Striem LB-15, LB-25, LB-35, LB-50, LB-125 Installation, Operation And Maintenance Manual

...
Striem
3100 Brinkerhoff
Kansas City, KS 66115
Tel: 913-222-1500 Fax: 913-291-0457
www.
striemco.com
LB-275
250 gallons
LB-15
15 gallons
LB-25
21 gallons
LB-35
38 gallons
LB-50
57 gallons
Sheet Descriptions
Sheet #1 - Series overview and Warranty information Sheet #2 - General installation guidelines and Operation/Maintenance guidelines Sheet #3 - Below Grade installation guidelines (LB-35, LB-50, LB-125, LB-275) Sheet #4 - Below and Above Grade installation guidelines (LB-15, LB-25) Sheet #5 - TeleGlide Riser installation guidelines (LB-35, LB-50, LB-125, LB-275) Sheet #6 - TeleGlide Riser installation guidelines (LB-15, LB-25)
Leak/Seal Testing
DO NOT AIR TEST UNIT OR TELEGLIDE RISER SYSTEM! Doing so may result in property damage, personal injury or death.
Base Unit:
To perform a leak/seal test on the base unit, cap/plug all plumbing connections, remove the cover, and fill the unit with water just above the
highest connection. Inspect unit and connections for leaks. Check water level at specific time intervals per local code.
TeleGlide Riser System:
If required by local code, the riser system may be leak/seal tested similar to the base unit.
CAUTION:
the riser(s) must be supported before filling with water to keep from tipping over. Once the riser system is in place and properly supported, cap/plug all plumbing connections on the main unit, remove the cover from the top of the riser assembly and fill the unit and riser system with water to finished grade level. Carefully, as the riser(s) will be very heavy from the weight of the water, inspect all gasket(s) and clamps (if applicable) for any leaks. Check the water level at specific time intervals per local code.
Lifetime Warranty
Effective March 2, 2015 Striem represents and warrants that polyethylene products will be free from any and all defects in material and workmanship, including corrosion, during the lifetime of the plumbing system in which the products were originally installed and will, at its option, agree to repair, replace, or supply credit to the original purchaser.
This warranty does not cover damage caused by the products’ normal usage, or wear and tear, nor does it cover damage from naturally occurring phenomenon, including, but not limited to, UV, freeze-related damage, or natural disasters. This warranty does not cover the purchaser’s cost of routine maintenance including replacement of parts required in routine maintenance.
This warranty does not cover fabricated steel products, or any monitoring equipment. This warranty shall be effective if, and only if, the products: * Were installed in accordance with Striem’s notes, specifications and instructions, for installation, operation, and maintenance; * Were installed in conformance with all applicable building and plumbing codes, and passed all applicable testing methods immediately following installation; * Have not been subjected to misuse or abuse, whether negligent or intentional; * Were never modified, repaired, or altered by any individual(s) not authorized by Striem.
This warranty is the purchaser’s sole and exclusive remedy, and acceptance of this exclusive remedy is a condition of the contract for the purchase of these products. In no event shall Striem be liable for any incidental, special, consequential or punitive damages, or for any costs, attorney fees, expenses, losses or delays claimed to be as a consequence of any damage to, failure of, or defect in any products including, but not limited to, any claims for loss of profits, transportation, removal and installation charges. This warranty is exclusive and in lieu of all other warranties or conditions, written or oral, expressed or implied.
LAB BASIN NEUTRALIZATION TANKS
(Models LB-15, LB-25, LB-35, LB-50, LB-125, and LB-275)
LB-125
110 gallons
LAB BASIN SERIES INSTALLATION,
OPERATION AND MAINTENANCE GUIDE
ECO:
10/22/18MJREV:
DATE:
DWG BY:
DESCRIPTION:
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
STRIEM, LLC.
ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF
STRIEM, LLC.
IS
PROHIBITED.
NOTES:
Striem Lab Basins are not to be installed in any other manner except as shown. Consult local codes for separate trapping requirements, cleanout locations and additional installation instructions. Vent required on outlet pipe only if outlet diptube is present.
SHEET NUMBER:
1 of 6
Striem
3100 Brinkerhoff
Kansas City, KS 66115
Tel: 913-222-1500 Fax: 913-291-0457
www.
striemco.com
FLOW
Set unit on level solid surface as close as possible to fixtures being served. If unit is to be installed below grade refer to below grade installation instructions. (sheet #3)
Isometric View
Connect inlet and outlet drainage lines to
unit. Mechanically couple pipes to
unit.
Do not solvent weld
.
Top View
FLOW
FLOW
LB-275 SHOWN
Locking collar
Cover
Closed top
inlet diffuser
to provide sewer
gas trap
Adapter
Vent
GENERAL NEUTRALIZATION TANK INSTALLATION INSTRUCTIONS
(LB-275 SHOWN)
OPERATION:
Striem Lab Basins are designed to neutralize or dilute (based on specific requirements) chemical wastewater and bring it to a more neutral state, rendering it acceptable for local wastewater treatment facilities. Diffusion Flow design and extended flow path improve neutralization over traditional cylindrical tanks. The most common neutralization situation occurs when acidic waste is filtered through a neutralizing media, most often a specific size and composition of limetsone.
Wastewater flows through the inlet connection and is forced to the bottom of the unit via diffuser. For neutralization tanks, the wastewater is then filtered through a neutralizing agent (Limestone with a Calcium Carbonate level of 90% or better is most common) and then exits the chemical waste tank though the outlet. For dilution tanks, intermittent chemical waste moves through a majority water solution from previous batches and then exits the chemical waste tank through the outlet.
MAINTENANCE
Remove the cover(s).
1. For the best maintenance contact a professional sewer and drain contractor. Proper mainentance is
2. essential to keep the Neutralization Tank in proper working order. Debris entering the tank from a sink or lab station may plug the invert or foul the neutralizing agent. If limestone is to be used as a neutralizing agent, the limestone will be depleted as it works to neutralize the incoming effluent. Once the limestone is depleted, the tank should be cleared of sludge, sediment, and debris before adding the new neutralizing agent.
A qualified professional should be responsible for the analysis of effluent, inspection, maintenance, and replacement of neutralizing agent.
Observe a regular schedule of maintenance. Start by inspecting the new system every month to three
3. months until a proper schedule can be established. The frequency will depend on the tank capacity and the content of the chemical waste passing through the system. Debris and sludge must be cleaned out periodically to allow the free flow of water through the tank. If it is
4. determined that the Neutralization Tank or System will encounter large amounts of debris or sediment, specify a Striem Solids Interceptor. As the limestone is depleted, the tank should be cleared of sludge, sediment, and debris before new
5. neutralizing agent is added. When limestone begins to foul, it often dissipates into a muddy substance and the level of the stone will begin to recede. When the stone is mostly fouled, the tank should be flushed with fresh water, the fouled debris removed from the tank, the tank cleaned, and new limestone added.
TROUBLESHOOTING TIPS:
Slow drainage is course for immediate inspection! Call a professional contractor for assistance. Call Striem for details on tank specifications.
LAB BASIN SERIES INSTALLATION,
OPERATION AND MAINTENANCE GUIDE
ECO:
10/22/18MJREV:
DATE:
DWG BY:
DESCRIPTION:
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
STRIEM, LLC.
ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF
STRIEM, LLC.
IS
PROHIBITED.
NOTES:
Striem Lab Basins are not to be installed in any other manner except as shown. Consult local codes for separate trapping requirements, cleanout locations and additional installation instructions Vent required on outlet pipe only if outlet diptube is present.
SHEET NUMBER:
2 of 6