Stuart Turner Submersible Diver 35 - 45 Boostamatic User Manual

Supplementary Instruction Sheet
- Boostamatic Diver Pumps -
The following information is to be read in conjunction with operation booklets, supplied
with the pump and control module.
IMPORTANT NOTES
Please read these instructions fully before starting the
The installation must comply with the relevant water supply,
electrical and building regulations and be installed by a competent person.
If in doubt, consult Stuart Turner Ltd. Further information can be found in the individual Diver and
Control Module instruction books.
APPLICATION
The Boostamatic Diver range is designed for pressure boosting applications in clean
fresh water systems, where under gravity, no flow is available.
WARNING AGAINST MISUSE
This pump set must not be used for any other application without the
written consent of Stuart Turner Limited and, in particular, must not be connected directly to the mains water supply or used outside the conditions specified in the limits of application.
This appliance is not intended for use by persons (including children)
with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the
appliance.
PRODUCT DESCRIPTION
Control Module
All models use the solid state IP65 rated pressure control module, mounted remotely
with the Diver units. The wetted materials of construction are brass, rubber and nylon 66.
- 1 -
Cont ...
SITING OF THE PUMP/PIPEWORK
WARNINGS:
Ensure pipework from pump is independently supported to prevent
forces being transferred to outlet branch.
Do not under any circumstances use the cable fitted as a means to
carry or lower the pump into position on installation. Attach a rope sling to the lifting eye.
Ensure the pump or controller cannot be subjected to freezing
conditions as damage may result.
Never run pump whilst sucking air/liquid as the motor will overheat. To
prevent this from happening always install pump in the vertical position and ensure fully submerged.
Typical Submersible Boostamatic Installation
Fig. 1
The pumps are supplied with a non-return valve which should be screwed into the pump outlet port using the supplied adaptor (Fig. 2). The purpose of the valve is to limit back flow and pressure on the pump and ensure discharge pipework is always primed with water. The pumps are also supplied with an outlet adaptor which allows for a 25 mm diameter bore hose. The pump should be installed vertically and should be submerged at all times to avoid overheating of the motor. When siting the pump ensure its base is raised slightly from the base of the sump reducing the possibility of blocking the pump inlet filter with debris. The discharge pipework must be independently supported to prevent forces being transferred to pump outlet branch.
If the pump is not to sit on the bottom of the sump or it is too deep, then it should be suspended by a rope attached to the lifting eye located on top of the pump.
All connections are to be as shown in Fig. 2 (ensure all joints are watertight). The control module is to be mounted remotely from the pump in a dry frost free enclosure or building (Fig. 1). Ensure the water flow is in the direction of the arrows that are moulded onto the pressure control module (vertically upwards).
The control module must be mounted in the vertical position and not mounted in any other way (on its side for instance).
The pump must be wired to the control module as detailed in wiring diagram section.
- 2 -
Cont ...
Hose adaptor (with pump)
Non-return valve (note direction arrow)
G 1 nipple
Diver pump
Fig. 2
Control module
Hose adaptor (with control module)
ELECTRICAL INSTALLATION
WARNINGS: The electrical installation must be carried out in accordance with the
current national electrical regulations and installed by a competent person.
In the interests of electrical safety a 30 mA residual current device
(R.C.D.) should be installed in the supply circuit. This may be part of a consumer unit or a separate unit. For submersible pump installations this device MUST be installed.
Before starting work on the electrical installation ensure the power
supply is isolated.
This appliance must be earthed. The motor and wiring must not be exposed to water. Do not allow the supply cord to contact hot surfaces, including the
motor shell, pump body or pipework. The cord should be safely routed and secured by cable clips.
Earthing
This appliance must be earthed via the supply cord.
Electrical Connection
The pressure control module provided with the submersible range is supplied loose for remote mounting. This must be permanently connected to the fixed wiring and is provided with a set of terminals located in the control module which allow the connection of a flexible supply cord. Means for disconnection must be incorporated in the fixed wiring according to the wiring rules.
- 3 -
Cont ...
A suitable method of connection would be via a double pole switched, fused connection
unit complying with BS 1363-4.
The connection unit should be mounted in an easily accessible position and should be
labelled if confusion is possible to allow easy identification of the pump isolating switch.
WARNINGS:
A residual current device having rated current not exceeding 30 mA
MUST be installed in the supply circuit.
Isolate power supply before putting your hands in the liquid. The pressure control module must be protected from the elements.
Wiring
The supply cord that connects the remotely mounted pressure control module to the mains supply is not provided. This cord must be sourced and provided by the installer. Cord selection should be chosen in accordance with the current involved/surrounding conditions and the fuse size required to protect the factory fitted pump supply cord (see fuse section).
The pump must also be connected to the pressure control module using the factory fitted pump supply cord which is provided with ends bared.
For information on cable fitting and connection, consult the wiring diagram and cable gland fitting instructions for the control module.
WARNING: The supply cord of this pump cannot be replaced. If the cord is damaged, the pump should be scrapped.
Wiring Diagrams
The supply cord and internal wiring within the terminal box are routed and secured to ensure compliance with the electrical standard EN 60335-1. It is essential that any disturbance of this internal wiring is avoided and the factory routing and securing of all internal wiring is always maintained.
1
3
2
V
U
6
5
4
N
L1
PRESSURE CONTROL MODULE
FUSE
L
SUPPLY 230 V
N
1 Phase 50 Hz
E
GREEN/YELLOW
BLUE BROWN
- 4 -
E
MOTOR
Fig. 3
Fuses
The following fuse size should be used.
Model Fuse Size (AMPS)
All Models 13
Intermediate Connecting Cord Replacement
The intermediate connecting cord (pump supply cord) which connects the pump to the control module cannot be replaced. If the cord is damaged the pump should be scrapped.
Cable Gland Fitting Instructions (Pressure Control Module)
See Pressure Control Module instruction book.
Intermediate Connecting Cord Extension (Boostamatic Diver 35 and 45)
The intermediate connecting cord which connects the pump to the control module is of a type suitable for outdoor use. Cord specification is as follows:
H07RN-F3 G 1.0 mm² - 10 amp rating.
If an extension cord is necessary a cord of the proper type and rating must be used.
In general for 230 volt pumps on distances up to 40 metres (inclusive of original cord length) the same specification cord as fitted to the pump can be used. For distances above 40 metres a larger cord size may be required due to voltage drop and advice must be obtained based upon installation details.
Any connectors or junction boxes must be specifically suited for outdoor use and installed in accordance with manufacturers instructions.
Any cable routed underground must be protected to local standards.
NOISE
The equivalent continuous A-weighted sound pressure level at a distance of 1 metre from the pumpset does not exceed 70 dB(A) for all models.
COMMISSIONING
WARNINGS:
The motor casing can become very hot under normal operating
conditions, care should be taken to ensure it cannot be touched during operation.
Do not run pump without guards and terminal box lids correctly fitted. Care should be taken to protect the pump from freezing. The pump chamber must be full of liquid at all times. Seal damage will
result if the pump runs dry.
Ensure electrical supply is compatible with the details that are stated on the pump rating plate. (The wrong voltage or frequency can be dangerous and may damage the pump.)
Priming
The pump should be fully submerged before starting, take care when submerging the pump to ensure all air is purged from the casing. This is done by slowly submerging the pump and gently agitating whilst doing so.
- 5 -
Cont ...
Starting The Pump
Turn on the electrical supply and the green L.E.D. ‘power on’ lights up. The yellow L.E.D. lights up when the pump is running (Fig. 4).
The pump will run until the system is completely charged and the maximum pressure reached. All taps or outlets on the system need to be operated starting with the highest outlet. This is to release air that may be trapped in the system. If the failure (red) L.E.D. lights up, this indicates that the pump is out of liquid or priming is incomplete. In the event of this happening, check liquid supply to pump. If all is in order keep the RESTART button depressed with a tap open and wait until the red failure light goes out. When the button is released and the tap closed, the pressure control module will stop the pump at its maximum pressure. Do not run against a closed valve for periods longer than 5
minutes.
Power on L.E.D. (Green)
Power on
Pump on
PRESSURE
Pump running L.E.D. (Yellow)
Failure L.E.D. (Red)
Failure
Restart
230V ~ 50-60 Hz, 6A max. 10bar max. Ambient 40°C max. Water Temp 65°C max.
CONTROL MODULE
STUART TURNER LTD
HENLEY-ON-THAMES
OXFORDSHIRE
RG9 2AD, ENGLAND
DISCONNECT SUPPLY BEFORE OPENING
Pressure Control Panel Fig. 4
Functioning
Once the commissioning operation is completed, the module will perform all pump control operations automatically. Note: After closing any outlet there will be a small delay time before the pump stops operating, which is normal. When particular operational breakdowns occur, such as liquid failure, the module recognises the breakdown and the red L.E.D. FAILURE light comes on. The pump stops operating to prevent damage caused by its working in the absence of liquid. After rectification of the failure, the system is restarted by depressing the restart button.
Carefully check pump and pipework for leaks whilst pump running and stationary before leaving the installation unattended.
For Further Technical Support
Note: When pumps are installed in another manufacturers original equipment, please contact the manufacturer for advice.
Phone the Stuart Turner Pump Assist team on 0844 98 000 97. Our staff are trained to help and advise you over the phone or arrange for a service engineer to call.
- 6 -
Cont ...
MAINTENANCE
WARNINGS:
Care should be taken to protect pump from frost and freezing.
Cleaners, disinfectants and descalents
On installations where chemical disinfectants or descalents are periodically used, the compatibility of the chemical solution regarding the pump must be considered.
Acid based descalents and aggressive cleaning agents must not come into contact with the pump. The pump must be removed from the system prior to the use of these products. The system should be flushed to remove all chemicals before the pump is re-connected.
If in any doubt as to the suitability of the chemical solutions refer to Stuart Turner Ltd.
STORAGE
If this product is not installed immediately on receipt, ensure that it is stored in a dry, frost
and vibration free location in its original packaging.
TROUBLE SHOOTING GUIDE
Symptoms Probable Cause Recommended Action
Pump will not start. Control module failure light illuminated.
Liquid supply low. Check liquid level in the supply tank and all stopcocks are
open. Reset the control module by depressing the restart button.
Inlet filter blocked (if fitted).
Electrical supply. Check all electrical switches are on.
Static inlet or outlet head is greater than permitted.
Remove and clean filter gauze. Reset control unit.
Is the correct fuse fitted? Is the circuit breaker set?
Re-position control module. (See siting of the pump and limits of application section).
- 7 -
Stuart Turner Ltd, Henley-on-Thames, Oxfordshire RG9 2AD ENGLAND
Tel: +44 (0) 1491 572655, Fax: +44 (0) 1491 573704
email: pumps@stuart-turner.co.uk web: www.stuart-turner.co.uk
V.A.T. REG. No. 199 0987 92. Registered in England No. 88368. Registered Offi ce: Market Place, Henley-on-Thames
Issue No. 0812/1-01 Pt. No. 19718
Loading...
+ 16 hidden pages