Stulz Compact CW Series Installation, Operation & Maintenance Manual

Page 1
Compact CW Series Installation, Operation & Maintenance Manual
A
(© Oct, 2007)
ir Technology Systems, Inc.
Page 2
A
Compact CW Series Installation, Operation & Maintenance Manual
CC = Compact CW System
Model Nomenclature
CC U-30 0-CW
U = Up-Flow Air Pattern
D = Down-Flow Air Pattern
Nominal Capacity in kW
CW = Chilled Water System
Number of Refrigeration Circuits
Notice
This document contains information protected by copyright. All rights are reserved. The owner of the equipment for which this manual is written may photocopy the contents of this manual for internal use only. No part of this docu­ment may be photocopied, reproduced, or translated into another language for use by anyone other than the owner of the equipment for which this manual is written without the prior written consent of Stulz Air Technology Systems, Inc. (SATS).
This document contains confidential and proprietary information of Stulz Air Technology Systems, Inc. Distributing or photocopying this document for external distribution is in direct violation of U.S. copyright laws and is strictly prohibited without the express written consent of SATS.
Unpublished — rights reserved under the copyright laws of the United States and of other countries. Other brands and tradenames are trademarks of their respective owners.
Copyright 2007 by Stulz Air Technology Systems, Inc. Printed in the United States of America. All rights reserved.
Stulz Air Technology Systems, Inc. 1572 Tilco Drive Frederick, MD 21704 USA
08/07
(© Oct, 2007)
ir Technology Systems, Inc.
Page 3
Compact CW Series Installation, Operation & Maintenance Manual
A
TABLE OF CONTENTS
1.0 Introduction ....................................... 1-1
1.1 General ...................................................... 1-1
1.2 Product Description ................................... 1-1
1.3 Product Warranty ...................................... 1-2
1.4 Safety ........................................................ 1-3
1.4.1 General ...................................................... 1-3
1.4.2 Safety Summary ........................................ 1-3
1.5 General Design .......................................... 1-4
1.5.1 Electric Box Access .................................. 1-4
1.5.2 Circuit Breakers/ Motor Start Protectors .... 1-4
1.5.3 Heaters...................................................... 1-4
1.5.4 Coils .......................................................... 1-4
1.5.5 Blower(s) ................................................... 1-4
1.5.6 Temperature/ Humidity Sensor ................... 1-5
1.5.7 Humidifier .................................................. 1-5
1.6 Optional Equipment ................................... 1-5
1.6.1 Condensate Pump ..................................... 1-5
1.6.2 Smoke Detector ........................................ 1-5
1.6.3 Firestat ...................................................... 1-5
1.6.4 Auto Transfer Switching ............................. 1-5
2.0 Installation .........................................2-1
2.1 Receiving the Equipment. .......................... 2-1
2.2 Site Preparation ......................................... 2-1
2.3 Rigging ...................................................... 2-2
2.4 Mounting/Placement .................................. 2-2
2.4.1 Precision A/C Unit ..................................... 2-2
2.5 Air Distribution Connection ........................ 2-3
2.5.1 Downflow Configuration Air Patterns ........... 2-3
2.5.2 Upflow Configuration Air Patterns ............... 2-3
2.6 Optional Equipment (Field Installed) .......... 2-5
2.6.1 Floor Stand ................................................ 2-5
2.6.2 Plenum Box Assembly .............................. 2-5
2.6.3 Remote Display ......................................... 2-5
2.6.4 Condensate Pump ..................................... 2-5
2.6.5 Remote Temperature/Humidity Sensor ....... 2-5
2.6.6 Remote Water Detector ............................. 2-6
2.7 Piping Connections .................................... 2-6
2.7.1 Chilled Water/Hot Water ............................ 2-6
2.7.2 Condensate Drain ...................................... 2-7
2.7.2.1 Gravity Drain .............................................. 2-7
2.7.2.2 Condensate Pump ..................................... 2-7
2.7.3 Humidifier .................................................. 2-7
2.8 Utility Connections .................................... 2-8
2.8.1 Main Power ............................................... 2-8
2.8.2 Controls ..................................................... 2-9
2.8.3 Optional Equipment ................................... 2-9
2.8.3.1 Remote Temperature/Humidity Sensor ....... 2-9
2.8.3.2 Remote Water Detector ............................. 2-9
2.9 System Settings and Adjustments ........... 2-10
2.9.1 Chilled Water Circuit ................................ 2-10
2.9.2 Humidifier Adjustment .............................. 2-10
2.8.3 Blower ..................................................... 2-10
3.0 Start-Up/Commissioning .................. 3-1
3.1 Operation ................................................... 3-1
3.2 Step by Step Start-Up Instructions ............. 3-1
3.3 Microprocessor Controller
Programming ............................................ 3-1
4.0 Maintenance/Repairs ....................... 4-1
4.1 Periodic General Maintenance ................... 4-1
4.1.1 A/C Unit..................................................... 4-1
4.1.1.1 Filter .......................................................... 4-1
4.1.1.2 Blower ....................................................... 4-1
4.1.1.3 Drain Pan .................................................. 4-1
4.1.1.4 Coils .......................................................... 4-1
4.1.1.5 Heat/Reheat .............................................. 4-1
4.1.1.6 Humidifier .................................................. 4-1
4.1.1.7 Condensate Pump ..................................... 4-1
4.2 Troubleshooting ...................................... 4-2/3
4.3 Field Service .............................................. 4-4
4.3.1 Piping ........................................................ 4-4
4.3.2 General Common Repairs/
Component Replacement ........................... 4-4
4.3.2.1 Humidifier Cylinder Replacement ............... 4-4
4.3.2.2 Filter Replacement .................................... 4-4
5.0 Product Support Group ................... 5-1
5.1 Technical Support ...................................... 5-1
5.2 Obtaining Warranty Parts .......................... 5-1
5.3 Obtaining Spare/Replacement Parts .......... 5-1
(© Oct, 2007)
i
ir Technology Systems, Inc.
Page 4
A
Compact CW Series Installation, Operation & Maintenance Manual
TABLE OF CONTENTS
List of Figures
Figure 1 Typical Internal Layout ............................ 1-4
Figure 2 Auto Transfer Disconnect Switches ........ 1-5
Figure 3 Preferred Power Selecton Switch ............ 1-5
Figure 4 Installation Clearance ............................. 2-1
Figure 5 Typical Installation Upflow ....................... 2-2
Figure 6 Typical Installation Downflow ................... 2-2
Figure 7 Downflow Configuration
Typical Air Patterns ................................ 2-3
Figure 8 Upflow Configuration Typical
Air Patterns (Top Discharge) ................... 2-4
Figure 9 Upflow Configuration Typical Air
Patterns (Top Ducted Discharge) ............ 2-4
Figure 10 Optional Floor Stand Installation ............. 2-5
Figure 11 Condensate Pump .................................. 2-7
Figure 12 Sample Nameplate ................................. 2-8
Figure 13 Electric Box ........................................... 2-9
Figure 14 Blower Assembly .................................. 2-10
(Continued)
Appendix A - Forms
Checklist for Completed Installation .........................A-1
Periodic General Maintenance
Checks and Service Checklist ..................................A-2
Appendix B - Glossary
Definition of Terms and Acronyms ............................B-1
ii
(© Oct, 2007)
ir Technology Systems, Inc.
Page 5
Compact CW Series Installation, Operation & Maintenance Manual
A
1.0 INTRODUCTION
1.1 General
Congratulations, the precision air conditioning system covered by this manual is designed and manufactured by Stulz Air Technology Systems, Inc. (SATS) using the latest, state-of-the-art control technology. Recognized as a world leader, SATS provides air conditioning systems with the highest quality craftsmanship using the finest materials available in the industry. The unit will provide years of trouble free service if installed and maintained in accordance with this manual. Damage to the unit from improper installation, operation or maintenance is not covered by the warranty.
STUDY the instructions contained in this manual. They must be followed to avoid difficulties. Spare parts are available from SATS to insure continuous opera­tion. Using substitute parts or bypassing electrical or cooling components in order to continue operation is not recommended and will VOID THE WARRANTY. Due to technological advancements, components are subject to change without notice.
All
Compact CW
indoors, unless otherwise noted on the equipment.
Compact CW™
floor mounted
systems are designed to be installed
1.2 Product Description
Compact CW
versatile and flexible floor mounted precision air conditioning systems in the industry. The unit is available in up-flow or down-flow configurations. The cooling capacity, in kW, will depend on the unit size, which can range from 30 to 180 kW, (1 kW = 3415 BTU/Hr). Refer to the unit nameplate to identify the model number and cooling capacity of your unit.
Compact CW
source of chilled water. The chilled water system is a closed loop circuit in which cold water is circulated through a chilled water coil. On demand for cooling, the microprocessor controller begins modulating the chilled water valve open. Chilled water flows to the coil at a rate that varies proportionally to the amount of cooling required to meet the user selectable tempera­ture setpoint. Heat from the surrounding air is trans­ferred through the finned tubing of the coil into the cold water. Water is then re-circulated back to the cold water source.
Compact CW
air to only one room.
systems are designed to be the most
systems operate with an external
systems have been designed to supply
NOTE
Compact CW
systems are strictly for non-resi-
dential applications.
The functional modes of operation, in addition to cooling, are heating, humidification and dehumidifica­tion, which provide complete environmental control of a conditioned space.
There are two air pattern configurations, upflow and downflow, and several cabinet sizes based on the type of system and capacity. Regardless of configuration, the
Compact CW
system is compact and versatile. See the Installation drawing provided with the unit for the layout and dimensions of the cabinet.
The
Compact CW
unit is provided with a factory mounted, main power disconnect switch with a lockable handle. The disconnect switch electrically isolates the unit during routine maintenance. The system incorpo­rates state of the art component protection with the use of motor start protectors and circuit breakers.
An operating manual for the system controller is provided under separate cover. Refer to that manual for detailed instructions on operating the system control­ler provided with your unit.
The standard controller for
Compact CW
precision A/C units sizes CCD/U-300 through CCD/U-900 is SATS model C1002. For larger units, CCD/U-1500 through CCD/U-1800, the standard controller is the SATS model C6000. These microprocessor controllers provide the following features: input/output monitoring status, full integrated control of heating, cooling, humidification and dehumidification; multi-unit control and remote communication with building management systems. The controller is typically factory mounted on the front hinged access door of the unit. As an option the controller may be remotely mounted to a wall or control panel.
C1002 C6000
SATS offers the C6000 microprocessor controller as an option for models CCD/U-300 through CCD/U-900 A/C units.
(© Oct, 2007)
1-1
ir Technology Systems, Inc.
Page 6
A
Compact CW Series Installation, Operation & Maintenance Manual
1.3 Product Warranty
SATS offers a two year standard limited warranty as stated below:

2-Year Standard Limited Warranty:
Stulz Air Technology Systems, Inc., warrants to the original buyer of its products that the goods are free from defects in material and workmanship. Stulz Air Technology Systems, Inc.’s obligation under this warranty is to repair or replace, at its option, free of charge to the customer, any part or parts which are determined by Stulz Air Technology Systems Inc. to be defective for a period of 24 months from date of shipment when a completed start-up form has been submitted to Stulz Air Technology Systems, Inc. within 90 days from shipment. In the event that a completed start-up form is not received by Stulz Air Technology Systems, Inc. within 90 days from shipment, the company’s obligation will be for a period of 12 months from date of shipment. Parts repaired or replaced under this warranty are shipped FOB Factory, and warranted for the balance of the original warranty period or for 90 days from the date of installation, whichever is greater.
Stulz Air Technology Systems, Inc.’s warranty does not cover failures caused by improper installation, abuse, misuse, misapplication, improper or lack of maintenance, negligence, accident, normal deterioration (including wear and tear), or the use of improper parts or improper repair.
Purchaser’s remedies are limited to replacement or repair of non-conforming materials in accordance with the written warranty. This warranty does not include costs for transportation, costs for removal or reinstallation of equipment or labor for repairs or replacement made in the field.
If any sample was shown to the buyer, such sample was used merely to illustrate the general type and quality of the product, and not to represent that the equipment would necessarily conform to the sample.
This is the only warranty given by the seller, and such warranty is only given to buyers for commercial or industrial purposes. This warranty is not enforceable until the invoice(s) is paid in full.
THE FOREGOING SHALL CONSTITUTE SATS’S ENTIRE LIABILITY AND YOUR EXCLUSIVE REMEDY. IN NO EVENT SHALL SATS BE LIABLE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL, CONSEQUENTIAL, OR EXEMPLARY DAMAGES, INCLUDING LOST PROFITS (EVEN IF ADVISED OF THE POSSIBILITY THEREOF) ARISING IN ANY WAY OUT OF THE INSTALLATION, USE OR MAINTENANCE OF THE EQUIPMENT. THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.


1-2

(© Oct, 2007)
ir Technology Systems, Inc.
Page 7
Compact CW Series Installation, Operation & Maintenance Manual
A
1.4 Safety
1.4.1 General
Stulz Air Technology Systems, Inc. uses NOTES along with CAUTION and WARNING symbols through- out this manual to draw your attention to important operational and safety information.
A bold text NOTE marks a short message in the information to alert you to an important detail.
A bold text CAUTION safety alert appears with information that is important for protecting your equipment and performance. Be especially careful to read and follow all cautions that apply to your applica­tion.
A bold text WARNING safety alert appears with information that is important for protecting you from harm and the equipment from damage. Pay very close attention to all warnings that apply to your application.
A safety alert symbol WARNING or CAUTION safety statement.
A safety alert symbol accompanies an electrical shock hazard WARNING or CAUTION safety state-
ment.
1.4.2 Safety Summary
accompanies a general
Always disconnect the main power supply to the equipment at the main power disconnect switch before beginning work on the equipment. A lock-out tag-out procedure should be followed to ensure that power is not inadvertently reconnected.
Equipment may contain components subject to Electrostatic Discharge (ESD). Before attempting to mount or service these electronic devices, ensure you have no charge built up by touching a ground source. When possible, use a wrist-grounding strap when working on or near electronic devices.
Never work on electrical equipment unless another person who is familiar with the operation and hazards of the equipment and competent in administering first aid is nearby.
All personnel working on or near equipment should be familiar with hazards associated with electrical maintenance. Safety placards/stickers have been placed on the unit to call attention to all personal and equipment damage hazard areas.
Certain maintenance or cleaning procedures may call for the use and handling of chemicals, solvents, or cleansers. Always refer to the manufacturer's Material Safety Data Sheet (MSDS) prior to using these materials. Clean parts in a well-ventilated area. Avoid inhalation of solvent fumes and prolonged exposure of skin to cleaning solvents. Wash exposed skin thoroughly after contact with solvents.
The following statements are general guidelines followed by warnings and cautions applicable throughout the manual.
Prior to performing any installation, operation, mainte­nance or troubleshooting procedure, read and under­stand all instructions, recommendations and guide­lines contained within this manual.
All maintenance and/or repairs must be performed by a journeyman, refrigeration mechanic or an air conditioning technician.
Never operate the unit with any cover, guard, screen, panel, etc., removed unless the instructions specifi­cally state otherwise, then do so with extreme caution to avoid personal injury.
Never lift any component in excess of 35 pounds without help. If a lifting device is used to move a unit, ensure it is capable of supporting the unit.
When working on electrical equipment, remove all jewelry, watches, rings, etc.
CAUTION
When the air conditioner is in the cooling mode, the return air-intake and discharge (supply) must be free of obstructions. Ensure panels are secure and latched into position.
CAUTION
Do not use cleaning solvents near open flame or excessive heat. Wear eye protection when blow­ing solvent from parts. The pressure-wash should not exceed 30 psig. Solvent solutions should be disposed of in accordance with local and state regulatory statutes.
CAUTION
The unit must be kept level and vertical in its normal installed position.
(© Oct, 2007)
1-3
ir Technology Systems, Inc.
Page 8
A
Compact CW Series Installation, Operation & Maintenance Manual
1.5 General Design
The Compact CW unit is housed in a steel frame type cabinet and is rated for indoor use. The exterior of the cabinet is coated with a powder coat finish to protect against corrosion. Hinged doors are located in the front of the cabinet for easy access to all components. Operator controls are conveniently located on the front of the cabinet. Figure 1 depicts a typical internal layout of a CCD-1800-CW unit and identifies the major components.
FILTER ACCESS
(DOWNFLOW UNITS)
COILS
ELECTRIC HEATERS
(OPTIONAL)
Figure 1- Typical Internal Layout
(Model CCD-1800-CW shown for reference)
1.5.1 Electric Box Access
The electrical components are protected behind the hinged access door located on the right side of the unit. The access door is safety interlocked with the main power service disconnect switch, (See Figure 4), preventing the door from opening when the switch in the “On” position. The switch must be turned “Off” to gain access to the electrical components.
The service disconnect switch may be used to turn the unit off for emergency shutdown or during routine
maintenance. The handle of the switch may be locked in the “Off” position to prevent unintended operation
.
CHILLED WATER VALVE
HUMIDIFIER (OPTIONAL)
PREFERRED POWER SELECTOR SWITCH (OPTIONAL)
AIR PROVING SWITCH & DIRTY FILTER SWITCH (OPTIONAL)
ELECTRIC BOX
CONDENSATE PUMP (OPTIONAL)
BLOWER(S)
BLOWER MOTOR
As an option, hot water re-heat may be selected. A hot water heating coil is factory installed in the supply air stream after the cooling coil to heat the supply air. A valve is provided to control the flow of hot water through the coil to maintain the correct re-heat temperature.
1.5.4 Coil(s)
The cooling and optional hot water re-heating coils are aluminum finned/copper tube construction. The coils are leak tested and cleaned before installation by the factory.
1.5.5 Blower(s)
1.5.2 Circuit Breakers / Motor Start Protectors
Individual overload protection is provided by circuit breaker(s) and motor start protectors. These switches must be manually re-set once the overload condition is cleared.
1.5.3 Heaters (Optional)
The precision A/C unit incorporates heaters for re-heating the supply air, as required to offset the sensible cooling of the system during the dehumidification cycle, and for the automatic heating mode. As a standard, electric resis­tance heating elements are factory installed in the supply airstream after the cooling coil to heat the supply air.
1-4
The unit is equipped with belt driven centrifugal blower(s) with forward curved blades. The quantity of blowers varies depending upon the capacity of the A/C unit. Each blower is dynamically and statically balanced to minimize vibration. The blower is con­tained in a double-width, double-inlet housing. The blower motor uses dual drive belts.
The blower motors are ODP industrial duty and utilize permanently lubricated ball bearings. The motor is mounted on an adjustable base for belt tensioning and is furnished with an adjustable pitch sheave to change the blower speed.
(© Oct, 2007)
ir Technology Systems, Inc.
Page 9
Compact CW Series Installation, Operation & Maintenance Manual
A
1.5.6 Temperature/Humidity Sensor
As a standard for room air control, a temperature/ humidity (T/H) sensor is factory mounted in the return air stream. The (T/H) sensor monitors the return air conditions and provides input signal(s) to the system controller to manage the operation of the A/C unit consistent with the setpoints entered in the system controller.
1.5.7 Humidifier (Optional)
Compact CW systems utilize an electrode, steam humidifier. The humidifier is factory installed inside the air conditioner and includes fill and drain valves and associated piping. Operation of the humidifier’s fill and drain cycles is based on water conductivity and is maintained by the humidifier controller. An operating manual for the humidifier is provided under separate cover. Refer to that manual for detailed information on operation of the humidifier.
1.6 Optional Equipment
1.6.1 Condensate Pump
source. If power is transferred, the system controller provides an alarm signal and the alarm display indicates which power source failed. When the primary power source is functionally restored, the A/C system load is automatically transferred back to the primary power source.
FRONT DOOR OF A/C SYSTEM
INDICATOR LIGHTS (OPTIONAL)
OPTIONAL DUAL DISCONNECT SWITCHES (LOCATION MAY VARY)
An optional condensate pump may be used for auto­matic removal of condensate from the air conditioner and flush water from the humidifier. An internal overflow safety switch is wired to the system controller to automatically shut down the precision A/C system should an overflow occur.
1.6.2 Smoke Detector
Optionally mounted in the return air stream, a photo­electric smoke detector is used to sense the presence of smoke and signal the controller when a smoke alarm condition exists.
1.6.3 Firestat
Optionally mounted in the return air stream, a fire detector senses high retun air temperature and signals the controller when a fire alarm condition exists.
1.6.4 Auto Transfer Switching
An automatic transfer, main power switching system is optionally available for critical operation. With this option, two main power service disconnect switches are provided on the door of the cabinet to connect two independent power sources, (see Figure 2). If the user selectable, main power source is interrupted, or if a phase loss or imbalance occurs, the automatic transfer switching circuitry immediately transfers operation of the precision A/C system to the secondary power
Figure 2- Auto Transfer Disconnect Switches
With the auto-transfer switching option, a preferred power selection switch is mounted inside the cabinet to the top of the electric box, (see Figures 1 & 3). This switch may be used to manually transfer the power source and/or to test the auto transfer switching function.
Figure 3- Preferred Power Selection Switch
1.6.4.1 Indicator Lights
As an additional option, an indicator light may be provided above each main power service disconnect switch for a visual indication that power is available.
(© Oct, 2007)
1-5
ir Technology Systems, Inc.
Page 10
A
Compact CW Series Installation, Operation & Maintenance Manual
40.0"
(
)
S
E
S
S
E
S
SCO
CH
2.0 INSTALLATION
2.1 Receiving the Equipment
Your
Compact CW
tested and inspected prior to shipment. To ensure that your equipment has been received in excellent condi­tion, make a visual inspection of the equipment immediately upon delivery. Carefully remove the shipping container and all protective packaging. Open the access doors and thoroughly inspect the unit interior for any signs of transit-incurred damage. If there is shipping damage, it must be noted on the freight carrier's delivery forms BEFORE signing for the equipment. Any freight claims MUST be done through the freight carrier. SATS ships all equipment FOB. SATS can assist in the claim filing process with the freight carrier. Should any damage be present, notify the SATS Product Support Group prior to attempting any repairs. Refer to section five of this manual for instructions.
precision A/C system has been
EE NOT
MINIMUM FRONT
CLEARANCE
ERVICE
DI
EE NOT
NNECT SWIT
A Data Package has been sent with your unit. It contains this manual, a supplemental microprocessor controller manual, system drawings, applicable MSDS’s, other component manuals, warranty registra­tion and other applicable instructions based on the configuration and options of your unit. The data package has been placed in your unit in a clear plastic bag. These documents need to be retained with the unit for future reference.
NOTE
Items that have been shipped loose, such as controllers, temperature/humidity sensors, wa­ter detectors, etc., are shipped inside the air conditioner, unless specified otherwise by the customer. The filter box or plenum box assem­bly (if applicable) is shipped separately. Unpack and store these items in a safe place unless you are using them immediately.
2.2 Site Preparation
Compact CW
access in mind. Component access panels are located on the front of the equipment. The number of panels may vary depending on size and configuration of the unit. Each unit has one front hinged panel for accessing the electrical box. In order to have full service access, no permanent obstructions can be placed in front of the unit. See Figure 4 for the mini­mum recommended clearance in front of the unit.
systems are designed with easy service
NOTE: FOR UPFLOW UNITS, ALLOW SPACE ON
IDES TO PERMIT ENTRANCE OF PIPING AND WIRING.
Figure 4- Recommended Installation Clearance
NOTE
Working clearance requirements need to be es­tablished prior to mounting the unit. Refer to lo­cal and national electrical codes.
To minimize the effects of the environment surrounding the conditioned space, certain steps must be taken. This is especially true for critical/precision room preparation (computer rooms/labs) requiring close tolerance control of temperature and humidity. The conditioned space should be well insulated and include a vapor barrier. The installer should ensure that the proper insulation rating is used based on the design of the space, which was the basis for the system selected. The following chart is a recom­mended minimum R-value (thermal resistance) to ensure optimum equipment operation.
STRUCTURE R-VALUE
Ceiling R-38
Wall R-21 Floor R-19 Door R-5
The vapor barrier is the single most important require­ment for maintaining environmental control in the conditioned space. The vapor barrier in the ceiling and
2-1
(© Oct, 2007)
ir Technology Systems, Inc.
Page 11
Compact CW Series Installation, Operation & Maintenance Manual
A
S
H
HINGED
OOR
OPTIONAL FLOOR STAND
OX
Y
(
)
HINGED
OOR
S
S
CH
walls can be a polyethylene film. Concrete walls and floors should be painted with a rubber or plastic based paint. Doors and windows should be properly sealed and a door sweep used to minimize leakage. Outside or fresh air should be kept to a minimum (as it adds to the cooling, heating, dehumidification and humidifying loads), while still maintaining the requirement of the Indoor Air Quality (IAQ) standard. Lack of attention to these factors can cause erratic operation, unstable room control and excessive maintenance costs.
2.3 Rigging
Compact CW
vertical position. Move the unit with a suitable device such as a forklift, roller bar, pallet jack or dollies. For reference, a weight table is provided on the installation drawing. Units are shipped on a skid to facilitate moving prior to installation. Units should always be stored indoors in a dry location prior to installation.
systems are designed to be kept in the
Figure 5- Typical Installation Upflow
PLENUM B ASSEMBL
OPTIONAL
ERVICE WIT
D
CAUTION
When moving the unit, it must be kept level and in the vertical position to prevent damage.
2.4 Mounting/Placement
Compact CW
signed to be located in the conditioned space. Ducted units may be located inside or outside the conditioned space, but are designed to supply air to only one room. The which allows the units to be placed in a corner or between cabinetry. It is recommended that the unit is positioned to obtain optimum air circulation.
Placement of the floor or ceiling registers is im­portant. If they are too close to the unit, the sup­ply air will be re-circulated back to the unit be­fore it has circulated throughout the space.
See Figures 5 and 6. The unit is designed to be located directly on top of the floor (typically upflow) or on a raised floor (typically downflow).
systems that are not ducted are de-
Compact CW
systems are front accessible,
NOTE
D
ERVICE
SWITC
Figure 6- Typical Installation Downflow
CAUTION
Ensure the mounting surface is capable of sup­porting the weight of the equipment. Before mount­ing the unit, refer to the weight table provided on the installation drawing. On some raised floor in­stallations, a floor stand is required, depending on the load capacity of the existing raised floor.
(© Oct, 2007)
2.4.1 Precision A/C Unit
The construction for unit rigidity and full service accessibil­ity without moving the unit. If a floor stand is used, refer to the installation drawing provided and cut out the raised floor to match the unit’s overall base dimension. If a floor stand is not used, cut out the
ir Technology Systems, Inc.
Compact CW
system uses a frame and panel
2-2
Page 12
A
Compact CW Series Installation, Operation & Maintenance Manual
N
SU
Y
T
N
SU
Y
T
raised floor to match blower discharge opening(s) and any required piping and wiring holes. Refer to the installation drawing supplied with the unit for dimen­sional information.
NOTE
Equipment must be level to operate properly.
2.5 Air Distribution Connection
2.5.1 Downflow Configuration Air Patterns
In a downflow configured unit, the conditioned supply air discharges through the bottom of the unit into a raised floor. There are two basic return air patterns: top free return and top ducted return (see Figure 7).
When determining ducting requirements, always consult your local or state codes. The duct system should be designed to allow the air to move with as little resistance as possible.
The return inlet is provided with a turned-in flange on top of the unit for connection of the ductwork. Refer to the installation drawing provided with the unit. The connection of ductwork to the unit may be made with either pop rivets or self-tapping screws.
2.5.2 Upflow Configuration Air Patterns
In an upflow configured unit, the conditioned supply air has two methods of discharge: ducted or through a 2 or 3-way grilled plenum box. There are two basic return air patterns: front free return and rear ducted return (see Figures 8 and 9).
The supply air outlet and the rear ducted return air inlet are provided with a flange for connection of the ductwork (refer to the installation drawing provided with the unit). The connection of ductwork to the unit may be made with either pop rivets or self-tapping screws.
RETUR
PPL
AIR OUTLE
RETUR
PPL
AIR OUTLE
TOP FREE RETURN
Figure 7- Downflow Configuration Typical Air Patterns
2-3
TOP DUCTED RETURN
(© Oct, 2007)
ir Technology Systems, Inc.
Page 13
Compact CW Series Installation, Operation & Maintenance Manual
A
A
N
SUPPLY
AIR OUTLE
N
SU
Y
T
TOP DISCHARGE 2 OR 3 WAY PLENUM BOX
SUPPLY
AIR OUTLET
SUPPLY
IR OUTLET
RETURN
AIR INLET
FRONT FREE RETURN
REAR DUCTED RETURN
Figure 8- Upflow Configuration Typical Air Patterns (Top Discharge)
TOP DUCTED DISCHARGE
PPL
AIR OUTLE
RETURN
AIR INLET
FRONT FREE RETURN
Figure 9- Upflow Configuration Typical Air Patterns (Top Ducted Discharge)
(© Oct, 2007)
R
R
REAR DUCTED RETURN
2-4
ir Technology Systems, Inc.
Page 14
A
Compact CW Series Installation, Operation & Maintenance Manual
2.6 Optional Equipment (Field Installed)
NOTE
Do not mount any optional equipment on the unit access doors.
2.6.1 Floor Stand
Install the floor stand directly on the sub-floor, ensuring the side with the "FRONT" label is facing the same direction as the front of the precision A/C unit (see Figure 10). Refer to the floor stand assembly drawing for the dimensions required to cut the raised floor. The optional floor stand is designed with adjustable feet on all the legs, allowing for leveling and and overall height adjustment. Refer to the floor stand assembly drawing for minimum and maximum height adjustability of your floor stand. To adjust the height, first loosen the middle nuts on each leg. Next, turn the top hex nuts to raise or lower the floor stand. Once the floor stand is level and even with the raised floor, lock all feet in place by tightening the middle hex nuts against the top hex nuts.
refer to the system drawings and the supplemental manual sent in the data package with your unit.
2.6.4 Condensate Pump
An optional, factory installed condensate pump may be provided for automatically eliminating condensate and humidifier flush water from the drain pan. The conden­sate pump is typically installed by the factory inside the A/C unit. If an optional, field installed condensate pump is selected, it should be located as near as possible to the air conditioning system. The pump should be positioned so the inlet hole in the pump is below the drain pan inside the A/C unit. The pump includes a mounting bracket with two holes to secure it in place. Ensure that the pump is level for proper operation.
2.6.5 Remote Temperature/Humidity Sensor
The remote (T/H) sensor must be located so that it will properly sense the temperature/humidity conditions to be controlled. Depending on the type of control desired (see Section 2.6.5.1), the sensor(s) may be factory mounted and/or shipped loose for field installation.
"FRONT" LABEL
FLOOR STAND LEG
THREADED ROD
TOP HEX NUT
MIDDLE HEX NUT
ISOLATION PAD
Figure 10- Optional Floor Stand Installation
2.6.2 Plenum Box Assembly
The plenum box assembly is shipped loose. To install the 2 or 3-way optional plenum box, place the assembly on top of the unit (see Figure 5). Remove the front grille for access to attach the plenum with the supplied self­tapping screws. Holes are pre-drilled in the unit and the plenum box assembly.
2.6.3 Remote Display
The T/H sensor should not be mounted near a door­way, near or above any heat producing equipment or in an area where it would be exposed to direct sunlight. Follow the steps below to mount the sensor.
COVER SCREW
Temperature/Humidity Sensor
1. Using a flat head screwdriver, remove the cover
plate from the base.
2. Place the base temporarily over the wire hole
opening in the wall. Level the base and mark the mounting hole locations through the two slots.
3. Drill the mounting holes and insert the wall
anchors provided.
4. Run the wires coming out of the wall through the
hole in the base, then secure the base with the screws provided.
5. Make the wiring connections. For wiring details,
see Section 2.8 (Utility Connections) and refer to the wiring diagram supplied with your unit.
As an option, a factory supplied control panel may be remote mounted. For mounting and wiring instructions,
2-5
6. Replace the unit cover plate on the base.
(© Oct, 2007)
ir Technology Systems, Inc.
Page 15
Compact CW Series Installation, Operation & Maintenance Manual
A
CAUTION
Take care not to damage the exposed tempera­ture/humidity sensors on the PC board while screw­ing in the cover fastening screw. The sensors can be damaged if handled improperly.
2.6.5.1 Types of control
Room Air Control (standard)- The A/C unit is provided with a temperature and humidity (T/H) sensor, factory mounted in the return air stream of the A/C unit. The return air temperature and humidity are monitored by the system controller and compared to limit values set at the factory. Control outputs are based on setpoints entered into the system controller by the user.
As an alternative to locating the T/H sensor inside the A/C unit, it may be field installed on a wall in the conditioned space for sensing actual room conditions.
Supply Air Control- As an option, a field installed T/H sensor may be used for supply air control. The sensor is field installed in the supply air stream. The supply air temperature and humidity are monitored by the system controller and compared to limit values set at the factory. Control outputs are based on setpoints entered into the system controller by the user.
Room Air Control with Supply Air Limitation- The controller monitors the T/H sensor located in the return air stream and the T/H sensor located in the supply air stream. Control is similar to “Room Air Control” except, the temperature setpoint is automati­cally increased by the controller when the measured supply air temperature exceeds the Start Temperature entered by the user. The extent of the setpoint increase is determined by a factor which the user enters in the controller as a gradient. A high gradient significantly corrects the failure to meet the supply air tempertaure but has the risk that the control circuit starts to hunt.
With humidity control, the setpoint shift acts in the opposite direction. If the starting humidity entered by the user is exceeded by the measured supply air humidity, the setpoint is autimatically reduced by the controller. The user may also enter a gradient factor for humidity control.
Supply Air Control with Room Air Limitation- Based on the same principle as “Room Air Control with Supply Air Limitation” however, in this case the setpoint shift works in the opposite direction on the basis that the supply air is colder than the return air. The temperature setpoint is automatically reduced by the system controller when the measured room air temperature exceeds the Start Temperature entered by the user. The humidity setpoint is automatically increased by the system controller when the mea­sured room humidity drops below the starting humidity entered by the user.
2.6.6 Remote Water Detector
The remote water detector is normally placed on the sub-floor or in a field supplied auxiliary drain pan located beneath the unit. SATS provides 2 types of water detectors:
Spot type water detector
-
Remove the protective cover and connect two control wires to the terminals on the base (terminal lugs are provided). Place the water detector(s) on the floor with the metal electrodes facing down. The base is provided with a mounting hole in the center which may be used to secure the water detec­tor in place. Replace the cover. When water is present, current will flow between the electrodes.
NOTE
Do not place the spot type water detector on an electrically conductive surface.
Cable type water detector
-
Lay the cable water detector flat across the sub-floor where water could collect. When water is present, current will flow between the two wires. A two conductor wire harness is provided with a quick connect fitting on the end. The harness mates to the fitting on the water detector and connects it to the control board inside the electric box.
2.7 Piping Connections
2.7.1 Chilled Water/Hot Water
Formula: New setpoint = old setpoint+ [gradient • (start value -actual
value)]
Example (temperature): 70.5 = 70 + [0.5 • (61 - 60)]
Example (humidity): 49 = 50 + [0.5 • (70 - 72)]
(© Oct, 2007)
For CCD (downflow) units, the pipe openings for the chilled water and optional hot water reheat piping are located in the base of the unit. For CCU (upflow) units, pilot holes are provided inside the unit in the lower side panel(s). These pilot holes may be enlarged from inside the unit. Refer to the installation drawing
2-6
ir Technology Systems, Inc.
Page 16
A
Compact CW Series Installation, Operation & Maintenance Manual
supplied with your unit for the location of the openings. Generally, all pipe connections (sweat connections) terminate inside the unit. Upflow (CCU) units may be provided with (optional) pipe connections protruding from the top of the unit.
For pipe connection sizes, refer to the following table:
INLET/OUTLET PIPE CONNECTIONS
CW HW
Model # (Inches O.D.) (Inches O.D.)
CCU/D-300 1 1/8” 7/8”
CCU/D-600 1 5/8” 7/8”
CCU/D-900 1 5/8” 7/8”
CCU/D-1500 2 1/8” 7/8”
CCU/D-1800 2 1/8” 7/8”
Field piping is not necessarily the same size as the unit connections. Piping should be sized to match the required system pressure drop and flow capacity, and may require reducing fittings to match the connection size on the air conditioner. A filling connection and several shrader valves are installed in the A/C unit. Refer to the piping diagram supplied with your unit.
The drain line must be located so it will not be ex­posed to freezing temperatures. The diameter of the drain line should be the full size of the connection.
NOTE
Pour some water into the condensate drain pan(s) prior to start-up. This fills the trap and prevents air from being drawn up the drain lines.
2.7.2.2 Condensate Pump
An optional condensate pump is normally factory installed. The drain connection line may be 1/2” ID vinyl tubing or a 1/2” O.D. copper (sweat connection) may be used.
If an optional field installed condensate pump is used, a p-trap must be installed to allow proper condensate drainage (see Figure 11). The height of the trap must be a minimum of 2 inches on standard systems to ensure proper water drainage. The condensate pump discharge line should be 1/2 inch O.D. (maximum) copper pipe to prevent excessive back flow to the condensate pump.
INLET 7/8" OD
OUTLET 1/2" OD
CAUTION
When installing and filling the chilled water and/ or hot water loops, all air must be bled from the piping system and the piping system must be cleaned prior to operating the system. Failure to do so could result in equipment problems.
NOTE
All chilled water lines must be insulated to prevent condensation from forming on the pipes.
2.7.2 Condensate Drain
2.7.2.1 Gravity Drain
A 7/8 inch OD copper (sweat type) line is provided to drain the condensate pan. An “S” trap is installed at the end of piping for the installer to connect a 7/8 inch ID drain line to remove water from the cabinet. This line also drains the optional humidifier.
NOTE
The humidifier drains (hot) water into the condensate drain during normal operation.
SEE NOTE 2
NOTES:
1. MIMIMUM HEIGHT IN INCHES.
2. P-TRAP MUST BE LOCATED IN THE INLET SIDE OF PUMP WHEN FIELD INSTALLED.
2.00
SEE NOTE 1
Figure 11- Condensate Pump
2.7.3 Humidifier
Compact CW
humidifier. The humidifier empties into the condensate drain line during the flush/drain cycle. A water supply line must be connected to the ¼ inch O.D. copper tubing connection supplied by the factory. The humidi­fier requires normal tap water for the water supply. If the supply water is high in particulate, an external filter may be needed. Do not use de-mineralized water. Refer to the humidifier operator’s manual, supplied with the equipment, for complete manufacturer’s informa­tion on the humidifier and the supply water recommen­dations.
systems utilize an electrode steam
2-7
(© Oct, 2007)
ir Technology Systems, Inc.
Page 17
Compact CW Series Installation, Operation & Maintenance Manual
A
2.8 Utility Connections
2.8.1 Main Power
The
Compact CW
460 and 575 volt three-phase configurations. It is imperative that the unit nameplate be examined to determine the operating voltage, frequency and phase of the system (see Figure 12). The nameplate also provides the full load amps (FLA), the current the unit will draw under full design load, the minimum circuit ampacity (MCA) for wire sizing, and the maximum fuse or HACR (Heating, Air Conditioning, Refrigeration) breaker size (MAX FUSE/CKT BKR) for circuit protec­tion. The unit's nameplate is located inside the cabinet, within the electrical box.
product offering is available in 208,
NOTE
If the nameplate states MAX FUSE/CKT BKR, it is required to use fuses or a HACR type cir­cuit breaker to protect the system. Other pro­tection devices are not allowed based upon the product listing.
The unit is provided with terminals for all required field­wiring connections. Refer to the electrical schematic supplied with the unit for all power and control field­wiring. It is important to identify the options that were purchased with the unit in order to confirm which field connections are required.
WARNING
Verify power is turned off before making connec­tions to the equipment.
NOTE
All wiring must conform to local and national elec­trical code requirements. Use of copper conduc­tors only is required. Wiring terminations may become loose during transit of the equipment; therefore, it is required to verify that all wiring terminations are secure.
It is important to verify that the main power supply coincides with the voltage, phase and frequency information specified on the system nameplate. The supply voltage measured at the unit must be within ±10% of the voltage specified on the system name­plate.
Each unit is provided with pilot holes for connection of main power and control field-wiring. These pilot holes are located on the
Compact CW
unit based on configuration. On a downflow configuration, the pilot holes are located in the floor of the cabinet. On an upflow configuration, pilot holes are located inside the cabinet in the side wall. These pilot holes may be enlarged from inside the unit. A label stating "MAIN POWER INPUT" is in close proximity. See the installation drawing supplied with your unit for pilot hole locations.
Terminate the main power wires at the line side of the main power disconnect switch, located within the electric box (see Figure 13). A separate equipment ground lug is provided within the electrical box for termination of the earth ground wire.
Figure 12- Sample Nameplate
(© Oct, 2007)
2-8
ir Technology Systems, Inc.
Page 18
A
Compact CW Series Installation, Operation & Maintenance Manual
2.8.2 Controls
7
6
5
1
SATS offers a wide range of control features to solve your air conditioning control/alarm requirements. The
Compact CW
system is furnished with a C1002 or C6000 Microprocessor controller. If it is mounted on the unit (standard), no utility connection is required. As an option a factory supplied display may be remote
2
mounted. A six-conductor cable harness is provided for interconnect wiring. Refer to the electrical drawing provided with the unit for details on interconnecting field wiring.
2.8.3 Optional Equipment
Figure 13- Electric Box
The number callouts in Figure 13 coincide with the numbered items listed below:
1. Control I/O Board
2. Interface Terminals
3. Main Power Disconnect Switch
4. Ground Lug
5. Power Switches/Motor Start Protectors (Quantity varies by size of A/C unit)
6. Water Detector Circuit Board (Optional)
7. Transformer Circuit Breakers
CAUTION
Improper wire connections may result in the re­verse rotation of the fans/blower motors and may eventually result in damage to the unit. To cor­rect this problem, exchange any two of the in­coming main power wires at the main power dis­connect switch. Do NOT rewire the unit's indi­vidual components.
CAUTION
3
Additional control conductors may be required depend­ing on the options purchased with the equipment.
4
Refer to the electrical diagram supplied with your unit to determine the total number of interconnecting conductors required for your system. It is important to note that control transformer(s) supplied with the equipment are sized and selected based upon the expected loads for each system.
CAUTION
Do not connect any additional loads to the sys­tem control transformers. Connecting additional loads to the factory supplied control transformer may result in overloading of the transformer.
NOTE
All wiring must be provided in accordance with local and national electrical code requirements.
2.7.3.1 Remote Temperature/Humidity Sensor
The remote temperature/humidity sensor requires a three conductor shielded cable, with the shield terminated at the unit electric box. Both the electric box and the sensor are provided with a terminal strip for the wire connections. Refer to the electrical schematic supplied with your unit for proper wire terminations.
Prior to unit operation, an adequate unit-to-earth ground must be connected to the unit.
2-9
2.7.3.2 Remote Water Detector
Each remote water detector used will require two conductors to be wired to the control terminal board within the unit electrical box (see Figure 13). The wire insulation must be rated at 600V. Refer to the electri­cal schematic supplied with your unit for proper wire terminations.
(© Oct, 2007)
ir Technology Systems, Inc.
Page 19
Compact CW Series Installation, Operation & Maintenance Manual
A
2.9 System Settings and Adjustments
2.9.1 Chilled Water Circuit
In a chilled water A/C unit, cooling is maintained by flowing chilled water through a cooling coil. A water valve proportionally opens to increase fluid flow as the temperature rises (or closes as the temperature falls). If the unit is turned off, the valve will return to the closed position, shutting off flow through the coil. Chilled Water control valves are available in 2-way or 3­way configurations. Refer to the piping drawing supplied with your unit to determine which type valve is provided.
Location and size of chilled water valves differs with the size of the A/C unit. The chilled water valves are factory set for the correct operation and should not require field adjustment.
2.9.2 Humidifier Adjustment
The humidifier has a capacity adjustment potentiom­eter on the humidifier control circuit board. The capac­ity potentiometer may need to be field adjusted if the humidifier is not supplying enough capacity for current room conditions.
It is recommended that if the humidifier capacity potentiometer requires adjustment, the adjustment is made in small increments and verified. Refer to the humidifier manual sent with your unit for the capacity potentiometer location.
CAUTION
Adjusting the capacity potentiometer too high may result in formation of condensation within the system.
2.9.3 Blower
The blower motor (see Figure 14) is supplied with an adjustable sheave (pulley), to change blower speed, and an adjustable base for belt tensioning. Use the following procedure to change the blower speed.
1. Turn the A/C system off.
2. Turn off all power to unit at the main power discon­nect switch; use lock-out tag-out procedure.
3. Remove the blower belt(s).
4. Loosen the set screw in the side of the motor sheave with an allen wrench.
5. Remove the sheave key.
6. Adjust blower speed by closing the sheave one half
turn to increase speed or opening the sheave one half turn to decrease speed.
7. Replace the sheave key and tighten set screw.
ADJUSTABLE SHEAVE
MOTOR
BASE LOCKING BOLT
JAM NUT
LOCK DOWN PLATE
MOTOR BASE
BLOWER
TENSION ROD ADJUSTMENT
Figure 14- Blower Assembly
8. Proper belt tension is achieved when the belt has a deflection of ¾ inch per foot of span between the blower and motor pulleys, with firm pressure placed mid-span on the blower belt. To adjust blower belt tension, loosen the locking bolt on the side of the motor base. Turn the jam nut away from the lockdown plate. Rotate the tension rod to move the motor on it’s base to increase or decrease belt tension. Re-tighten the jam nut and tighten the locking bolt on the motor base.
CAUTION
If the belt tension is too tight, it will cause premature blower and/or motor bearing failure. If the belt is too loose, the belt will slip and cause belt squeals and eventual belt failure.
9. Restore power to system.
10. Check the current draw on the blower motor to make sure it does not exceed the nameplate rating of the motor.
11. If current draw exceeds nameplate rating of motor, repeat steps 1 through 9 to decrease the blower speed. If the motor pulls too much current, slow the blower down by opening the adjustable sheave one half turn at a time, until the motor current is at or below the nameplate FLA.
12. Check the motor overload on the blower starter to confirm its setting is correct for the FLA of the motor.
(© Oct, 2007)
2-10
ir Technology Systems, Inc.
Page 20
A
Compact CW Series Installation, Operation & Maintenance Manual
3.0 START-UP/COMMISSIONING
3.1 Operation
For new installations, ensure the unit is ready to operate by going through the Checklist for Completed Installation, located in Appendix A, prior to start-up.
NOTE
A Warranty Registration and Start-Up Checklist is provided with the unit data package. It should be completed during start-up and sent to SATS. This checklist should be used as a guideline for items that need to be confirmed during start-up.
Start-up must be performed by a journeyman, refrig­eration mechanic or an air conditioning technician.
3.2 Step by Step Start-Up Instructions
1. Replace all equipment removed prior to performing start-up checks.
2. Ensure that the control circuit breakers, fan motor starter switch and additional built in optional equipment power switches are turned on.
3. Apply power to the main power disconnect switch.
4. Turn on the A/C unit at the system controller and set the desired values (setpoints) for room temperature and humidity. (Refer to the separate controller operation instructions included in the data package with your unit.)
5. Ensure that all blowers and fans are rotating correctly and freely without any unusual noise.
Compact CW
system at the
8. Test dehumidification operation by creating a demand for dehumidification. If necessary, set the dehumidification setpoint 10% below actual room conditions (the set point may already be below the actual room conditions, especially at start-up). The chilled water valve should open to begin the dehumidification process. While in this mode, room temperature may decrease and the reheat function may activate. As conditions in the room change, you may have to readjust the setpoint as you check operation. An adequate heat load within the space is required.
9. For Electric Reheat, use an amp meter on the heater circuit to determine if the heater is opera­tional. For Hot Water Reheat ensure that the control signal has energized the control valve and the temperature of the water has decreased as it passes through the unit. In all cases, 1 to 6 hours might be required to see a desired level or decrease in humidity in the conditioned space. Once room conditions have been programmed or set, a repeat visit to the conditioned space may be required to ensure the dehumidification mode is meeting the room’s requirements.
3.3 Microprocessor Controller Programming
The microprocessor controller is factory programmed based on the optional features selected. Most applica­tions require no field start-up or program adjustment beyond setting the current date and time. Separate operating instructions for the controller have been sent with your unit, including each feature's factory "default" setting and the available adjustment range, if appli­cable.
6. Test cooling operation by setting the temperature setpoint below actual room temperature. The chilled water valve should open and the discharge air should feel cooler than the return air.
7. Test humidification operation by creating a demand for humidification. Use an amp meter to determine current draw of the humidifier. Visually check for vapor leaving the steam head or feel if the cylinder is warm to verify if the humidifier is operational. In all cases, 1 to 6 hours might be required to see a desired level or rise in humidity in the conditioned space. Once room conditions have been programmed or set, a repeat visit to the conditioned space may be required to ensure the humidifier is meeting the room's requirements.
3-1
(© Oct, 2007)
ir Technology Systems, Inc.
Page 21
Compact CW Series Installation, Operation & Maintenance Manual
A
4.0 MAINTENANCE
4.1 Periodic General Maintenance
Systematic, periodic general maintenance of the
Compact CW
system performance. General maintenance should include, but is not limited to the following: replacing filters and humidifier cylinders, tightening electrical connections, checking the water lines to ensure they are free of debris, ensuring no air is in the water line(s), cleaning the interior of the unit, checking belt tension and inspecting the unit’s components visually.
Use copies of the Periodic General Maintenance Checklist in this manual (see Appendix A) to record periodic general maintenance inspections. For assistance, contact the SATS Product Support Group. Ensure adherence to all safety statements while performing any type of maintenance.
unit is recommended for optimum
WARNING
This equipment should be serviced and repaired by a journeyman or a qualified refrigeration technician only.
WARNING
This unit employs high voltage equipment with rotating components. Exercise extreme care to avoid accidents and ensure proper operation.
Hazardous voltage will still be present inside the electric box at the motor start protectors and at the heater and humidifier circuit breakers, even with the unit turned off at the microprocessor controller. To isolate the unit for maintenance, turn off power at the main power disconnect switch. Always disconnect main power prior to performing any service or repairs.
4.1.1
4.1.1.1 Filter
The filter is usually the most neglected item in an air conditioning system. To maintain efficient operation, the filter should be checked at least monthly and replaced as required.
4.1.1.2 Blower
The blower motor is provided with permanently lubri­cated bearings and should not require maintenance for the lifetime of the equipment. Periodic checks of the blower system should include checking the blower motor mounts, housing, belts and blower wheel. Check that all mounts are secure and the blower wheel is tightly mounted on the shaft and does not rub against the fan housing. The blower vanes should be kept free of debris.
4.1.1.3 Drain Pan
To ensure proper drainage, inspect the drain pan regularly. Make sure the drain pan outlets are always free of debris and ensure the drain pan does not leak.
4.1.1.4 Coils
The coil(s) should be inspected semi-annually and cleaned as required, following standard coil cleaning practices. Using a brush, clean the coil fins of all debris that will inhibit airflow. This can also be done with compressed air or with a commercial coil cleaner. Check for bent or damaged coil fins and repair as necessary. Check all piping for signs of leaks.
4.1.1.5 Heat/Reheat
Compact CW
Air quality conditions of spaces vary and filters should be checked based on those conditions.
Precision A/C Unit
NOTE
WARNING
Turn off power to the unit unless you are per­forming tests that require power. With power and controls energized, the unit could begin operat­ing at any time. To prevent personal injury, stay clear of rotating components as automatic con­trols may start them unexpectedly.
(© Oct, 2007)
The heat/reheat equipment should be inspected semi­annually to ensure it is operational. If you have electric heat/reheat, inspect the heating elements to ensure they are free of debris.
4.1.1.6 Humidifier
The steam cylinder has a limited lifetime and must be replaced periodically. Because water conditions and humidifier usage rates vary greatly, it is difficult to establish intervals for changing the cylinder. Individual maintenance schedules must be determined for each location, based upon periodic examination of the
4-1
ir Technology Systems, Inc.
Page 22
A
Compact CW Series Installation, Operation & Maintenance Manual
humidifier. A change cylinder light on the humidifier cabinet will illuminate (red) when the cylinder requires replacement.
NOTE
The red light may illuminate during initial start­up but it doesn’t necessarily mean the cylinder
4.1.1.7 Condensate Pump
The condensate pump should be inspected semi­annually and cleaned. Ensure that the float works freely. Wipe the float with a wet cloth and detergent to remove dirt. Clean the tank bottom. Check that the discharge line is open and water can pass through it freely.
needs to be replaced.
Refer to the humidifier operator’s manual supplied under separate cover for detailed instructions for changing the cylinder.
4.2 Troubleshooting
Turn off all power to the unit before conducting any troubleshooting procedures, unless the procedure specifi­cally requires the system to operate. For troubleshooting purposes, the system may be operated with the doors open by using the yellow knob to turn the shaft of the main power disconnect switch to the "On" position. When the switch is turned on, high voltage will be present inside the cabinet. Exercise caution to prevent injury. Keep hands, clothing and tools clear of the electrical terminals and rotating components. Ensure that your footing is stable at all times.
SYMPTOM PROBABLE CAUSE RECOMMENDATION
Chilled Water Valve Fails a. Temperature setpoint too high Adjust to correct temperature setting to Open or Close
b. No control power to the valve Valve actuator is wired incorrectly.
Check wiring schematic and rewire if required.
c. Actuator failed Replace actuator
Blower(s) Fail to Start a. Power failure Check main voltage power source
input cable
b. Control transformer circuit Check for short circuit or ground fault, breaker tripped if none re-set circuit breaker.
c. Motor starter protector tripped Reset motor starter protector and check
amperage of motor. Compare to setting on motor starter protector and adjust to FLA.
d. Condensate overflow switch open. 1. Ensure unit is level
2. Check that condensate pan is draining properly. Clear obstructions.
e. Defective contactor Repair or replace
Control is Erratic Wiring improperly connected or Check wiring against schematic
broken diagram
4-2
(© Oct, 2007)
ir Technology Systems, Inc.
Page 23
Compact CW Series Installation, Operation & Maintenance Manual
A
SYMPTOM PROBABLE CAUSE RECOMMENDATION
System Short of Capacity a. Low Chilled Water flow Check for leaks. Repair and recharge
system.
b. Supply water temperature too high Check chilled water supply
c. Reduced airflow Check filters
d. Dirty Coil Clear coil fins of debris
Electric Heater a. Circuit breaker tripped Check for short circuit, reset circuit Inoperable breaker
b. Temperature setpoint too low Increase temperature setpoint
c. Overheat switch open Insufficient air flow across heater
elements. Check for dirty filters or obstructions that may reduce air flow. Correct or replace as needed.
d. Manual reset overheat safety Reset manual overheat safety switch switch tripped (see item immediately above).
e. Heater element burned out Check continuity with an ohmmeter
Replace heater element
Hot Water Heater a. Low hot water flow Check hot water flow at supply source Inoperable Inspect piping for leaks or obstructions
b. Low hot water supply temperature Check hot water supply
c. Temperature setpoint too low Increase temperature setpoint
d. Control power interrupted Check for loose or broken wires
Humidifier Inoperable a. Water supply has been turned Connect and/or turn on water supply Note:
See Humidifier
off or not connected
Manual for Additional Help
b. Humidifier switch is in “Off” position Turn switch to “Auto/On” position
c. Electrical connections are loose Tighten electrical connections
d. Humidifier circuit breaker tripped Check for over current by the humidifier
electrodes. Drain water from tank and refill. Reset circuit breaker.
e. Relative humidity is above setpoint. Adjust humidity setpoint
f. Electrode canister change cylinder 1. Consult humidifier manual light is on
2. Water conductivity is too low and water is at the top of the cylinder, (see next item).
(© Oct, 2007)
g. Water conductivity is too low Add a teaspoon of table salt to the water
through the top of the cylinder. Typically only required on initial start-up.
4-3
ir Technology Systems, Inc.
Page 24
A
Compact CW Series Installation, Operation & Maintenance Manual
4.3 Field Service
NOTE
Do not attempt to make repairs without the proper tools.
It may be necessary to perform repairs on the A/C system. If field repairs are necessary, the following procedures apply:
1. All electrical connections should be checked to ensure they are tight and properly made.
2. Check all circuit breakers, contacts and wiring. The contacter should be examined and replaced if contacts are worn or pitted.
4.3.1 Piping
When replacing components within the cabinet of the unit, the following consumable materials are recom­mended: Use Silfos alloy for copper-to-copper (piping discharge or suction line repairs). Silver solder (Stay­Silv #45) and flux are to be used on copper-to-brass or copper-to-steel repairs.
When component replacement is complete, remove all traces of flux. After any repair, pressure check the system to check for leaks prior to recharging the system.
4.3.2 General Common Repairs/
Component Replacement
4.3.2.1 Humidifier Cylinder Replacement
After an extended period of operation a red light will illuminate on the humidifier cabinet indicating that the cylinder is completely used and a replacement cylinder must be installed. The cylinder is disposable and cylinder life is dependent on water supply condi­tions and humidifier usage. The following procedures are to be followed when replacing the cylinder.
CAUTION
Failure to replace the cylinder at the end of cyl­inder life may result in humidifier damage.
3. When drained, push the “Auto On/Off/Drain” switch to the “Off” position.
4. Turn off power at the main power disconnect switch.
5. The power wires to the cylinder are attached by cylinder plugs to the electrode pins on top of the cylinder. Pull these plugs vertically off the pins.
CAUTION
The cylinder and steam hose may be hot and burns may result.
6. Loosen the steam hose clamp(s) and pull the steam hose off vertically.
7. Lift the cylinder straight up to disengage it from the humidifier.
8. Place the new cylinder on the side mounting slots within the unit, ensuring the cylinder mounting stubs are seated properly.
9. Replace the cylinder plugs on the pins, ensuring the white sensor plug goes on the single pin, which is offset from the others.
10. Ensure the plugs are secured on the pins. If the plugs are loose, they may be temporarily squeezed together, however, the plugs must be replaced since a loose plug could generate enough heat to melt and destroy the plug.
11. Replace the steam hose and tighten the clamp(s).
12. Turn on main power at the main power disconnect switch.
13. Push the “Auto On/Off/Drain” switch to the “Auto On” position.
14. Turn on the water supply to the humidifier.
15. Re-adjust the humidity setpoint.
If the humidifier is to be shut down for an extended period, always drain the cylinder first. Follow the above steps (1 through 4) ensuring the “Auto On/Off/Drain” switch is in the “Off” position. Failure to do this will drastically shorten the cylinder life.
4.3.2.2 Filter Replacement
NOTE
Decrease the humidity setpoint below ambient humidity to allow the cylinder to cool down be­fore removing the cylinder.
1. Turn off water supply to the humidifier.
2. Drain the cylinder by pushing the “Auto/On-Off­Drain” switch to the “Drain” position.
4-4
The filters are located either internal to the cabinet or external to the cabinet, depending on the configuration of the unit. Regardless of location, all filter access locations, except for the front hinged access door, are labeled "FILTER ACCESS". Remove the old filter(s). Insert the new filter(s), ensuring directional airflow arrows on the filters are correct, then close the access panel.
(© Oct, 2007)
ir Technology Systems, Inc.
Page 25
Compact CW Series Installation, Operation & Maintenance Manual
A
5.0 PRODUCT SUPPORT GROUP
SATS provides to its customers a Product Support Group (PSG) which not only provides technical support and parts but the following additional services, as requested: performance evaluations, start-up assistance and training.
5.1 Technical Support
The SATS Product Support Group (PSG) is dedicated to the prompt reply and solution to any problem encountered with a unit. Should a problem develop that cannot be resolved using this manual, you may contact PSG at (240) 529-1399 Monday through Friday from 8:00 a.m. to 5:00 p.m. EST. If a problem occurs after business hours, dial the page number (301) 414-4514 and follow the steps below:
1. Wait for the dial tone.
2. Dial your telephone number (including area code).
3. Press the pound (#) key.
A written (or faxed) purchase order is required on warranty parts and must be received prior to 12:00 p.m. for same day shipment. The purchase order must contain the following items:
Purchase Order Number
Date of Order
SATS Stated Part Price (obtained from PSG)
Customer Billing Address
Shipping Address
Customer's Telephone and Fax Numbers
Contact Name
Unit Model No., Serial No. & SATS Item No.
The customer is responsible for the shipping cost incurred for returning the defective part(s) back to SATS. Return of defective part(s) must be within 30 days at which time an evaluation of the part(s) is conducted and if the part is found to have a manufac­turing defect a credit will be issued.
4. Wait for a busy signal.
5. Hang up the telephone.
One of our service technicians will return your call. When calling to obtain support, it is vital to have the following information readily available, (information is found on unit's nameplate):
Unit Model Number (CCU/D-XXX-XX)
SATS Item Number (123456)
Unit Serial Number (1234567)
Description of Problem
5.2 Obtaining Warranty Parts
Warranty inquires are to be made through the Product Support Group (PSG) at (240) 529-1399 Monday through Friday from 8:00 a.m. to 5:00 p.m. EST. A service technician at SATS will troubleshoot the system over the telephone with a field service techni­cian to determine the defect of the part. If it is deter­mined that the part may be defective a replacement part will be sent UPS ground. If the customer requests that warranty part(s) be sent by any other method than UPS ground the customer is responsible for the shipping charges. If you do not have established credit with SATS you must provide a freight carrier account number.
When returning defective part(s), complete the Return Material Authorization Tag and the address label received with the replacement part.
See SATS Standard Warranty located in section one of this manual.
5.3 Obtaining Spare/Replacement Parts
Spare and replacement parts requests are to be made through the Product Support Group (PSG) by fax (301) 620-1396, telephone (240) 529-1399 or e-mail (parts@stulz-ats.com). Quotes are given for specified listed parts for a specific unit.
SATS accepts Visa and MasterCard. SATS may extend credit to its customers; a credit application must be prepared and approved (this process could take one week).
A 25% minimum restocking charge will be applied on returned stocked parts that were sold as spare/ replacement parts. If the returned part is not a stocked item, a 50% restocking charge may be applied. Additionally a Return Material Authorization Number is required when returning parts. To receive credit for returned repair/replacement parts, the parts must be returned to SATS within 30 days of the purchase date. Spare part sales over 30 days old will be considered final and the parts will remain the sole property of the ordering party.
(© Oct, 2007)
5-1
ir Technology Systems, Inc.
Page 26
A
Compact CW Series Installation, Operation & Maintenance Manual
NOTES
(© Oct, 2007)
ir Technology Systems, Inc.
Page 27
Compact CW Series Installation, Operation & Maintenance Manual
A
A
ir Technology Systems, Inc.
APPENDIX A - FORMS
Stulz Air Technology Systems Inc.
Frederick, Maryland USA 21704
Telephone: (301) 620-2033 Facsimile: (301) 620-1396
Checklist for Completed Installation
1 Proper clearances for service access have
been maintained around equipment.
2 Equipment is level and mounting fasteners (if
applicable) are tight.
3 Piping completed to refrigerant or coolant loop
(if required).
4 All field installed piping leak tested.
Frederick, Maryland USA 21704
Telephone: (301) 620-2033
Facsimile: (301) 620-1396
12 Ductwork completed or optional plenum
installed (if required).
13 Incoming line voltage matches equipment
nominal nameplated rating ± tolerances.
14 Main power wiring connections to the
equipment, including earth ground, have been properly installed.
5 Refrigerant charge added (if required).
6 Condensate pump installed (if required).
7 Condensate drain line connected and trap is
filled with water.
8 Water supply line connected to humidifier
(if required).
9 Safety pan installed under ceiling mounted
equipment (if required).
10 Filter box installed (if required).
11 Filter (s) installed (if required).
15 Customer supplied main power circuit breaker
(HACR type) or fuses have proper ratings for equipment installed.
16 All wiring connections are tight.
17 Control wiring connections completed to
optional equipment and devices including wiring to a wall mounted control panel (if required).
18 Foreign materials have been removed from
inside and around all equipment installed (shipping materials, construction materials, tools, etc.).
19 Inspect all piping connections for leaks during
initial operation.
(© Oct, 2007)
A-1
ir Technology Systems, Inc.
Page 28
A
Compact CW Series Installation, Operation & Maintenance Manual
(© Oct, 2007)
ir Technology Systems, Inc.
Page 29
Compact CW Series Installation, Operation & Maintenance Manual
A
A
ir Technology Systems, Inc.
Frederick, Maryland USA 21704
Telephone: (301) 620-2033
Facsimile: (301) 620-1396
Periodic General Maintenance Checks and Services Checklist
Date: ____________________________ Prepared By: ___________________________
Model Number: ____________________________ Serial Number: __________________________
Item Number: ____________________________
Monthly
Filters Blower Section Condensate Drain
❏ ❏
Miscellaneous
❏ ❏ ❏
Cleanliness No Obstructions
Check Chilled Water/Hot Water circuits for Air (bleed as required) Coils Clean and Clear of Obstructions Humidifier Cylinder and Controls Operate Properly
❏ ❏
Blower Turns Belts (if applicable)
❏ ❏
Drain is Open Condensate Pan Safety Switches Operate Freely
Semi-Annually
❏ ❏
Tighten Electrical Connections
Check Contacts on Contactors
for Pitting
Heat/Reheat Operational
❏ ❏ ❏
Clean Unit as Necessary
Clean Coils
Clean Condensate Pump
Annually
Inspect Chilled Water System for Leaks and Corrosion Conduct a Complete Check of All Services Listed Above and Clean Unit's Interior
Notes:
___________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ ___________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ ___________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ ___________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________
Signature:________________________________
*** If factory assistance is required for any reason, provide the model number, serial number, and SATS item
number found on the unit nameplate. This will speed the process and ensure accuracy of information. ***
(© Oct, 2007)
A-2
ir Technology Systems, Inc.
Page 30
A
Compact CW Series Installation, Operation & Maintenance Manual
(© Oct, 2007)
ir Technology Systems, Inc.
Page 31
Compact CW Series Installation, Operation & Maintenance Manual
A
Appendix B- Glossary
Definition of Terms and Acronyms
SATS - Stulz Air Technology Systems, Inc.
BTU/Hr - British Thermal Units per Hour
CFM - Cubic Feet per Minute
CNDCT - Conductor
CW - Chilled Water
ESD - Electrostatic Discharge
º F - Degrees Fahrenheit
FLA - Full Load Amps
FOB - Freight on Board
HACR - Heating, Air Conditioning, Refrigeration
HP - Horse Power
Hz - Hertz
IAQ - Indoor Air Quality
in. w.g. - Inches of Water Gauge
KVA - Kilo Volt Amps
kW - Kilowatt
MAX CKT BKR - Maximum Circuit Breaker
MAX FUSE - Maximum Fuse
MCA - Minimum Circuit Ampacity
MSDS - Material Safety Data Sheet
NEC - National Electric Code
NFPA - National Fire Protection Agency
PH - Phase
PSG - Product Support Group
PSI - Pounds per Square Inch
PSIG - Pounds per Square Inch Gauge
RLA - Run Load Amps
R-Value - Thermal Resistance
SPDT - Single Pole, Double Throw
V - Volt
VAC - Volt, Alternating Current
(© Oct, 2007)
B-1
ir Technology Systems, Inc.
Page 32
A
Compact CW Series Installation, Operation & Maintenance Manual
(© Oct, 2007)
ir Technology Systems, Inc.
Loading...