Strebel S-HR 15, S-HR 24, S-HR 24T, S-HR 35, S-HR 35T Installation Instructions Manual

...
Page 1
INSTALLATION INSTRUCTIONS
8G.51.21.01/11.99 changes reserved
Page 2
Page 3
Installation instructions S-HR series page 3
S-HR 15 S-HR 24/24T S-HR 35/35T S-HR 51/51T S-HR 60
Contents page
1 Description of the unit ................................................................................................................... 4
3 Mounting of the unit ....................................................................................................................... 4
3.1 Dimensions ......................................................................................................................... 5
4 Connecting the unit ....................................................................................................................... 6
4.1 Central heating system .......................................................................................................7
4.2 Expansion tank.................................................................................................................... 8
4.3 Underfloor heating systems............................................................................................... 10
4.4 Gas pipe ............................................................................................................................ 10
4.5 Hot water supply (S-HR-T) ................................................................................................ 10
4.6 Condensation discharge pipe ............................................................................................ 10
4.7 Flue gas exhaust system and air supply system ............................................................... 11
5 External calorifiers ....................................................................................................................... 12
6 Electrical connection ................................................................................................................... 12
7 Control of the unit ........................................................................................................................ 14
7.1 Explanation of the function keys........................................................................................ 14
8 Filling and venting of unit and installation .................................................................................... 15
8.1 Central heating system ..................................................................................................... 15
8.2 Hot water supply ............................................................................................................... 15
9 Putting the unit into operation...................................................................................................... 16
9.1 Central Heating system ..................................................................................................... 16
9.2 Hot water supply ............................................................................................................... 16
9.3 Adjustments ...................................................................................................................... 16
10 Switching off the unit ................................................................................................................... 20
11 Commissioning and maintenance ............................................................................................... 20
11.1 Checking for contamination ............................................................................................... 20
11.2 Checking of the zero pressure control ............................................................................... 20
11.3 Checking the CO2 .............................................................................................................. 21
11.4 Maintenance...................................................................................................................... 22
11.5 Further checks .................................................................................................................. 22
11.6 The frequency of maintenance .......................................................................................... 22
12 Technical specifications .............................................................................................................. 23
13 Diagram showing various parts of the unit .................................................................................. 24
14 Example diagrams for connecting the unit .................................................................................. 26
14.1 Radiator installation without thermostat valves ................................................................. 26
14.2 radiator installation with thermostat valves only ................................................................ 27
14.3 radiator installation with an under floor heating zone ........................................................ 28
14.4 radiator installation and an independent underfloor heating zone ..................................... 29
14.5 two independent radiator zones ........................................................................................ 30
15 Error indication ............................................................................................................................ 31
Page 4
Installation instructions S-HR series page 4
1 Description of the unit
The STREBEL S-HR Boiler is a room sealed, condensating and modulating central heating unit, with or without an integrated hot water facility. The built-in fan sucks the combustion air from outside and provides full premixing of the gas and air. The gas mixture is guided through the ceramic burner which is fitted above the heat exchanger. As a result of the small flame height a compact construction is possible. The combustion gasses are exhausted after passing through the stainless steel heat exchanger. The formed condensation water is discharged through the waste trap.
The unit has been tested according to valid CE* standards and has a CE* certificate. The operating efficiency of the unit is higher than 98% (on top value). As a result of its compact construction the radiation, convection and stand by losses are very low. The emission of damaging substances is far below the standard set for equipment with the gas quality-control label for clean combustion.
The unit is provided with an automatic venting program. In case of a recently topped up or filled up installation this program takes care of the removal of any present air. In this case the control will check the water pressure and if it is too low, will report this on the display.
The unit anticipates the heat requirement of the central heating installation or the hot water supply. As a result the unit will adjust its capacity to the installation and will switch on less often, which means that the unit will operate longer and at a low level. It is possible that the unit will only have to switch on once an hour. In this case the aim is to obtain maximum comfort and efficiency.
In order to be able to anticipate installation noises the unit has a so-called gradient control. After the unit goes into operation this control provides a uniform increase of power, instead of immediately burning at full power. When the installation does require full power the control will adjust as required. By this means a uniform increase of the water temperature is effected. If an outside sensor is connected, the control can operate weather-dependent. This means that the control measures the outside temperature and the flow water temperature. On the basis of this data the control calculates the optimal flow water temperature in the installation.
The S-HR-T combination unit provides a hot water supply by means of a high output calorifier fitted on the right hand side of the unit. An adjustable thermostatic mixing valve is fitted which provides a constant hot water temperature (60
°
C factory setting).
2 Scope of the delivery
The unit is supplied ready for use. The supply kit is composed as follows:
- Unit with casing;
- Automatic vent (inside the unit);
- Safety valve (inside the unit);
- Inlet combination and safety valve (only with S-HR­T units);
- Suspension bracket
- Filling and draining valve with T-piece;
- Fixing material consisting of plugs and screws;
- Template on the package wrapper;
- Installation instructions
- Operating manual;
- Installation and user card.
3 Mounting of the unit
The unit can be mounted practically to every wall with the mounting bracket and the included fixingequipment. The wall must be flat and of sufficient strength in order to be able to carry the unit weight. Above the unit there must be at least 250 mm working space in order to be able to fit a twin supply and exhaust system or 500mm when fitting a horizontal coaxial flue system. On the left side of the unit at least 50 mm and on the right side 10 mm must be reserved in connection with fitting or removing of the casing. The location of the unit can be determined by using the template on the inside of the wrapper.
Page 5
Installation instructions S-HR series page 5
3.1 Dimensions
Dimensions (in mm) figure 1
wall
C
E
F
A
U
T
S
wall
B
M
N
P
Q
R
B
wall
D
H
J
K
1050
G
Dimensions table 1
tinufoepyt
RH-S
51
RH-S
42
RH-S
T42
RH-S
53
RH-S
T53
RH-S
15
RH-S
T15
RH-S
06
A thgieh
mm086086086086086086086086
B htdiw
mm0050050480050480660001066
C htped
mm073073073073073073073073
D tsuahxesageulf/edistfel
mm533533533533533594594594
E
tsuahxesageulf/ertnecotertnec
ylppusdna
mm021021021021021021021021
F tsuahxesageulf/kcab
mm072072072072072072072072
G epipsag/edistfel
mm5656565656565656
H epipwolf/edistfel
mm581581581581581581581581
J epipnruter/edistfel
mm582582582582582544544544
K epipnoitasnednoc/edistfel
mm073073073073073035035035
L epipknatnoisnapxe/edistfel
mm034034095
M epipretawdloc/edistfel
mm527527588
N epipretawtoh/edistfel
mm597597559
P *gfothgnelepip
mm8181818181818181
Q *kdnacfothgnelepip
mm0404040404040404
R *wdnae;r;afothgnelepip
mm0606060606060606
S *cepipfoertnec/kcab
mm5252525252525252
T *gepipfoertnec/kcab
mm0404040404040404
U *w;k;e;r;aepipfoertnec/kcab
mm0505050505050505
Page 6
Installation instructions S-HR series page 6
4 Connecting the unit
The unit has the following connection pipes;
- The central heating pipes, hot and cold water pipes can be connected to the installation by means of compression fittings;
- The gas pipe of the unit is provided with a female thread into which the tail piece of the gas valve can be screwed;
- The condensation discharge pipe consist of an oval 24 mm plastic pipe. The discharge pipe can be con­nected to this by means of an open connection. If the open connection is fitted in a different location, then the pipe can be lengthened by means of a 32 mm PVC sleeve;
- The flue gas exhaust system and air supply system consist of 2 x 80 mm connections.
connection diameters table 2
unit pipes bottom figure 2
G A R C E K W
ceiling
wall
minimum 250 mm or 500 mm
tinufoepyt
RH-S
51
RH-S
42
RH-S
T42
RH-S
53
RH-S
T53
RH-S
15
RH-S
T15
RH-S
06
ylppusrianoitsubmoc
mm0808080808080808
tsuahxesageulf
mm0808080808080808
G-epipsag
edisni"½edisni"½edisni"½edisni"½edisni"½edisni"¾edisni"¾edisni"¾
A-epipwolfgnitaehlartnec
mm8282828282535353
R-epipnrutergnitaehlartnec
mm8282828282535353
C-epipegrahcsidnoitasnednoc
mm4242424242424242
E-epiplessevnoisnapxe
mm222222
K-epipretawdloc
mm515151
W-epipretawtoh
mm515151
Page 7
Installation instructions S-HR series page 7
4.1 Central heating system
The unit pipes can be connected to the installation by means of compression fittings. Reducers should be used for connecting to thick-walled pipe (welded or threaded). When removing the plastic sealing caps from the pipes, contaminated testing water can be released.
The unit has a self-adjusting and self-protecting control system for the load and the pump capacity. By this means the temperature difference between the supply and return water is checked. The circulation pump will be able to supply the given water displacement with an installation resistance of up to 20 kPa, for this see table 3.
If an unacceptable temperature is detected, then the control will repeatedly try to achieve water flow, and if this does not work then the unit will switch off.
The S-HR 60 unit has a circulation pump which has a residual suction head for the installation of 12 kPa. This means that the unit can function normally in installations which have an installation resistance of up to 12 kPa and in cascade installations. If the installation resistance is higher than 12 kPa, the unit will automatically reduce in power.
If the capacity of the unit pump is insufficient, an extra external pump can be installed in series with the unit. The electrical side of this external circulation pump can be connected in the Control Tower, by which means this pump switches at the same times as the unit pump. The maximum absorbed current consumption of the external circulation pump may be 230 W (1 Amp). Use with a low velocity header can also be selected. In this case a larger secondary sided water output has to be taken into account, in order to affect the height of the water temperature.
If the installation resistance is higher than the stated value the pump will rotate at maximum pump capacity and the load will be adjusted until an acceptable temperature difference between supply and return wa­ter has been obtained. If, after this, the temperature difference remains too much then the unit will switch itself off and wait until an acceptable temperature has arisen.
available water flow at full load table 3
external installation pump in series figure 3
tinufoepyt etarwolfretaw
D C°02T
elbissimrep
ecnatsisernoitallatsni
nim/lh/laPkrabm
51RH-S
9.900653053
T42/42RH-S
1,5108952052
T53/53RH-S
1,22423102002
T15/15RH-S
1,23929102002
06RH-S
9,73172221021
pump index lines graph 1
0 0,5 1 1,5 2 2,5
Q(m³/h)
7
6
5
4
3
2
1
0
H(m)
min (25%)
max (100%)
pump index line ARS 25-75
S-HR 15/24/35
S-HR 24T/35T
S-HR 51T
S-HR 51/60
pump index line ARS 25-70
Page 8
Installation instructions S-HR series page 8
As standard the unit is provided with a water filter in the return pipe of the unit. With this, possible contamination of the central heating water is prevented from ending up in the unit. The unit is also provided with an internal safety valve set at 3 bar. This is connected to the discharge construction to the waste together with the condensation discharge.
If all, or a large part of the radiators are provided with thermostatic radiator valves it is advisable to use a pressure difference control (by pass) in order to prevent flow problems in the installation.
The unit is designed to be used on sealed system only.
Additives in the installation water are only permitted in consultation with STREBEL LTD.
When using more than one unit in an installation please refer to the cascade installation instructions.
4.2 Expansion tank
All STREBEL S-HR-T units are provided with an expansion tank on top of the calorifier. This expansion tank is connected to the three-way valve and the circulation pump. By this means the expansion water, when functioning for the hot water supply, is prevented from being shut off from the expansion tank when the radiator thermostat valves are fully closed. A second expansion tank in the installation is not a problem.
The STREBEL S-HR units are not equipped with an expansion tank pipe. If a S-HR unit is combined with an Comfort calorifier, the expansion tank connection is included in the internal piping of the Comfort calorifier, to which the expansion tank can be connected. If a different calorifier is used then one has to take into account that the expansion tank should be connected between the three-way valve and the unit circulation pump.
In connection with correct functioning of the unit it is necessary for the expansion tank to be connected to the expansion tank pipe of the unit.
The expansion tank which is used should be geared to the water content of the installation. The pre-pressure depends on the installation height above the mounted expansion tank.
external installation pump with low velocity header figure 4
choice of expansion tank table 4
evobathgiehnoitallatsni
lessevnoisnapxeeht
ehtfoerusserp-erp lessevnoisnapxe
m5rab5,0
m01rab0,1
m51rab5,1
Page 9
Installation instructions S-HR series page 9
The STREBEL S-HR24 and S-HR35 units can be provided with an expansion tank module. By this means the external expansion tank is cancelled. This expansion tank module is placed behind the S-HR unit, by which means the expansion tank is not noticeable. If the S-HR unit is provided with a STREBEL Comfort calorifier the overall depth will be equal. The content of the two expansion tanks is 20 litres. The pre-pressure is 1 bar.
The expansion tank module can be supplied with the necessary pipes to connect with the S-HR unit. The connecting pipes for the installation correspond with those of the unit and have the same centre-to-centre distance to the wall. When checking the expansion tanks these are accessible via the left, right and upper sides. From these sides the tanks are also removable and the unit does not have to be dismantled.
The space which is required for mounting the expansion tank module corresponds with the required space for mounting a S-HR unit. The included template and mounting strip for the S-HR unit can be used for the expansion tank module. The S-HR unit is fitted on to this after the expansion tank module has been mounted. The necessary mounting strip for the unit is present on the module.
expansion tank module figure 5
side view of the module with S-HR unit figure 7 (dimensions in mm)
515
wall
145
370
front view of the expansion tank module figure 6 (dimensions in mm)
480
660105
Article numbers:
- the expansion tank module without pipe connections AEMO209U
- pipe connections for expansion tank module ALE0004U
Page 10
Installation instructions S-HR series page 10
4.3 Underfloor heating systems
When connecting or using an underfloor heating system fitted with plastic pipes one has to take into account that the plastic pipes used meet the DIN 4726/4729 standard. It is stated in this standard that the pipes may not have a higher oxygen transmittance than 0.1 g/m³.d at 40°C. If the system does not meet this DIN standard, then the underfloor heating section will have to be separated from the central heating unit by means of a plate heat exchanger.
In case of non-compliance with the regulations concerning plastic underfloor heating pipes, no claims can be made against the guarantee conditions.
4.4 Gas pipe
The unit pipe is equipped with a female thread, into which the tail piece of the gas valve can be screwed.
The Gas Safety (Installation and Use) Regulations 1994: It is the law that all gas appliances are installed by CORGI registered contractors in accordance with the above regulations. Failure to install appliances correctly could lead to prosecution. It is in your own interest, and that of safety, to ensure that the law is complied with.
For good operation of the unit it is necessary that the pre-pressure of the unit is higher than 20 mbar.
Make sure that the gas pipe work does not contain dirt, particularly with new pipes.
4.5 Hot water supply (S-HR-T)
The unit pipes can be connected to the installation by means of compression fittings. The unit is provided with an inlet combination and safety valve set at 8 bar. Together with the condensation discharge and the discharge of the central heating safety valve (3 bar) this is connected to one waste connection pipe.
A flow regulation valve is fitted in the cold water pipe. The flow regulation valve provides that a quantity of water is supplied which has a guaranteed outlet temperature of 60°C (assuming a cold water temperature of 10°C). The quantity of water is virtually unaffected by the water pressure. With a water pressure lower than 1.5 bar it is advisable to remove the inside mechanism of the flow regulation valve. Connecting of the drinking water installation should be done according to the water BYE-laws.
4.6 Condensation discharge pipe
The collective condensation discharge pipe should be connected to the waste by means of an open connection. By this means the possibility of sewer gases ending up in the unit is prevented. The waste connection should have a minimum diameter of 25 mm.
The following components are connected to the collective condensation discharge pipe:
- Condensation discharge;
- Safety valves;
- Inlet combination (S-HR-T)
Discharging of the condensation water to the precipitation discharge is not permitted in view of the danger of it freezing.
Before putting the unit into operation fill the trap with 300 ml of water.
inlet combination and safety valve figure 8
Page 11
Installation instructions S-HR series page 11
4.7 Flue gas exhaust system and air supply system
The unit connection diameter is Ø 80 mm. to which the flue gas discharge and air supply system can be fitted with or without bends. The maximum usable pipe length is stated in table 5.
It is advisable to use stainless steel discharge equipment for the flue gas discharge. By using the STREBEL icicle-free trough the roof kit, ice-forming around the flue terminal is prevented. For the air supply plastic can be chosen. If a plastic discharge system is installed the unit has to be equipped with a flue gas thermostat. This flue gas thermostat is available from STREBEL LTD.
With the flue gas discharge system and air supply system the following is meant:
- the flue gas discharge pipe;
- the air supply pipe;
- through the roof kit or wall terminal.
The flue gas exhaust and the air supply installation must be installed in accordance with British Standards.
The exhaust system should always be installed sloping towards (30 mm/m) the unit, in order for condensation water not to gather in the exhaust system. With condensation water flowing back to the apparatus the chance of ice forming on the trough the roof kit is minimal. In case of horizontal outlets the supply system has to be installed sloping outside in order to prevent rain coming in.
It is superfluous to install an extra condensation collecting unit.
In operation, the unit produces a white condensation plume. This condensation plume is harmless but can be experienced as disturbing especially in the case of outlets in the wall. For this reason it is advisable to exit at roof level.
The apparatus is not suitable as an open unit. This means that the combustion air always has to be brought from outside.
Where the unit is installed in a compartment, ventilation is required as per BS 5440.
For further information regarding the supply range of the exhaust and supply system please contact STREBEL LTD.
supply and exhaust system figure 9
length supply and exhaust system table 5
ehthtobrofsisertemnihtgnelepipdetatsmumixamehT ecnatsidehtsidnametsystsuahxeehtsallewsaylppus
.lanimretllawrofoorehtdnatinuehtneewteb
tinufoepytepipmumixam
htiwsertemnihtgnel
mm08foretemaida
epipmumixam
htiwsertemnihtgnel
mm09foretemaida
51RH-S
0304
T42/42RH-S
5204
T53/53RH-S
8163
T15/15RH-S
0102
06RH-S
631
eht,metsystsuahxeroylppusehtnisdnebgnisunehW
ecnatsiserehthtiwsdnopserrocsiht,wolebdenoitnemhtgnel
.htgnelepipehtotdeddaebotsah,dnebehtfo
dnamm08øtcudtsuahxesertem01htiw42RH-S:elpmaxE
5,21=ertem52,1x2+sertem01:snaemsihT.sdneb°09x2
.ertem
°09dneb
52,15,1
°54dneb
152,1
Page 12
Installation instructions S-HR series page 12
5 External calorifiers
Various external calorifiers can be connected to a S-HR unit, depending on the comfort requirements. The wiring of the calorifier thermostat can be connected to the connection block in the Control Tower by means of the relevant plug. Calorifiers which are used together with the S-HR boiler should be of the quick recovery type.
S-HR51 and S-HR60 Consult STREBEL when using calorifiers with lower absorption than 20kW or primary pipe and/or coil size less than 3/4 inch.
S-HR with calorifier figure 14
6 Electrical connection
The unit complies with the CE machine guidelines 89/ 392/EEC.
The installation must be in accordance with:
- Current I.E.E. Regulations;
- Local Regulations;
- A visible electrical isolation switch must be fitted adjacent to the boiler complete with an earth.
The apparatus complies with the following regulations:
- low-voltage guideline 73/23/EEC
- EMC guideline 89/336/EEC
Furthermore the following general regulations are valid:
- no modifications may be made to the wiring of the unit;
- all connections must be made to the connection block.
The Brain room thermostat and controls must be connected to their allocated connections. All other types or makes of room thermostats or controls which are used must have a potential-free contact
When using an on/off thermostat or control, it is possible that an anticipating resistance must be installed in order to prevent too high temperature fluctuations. As a stand­ard rule this means mercury thermostats. This resis­tance wire is present in the Control Tower and must be connected to clamps 23 and 27. The anticipating resis­tance in the room thermostat has to be set at 0.11 A.
For more detailed questions regarding the components which are not supplied by STREBEL, the supplier concerned should be contacted.
The connections of the Brain Interface and the wiring of the three-way valve with the calorifier sensor are only applicable if they are installed in the Control Tower.
230 Volts for
external pump
mains power
supply
230 Volts for
external control
230 Volts
internal or external
three-way valve motor
and calorifier sensor
Brain
clock thermostat
On/off thermostat or
control
Connection block in the Control Tower
STREBEL outside
sensor
External safety
contact
24 Volts
maximum 100 mA
Page 13
Installation instructions S-HR series page 13
electrical connecting diagram figure 11
Page 14
Installation instructions S-HR series page 14
7 Control of the unit
The unit is provided with a self-adjusting control called the Control Tower. This control takes over a large part of the manual adjustments which means putting the unit into operation has been extensively simplified. After plugging the plug into the wall socket the unit will not undertake any operating action and no operating lamps will be lit.
On the display the relevant status will be shown. Rea­ding out of the status can be done in two ways.
The first way is a simple read out called the Good status. The unit will only show the indication. During this read out the unit can be in normal operation without this showing in any other way. If it is necessary to show a report it will be shown on the display.
The second way is the technical way which shows a more extensive read-out with, among others, the position in which the unit is active with the flow water temperature and the water pressure of the central heating system. The second level is reached from the indication after pressing the STEP key for 5 seconds. Returning to the indication is done the same way.
Only when activating the operating program pump circulating after filling up the installation, will the automatic venting program start as standard after
pressing the PC program key. This automatic venting program takes 15 minutes and stops
automatically. After this the unit will function for the activated part.
In case of a heat requirement, which arises for central heating or hot water, a certain flow water temperature will be calculated. This calculated water temperature is called the T-set value. This value becomes active in case of a demanding room thermostat after which the unit power will be adjusted. With a recently started unit a build-up delay of the T-set valve is active. The main purpose of this is to prevent the unit going into operation at full power due to which disturbing noises and unnecessary temperature peaks can arise. In the case of heat requirement from the hot water supply the T-set valve on the central heating return water temperature is adjusted. Depending on the amount of domestic water which is withdrawn from the calorifier, the central heating return water temperature, which adjusts the load of the unit, will vary.
Each time the mains power supply to the boiler is broken, the automatic venting pro­gram will re-start once there is power to the boiler.
7.1 Explanation of the function keys
Key functions from the and the extensive indication are:
-
Central Heating program key, see chapter
10.1;
- Hot Water program key, see chapter 10.2;
- PC program key, adjusts the pump to continuous water circulation in the central heating system, or
according to the pump overrun times on the relevant programs;
- Mode key, after briefly pressing, a selection of the data chapters can be retrieved. After pressing for 5 seconds it is possible to enter the code as described in chapter 10.3;
- Step key, after briefly pressing, the water pressure can be retrieved and pages per chapter can be retrieved. After pressing for 5 seconds it switches from indication to technical indication and the other way round;
- Reset key, after briefly pressing, for: unlocking errors; ending the access code; ending the automatic venting program, only when the access code is entered and the reset key is pressed briefly. After pressing for 5 seconds an operating stop is made, for example, for activating the automatic venting program.
Other key functions from the other indications are:
- Central Heating key then has the + function;
- Hot Water key then has the - function;
- PC key then has the store function, which means that by means of this key a modified setting is
confirmed;
- Step key for scrolling in a data chapter.
Page 15
Installation instructions S-HR series page 15
8 Filling and venting of unit and
installation
Filling of the installation can be carried out according to the usual method. In order to read out the central heating water pressure the unit plug should be plugged into the socket. The circulation pump will not begin to operate as long as the operating lamps are off. The control display will show a indication, which means that the control is signalling insufficient water pressure. If the installation is filled and the water pressure rises then the water pressure will automatically be shown with an alternating text. If the water pressure rises to above 1.5 bar then after a short stop text the indication will appear, which means the water pressure is sufficient and the unit is ready for operation. In order to be able to read out a constant water pressure the Step key should be pressed in and in order to obtain a constant readout the Step key should be pressed briefly again.
If the water pressure in the unit becomes too high (>3.5 bar) a text appears, by which means the burner is switched off. After draining the water from the installation, by which means the water pressure arrives below 3 bar, the text disappears and the burner is activated.
In order to go from a read-out to a technical
readout the Step key should be pressed for 5 seconds. This read-out can be selected if the user requires a technical read out. In order to return to the
read-out the Step key must be pressed again for 5 seconds.
8.1 Central heating system
For filling the central heating installation you use the filling and draining valve.
Filling is done as follows:
- Plug the unit plug into the wall socket and leave the
operating lamps off;
- Connect the filling hose to the cold water tap and let
it fill with water;
- Connect the filled filling hose to the filling and
draining valve and open this valve;
- Open the cold water tap and fill the installation
slowly;
- The unit has an automatic vent which removes the
air which is present;
- Start venting the radiators and pipes at the lowest
point;
- Bring the installation to pressure (1.5 to 2 bar) after
all radiators and pipes have been vented;
- Close the cold water tap and the filling and draining
valve;
- Activate the automatic venting program by pressing the pump key which means the pump lamp will be lit. Allow the control to finish its venting program. The
pump will circulate a number of times around the boiler as well as the central heating installation. Also, if a three-way valve, if present, this will be adjusted to the boiler and central heating installation a number of times. The pump will be stopped regularly in order to allow possible present air to escape.
- Check the water pressure and if required top up. The working pressure in the installation should be bet­ween 1.5 and 2 bar in cold state.
- After finishing the automatic venting program the key
can be switched off again.
It can take a while before all air has dis­appeared from a filled installation. Especially in the first week noises can be heard which indicate the presence of air. The automatic air vent in the unit will make this air disappear, by which means the water pressure can reduce during this period and therefore topping up with water will have to be done.
8.2 Hot water supply
Apply the water pipe pressure to the calorifier (open main valve and/or stop valve of the inlet combination valve).
Vent the calorifier and the hot water installation by opening a hot water tap. Leave the tap open for as long as required until all air has disappeared from the calorifier and the pipes and only water is flowing from the tap.
Page 16
Installation instructions S-HR series page 16
9 Putting the unit into operation
Before putting the unit into operation make sure, that the unit and the installation are well vented. Vent the gas pipe and open the gas valve for the unit. The unit does not require adjustment of burner pressure and air quantity because it is self-adjusting and is factory-set at the correct value.
9.1 Central Heating system
Provided there is a heat requirement from the thermostat or control, the central heating program will
be put into operation by means of the
key (central
heating program). The circulation pump will start circulating and the unit will start the burner.
9.2 Hot water supply
Provided there is a heat requirement from the boiler the hot water program will be put into operation by means of
the key (hot water program).
9.3 Adjustments
In the Control Tower a number of adjustments can be made. These adjustments can be fed in easily by means of the keys on the unit. However, a distinction is made between adjustments which are done by the user and adjustments done by the installer. At users level adjustments can only be made from the technical read-out in other words from the display read­out with the operating function and the water temperature. Adjustments can not be made from the
indication.
The next two chapters are accessible after pressing the Mode key:
Chapter 1 The normal operating functions such as the simple
read out or the technical with the
read out.
Chapter 2 The chapter in which adjustments can be made.
Page 17
Installation instructions S-HR series page 17
User adjustments To switch from the
level to the opera-ting status level with the read out of the operating functions , the water tempe-rature and the water pressure , the following acts must be carried out. From the display read-out, press the Step key for 5 seconds after which the operating status and the water temperature will be shown for 8 seconds and the water pressure for 2 seconds. If, after this, the Mode key is pressed briefly the adjustments chapter is displayed by means of the text . By pressing the Step key briefly the adjustment facilities are shown. Adjustment of the fixed value can be done by means of the + or the - key. Confirmation of the new setting is done with the Store key.
* Brain thermostat Most of the adjustments which are stated in tables 6 and 7 are unnecessary when in combination with the Brain and will be taken care of by the Brain itself and do not have to be adjusted. Most of the data in table 8 can be requested by the Brain. For further information with regard to the Brain thermostat we refer to the Brain thermostat installation manual.
In order to gain access to the adjustments at installers level the entrance code has to be fed in first. For this the following operations have to be carried out.
Press the Mode key for 5 seconds. The text
is shown, after which a random number
appears on the display. By means of the + or the
- key the code can be fed in. After pressing the Store key the code is confirmed. With this entrance to the installers level is given.
The next chapters are shown after pressing the Mode key:
Chapter 3 The chapter where information can be retrieved.
Chapter 4 The chapter in which adjustments can be made for service purposes.
Chapter 5 The chapter in which error data can be retrieved.
user adjustment possibilities table 6
stnemtsujdaretemarapresU
petS noitpircsed yrotcaf egnar
1
gnitaehlartnec.pmetretawwolfmumixamC°58C°09-02
2
metsysgnitaehlartnecfoepyt104-1
10
srotcevnoc;gnitaehria;srotaidar
retawwolfxamTC°58.motua
enilgnitaehrotcafK3.2.motua
tneidargnim/C°5.motua
laitnereffidraegC°6.motua
20
lanoitiddasagnitaehroolfrednurosaeraecafrusegralhtiwsrotaidar
gnitaeh
retawwolfxamTC°07.motua
enilgnitaehrotcafK8.1.motua
tneidargnim/C°5.motua
laitnereffidraegC°5.motua
30
gnitaehlanoitiddasasrotaidarhtiwgnitaehroolfrednu
retawwolfxamTC°06.motua
enilgnitaehrotcafK5.1.motua
tneidargnim/C°4.motua
laitnereffidraegC°4.motua
40
gnitaehroolfrednulluf
retawwolfxamTC°05.motua
enilgnitaehrotcafK0.1.motua
tneidargnim/C°3.motua
laitnereffidraegC°3.motua
*01
erutarepmetyadenilgnitaehtnemtsujdaenif05tot5-
*11
erutarepmetthginenilgnitaehtnemtsujdaenif05tot5-
32
erutarepmetytefastsorfC°3-C°01tot02-
13
rednilyclanoitiddafoerutarepmetffo-hctiws
reliobRH-Shtiw
C°36C°08-04
84
)06/15RH-S(yticapacpmupmuminim)%05(%52%001-52
Page 18
Installation instructions S-HR series page 18
Installers adjustments Adjustments whereby technical knowledge is required have been classified under the installers level. Access to this level is obtained after feeding in a code, after which adjustments for user and installer are visible. For going to the Adjustments Parameters chapter the Mode key should be
pressed once after which it is shown with the text. Scrolling in the Parameter chapter can be done by means of the Step key. Adjusting the fixed value can be done by means of the + or the - key. Confirming the new adjustment is done with the Store key.
Information chapter. After feeding in the access code the information can be read out according to table 8. In order to select the information chapter the Mode key must be pressed twice after feeding in the code. New adjustments can not be done in this chapter. Scrawling in the information chapter is possible by means of the Step key.
installer adjustment possibilities table 7
rellatsnistnemtsujdaretemarapartxE
petS noitpircsed yrotcaf egnar
3
Wknignitaehlartnecrewopxammumixamxam-nim
*4
elpicnirplortnoc
tatsomrehtffo/nohtiw
01-0
0
tatsomrehtffo/no%001
1
tnednepedrehtaewffo/no%001
*5
rotcafKenilgnitaeh3.25.3-2.0
*6
tnenopxeenilgnitaeh4.14.1-1.1
*7
enozetamilcenilgnitaeh01-0-02-
*41
deepstneidarg751-0
*51
noitcuderthginretfaretsoob01fo0
0
on
1
sey
63
evlavyaw-eerhtfoepyt03-0
0
0102CV
1
gnitaludom0496CV
34
Wkniretawtohrewoprewopxammumixamxam-nim
94
yticapacpmupxam
gnitaehlartnec
%001%001-04
98
ecafretnignittessserdda07-1-
1-
eraps
0
niarB
7-0
edacsaCni8-1reliob
installer information possibilities table 8
rellatsniedomnoitamrofnI
petS noitpircsed eulav
1
1TerutarepmetretawwolfC°
4
2TerutarepmetretawnruterC°
5
3TerutarepmetretawreifirolacC°
7
4TerutarepmetedistuoC°
8
5TerutarepmetsageulfC°
61
%nirewoptneserp%
71
WknirewoptneserpWk
81
WknidaoltneserpWk
02
noitacinummocsublortnoc
12
latotnoitpmusnocJGJG
22
gnitaehlartnecnoitpmusnocJGJG
32
retawtohnoitpmusnocJGJG
42
sruohnurrenrubforebmunlatotruoh
52
gnitaehlartnecsruohnurrenrubforebmunruoh
62
retawtohsruohnurrenrubforebmunruoh
23
retnuocsruohforebmunlatotruoh
64
deriuqerecivressisruohynamwohnihtiwruoh
Page 19
Installation instructions S-HR series page 19
Service chapter. After the access code has been fed in it is possible to temporarily manually adjust the number of revolutions of the fan in the service chapter (table 9). In order to select the service chapter the Mode key has to be pressed 3 X after feeding in the access code. By means of the Step key the first function is displayed with the text Off. By means of the + or - key a required number of revolutions for the fan can be selected while the unit is operating. With Step 4 it is possible to activate the showroom position by pressing the + key after which the text on appears in the display. After this a simulated water pressure of 1.9 bar and a water temperature will be indicated. Pump or burner action is not possible. After a voltage interruption or a reset the showroom position is switched off.
Error chapter. After the access code has been fed in the Error chapter can be read (table 10). In order to select the Error chapter it is necessary to press the Mode key 4 X after feeding in the access code. By means of the Step key the functions are shown which were stored when the unit went into an error state. The first error which is shown is the last, the next error is the second last, etc.
In order to return to the normal technical read out whereby the water temperature and water pressure are shown, the Standby chapter must be requested by means of the Mode key. After a few seconds the text standby will be replaced by the technical read-out. Other wise returning to the Good read-out automatically occurs after 20 minutes in the event that no more keys have been used.
Green key function The green key function can be used in order to activate the factory settings. By this means the modified settings are cancelled. The following actions must be carried
out. Make sure that chapter is shown in the display by means of the Mode key. After this press the Store key. The word Copy becomes visible and the factory settings will be active again.
installer service possibilities table 9
installer error possibilities table 10
rellatsniedomrorrE
petS noitpircsed eulav
1
rebmunrorre
2
tinusutatsgnitarepo
3
1TerutarepmetretawwolfC°
4
2TerutarepmetretawnruterC°
5
daolWk
6
yticapacpmup%
rellatsniedomecivreS
petS noitpircsed
1
nonoitcnufrenrubhtiwnoitareponireliob
2
fforenrubdnaelbatsujdanaf
3
norenrubhtiwelbatsujdapmup
4
evitcanon=FFOdnaevitca=NOnoitisopmoorwohs
Page 20
Installation instructions S-HR series page 20
10 Switching off the unit
In some situations it may be that the entire unit must be switched off. By switching off the three keys with the lamps for central heating, hot water and pump program, the unit is switched off. STREBEL advise to leave the plug in the wall socket, by which means the circulation pump and the three-way valve are activated once every 24 hours in order to prevent jamming.
In the event of frost danger it is advisable to drain the unit and/or the installation.
11 Commissioning and
maintenance
The top of the casing is hooked behind a locking edge and is locked behind the door on the front of the casing with a screw. After removing this screw the casing must be lifted at the bottom by which means it is released from the locking edge. Then the casing can be removed forward.
With the S-HR settings such as burner pressure and adjustment of the air quantity are unnecessary, due to the fact that the unit operates with a so-called zero pressure control. By this means the correct gas quantity is controlled by the suction operation of the fan. The fine adjustment which is carried out at the factory is once­only, which means that adjusting of these values is unnecessary.
11.1 Checking for contamination
In order to be able to check the unit for contamination in the following running years it is advisable to measure the maximum air displacement in the unit when putting the unit into operation. This value can be different with each type of unit.
In order to be able to measure this value the following operations must be carried out:
- in order to enter the service chapter feed in the access code as described on page 18;
- select the manual fan setting without burner action Step , by means of the Step key which will indicate that the fan is off ;
- connect the digital pressure gauge hose to the uppermost measuring nipple of the gas block according to figure 12 (open it before fitting the hose);
- take the fan to its maximum number of revolutions by means of the + key;
- measure the pressure difference and write down this value;
- when next servicing the unit the value of the fan output may not have reduced by more that 20% compared to the value during commissioning. If this value is lower than 20% the unit does not require maintenance.
11.2 Checking of the zero pressure control
The zero pressure control is set at the factory. This can be checked by means of the following action;
- make sure that the unit is in operation and that it can discharge the heat which it produces;
- in order to enter the service chapter feed in the access code as described on page 18;
- select the manual fan adjustment with burner action Step by means of the Step key, which will indicate that the manual operation is off ;
measuring point air pressure difference figure 12
Page 21
Installation instructions S-HR series page 21
- connect the digital pressure gauge hose to the uppermost measuring nipple of the gas block according to figure 13;
- activate the manual control by briefly pressing the - key;
- take the fan to minimum load by means of the - key, after which the measured pressure difference must be between 0 and -4 Pa ;
- ending the manual selection is done by pressing the - key until the minimum load is displayed. After
pressing this key again the text
is shown
which means that the manual selection is off.
If it is determined that the zero pressure control deviates too much, then it can be corrected by means of the adjustment screw on the gas block.
- place the lance of the CO
2
gauge in the location
according to figure 14;
- adjust to maximum load by means of the + key;
- ending the manual selection is done by pressing the - key until the minimum load is shown. After
pressing this key again the text
is shown
which means that the selection is off.
11.3 Checking the CO
2
The CO2 percentage is factory-set. This can be checked by means of the following actions:
- put the unit into operation by means of the service chapter as described in chapter 11.2;
- adjust the CO2 percentage according to table 11. The CO2 percentage can be adjusted by means of the adjustment screw according to figure 15.
adjustment screw zero pressure control figure 13
measuring point for CO
2
figure 14
adjustment screw CO
2
figure 15
Page 22
Installation instructions S-HR series page 22
11.4 Maintenance
If it is necessary to clean the unit the following actions to the following components must be carried out:
The air unit Dirt which is sucked in by the air supply pipe will end up in the bottom of the air box. This dirt can be cleaned with a cloth with a simple (non-abrasive) cleaning agent.
Do not use an abrasive agent for cleaning, this causes disturbing scratches in the air box.
The burner ceramic bricks and heat exchanger These components should only be cleaned if it is determined that the maximum Pa is no longer obtained as described in chapter 12.1.
The fan unit must be removed in order to be able to inspect the heat exchanger. In this case the following actions must be carried out:
- close the gas valve and isolate the units electrical supply;
- turn the Control Tower forward around its left hinge point and remove the plastic air box;
- loosen the nut of the gas pipe under the gas block;
- loosen the small crosshead screw on the red electrical connection adaptor of the gas block;
- remove the electrical connection plug from the fan motor;
- loosen the front crosshead screw of the black plastic air inlet damper;
- after this turn the two clamping rods ¼ turn and remove them by pulling them forward;
- slightly lift the fan unit and remove it towards the front of the heat exchanger;
- the fan unit and the air inlet damper can be checked for contamination and if necessary cleaned;
- now remove the burner ceramic bricks by slightly lifting them upward and removing them in the same direction as the heat exchanger fan unit;
- the burner ceramic bricks and the heat exchanger can be cleaned by means of a soft brush;
Refitting of the components is done in reverse.
The following components require extra attention before and after refitting:
- make sure that the gasket for the ceramic bricks is fitted onto the heat exchanger precisely;
- make sure that the fan unit clamping rods have been pushed backward sufficiently and that they have again been turned ¼ turn;
- make sure that the gas connection under the gas block is tightened;
The waste trap In order to check the waste trap for contamination the following actions must be carried out:
- make sure that the unit is off by isolating the units electrical supply;
- turn the Control Tower forward around its left hinge point;
- turn the waste trap cup to the left until it is released from the screw thread;
Do not use pliers or wrenches for removing the waste trap cup
Refitting is done in reverse order.
11.5 Further checks
Checking the ionisation current.
- ionisation determines if there is a flame present with correct combustion. The measurement is done by means of connecting a Micro ampere gauge in series with the ionisation thread. The minimum allowed ionisation is 2 µA. The unit will modify its load anyway if the ionisation reaches the bottom limit of 2 µA.
Checking by means of a visual inspection.
- A visual inspection entails viewing and checking of a number of components with regard to their functioning. The safety valve may not show any traces of leaks. The waste trap should be clean. The central heating water filter only requires cleaning if the circulation pump is adjusted at maxi­mum speed and the maximum DT is exceeded.
11.6 The frequency of maintenance
STREBEL advise to carry out an inspection to the unit every two years and an overhaul every four years. When doing this the circumstances of the units location must be taken into account, From this one can determine whether to deviate from this advice.
Page 23
Installation instructions S-HR series page 23
12 Technical specifications
unit specifications table 11
epytecnailppa
RH-S
51
RH-S
42
RH-S
T42
RH-S
53
RH-S
T53
RH-S
15
RH-S
T15
RH-S
06
)sH(tupni
Wk0,510,420,420,530,530,150,150,06
)iH(tupni
Wk5,316,126,125,135,139,549,540,45
)C°06/08yticapac(egnarnoitaludom
Wk3,31-5,32,12-5,32,12-5,39,03-9,49,03-9,40,54-8,80,54-8,89,25-8,8
)C°03/05yticapac(egnarnoitaludom
Wk4,41-9,30,32-9,30,32-9,36,33-3,56,33-3,59,44-5,99,44-5,92,75-5,9
)daollluftaC°06/08(ycneiciffe
%8989898989898989
)daollluftaC°03/05(ycneiciffe
%701701701701701601601601
776NEhtiwecnadroccaniycneiciffe
%901901901901901901901901
xONfonoissimeylraey
mpp2121212121212121
OCfonoissimeylraey
mpp1111111111111111
OC
2
%99999 5,95,95,9
)daollluftaC°06/08ta(erutarepmetsageulf
C°5656567676868686
)daolwoltaC°03/05ta(erutarepmetsageulf
C°1313131313131313
lortnocrenrub
noitaludomsselpets
02G)C°0/rabm3101ta(noitpmusnocsag
h/³m23,101,201,270,370,374,474,462,5
epytrenrub
cimareccimarecmaof
epyttnerruc
zH/V05/03205/03205/03205/03205/03205/03205/03205/032
dedrocerrewopcirtcelemumixam
W221221221541541091091091
dedrocerrewopcirtceleybdnats
W55555555
92506NEotgnidroccanoitcetorpfoeerged
04PI04PI04PI04PI04PI04PI04PI04PI
)ten(thgiew
gk0505373567366836
desab-HCyticapacretaw
l5,35,35,3 55777
desab-WHDyticapacretaw
l414131
HCemitnurrevopmup
nim5151515151515151
WHDemitnurrevopmup
nim 111
muminimerusserpretaw
rab11111111
mumixamerusserpretaw
rab33333333
erutarepmetretawwolfmumixam
C°0909090909090909
C°06taetarwolfpat
nim/l65,85,21
C°54taetarwolfpat
nim/l5,85,215,71
epytpmup
oliW
SRA
07/52
SRA
07/52
SRA
07/52
SRA
07/52
SRA
07/52
SRA
57/52
SRA
57/52
SRA
57/52
daehpmupelbaliava
aPk5352520202020221
tnetnoclessevnoisnapxe
l2121
erusserp-erplessevnoisnapxe
rab11
Page 24
Installation instructions S-HR series page 24
G gas pipe A flow connection central heating R return connection central heating C condensation pipe E expansion tank pipe (S-HR-T) K cold water pipe (S-HR-T) W hot water pipe (S-HR-T)
T1 flow sensor T2 return sensor T3 calorifier sensor HWS (S-HR-T) T5 flue gas sensor (if fitted)
P1 water pressure sensor
13 Diagram showing various parts of the unit
unit diagram figure 16
GAR CE KW
T1
T2
P1
10
11
12
13
2
1
8
14
4
5
3
T5
6
7
18
T3
16
15
9
17
Page 25
Installation instructions S-HR series page 25
P1 4T12 13195187 6 T3920
T2 C 11 E K13 14 15 16 17WG21 A10 RT5
1 heat exchanger 2 ignition unit 3 fan unit 4 air inlet damper 5 gas block 6 safety valve 7 automatic air vent 8 ceramic burner bricks 9 calorifier HWS (S-HR-T) 10 operating panel
unit description figure 17
11 Control Tower 12 water filter return central heating 13 three-way valve (S-HR-T) 14 circulation pump 15 inlet combination valve (S-HR-T) 16 safety valve (S-HR-T) 17 thermostatic mixing valve (S-HR-T) 18 flue gas discharge 19 combustion air supply 20 air unit 21 type plate
Page 26
Installation instructions S-HR series page 26
1 STREBEL S-HR unit 2 expansion tank 3 outside sensor ARV1205U 4 drain points 5 Brain thermostat AA1RT15G
14 Example diagrams for connecting the unit
14.1 Radiator installation without thermostat valves
connecting of the unit to a radiator installation without thermostat valves figure 18
1
2
3
4
5
Page 27
Installation instructions S-HR series page 27
1 STREBEL S-HR unit 2 expansion tank 3 outside sensor ARV1205U 4 drain points 5 Brain thermostat AA1RT15G 6 by-pass
tra thermostatic radiator valve
14.2 radiator installation with thermostat valves only
connecting of the unit to a radiator installation with thermostat valves only figure 19
1
2
3
4
5
6
Page 28
Installation instructions S-HR series page 28
14.3 radiator installation with an under floor heating zone
connecting of the unit to a radiator zone and an underfloor heating zone figure 20
1
2
3
4
5
6
7
8
9
10
11
12
13
1 STREBEL SUPER HR unit 2 expansion tank 3 outside sensor ARV1205U 4 drain points 5 Brain thermostat AA1RT15G 6 underfloor heating 7 2-core sleeve cable 8 zone controller AA1RR15G 9 zone three-way valve 10 zone pump 11 zone non return valve 12 zone flow sensor 13 adjustment valve
Page 29
Installation instructions S-HR series page 29
14.4 radiator installation and an independent underfloor heating zone
connecting of the unit to a radiator installation and an independently controlled underfloor heating zone figure 21
1
2
3
4
5
6
7
8
9
10
11
12
14
13
1 STREBEL S-HR unit 2 expansion tank 3 outside sensor ARV1205U 4 drain points 5 Brain thermostat Master AA1RT15G 6 underfloor heating 7 2-core sleeve cable 8 group controller AA1RR15G 9 three-way valve group controller 10 pump group controller 11 return valve group controller 12 flow sensor group controller 13 adjustment valve 14 Brain thermostat zone controller AA1RT15G
Page 30
Installation instructions S-HR series page 30
14.5 two independent radiator zones
connecting of the unit to two independently controlled radiator zones figure 22
1
2
3
4
5
6
7
8
9
10
11
12
13
14
1 STREBEL S-HR unit 2 expansion tank 3 outside sensor ARV1205U 4 draining possibility 5 Brain thermostat Master AA1RT15G 6 2-core sleeve cable 7 group controller AA1RR15G 8 three-way valve group controller 9 pump group controller 10 return valve group controller 11 flow sensor group controller 12 Brain thermostat group AA1RT15G 13 adjustment valve 14 low velocity header
Page 31
Installation instructions S-HR series page 31
15 Error indication
A detected error is indicated on the display by means of blocking or error messages. A distinction should be made between these two messages due to the fact that blocking can be of a temporary nature, however, error messages are fixed lockings. The control will try its utmost to prevent locking and will temporarily switch off the unit by blocking it. Hereunder is a list of some messages.
Blocks with a number in the last 2 positions.
Block 01:
External safety contact cut off
Block 11:
Maximum DT of flow and return sensor in central heating has repeatedly been exceeded. During the block normal operation of the hot water supply is possible. The pump continues to operate at minimum capacity during the block.
Block 12:
Maximum DT of flow and return sensor in domestic hot water has repeatedly been exceeded. During the block normal operation of the central heating installation is possible. During the block the pump continues to operate at minimum capacity.
Block 60:
Incorrect parameter setting of the minimum or maximum power.
Block 67:
A DT has been detected between flow and return sensor whereas the burner is not in operation. After the DT has disappeared the block will disappear.
Block 80:
Maximum flue gas temperature has been exceeded (if present). The block will not be cancelled until the flue gas temperature has arrived below the temperature.
Block 81:
The flue gas sensor is not connected although it was connected to the control. The burner is blocked until the flue gas sensor is reconnected.
Block 82:
The flue gas sensor has short-circuited, heat requirement blocked and pump capacity at minimum.
Block 85:
The control has not detected a water flow. The venting cycle is started. If during this cycle water flow is detected, the venting cycle is ended and the burner is released.
Error with a number in the last two positions.
Error 00: Poor flame-forming Error 01: short-circuit of 24 volt circuit
Error 02: no flame-forming Error 04: adjustment or error for voltage interruption
Error 05: adjustment Error 12: fuse 24 volt/3AT faulty Error 18: maximum flow temperature exceeded
Error 19: maximum return temperature exceeded Error 28: number of revolutions not reported back from fan
Error 69: no or incorrect display Error 80: maximum flue gas sensor temperature exceeded
Page 32
This renewed publication cancels all previous installation instructions.
The company reserves the right to change the specifications and dimensions without prior notice
E. & O. E.
Page 33
central heating progr. on / off
hot water progr. on / off
pump progr. on / off
Reset key
Step key
display
Explanations of symbols and signs on the Control Tower display.
0 1 2
No heat requirement Ventilation phase Ignition phase Burner active on central heating Burner active on hot water Fan check Burner off when room thermostat is demanding Pump overrun phase for central heating Pump overrun phase for hot water Burner off because of too high flow water temperature Automatic venting programme
3 4 5
6 7 8 9 A
Water pressure is too low (<1,0 bar), flashing FILL will be altered with indication of water pressure, unit power of 50% is possible. The installation needs to be topped up.
Water pressure is too low (<0,7 bar), FILL indication remains continuously visible, the unit is taken out of operation. The installation needs to be topped up.
Water pressure is too high (>3,5 bar), HIGH indication remains continuously visible, the unit is taken out of operation. The installation pressure needs to be decreased by draining water.
Operation indication (in the first display position)
Mode key ~ Selecting chapters
Step key ~ Scrolling in a chapter
Reset key ~ Unlocking the unit in case of error
Mode key
STREBEL LTD. 1F, Albany park industrial estate frimley road, camberley surrey GU15 2PL Telephone: (01276) 685422 Fax: (01276) 685405
Loading...