Sub-Zero SZ-7510-P-DI Operating Instructions Manual

Page 1
OPERATING
INSTRUCTIONS
SZ-7510-P-DI
www.subzero.co
1
4
GENERAL DESCRIPTION The Sub-Zero Series SZ-7510-P-DI are aesthetically superior
Additionally these controllers offer several protection features that are easily understood by the examples in the instructions below. The controller can be used for heating applications, when the P1 parameter is set to “1” .
A number of parameters are displayed alphanumerically to set up the instrument for each specific application.
The SZ-7510-P-DI controller can be used for several
O O
applications with a measuring range from -50 C to 99 C.
Instructions :
Function: To set the cut out point of the controller.
Display will change to set range. The set point range can now be changed by using the UP/DOWN key. After setting the desired range, press the set key and you will see “- - -” which confirms that the set point has been stored in memory.
Set point
Press and hold the SET key for 2 Seconds.
O
-50
C
O
99
C
O
10 C
Min
Max
Fac.
3
INDEX
Para. Page
Description
P1 P2 P3 P4 P5 P6 d0 d1 d2 d3 LP E1 FS EP
3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22
2
INDIA
To set other Parameters.
Display will show P1 & flash. To go to other parameters, use UP/DOWN keys.
Press & hold the DOWN(prg) key for 2 seconds.
prg
SET
To set the SET Point of the controller. How to set other parameters. To set Heating or Cooling function. Max High Temp limit & alarm. Min Low Temp limit & alarm. To set Differential (Hysterisis). Probe calibration. Time Delay (relay restart after cutoff)
Keypad lock. Relay status on probe failure. Restore factory defaults. End Programming. Operating messages. Technical Data. Wiring diagram. Panel cutout & dimensions.
Activate or deactive digital input function. Set reset mode for digital input Set the count mode for CCF Set the number of count for CCF
Page 2
5
P1 Parameter
Function: To set controller for heating or cooling.
0 1 0
To change the P1 parameter, press the SET key.
Use UP/DOWN keys to get desired range & press set to confirm. 0: Cooling mode and 1: Heating mode.
Min Max
Fac.
6
7
8
P4 Parameter
Function: To set the differential.
To change the P4 parameter, press the SET key.
Use UP/DOWN keys to set desired range. Differential between cut out and cut in temperature can be set
O O
between 1 C to 20 C.
O
1 C
Min Max
Fac.
O
20 C
O
2 C
Example (in cooling mode): If the
O
set point is set at 10 C and
O
differential is set at 2 C, then when
O
the system reaches 10 C, the relay will cut out. Since the differential is 2, the relay will cut in (restart) at
O O O
12 C (10 C+2 C).
9
P5 Parameter
Function: To set probe calibration.
To change the P5 parameter, press the SET key.
Use UP/DOWN keys to set desired range. In time it may be possible that the display may be offset by a degree or so. To compensate for this error, you may need to add or minus the degrees required to achieve the correct temperature. Setting range
O O
is from -10 C to +10 C.
O
-10 C
Min Max
Fac.
O
10 C
O
0 C
Example: The temperature on
O
the display is 28 C, whereas the
O
actual temperature is 30 C. You will need to set the P5 mode to 2, which means that once out of the programming mode, the temperature will show
O O O
30 C (28 C + 2 C).
10
Function: To set minimum allowable low temperature set point.
Use UP/DOWN keys to set desired range. Once set at a particular range, this will not allow the set point to go below this range.
Example: Setting this parameter at
O
-30 C will not allow the set point to
O
go below -30 C. Also, if the
O
temperature reaches -30 C, the display will show Lt (LowTemp.) indicating that the temperature has gone below the range in this parameter.
P3 Parameter
O
-50 C
Max
Fac.
O
XX CO-50 C
To change the P3 parameter, press the SET key.
Min
(Message on display)
P6 Parameter
0 Min
99 Min
3 Min
Function: To set time delay between relay restart time.
To change the P6 parameter, press the SET key.
Min
Max
Fac.
Use UP/DOWN keys to set desired range. This parameter is used to protect the compressor from restarting in a short period of time and can be set between 0 to 99 minutes.
Example: If this parameter is set at 3 minutes, the relay will cut off at the set temperature, but will not restart for a minimum of 3 minutes, even if the differential is achieved earlier. This parameter is good to protect the life of the compressor when there are power fluctuations and the compressor is switched off and on within a few seconds.
P2 Parameter
Function: To set maximum allowable high temperature limit.
O
XX C
To change the P2 parameter, press the SET key.
Max
Fac.
Use UP/DOWN keys to set desired range. Once set at a particular range, this will not allow the set point to go above this range.
O
99 CO99 C
Example: Setting this parameter
O
at 25 C will not allow the
O
set point to go above 25 C. Also,
O
if the temperature reaches 25 C, the display will show Ht (High Temp.) indicating that the temperature. has gone above the range in this parameter.
Min
(Message on display)
Flashing
Time delay in progress
Page 3
15
LP Parameter.
0 1 0
Function: To lock keypad.
To change the LP parameter press the SET key.
Use UP/DOWN keys to set desired range. This parameter can lock the keypad so that tampering is not possible by by-standers. 0 = keypad unlocked 1 = keypad locked
When locked all parameters can only be viewed, but not modified.
Min Max
Fac.
16
E1 Parameter
0 2
2
Function : Relay status on Probe Failure.
Min Max
Fac.
To change the E1 parameter press the SET key.
Use UP/DOWN keys to set desired range. When set to 0 = Relay status is ON. 1 = Relay performs a duty cycle 10 minutes ON and 4minutes OFF. 2 = Relay status is OFF.
11
d0 Parameter
0 2 1
Function : To activate or deactive digital input function.
To change the d0 parameter press the SET key
Use UP/DOWN keys to set desired range.
0: Digital input disable. 1: DI with 230VAC present 2: DI with 0VAC present.
Min Max
Fac.
Example : If this parameter is set to 0, controller will not sense any digital input. If set to 1, when 230VAC is present, controller will treat it as a fault and turn off the compressor and DI ( )will flash. If set to 2, when 0VAC is present, controller will treat it as a fault and turn off the compressor and DI ( )will flash.
12
d1 Parameter
Function : To set reset mode for digital input.
0 1 0
Min Max
Fac.
To change the d1 parameter press the SET key
Use UP/DOWN keys to set desired range.
0: Auto reset. 1: Manual reset.
Example : If this parameter is set to 0, then incase of a fault in d0 parameter, unit will auto reset after fault is cleared. If this parameter is set to 1, then incase of a fault in d0 parameter, unit will allow reset after pressing AUTO/MAN button. (after d0 fault is cleared).
14
13
Use UP/DOWN keys to set desired range.
This parameter sets the permissible number of reset cycles of compressor. When number of compressor reset cycles within 1 Hr. goes above the d3 parameter, controller switch to manual reset mode and “CCF” led will be ON.
NOTE: This parameter saves the compressor from multiple (more than max.10 nos.) reset within 1 Hr.
Use RST key to reset this CCF fault.
Use UP/DOWN keys to set desired range.
0: CCF count increment with each Comp. OFF and DI fault.
1: CCF count increment only with DI fault.
d3 Parameter
d2 Parameter
0
0
1015
0
Min
Min
Max
Max
Fac.
Fac.
To change the d2 parameter press the SET key
To change the d2 parameter press the SET key
Function : To set the number of reset cycles of compressor.
Function : To set the count mode for CCF .
CCF- compressor count fault.
RST
AUTO
MAN
Page 4
20
Technical data:
Dimensions: Front : 75 X 34.5 MM, Depth 7 MM (w/o back lid)
: 1 Mounting: Flush panel mounting with fasteners Frontal protection : I.P65 Connections: Screw terminal blocks. 2.5sqmm one
wire/ terminal only
Display: 2 X14.2 mm (0.56") LED Data storage: Non-volatile EEPROM memory Power input: 230Vac +/-10%,50-60Hz.
Other on request
O O
Operating temp.: 5 C to 50 C(non-condensing)
O O
Storage temp: -20 C to 70 C(non-condensing) Output:1 SPDT relay 8 (3)A, 250Vac. Input: NTC probe, SZ-N75
O O
Range: -50 C to 99 C
O
Resolution: 1 C
O
Accuracy: +/- 1 C
O O
Probe tolerance: +/- 0.3 C at 25 C
Housing : Black, ABS Plastic Front Cover : Red Polycarbonate plastic.
18
EP Parameter.
To end programming press the SET key
Once the SET key is pressed, the
control goes into the normal mode
and displays the temperature and
all settings are recorded.
Function: To end programming.
21
NEUTRAL
To
SZ-N75
Compressor, Contactor
or Heater 8(3)A max
PHASE
Caution:Wiring for 230Vac load only
230V
NO NC C
7
11 12
8
5
3 4
1
6
PROBE
COMP.
Phase from
Digital Input
trip contact
Neutral
3
1
4
2
35mm
71mm
19mm
15mm
MAX
71
29
Panel cutout
22
RST
SZ-7510-P-DI
prg
SET
-
DI
CCF
AUTO
MAN
RST
19
Operating messages and Icon status
Parameter
Message
Description
P2
Ht
Temperature above the maximum limit of the set point.
P3
Lt
Temperature below the minimum limit of the set point.
PP
Probe short circuit, circuit open or without
0 0
probe, or temperature > 99 C or <-50 C
SP, P4
Comp. Relay on/off
On/Off
P6
Time delay in progress
Flashing
LP
Keypad locked/unlocked
d0,d1
d2,d3
Digital input fault ON
Compressor count fault : CCF
On
On/Off
DI
On
CCF
17
FS Parameter
Function : To restore default settings of the controller.
0
1 0
Min Max
Fac.
To change the FS parameter press the SET key.
When set to 1 all parameters are programmed to factory values. Useful to debug setting related problems.
Page 5
25
Disclaimer: This manual & its contents remain the sole property
of A.S. CONTROLS Pvt. Ltd, India and shall not be reproduced or distributed without authorisation. Although great care has been taken in the prepartion of this document, the company or its vendors in no event will be liable for direct, indirect, special, incidental or consequential damage arising out of the use or inability to use the product or documentation, even if advised of the possibility of such damages. No part of this manual may be reproduced or transmitted in any form or by any means without the prior written permission of the company. A.S. CONTROLS Pvt. Ltd, reserves the right to make and changes or improvements without prior notice.
Warranty: This product is warranted against defects in materials and workmanship for a period of one year from the date of purchase. During the warranty period, product determined by us to be defective in form or function will be repaired or, at our option, replaced at no charge. This warranty does not apply if the product has been damaged by accident, abuse, and misuse or as a result of service or modification other than by the company. This warranty is in lieu of any other warranty expressed or implied. In no event shall the company be held liable for incidental or consequential damages, including lost revenue or lost business opportunity arising from the purchase of this product..
INDIA
Ball Valves
Globe Valves
Hand Valves
Flow Switches
Solenoid Valves
OUR OTHER PRODUCTS
Cold Room Controller
Chiller Controller
Two Compressors Controller
Heating Controller Humidity Controller Pressure Controller
TM
24
CAUTION
WIRING: The probe and its corresponding wires should never be installed in a conduit next to control or power supply lines. The electrical wiring should be done as shown in the diagram. The power supply circuit should be connected to a protection switch. The terminals admit wires of upto 2.5sq mm.
WARNING: Improper wiring may cause irreparable damage and personal injury. Kindly ensure that wiring is done by qualified personnel only.
Maintenance: Cleaning: Clean the surface of the controller with a soft moist cloth. Do not use abrasive detergents, petrol, alcohol or solvents.
Notice: The information in this document is subject to change in order to improve reliability , design or function without prior notice and does not represent a commitment on the part of the company. In no event will the company be liable for direct, indirect, special, incidental or consequential damage arising out of the use or inability to use the product or documentation, even if advised of the possibility of such damages. No part of this manual may be reproduced or transmitted in any form or by any means without the prior written permission of the company.
23
Installation : Fixing and dimensions of panel models:
To fix the unit, slide the fastener 1 through the guides 2 as per the position shown in the figure. Move the fastener in the direction of the arrow, pressing tab 3 it permits to move the fastener in the opposite direction of the arrow. Once the controller has been connected, they should be covered with the lid 4 . Silicon sealant should be applied along the perimeter of the panel cut out or a rubber ‘O’ ring supplied before the unit is fitted to obtain IP65 grade.
Controller :Controller should be installed in a place protected by vibration, water and corrosive gasses and where ambient temperature does not exceed the values specified in the technical data. Probe :To give a correct reading, the probe must be installed in a place protected from thermal influences, which may affect the temperature to be controlled.
Loading...