 all parameters are programmed to default values. Useful to debug setting related problems.
0 1 0
Min Max
Fac.
8
9
EP Parameter
Function : To end programming.
To end programming press the SET key
Once the SET key is pressed, the controller goes into the normal mode and displays the temperature and all settings are recorded.
This key will reset the relay and mute the buzzer alarm.
Reset key
RST
10
Operating messages and Icon status
Parameter
Set Point
AL , P3
Message Description
Lt
Temperature is equal to the set point.
PP
Probe short circuit, circuit open or without
0 0
probe, or temperature >50 C or < -50 C
Alarm (Lt or PP)
LP
Keypad locked/unlocked.
O
SP + 2 C
Compressor Relay On/Off.
On/Off
On/Off
Flashing
9
12
+
-
BUZZER
To SZ-B75
(10Vdc, 10mA max)
Low TempTrip Lamp
or Other Load (5A max)
Compressor or
Contactor
or Heater
8(3)A max)
Caution : Wiring Shown for 230Vac Loads Only.
12
11
15 16
Installation : Fixing and dimensions of panel models:
To fix the unit, slide the fastener 1 through the guides 2 as per the position shown in the figure. Move the fastener in the direction of the arrow, pressing tab 3 it permits to move the fastener in the opposite direction of the arrow. Once the controller has been connected, they should be covered with the lid 4 Silicon sealant should be applied along the perimeter of the panel cut out or a rubber ‘O’ ring supplied before the unit is fitted to obtain IP65 grade.
Alarm (Buzzer) : Only use SZ-B75 buzzer with SZ­7512-P series controller. Use of any other type of result in permanent damage to the controller and may cause personal injury.
Controller :Controller should be installed in a place protected by vibration, water and corrosive gasses and where ambient temperature does not exceed the values specified in the technical data. Probe :To give a correct reading, the probe must be installed in a place protected from thermal influences, which may affect the temperature to be controlled.
CAUTION
WIRING: The probe and its corresponding wires should never be installed in a conduit next to control or power supply lines. The electrical wiring should be done as shown in the diagram. The power supply circuit should be connected to a protection switch. The terminals admit wires of upto 2.5sq mm.
WARNING: Improper wiring may cause irreparable damage and personal injury. Kindly ensure that wiring is done by qualified personnel only.
Maintenance: Cleaning: Clean the surface of the controller with a soft moist cloth. Do not use abrasive detergents, petrol, alcohol or solvents. Notice: The information in this document is subject to change in order to improve reliability , design or function without prior notice and does not represent a commitment on the part of the company. In no event will the company be liable for direct, indirect, special, incidental or consequential damage arising out of the use or inability to use the product or documentation, even if advised of the possibility of such damages. No part of this manual may be reproduced or transmitted in any form or by any means without the prior written permission of the company.
13
GASKET
PANEL
Side Lock
CONTROLLER
14
SZ-7512-P
prg
SET
O
C
RST
3
1
4
2
34.5mm
71mm
19mm
10mm
MAX
71mm
29mm
Panel cutout
PANEL
Suggested Wiring Diagram
PROBE
230VNCCNO
RELAY
11
10
Technical data :
Display : 14.2 mm (0.56") LED. Data storage : Non-volatile EEPROM memory Power input : 230Vac,+/-10%, 50Hz/60Hz. Others on
request.
O O
Operating temp. : 5 C to 50 C(non-condensing).
O O
Storage temp : -20 C to 70 C(non-condensing). Output : 1 SPDT relay 8(3)A, 250Vac Input : NTC probe, SZ-N75
O O
Range : -50 C to 50 C
O
Resolution : 1 C
O
Accuracy : +/-1 C
O O
Probe tolerance at 25 C : +/-0.3 C Alarm (buzzer) : SZ-B75, 10Vdc, 10mA
Housing : Black ABS plastic. Front cover : Polycarbonate plastic. Dimensions : Front - 75 x 34.5 mm,
Depth 71 mm (w/o back lid).
Panel Cutout : 29mm x 71mm Mounting : Flush panel mounting with fasteners. Protection : Front panel is water proof & IP 65 rated . Connections : Screw terminal blocks.
2.5 sq.mm wire terminal only
INDIA
Ball Valves
Globe Valves
Hand Valves
Flow Switches
Solenoid Valves
OUR OTHER PRODUCTS
Cold Room Controller
Chiller Controller
Two Compressors Controller
Heating Controller Humidity Controller Pressure Controller
TM
00 / 25.11.09
18
LIMITATION OF LIABILITY : ASCPL's total liability for any and all losses and damages arising out of any cause whatsoever shall in no event exceed the purchase price of the products or parts in respects of which such cause arises, whether such cause be based on theories of contract, negligence, strict liability, tort or otherwise.
In no event is ASCPL responsible for any consequential or punitive damages or losses of any nature whatsoever. ASCPL shall not be liable for, and buyer assumes any liability for, all personal injury and property damage connected with the
17
Warranty : All Subzero products manufactured by A.S.Controls Pvt. Ltd (thereafter reffered to as ASCPL) are under warranty against defects in workmanship and materials for a period of one year from date of shipment from factory. This warranty is in force only when products are properly installed,maintained and operated in use and service as specifically stated in Subzero catalogues.
Defective products, or parts there of returned to the factory with transporatation charges prepaid and found to be defective by factory inspection, will be replaced or repaired at ASCPL's option, free of charge, Ex-factory. Warranty does not cover products that have been altered, or repaired in the field, or
damaged in transit, or have suffered accidents, misuse, or abuse. Products disabled by dirt or other foreign substances will not be considered defective. This warranty does not cover any cosmetic issues, such as product damaged by accident, abuse and misuse as a result of service or modification other than company. Repair or change in parts or replacement of parts or products does not extend the warranty.
The express warranty set forth above constitutes the only warranty applicable to ASCPL products, and is in lieu of all other warranties, expressed or implied. No employee, agent, dealer or any other person is authorised to give any warranties on behalf of ASCPL, nor to assume for ASCPL, any other liability in connection with any of its products.
19
handling, transporatation, possession, further manufacture, other use or resale of the products, whether used alone or in combination with any other products or materials. ASCPL makes NO other warranty, expressed or implied, and makes no warranty of merchantibility or fitness for any particular purpose.
From time to time buyers might call to ask ASCPL for technical advice based upon limited facts disclosed to ASCPL. If ASCPL furnishes technical advice to the buyer, whether or not at buyer's request, with respect to application, further manufacture or use of the products or parts, ASCPL shall not be liable for such technical advice or any such advice provided to buyer by any third party and buyer assumes all risks of such advice and results thereof.
NOTICE TO USERS OF PRODUCTS : The Limited Warranty stated above is a factory warranty to the first purchasers of ASCPL products. Since many users have purchased these products from ASCPL distributors, the user must within thirty (30) days after user's discovery of what the user believes is a defect, notify in writing and return the product to the distributor from whom he purchased the product/part. The distributor may or may not at the distributor's option choose to submit the products/parts to ASCPL pursuant to this limited warranty. Failure by the buyer to give such written notice within 30 (thirty) days shall be deemed an absolute and unconditional waiver of buyers claim for such
20
defects. Acceptance of any alleged defective product/parts by ASCPL's distributor for replacement or repairs under the terms of ASCPL's limited warranty in no way determines ASCPL's obligations under this Limited Warranty.
Because of a policy of continous product improvement, ASCPL reserves the right to change designs, materials or specifications without notice.
Disclaimer: This manual & its contents remain the sole property of A.S. CONTROLS Pvt. Ltd, India and shall not be reproduced or distributed without authorisation. Although great care has been taken in the prepartion of this document, the company or its vendors in no event will be liable for direct, indirect, special, incidental or consequential damage arising out of the use or inability to use the product or documentation, even if advised of the possibility of such damages. No part of this manual may be reproduced or transmitted in any form or by any means without the prior written permission of the company. A.S. CONTROLS Pvt. Ltd, reserves the right to make and changes or improvements without prior notice.
Loading...