Sub-Zero SZ-7510-P-DI Operating Instructions Manual

OPERATING
INSTRUCTIONS
SZ-7510-P-DI
www.subzero.co
1
4
GENERAL DESCRIPTION The Sub-Zero Series SZ-7510-P-DI are aesthetically superior
Additionally these controllers offer several protection features that are easily understood by the examples in the instructions below. The controller can be used for heating applications, when the P1 parameter is set to “1” .
A number of parameters are displayed alphanumerically to set up the instrument for each specific application.
The SZ-7510-P-DI controller can be used for several
O O
applications with a measuring range from -50 C to 99 C.
Instructions :
Function: To set the cut out point of the controller.
Display will change to set range. The set point range can now be changed by using the UP/DOWN key. After setting the desired range, press the set key and you will see “- - -” which confirms that the set point has been stored in memory.
Set point
Press and hold the SET key for 2 Seconds.
O
-50
C
O
99
C
O
10 C
Min
Max
Fac.
3
INDEX
Para. Page
Description
P1 P2 P3 P4 P5 P6 d0 d1 d2 d3 LP E1 FS EP
3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22
2
INDIA
To set other Parameters.
Display will show P1 & flash. To go to other parameters, use UP/DOWN keys.
Press & hold the DOWN(prg) key for 2 seconds.
prg
SET
To set the SET Point of the controller. How to set other parameters. To set Heating or Cooling function. Max High Temp limit & alarm. Min Low Temp limit & alarm. To set Differential (Hysterisis). Probe calibration. Time Delay (relay restart after cutoff)
Keypad lock. Relay status on probe failure. Restore factory defaults. End Programming. Operating messages. Technical Data. Wiring diagram. Panel cutout & dimensions.
Activate or deactive digital input function. Set reset mode for digital input Set the count mode for CCF Set the number of count for CCF
5
P1 Parameter
Function: To set controller for heating or cooling.
0 1 0
To change the P1 parameter, press the SET key.
Use UP/DOWN keys to get desired range & press set to confirm. 0: Cooling mode and 1: Heating mode.
Min Max
Fac.
6
7
8
P4 Parameter
Function: To set the differential.
To change the P4 parameter, press the SET key.
Use UP/DOWN keys to set desired range. Differential between cut out and cut in temperature can be set
O O
between 1 C to 20 C.
O
1 C
Min Max
Fac.
O
20 C
O
2 C
Example (in cooling mode): If the
O
set point is set at 10 C and
O
differential is set at 2 C, then when
O
the system reaches 10 C, the relay will cut out. Since the differential is 2, the relay will cut in (restart) at
O O O
12 C (10 C+2 C).
9
P5 Parameter
Function: To set probe calibration.
To change the P5 parameter, press the SET key.
Use UP/DOWN keys to set desired range. In time it may be possible that the display may be offset by a degree or so. To compensate for this error, you may need to add or minus the degrees required to achieve the correct temperature. Setting range
O O
is from -10 C to +10 C.
O
-10 C
Min Max
Fac.
O
10 C
O
0 C
Example: The temperature on
O
the display is 28 C, whereas the
O
actual temperature is 30 C. You will need to set the P5 mode to 2, which means that once out of the programming mode, the temperature will show
O O O
30 C (28 C + 2 C).
10
Function: To set minimum allowable low temperature set point.
Use UP/DOWN keys to set desired range. Once set at a particular range, this will not allow the set point to go below this range.
Example: Setting this parameter at
O
-30 C will not allow the set point to
O
go below -30 C. Also, if the
O
temperature reaches -30 C, the display will show Lt (LowTemp.) indicating that the temperature has gone below the range in this parameter.
P3 Parameter
O
-50 C
Max
Fac.
O
XX CO-50 C
To change the P3 parameter, press the SET key.
Min
(Message on display)
P6 Parameter
0 Min
99 Min
3 Min
Function: To set time delay between relay restart time.
To change the P6 parameter, press the SET key.
Min
Max
Fac.
Use UP/DOWN keys to set desired range. This parameter is used to protect the compressor from restarting in a short period of time and can be set between 0 to 99 minutes.
Example: If this parameter is set at 3 minutes, the relay will cut off at the set temperature, but will not restart for a minimum of 3 minutes, even if the differential is achieved earlier. This parameter is good to protect the life of the compressor when there are power fluctuations and the compressor is switched off and on within a few seconds.
P2 Parameter
Function: To set maximum allowable high temperature limit.
O
XX C
To change the P2 parameter, press the SET key.
Max
Fac.
Use UP/DOWN keys to set desired range. Once set at a particular range, this will not allow the set point to go above this range.
O
99 CO99 C
Example: Setting this parameter
O
at 25 C will not allow the
O
set point to go above 25 C. Also,
O
if the temperature reaches 25 C, the display will show Ht (High Temp.) indicating that the temperature. has gone above the range in this parameter.
Min
(Message on display)
Flashing
Time delay in progress
Loading...
+ 3 hidden pages